Honeywell EXCEL 10 W7753A User Manual

Put Bar Code Here
Excel 10 W7753A Unit Ventilator Controller
INSTALLATION INSTRUCTIONS

PRODUCT DESCRIPTION

The W7753A Unit Ventilator Controller is a Free Topology Transceiver (FTT) L in the Excel 10 family product line.
This controller can be used to monitor/control HVAC equipment, lighting, and other miscellaneous loads in a distributed network. The controller is field-mounted to the equipment that it controls, and the controller wiring is attached to the screw terminals located on the controller (see Fig. 1).
ONMARK® Compliant Unit Vent controller
31
30 29 28
DI-4 GND
DI-3
DI-2 GND DI-1
27
26 25
24
23 22
21
VAC
24
24
1
VAC
COM
OUT
OUT
20
2
3
4
OUT
OUT
The W7753A Controller communicates via the 78 kilobaud Echelon® LonWorks® E-Bus Network.
Allowable input/output connections consist of wall module points plus two additional resistive sensor inputs, two voltage/ current inputs, four digital inputs and eight digital Triac outputs.
For the W7753A, any hardware driven by the Triac outputs must have a minimum current draw, when energized, of 25 mA and a maximum current draw of 500 mA.
19 18
17
OUT
16
6
7
8
OUT
OUT
OUT
5
E
GND
1
LED
BYPASS
23
SNSR
GND
SET PT
AI-1
GND
A1-2
AI-3
5
OHM
67
89
4
OHM
GND
V/mA
10 11 12
AI-4
V/mA
22VDC
OUT
13 14
E-BUS
E-BUS
JACK
15
J3
Fig. 1. Excel 10 W7753A Unit Ventilator Controller.
M12688
95-7520—02
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER

INSTALLATION

Mount the W7753A in a position that allows clearance for wiring, servicing and controller removal. Avoid mounting the W7753A in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller, or in areas where escaping gas or other explosive vapors are present. See Fig. 2 for mounting dimensions.
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
DI-4
GND
DI-3 DI-2
GND
DI-1
24
VAC
24 VAC COM
The controller enclosure on the W7753A is constructed of a sheet metal housing and a plastic factory snap-on cover. The controller mounts using two screws inserted through the plastic cover. Use the screws appropriate for the mounting surface. The W7753A can be mounted in any orientation. Ventilation openings were designed into the cover to allow proper heat dissipation regardless of the mounting orientation.
The W7753A can also be mounted using DIN rail (obtain locally). If using DIN rail also purchase from Augat Inc. part number 2TK2D DIN rail (adapter) two each (See Fig. 3).
2-1/8
(54)
1
OUT
2
OUT
3
OUT
4
OUT
5
OUT
6
OUT
OUT
7
8
OUT
5-5/8 (143)
E
BYPASS
SNSR
GND
SET PT
AI-1
GND
AI-2
AI-3
GND
AI-4
22VDC
LED
GND
1 23 456 789101112131415J3
OHM
5-3/16 (132)
OHM
V/mA
6 (152)
V/mA
OUT
E-BUS
E-BUS
JACK
Fig. 2. W7753A mounting dimensions in in. (mm).
3-1/16
(77)
M12689
95-7520—02 2
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
Power
The 24 Vac power from an energy-limited Class II Power Source must be provided to each W7753A Controller. To conform to Class II restrictions (U.S. only), transformers must not be larger than 100 VA.
2
A transformer that meets CE mark requirements and that meets the Low Voltage Directive (LVD) requirements must be used in Europe for all installations of this product. More than
3
one W7753A Controller can be powered by a single transformer. Fig. 4 shows power wiring details for a single controller and Fig. 5 depicts multiple controllers using one transformer.
1
M6857
Fig. 3. W7753A DIN rail mounting.

Wiring

All wiring must comply with applicable electrical codes and ordinances or as specified on installation wiring diagrams. Controller wiring on the W7753A is terminated to the screw terminal blocks located on the top and the bottom of the controller.
NOTES:
For multiple controllers operating from a single
transformer, the same side of the transformer secondary must be connected to the same power input terminal in each controller. The ground terminal (1 on the W7753A) must be connected to a verified earth ground for each controller in the group (see Fig. 5). (Controller configurations are not necessarily limited to three controllers, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer (U.S. only). See System Engineering form 74-2964 for power wiring recommendations.)
All loads on an Excel 10 W7753A Controller must
be powered by the same transformer that powers the Excel 10 W7753A Controller. A W7753A Controller can use separate transformers for controller power and load power.
Keep the earth ground connection (terminal 1)
wire run as short as possible. Refer to Fig. 9 through 14.
—Do not connect the analog or digital ground
terminals (5, 8, 11, 27 and 30) to earth ground. Refer to Fig. 9 through 14.
IMPORTANT
Use the heaviest gauge wire available, up to 14 AWG (2.0 mm (1.0 mm
2
) with a minimum of 18 AWG
2
), for all power and earth ground wiring. Screw type terminal blocks are designed to accept up to two 14 AWG (2.0 mm2) conductors, one on each side of the terminal screw. More than two wires that are 14 AWG (2.0 mm2) can be connected with a wire nut. Include a pigtail with this wire group and attach the pigtail to one side of the terminal block.
OUTPUT DEVICE POWER
TRANSFORMER
CONNECT POWER TO TERMINALS 24 AND 25
W7753A
1
EARTH GROUND
TRIAC LINES TO ACTUATORS AND CONTACTORS
25
24
2022
M12681
Fig. 4. Power wiring details; one Excel 10 per transformer.
NOTES:
Unswitched 24 Vac power wiring can be run in the
same conduit as the E-Bus cable.
Maintain at least three-inch (76 mm) separation
between Triac outputs and E-Bus wiring throughout the installation.
See the following IMPORTANT on Heating and Cooling Equipment (UL 1995, U.S. only).
IMPORTANT
If the W7753A Controller is used on Heating and Cooling Equipment (UL 1995, U.S. only) and the transformer primary power is more than 150 volts, connect the transformer secondary to earth ground (see Fig. 6). For these applications, only one W7753A Excel 10 controller can be powered by each transformer.
3 95-7520—02
M12682
24 VAC
120/240 VAC
TRANSFORMER
W7753A
EARTH GROUND
24
25
1
W7753A
EARTH GROUND
24
25
1
W7753A
EARTH GROUND
24
25
1
M12680
24 VAC
LINE VOLTAGE GREATER THAN 150 VAC
TRANSFORMER
W7753A
EARTH GROUND
EARTH
GROUND
IF THE W7750 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND ONE SIDE OF TRANSFORMER SECONDARY.
1
1
1
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
Fig. 5. Power wiring details for two or more Excel 10s per transformer.
Fig. 6. Transformer power wiring details for one Excel 10
used in UL 1995 equipment (U.S. only).
Communications
Refer to E-Bus Wiring Guidelines, form 74-2865, for a complete description of E-Bus network topology rules. Approved cable types for E-Bus communications wiring are Level IV 22 AWG (0.34 mm unshielded, twisted pair, solid conductor wire. For nonplenum areas, U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair) can be used. In plenum areas, U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair) can be used. Communications wiring can be run in a conduit, if needed, with non-switched 24 Vac or sensor wiring. If a longer E-Bus network is required, a Q7740A 2-way or Q7740B 4-way repeater can be added to extend the length of the E-Bus. Also a Q7751A Router can be added to partition the system into two segments and effectively double the length of the E-Bus. Only one router is allowed with each Excel 10 Zone Manager, and each network segment can have a maximum of one repeater.
Pull the cable to each device on the E-Bus and connect to communication terminals 14 and 15 (W7753A).
2
) plenum and non-plenum rated
NOTES: (For Communications Wiring)
All field wiring must conform to local codes and
ordinances (or as specified on the installation drawings).
Approved cable types for E-Bus communications
wiring is Level IV 22 AWG (0.34 mm
2
) plenum and non-plenum rated unshielded, twisted pair, solid conductor wires. For nonplenum areas, U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair) can be used. In plenum areas, U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair) can be used.
Unswitched 24 Vac power wiring can be run in the
same conduit as the E-Bus cable.
Do not bundle output wires with sensor, digital
input or communications E-Bus wires.
Do not use different wire types or gauges on the
same E-Bus segment. The step change in line impedance characteristics would cause unpre­dictable reflections on the E-Bus. When using dif­ferent types is unavoidable, use a Q7751A Router at the junction.
In noisy (high EMI) environments, avoid wire runs
parallel to noisy power cables, motor control cen­ters, or lines containing lighting dimmer switches, and keep at least 3 in. (76 mm) of separation between noisy lines and the E-Bus cable.
Each daisy-chained E-Bus segment that is on one
side of a Q7751A,B Router (can contain up to 60 Excel 10s) and has a length greater than 1640 ft. (500m) must have two E-Bus 209541B Termination Modules, one at each end of the daisy-chain wiring run.
Make sure that neither of the E-Bus wires is
grounded.
NOTE: If a 209541B Termination Module is required at a the
UV controller, connect two of the three termination module wires to the E-Bus terminals. Selecting the appropriate two wires depends on the E-Bus network topology. Refer to the E-Bus Wiring Guidelines, form 74-2865, and the Excel 10 FTT Termination Module Installation Instructions, form 95-7554. For example, using a doubly terminated daisy-chained bus topol­ogy, if controllers are on either end of an E-Bus wire run, mount the termination module on the appropri­ate terminals as shown in Fig. 7.
95-7520—02 4
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
W7753A
W7753A
1415 1415
BROWN
ORANGE
PART NO. 209541B TERMINATION MODULE
PART NO. 209541B TERMINATION MODULE
W7753A
BROWN
1415
ORANGE
M12690
Fig. 7. Termination modules (place a wire nut on each remaining wire that is not connected to a controller or device).
2
NOTE: When two or more wires are to be attached to the same terminal, other than 14 AWG (2.0 mm
), be sure to twist them
together. Deviation from this rule can result in improper electrical contact. See Fig. 8.
Wire to the terminal blocks as follows:
1. Strip 3/8 in. (10 mm) insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
3. If two or more wires are being inserted into one terminal location, strip 1/2 in. (13 mm) of insulation from the con­ductors then twist the wires together a minimum of three turns before inserting them.
4. Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tightening the screw.
5. Pull on each wire in all terminals to check for good mechanical connection.
Wiring Details
The W7753A Controller has the terminal arrangements shown in Fig. 9 through 14. Connection for operator access to the E-Bus is provided by plugging the Serial LonTalk® Adapter (SLTA) connector into the E-Bus jack.
NOTE: If an Excel 10 Controller or Zone Manager is not
connected to a good earth ground, the controller internal transient protection circuitry is compromised and the function of protecting the controller from noise and power line spikes cannot be fulfilled. This can result in a damaged circuit board and require replacement of the controller. Refer to job drawings for specific installation wiring diagrams.
3/8 (10)
STRIP 3/8 IN. (10 MM) FROM WIRES
1. 2. TWIST WIRES TOGETHER TO BE ATTACHED AT ONE TERMINAL.
WITH PLIERS (A MINIMUM OF THREE TURNS).
Fig. 8. Attaching two or more wires at terminal blocks.
5 95-7520—02
TWO 14 AWG
2
) WIRES
(2.0 MM
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
M10086
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
31 30 29 28 27 26 25 24 23 22 21 20
OUT 1
OUT 2
24 VAC COM
TRIAC EQUIVALENT CIRCUIT
DI-4
DI-3
GND
W7753A
DI-2
GND
24 VAC
DI-1
19 18 17 16
OUT 3
OUT 4
OUT 7
OUT 6
OUT 5
OUT 8
UNIT VENTILATOR CONTROLLER
GND
SETPT
LED
GND
AI-1 OHM
9 10
FAN
BYPASS
SNSR
LED
BYPASS
E GND
1234 5 6 7 8
GND
3 41 2
NET 1
SENSOR
7 85 6
NET 2
SET PT
GND
AI-3 V/mA
AI-2 OHM
9 10 11 12 14 J3 15
E-BUS
E-BUS
JACK
AI-4 V/mA
22 VDC OUT
13
E-BUS
OUTSIDE AIR CO SENSOR
TR23-F5 WALL MODULE
M29164
Fig. 9. Typical W7753A unit ventilator application wiring
diagram with T7770F wall module. (For note 2, refer to
Fig. 8.)
WINDOW CONTACT (CONTACT CLOSED = WINDOWCLOSED)
3
OCCUPANCY SENSOR (CONTACT CLOSED = OCCUPIED)
3
31 30 29 28 27 26 25 24 23 22 21 20
OUT 1
OUT 2
24 VAC COM
TRIAC EQUIVALENT CIRCUIT
DI-4
DI-3
GND
W7753A
DI-2
GND
24 VAC
DI-1
OUT 3
OUT 4
19 18 17 16
OUT 6
OUT 5
UNIT VENTILATOR CONTROLLER
AI-4 V/mA
22 VDC OUT
13
2
E-BUS
GND
SNSR
SETPT
LED
BYPASS
E GND
12345678
1
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM WITH A MINIMUM OF 18 AWG (1.O MM
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
3
CONTACTS MUST BE SUITABLE FOR DRY SWITCHING, 5V AT 10 mA. USE SEALED TYPE, GOLD FLASHED OR PIMPLED CONTACTS.
GND
AI-1 OHM
9101112 14 J315
GND
AI-3 V/mA
AI-2 OHM
2
), FOR EARTH GROUND WIRE.
24 VAC
OUT 7
E-BUS
M12692
+
-
OUT 8
E-BUS
JACK
2
)
95-7520—02 6
Fig. 10. Typical window and occupancy sensor wiring
diagram. (For note 2, refer to Fig. 8.)
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
12345678
E-BUS
24 VAC
W7753A UNIT VENTILATOR CONTROLLER
1
2
E-BUS
E GND
GND
SNSR
SETPT
LED
BYPASS
GND
GND
9101112 14 J315
31 30 29 28 27 26 25 24 23 22 21 20
24 VAC COM
E-BUS
JACK
22 VDC OUT
19 18 17 16
AI-1 OHM
AI-2 OHM
AI-4 V/mA
OUT 7
OUT 6
OUT 5
OUT 4
OUT 8
OUT 1
OUT 3
OUT 2
AI-3 V/mA
13
DI-2
DI-4
DI-1
DI-3
M12695
GND
GND
TRIAC EQUIVALENT CIRCUIT
C7600C
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM
2
) WITH
A MINIMUM OF 18 AWG (1.O MM
2
), FOR EARTH GROUND WIRE.
TO ASSURE PROPER ELECTRICAL CONTACT, WIRESMUST BE TWISTED TOGETHER BEFORE INSERTIONINTO THE TERMINAL BLOCK.
+
S
C7600C
+
S
ENTHALPY (4 TO 20mA)
HUMIDITY (4 TO 20mA)
MMC325 PNEUMATIC TRANSDUCER
24 (H)
24 (N)
24 (H)
24 (N)
INCREASE
DECREASE
OUT 1
PNEUMATIC VALV E
OUT 3
OUT 2
1
31 30 29 28 27 26 25 24 23 22 21 20
DI-3
GROUND
DI-2
GROUND
DI-4
2
DI-1
24 VAC
24 VAC COM
W7753A UNIT VENTILATOR CONTROLLER
M
B
19 18 17 16
OUT 5
OUT 4
M
3
+
24 VAC
-
OUT 7
OUT 6
OUT 8
1
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN; REVERSING TERMINATIONS RESULTS IN EQUIPMENT MALFUNCTION.
2
OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER.
3
USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE MUST BE 6 FT. (1.8M) OR LONGER.
Fig. 11. Typical Pneumatic Transducer to W7753A.
Fig. 12. Typical 4 to 20 mA Humidity and Enthalpy Sensor
to W7753A. (For note 2, refer to Fig. 8.)
M12693
7 95-7520—02
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
+
24 VAC
-
31 30 29 28 27 26 25 24 23 22 21 20
OUT 1
OUT 3
OUT 2
24 VAC COM
TRIAC EQUIVALENT CIRCUIT
DI-4
DI-3
GND
W7753A
DI-2
GND
24 VAC
DI-1
UNIT VENTILATOR CONTROLLER
GND
SNSR
SETPT
LED
BYPASS
E GND
12345678
1
GND
AI-1 OHM
GND
AI-3 V/mA
AI-2 OHM
9101112 14 J315
19 18 17 16
OUT 6
OUT 5
OUT 4
E-BUS
AI-4 V/mA
22 VDC OUT
13
2
OUT 7
E-BUS
OUT 8
E-BUS
JACK
ML7984B
PWM VALVE ACTUATOR
24 (H)
24 (N)
PWM
(H 24 VAC)
PWM OUTPUT
T6 T5 C B W R
2
3
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM OF 18 AWG (1.O MM
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
3
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN:REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.
4
TURN POWER OFF BEFORE SETTING THE DIP SWITCHES.
FROM CNTRL
PWM VALVE ACTUATOR
1234
ON
OFF
CONFIGURATION DIP SWITCHES (LOCATED ADJACENT TO THE INPUT TERMINAL BLOCK)
2
), FOR EARTH GROUND WIRE.
4
2
) WITH A MINIMUM
M12694
Fig. 13. Typical PWM Valve Actuator to W7753A. (For note 2, refer to Fig. 8.)
NOTE: Make sure to set the Configuration DIP Switch as shown in Fig. 13. Switches 1 through 3 set the timing of the ML7984B
valve actuator to match the W7753A outputs (0.1 sec. Min. with a max. time of 25.6 sec.). Switch 4 determines the action of the actuator (Off = Direct Acting, On = Reverse Acting).

CHECKOUT

W7753A Checkout

Step 1. Check Installation and Wiring
Inspect all wiring connections at the W7753A terminals and verify compliance with installation job drawings. If any wiring changes are required, first be sure to remove power from the controller before starting work. Pay particular attention to: — 24 Vac power connections. Verify that multiple controllers
powered by the same transformer are wired with the transformer secondary connected to the same input terminal numbers on each W7753A. See Fig. 5. (Controller configurations are not necessarily limited to three controllers, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer (U.S. only). See System Engineering, form 74-2964, for power wiring recommendations.
— Controller wiring. Be sure that each controller is wired
(terminal 1) on the W7753A to a verified earth ground using a wire run as short as possible with the heaviest gauge wire available, up to 14 AWG (2.0 mm minimum of 18 AWG (1.0 mm
2
) for each controller in the
group. See Fig. 4.
— Verify Triac wiring to external controllers uses the proper
load power/24 Vac hot terminal (terminal 25 on the W7753A).
NOTE: All wiring must comply with applicable electrical
codes and ordinances or as specified on installation wiring diagrams.
2
) with a
31 30 29 28 27 26 25 24 23 22 21 20
OUT 1
OUT 2
24 VAC COM
TRIAC EQUIVALENT CIRCUIT
DI-4
DI-3
GND
W7753A
DI-2
GND
24 VAC
DI-1
OUT 3
OUT 4
19 18 17 16
OUT 7
OUT 6
OUT 5
OUT 8
UNIT VENTILATOR CONTROLLER
AI-4 V/mA
22 VDC OUT
13
2
E-BUS
E-BUS
E-BUS
2
) WITH
M12696
GND
SNSR
SETPT
LED
BYPASS
E GND
12345678
1
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM A MINIMUM OF 18 AWG (1.O MM
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRESMUST BE TWISTED TOGETHER BEFORE INSERTIONINTO THE TERMINAL BLOCK.
C7600B
+V
OUT
GND
AI-1 OHM
HUMIDITY SENSOR (2 TO 10 VOLT)
GND
2
), FOR EARTH GROUND WIRE.
GND
AI-3 V/mA
AI-2 OHM
9101112 14 J315
Fig. 14. Typical 2 to 10 Volt DC humidity sensor to
W7753A. (For note 2, refer to Fig. 8.)
JACK
95-7520—02 8
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
Verify Termination Module Placement
The installation wiring diagrams should indicate the locations for placement of 209541B Termination Module(s). Refer to the E-Bus Wiring Guidelines, form 74-2865, and the Excel 10 FTT Termination Module Installation Instructions, form 95-7554. Correct placement of the termination module(s) is required for proper E-Bus communications.
Step 2. Startup
W7753A CONTROLLER STATUS LED
The LED on the front and center of a W7753A Controller provides a visual indication of the status of the controller. See Fig. 15. When the W7753A receives power, the LED should appear in one of the following allowable states:
1. Off—no power to the processor.
2. Continuous On—processor is in initialized state.
3. Slow Blink—controlling, normal state.
4. Fast Blink—when the Excel 10 has an alarm condition.
W7753A
31 30
29 28 27
26 25
24
23 22
21
20
DI-4 GND
GND DI-1
24
24
1
VAC
VAC
COM
OUT
DI-3
DI-2
19 18 17
2
3
4
OUT
OUT
OUT
16
5
6
7
8
OUT
OUT
OUT
OUT
• Node Number: This is the Excel 10 node that has the alarm condition (see Network Statics).
Alarm Type: The specific alarm being issued. An Excel 10 can provide the alarm types listed in Table 1.
Broadcasting the Service Message
The Service Message allows a device on the E-Bus to be positively identified. The Service Message contains the controller ID number and, therefore, can be used to confirm the physical location of a particular Excel 10 in a building.
There is one method of broadcasting the Service Message from an Excel 10 W7753A Controller. This uses a hardware push button on the side of the controller (see Fig. 16).
When an Assign ID command is issued from the commissioning tool, the node goes into the SERVICE_MESSAGE mode for five minutes. In the SERVICE_MESSAGE mode, pressing the service pin on the controller or the bypass button on a wall module causes the Service Message to be broadcast on the network. All other functions are normal in the SERVICE_MESSAGE mode.
Step 3. I/O Tests
The controller must be configured using the Excel 10 E-Vision PC configuration tool. Once this is done, the W7753A can be commanded to MANUAL mode, and each output can be exercised/viewed to verify proper wiring connections and equipment operation. See the Excel 10 E-Vision Users Guide, form 74-2588 for details on configuring and testing W7753A Controllers.
E
LED
BYPASS
SNSR
23
GND
SET PT
AI-1
GND
OHM
45678
A1-2 OHM
910
AI-3 V/mA
GND
11 12
AI-4
V/mA
22VDC
OUT
13 14
E-BUS
E-BUS JACK
15
J3
M12697
GND
1
STATUS LED
Fig. 15. LED location on W7753A.
ALARMS
When an Excel 10 has an alarm condition, it reports it to the central node on the E-Bus (typically, the Excel 10 Zone Manager, or Small Building Controller). See Table 1. The information contained in an alarm message follows:
• Subnet Number: This is the E-Bus subnet that contains the Excel 10 node that has the alarm condition. Subnet 1 is on the Zone Manager side of the router; Subnet 2 is on the other side of the router.
SERVICE PIN BUTTON
M10094
Fig. 16. Location of the service pin button.
Step 4. Verify Sequences of Operation
For the detailed descriptions of the sequences of operation, see the Excel 10 Unit Ventilator System Engineering, form 74-2964 Appendix B.
9 95-7520—02
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
Table 1. Excel 10 Alarms.
Alarm type
Name of alarm or error bit
number
NO_ALARM 0 No alarms presently detected.
INPUT_NV_FAILURE 1 One or more NV inputs have failed while receiving an update within their
specified FAILURE_DETECT_TIME.
NODE_DISABLED 2 The control algorithm stopped because the controller is in DISABLED_MODE,
or FACTORY_TEST mode. The control is shut down and disabled until power is cycled or the node is reset. See NOTE 1 below.
SENSOR_FAILURE 3 One or more sensors have failed. FROST_PROTECTION_ALARM 4 The space temperature is below the frost alarm limit 42.8°F (6°C) when the
mode is FREEZE_PROTECT. The alarm condition remains until the temperature exceeds the alarm limit plus hysteresis.
INVALID_SET_POINT 5 One of the Setpoints is not in the valid range.
LOSS_OF_AIR_FLOW 6 The Fan Status DI indicates that there is no air flow when the node is
commanding the fan to run. The control is shut down and disabled until power is cycled or the node is reset. The alarm is not issued until FanFailTime seconds have elapsed since the loss-of-flow condition was first reported.
DIRTY_FILTER 7 The pressure drop across the filter exceeds the limit and the filter requires
maintenance. The control runs normally.
SMOKE_ALARM 8 The smoke detector has detected smoke and the node has entered an
emergency state.
IAQ_OVERRIDE 9 The indoor air quality sensor has detected that the indoor air quality is poorer
than the desired standard and additional outdoor air is being brought into the conditioned space.
LOW_LIM_ECON_CLOSE 10 The economizer has to close beyond the minimum position to prevent the
discharge air temperature from going below the discharge temperature low limit.
DRIP_PAN_FULL 11 Drip pan maintenance is required. Cooling control is disabled. Fan continues to
run.
FREEZE_STAT 12 Very Cold Temperature detected inside the Unit Ventilator Cabinet. Control
closes OA Damper, and open heat valve.
OAQ_ALARM 13
The configured outdoor air quality sensor has detected CO or CO
2
levels that exceeds OaQStPt (plus 30 ppm hysteresis). When there is an OAQ_ALARM, the economizer damper is closed.
RETURN_TO_NORMAL 128 Return to no alarm after being in an alarm condition. This code is added
numerically to another alarm code to indicate that the alarm condition has returned to normal.
ALARM_NOTIFY_DISABLED 255 The alarm reporting was turned off by the nviManualMode. No more alarms are
reported until nviManualMode turns on alarm reporting or upon application restart.
NOTE: The node can be reset by switching the node to MANUAL and then switching to the normal operating mode
(using DestManMode).
Also, the Excel 10 network variables, AlarmLogX, where X is 1 through 5, that store the last five alarms to occur in the controller, are available. These points can be viewed through XBS, XI584 or E-Vision.
95-7520—02 10
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
11 95-7520—02
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
Honeywell GmbH
Böblinger Straße 17
D-71101 Schönaich
customer.honeywell.com
® U.S. Registered Trademark © 2009 Honeywell International Inc. 95-7520—02 K.K. Rev. 03-09
Loading...