Honeywell EXCEL 10 W7753A User Manual

Put Bar Code Here
Excel 10 W7753A Unit Ventilator Controller
INSTALLATION INSTRUCTIONS

PRODUCT DESCRIPTION

The W7753A Unit Ventilator Controller is a Free Topology Transceiver (FTT) L in the Excel 10 family product line.
This controller can be used to monitor/control HVAC equipment, lighting, and other miscellaneous loads in a distributed network. The controller is field-mounted to the equipment that it controls, and the controller wiring is attached to the screw terminals located on the controller (see Fig. 1).
ONMARK® Compliant Unit Vent controller
31
30 29 28
DI-4 GND
DI-3
DI-2 GND DI-1
27
26 25
24
23 22
21
VAC
24
24
1
VAC
COM
OUT
OUT
20
2
3
4
OUT
OUT
The W7753A Controller communicates via the 78 kilobaud Echelon® LonWorks® E-Bus Network.
Allowable input/output connections consist of wall module points plus two additional resistive sensor inputs, two voltage/ current inputs, four digital inputs and eight digital Triac outputs.
For the W7753A, any hardware driven by the Triac outputs must have a minimum current draw, when energized, of 25 mA and a maximum current draw of 500 mA.
19 18
17
OUT
16
6
7
8
OUT
OUT
OUT
5
E
GND
1
LED
BYPASS
23
SNSR
GND
SET PT
AI-1
GND
A1-2
AI-3
5
OHM
67
89
4
OHM
GND
V/mA
10 11 12
AI-4
V/mA
22VDC
OUT
13 14
E-BUS
E-BUS
JACK
15
J3
Fig. 1. Excel 10 W7753A Unit Ventilator Controller.
M12688
95-7520—02
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER

INSTALLATION

Mount the W7753A in a position that allows clearance for wiring, servicing and controller removal. Avoid mounting the W7753A in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller, or in areas where escaping gas or other explosive vapors are present. See Fig. 2 for mounting dimensions.
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
DI-4
GND
DI-3 DI-2
GND
DI-1
24
VAC
24 VAC COM
The controller enclosure on the W7753A is constructed of a sheet metal housing and a plastic factory snap-on cover. The controller mounts using two screws inserted through the plastic cover. Use the screws appropriate for the mounting surface. The W7753A can be mounted in any orientation. Ventilation openings were designed into the cover to allow proper heat dissipation regardless of the mounting orientation.
The W7753A can also be mounted using DIN rail (obtain locally). If using DIN rail also purchase from Augat Inc. part number 2TK2D DIN rail (adapter) two each (See Fig. 3).
2-1/8
(54)
1
OUT
2
OUT
3
OUT
4
OUT
5
OUT
6
OUT
OUT
7
8
OUT
5-5/8 (143)
E
BYPASS
SNSR
GND
SET PT
AI-1
GND
AI-2
AI-3
GND
AI-4
22VDC
LED
GND
1 23 456 789101112131415J3
OHM
5-3/16 (132)
OHM
V/mA
6 (152)
V/mA
OUT
E-BUS
E-BUS
JACK
Fig. 2. W7753A mounting dimensions in in. (mm).
3-1/16
(77)
M12689
95-7520—02 2
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
Power
The 24 Vac power from an energy-limited Class II Power Source must be provided to each W7753A Controller. To conform to Class II restrictions (U.S. only), transformers must not be larger than 100 VA.
2
A transformer that meets CE mark requirements and that meets the Low Voltage Directive (LVD) requirements must be used in Europe for all installations of this product. More than
3
one W7753A Controller can be powered by a single transformer. Fig. 4 shows power wiring details for a single controller and Fig. 5 depicts multiple controllers using one transformer.
1
M6857
Fig. 3. W7753A DIN rail mounting.

Wiring

All wiring must comply with applicable electrical codes and ordinances or as specified on installation wiring diagrams. Controller wiring on the W7753A is terminated to the screw terminal blocks located on the top and the bottom of the controller.
NOTES:
For multiple controllers operating from a single
transformer, the same side of the transformer secondary must be connected to the same power input terminal in each controller. The ground terminal (1 on the W7753A) must be connected to a verified earth ground for each controller in the group (see Fig. 5). (Controller configurations are not necessarily limited to three controllers, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer (U.S. only). See System Engineering form 74-2964 for power wiring recommendations.)
All loads on an Excel 10 W7753A Controller must
be powered by the same transformer that powers the Excel 10 W7753A Controller. A W7753A Controller can use separate transformers for controller power and load power.
Keep the earth ground connection (terminal 1)
wire run as short as possible. Refer to Fig. 9 through 14.
—Do not connect the analog or digital ground
terminals (5, 8, 11, 27 and 30) to earth ground. Refer to Fig. 9 through 14.
IMPORTANT
Use the heaviest gauge wire available, up to 14 AWG (2.0 mm (1.0 mm
2
) with a minimum of 18 AWG
2
), for all power and earth ground wiring. Screw type terminal blocks are designed to accept up to two 14 AWG (2.0 mm2) conductors, one on each side of the terminal screw. More than two wires that are 14 AWG (2.0 mm2) can be connected with a wire nut. Include a pigtail with this wire group and attach the pigtail to one side of the terminal block.
OUTPUT DEVICE POWER
TRANSFORMER
CONNECT POWER TO TERMINALS 24 AND 25
W7753A
1
EARTH GROUND
TRIAC LINES TO ACTUATORS AND CONTACTORS
25
24
2022
M12681
Fig. 4. Power wiring details; one Excel 10 per transformer.
NOTES:
Unswitched 24 Vac power wiring can be run in the
same conduit as the E-Bus cable.
Maintain at least three-inch (76 mm) separation
between Triac outputs and E-Bus wiring throughout the installation.
See the following IMPORTANT on Heating and Cooling Equipment (UL 1995, U.S. only).
IMPORTANT
If the W7753A Controller is used on Heating and Cooling Equipment (UL 1995, U.S. only) and the transformer primary power is more than 150 volts, connect the transformer secondary to earth ground (see Fig. 6). For these applications, only one W7753A Excel 10 controller can be powered by each transformer.
3 95-7520—02
M12682
24 VAC
120/240 VAC
TRANSFORMER
W7753A
EARTH GROUND
24
25
1
W7753A
EARTH GROUND
24
25
1
W7753A
EARTH GROUND
24
25
1
M12680
24 VAC
LINE VOLTAGE GREATER THAN 150 VAC
TRANSFORMER
W7753A
EARTH GROUND
EARTH
GROUND
IF THE W7750 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND ONE SIDE OF TRANSFORMER SECONDARY.
1
1
1
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
Fig. 5. Power wiring details for two or more Excel 10s per transformer.
Fig. 6. Transformer power wiring details for one Excel 10
used in UL 1995 equipment (U.S. only).
Communications
Refer to E-Bus Wiring Guidelines, form 74-2865, for a complete description of E-Bus network topology rules. Approved cable types for E-Bus communications wiring are Level IV 22 AWG (0.34 mm unshielded, twisted pair, solid conductor wire. For nonplenum areas, U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair) can be used. In plenum areas, U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair) can be used. Communications wiring can be run in a conduit, if needed, with non-switched 24 Vac or sensor wiring. If a longer E-Bus network is required, a Q7740A 2-way or Q7740B 4-way repeater can be added to extend the length of the E-Bus. Also a Q7751A Router can be added to partition the system into two segments and effectively double the length of the E-Bus. Only one router is allowed with each Excel 10 Zone Manager, and each network segment can have a maximum of one repeater.
Pull the cable to each device on the E-Bus and connect to communication terminals 14 and 15 (W7753A).
2
) plenum and non-plenum rated
NOTES: (For Communications Wiring)
All field wiring must conform to local codes and
ordinances (or as specified on the installation drawings).
Approved cable types for E-Bus communications
wiring is Level IV 22 AWG (0.34 mm
2
) plenum and non-plenum rated unshielded, twisted pair, solid conductor wires. For nonplenum areas, U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair) can be used. In plenum areas, U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair) can be used.
Unswitched 24 Vac power wiring can be run in the
same conduit as the E-Bus cable.
Do not bundle output wires with sensor, digital
input or communications E-Bus wires.
Do not use different wire types or gauges on the
same E-Bus segment. The step change in line impedance characteristics would cause unpre­dictable reflections on the E-Bus. When using dif­ferent types is unavoidable, use a Q7751A Router at the junction.
In noisy (high EMI) environments, avoid wire runs
parallel to noisy power cables, motor control cen­ters, or lines containing lighting dimmer switches, and keep at least 3 in. (76 mm) of separation between noisy lines and the E-Bus cable.
Each daisy-chained E-Bus segment that is on one
side of a Q7751A,B Router (can contain up to 60 Excel 10s) and has a length greater than 1640 ft. (500m) must have two E-Bus 209541B Termination Modules, one at each end of the daisy-chain wiring run.
Make sure that neither of the E-Bus wires is
grounded.
NOTE: If a 209541B Termination Module is required at a the
UV controller, connect two of the three termination module wires to the E-Bus terminals. Selecting the appropriate two wires depends on the E-Bus network topology. Refer to the E-Bus Wiring Guidelines, form 74-2865, and the Excel 10 FTT Termination Module Installation Instructions, form 95-7554. For example, using a doubly terminated daisy-chained bus topol­ogy, if controllers are on either end of an E-Bus wire run, mount the termination module on the appropri­ate terminals as shown in Fig. 7.
95-7520—02 4
Loading...
+ 8 hidden pages