Honeywell EXCEL 10 W7751H User Manual

Excel 10 W7751H Smart VAV Actuator
INSTALLATION INSTRUCTIONS

BEFORE INSTALLATION

The W7751H Smart VAV Actuator is a factory-combined Excel 10 Variable Air Volume (VAV) Box Controller and an ML6174 Direct-Coupled Actuator with De-clutch mechanism. The actuator/controller assembly is field mounted to the VAV box damper shaft similar to the mounting of a standard actuator, and the controller wiring is terminated to the screw terminals that are located under a snap-on cover. See Fig. 1. The Smart VAV Actuator is a Free Topology Transceiver (FTT) L
ONMARK® compliant controller. The W7751H2025 is for
smoke control use.
The ML6174 Direct-Coupled Actuator with De-clutch mechanism (see Fig. 2 for location) allows the installer to manually open or close the VAV box damper connected to the W7751H without power or software tool to command it.
The controller in the W7751H contains a Microbridge flow­through pressure sensor and communicates via the 78 kilobaud Echelon® L
Triac output loads must draw a minimum current of 25 mA at 24 Vac, 60 Hz nominal. Triac maximum current rating: 77 mA.
The actuator on the W7751H mounts directly onto the VAV box damper shaft and has up to 70 lb-in. torque (8 Nm), 90 degree stroke, and 90 second timing at 60 Hz.
The actuator on the W7751H can accommodate the optional field-installed auxiliary switches.
NOTE: Mounting thermostat/sensor greater than 20 ft from
the W7751H2025 requires 14506944-001 Transient Protectors. They must be installed on the thermostat/ sensor leads from the T7770C pins 3, 4, 5, 6, and 7.
ONWORKS® Bus Network.

INSTALLATION

Horizontally mount the W7751H on the damper shaft and allow clearance for wiring, servicing and module removal. Avoid mounting the W7751H in areas where acid fumes or other deteriorating vapors can attack the metal parts of the actuator, or in areas where escaping gas or other explosive vapors are present. See Fig. 2 for mounting dimensions.
60
CW
45
CCW
CW
45
CCW
60
M19924
Fig. 1. Excel 10 Smart VAV Actuator.
IMPORTANT
The assembly is intended only for horizontal shaft mounting, to assure proper heat dissipation from the controller housing. The Smart VAV Actuator must not be mounted with the controller at the top.
95-7553-04
EXCEL 10 W7751H SMART VAV ACTUATOR
MAINTAIN A MINIMUM DISTANCE OF 3 IN. (76 MM) FROM OTHER DEVICES OR PANELS FOR REMOVING CONTROLLER COVER
1-13/16 (46)
1-5/16 (33)
DE-CLUTCH LEVER
3-3/4 (95)
MAINTAIN A MINIMUM DISTANCE OF 4 IN (100 MM) FROM OTHER DEVICES OR PANELS FOR ATTACHING PNEUMATIC AIR FLOW TUBING
60
4-1/16 (103)
CCW
CW
45
3-5/8 (92)
CW
CCW
45
1
(25)
60
1-13/16
(46)
5-7/8 (149)
Fig. 2. W7751H mounting dimensions in in. (mm).
The W7751H assembly is field mounted to the VAV box damper shaft, the same as used for a typical actuator. The actuator on the W7751H opens or closes a damper by driving the damper shaft in either the counterclockwise (CCW) or clockwise (CW) direction. The actuator has a mounting tab on the bottom for securing to a VAV box damper. The mounting tab is accessible through a hole in the controller with its cover removed (see Fig. 3). The tab is sized for a 1/4 in. (6 mm) screw or pin (not included).
The controller enclosure on the W7751H is constructed of a sheet metal housing and a plastic snap-on cover. Controller wiring on the W7751H is terminated to screw terminal blocks located under the snap-on cover. See Wiring section. The sheet metal housing has two 1/2 inch (13 mm) knockouts (see Fig. 2) compatible with 1/2 inch (13 mm) or 3/4 inch (19 mm) conduit.
NOTE: The assembly is intended only for mounting to a
horizontal shaft.
3-3/4
(95)
2-1/8
(54)
3/4
(19)
DE-CLUTCH LEVER
1-15/16 (49)
3/4
(19)
M10523
The W7751H actuator is shipped in the fully clockwise (CW) position (90 degree). The W7751H Assembly must be mounted to a horizontal damper shaft to assure proper heat dissipation from the controller housing. Mount the W7751H so that the actuator is parallel with the VAV box damper housing. In general, it is recommended that a washer or spacer be added between the VAV box damper housing and the actuator mounting tab to keep them parallel. See Fig. 4.
CAUTION
Equipment Damage Hazard. Mounting actuator unevenly with damper housing can damage actuator.
Mount actuator flush with damper housing or add spacer between mounting tab and damper box housing. (See Fig. 4.)
95-7553—04 2
EXCEL 10 W7751H SMART VAV ACTUATOR
A
A
CW
CCW
60
CW
45
PULL TOP OF COVER OUT, THEN DOWN, FOR REMOVAL
CCW
45
60
CIRCUIT BOARD TERMINAL BLOCKS
60
CW
45
CCW
CW
60
CCW
45
MOUNTING TAB
M10000
Fig. 3. Cover removal and mounting tab/terminal block access.
3. The direction the damper shaft rotates to open the
damper (CW or CCW), see Fig. 5.
1MM (1/32 IN.)
4. The damper opening angle (45, 60, or 90 degrees).
TYPE A DAMPER
IR
FLOW
CW TO OPEN, CCW TO CLOSE
TYPE B DAMPER
IR
FLOW
M2067B
1MM
Fig. 5. Determining rotation direction (CW or CCW)
(1/32 IN.)
M20884
Fig. 4. Mounting W7751H to VAV box damper housing
when actuator is not parallel to VAV box damper housing.
Before mounting the W7751H onto the VAV box damper shaft, determine the following:
1. The damper shaft diameter, 3/8 to 1/2 in. (10 to 13 mm).
2. If the length of the VAV box damper shaft is less than
1-3/8 in. (35 mm), use the Short Shaft Adapter Kit (not
If damper shaft diameter is 3/8 inch (10 mm) round or square, use part 201391 Shaft Adapter (shipped with the W7751H Smart VAV Actuator). Ensure it is placed opposite set screws. See Fig. 6. The adapter centers a 3/8 in. (10 mm) shaft in the hub. Failure to use the adapter on a 3/8 in. (10 mm) shaft causes the mounting tab to loosen. A 1/2 in. (13 mm) shaft does not require the use of the adapter.
CCW TO OPEN, CW TO CLOSE
for damper opening.
included), part no. 4074EVK.
3 95-7553—04
EXCEL 10 W7751H SMART VAV ACTUATOR
SHAFT ADAPTER
M2064
Fig. 6. Use Damper Shaft Adapter for 3/8 in. (10 mm)
diameter round or square damper shafts.
The W7751H is shipped with the actuator rotated in the fully clockwise (CW) position. The installation procedure varies depending on the damper direction and angle:
1. If the damper rotates clockwise (CW) to open, and the angle of the damper open to closed is 90 degrees, manually open the damper fully to the clockwise direction and mount the W7751H to the VAV damper box and shaft. Tighten the Allen set screws. The part no. 201614 Range Stop Pin, which is shipped with the W7751H Smart VAV Actuator, is unnecessary. When the W7751H closes, the damper rotates CCW 90 degrees to fully close.
2. If the damper rotates clockwise (CW) to open, and the angle of the damper open to closed is 45 or 60 degrees, manually open the damper fully to the clockwise direction and mount the W7751H to the VAV damper box and shaft. Tighten the Allen set screws. Insert the part no. 201614 Range Stop Pin, which is shipped with the W7751H Smart VAV Actuator, in either the 45 or 60 degree CCW slot, whichever applies (see Fig. 7). The range stop pin must go all the way through the housing. The pin can only be installed in the CCW slots when the actuator is in the CW position. When the W7751H closes, the damper rotates CCW either 45 or 60 degrees to fully close.
3. If the damper rotates counterclockwise (CCW) to open, and the angle of the damper open to closed is 90 degrees, manually close the damper fully to the clockwise direction and mount the W7751H to the damper box and shaft. Tighten the Allen set screws. The part no. 201614 Range Stop Pin, which is shipped with the W7751H Smart VAV Actuator, is unnecessary. When the W7751H opens, the damper rotates CCW 90 degrees to fully open.
NOTE: Be aware that the damper is closed. Until the
W7751H is powered and the damper is driven open, starting the fan system with all the VAV box dampers closed can cause duct over­pressurization and damage.
4. If the damper rotates counterclockwise (CCW) to open, and the angle of the damper open to closed is 45 or 60 degrees, see the following NOTE.
NOTE: Special precautions must be taken for this
application. Mount the W7751H to the damper box. (Do not tighten the Allen set screws yet). Before the part no. 201614 Range Stop Pin, which is shipped with the W7751H Smart VAV Actuator, can be inserted in either the 45 or 60
degree CW slot, the damper actuator must be driven fully open (CCW). To do this, the controller on the W7751H must be wired, powered, and connected to the portable PC via the Serial LonTalk
®
Adapter (SLTA). The SLTA connects to the controller on the W7751H via the jack for Network Access on T7770 Wall Module or by the B-Port on the Q7750A Zone Manager. From E-Vision Software, drive the actuator on the W7751H fully CCW, and insert the range stop pin in either the 45 or 60 degree CW slot, whichever applies (see Fig. 7). The range stop pin must go all the way through the housing. The pin can only be installed in the CW slots when the actuator is in the CCW position. (Disconnect the portable PC once programming has been completed.) Manually open the damper shaft fully (CCW) and then tighten the Allen set screws. When the W7751H closes, the damper will rotate CW 45 or 60 degrees to fully close.
CW
60
RANGE STOP PIN
ACTUATOR PLATES
CCW
CW
45
CCW
60
45
M10002
Fig. 7. Properly inserting range stop pin.
The Honeywell Software Tool’s (miscellaneous parameter for rotation direction) defaults to CW to Open, which applies to the damper direction and angle in items 1 and 2 above. The parameter must be changed to CCW to Open if the damper shaft rotates in this direction, which applies to the damper direction and angle in items 3 and 4 above.
IMPORTANT
It is advisable to leave the dampers in an open position after W7751H installation to avoid the possibility of overpressurizing the ductwork on fan startup. Use the De-clutch lever (see Fig. 2 for De-clutch lever location) to open the box damper on W7751H controllers that are powered down, to prevent overpressurization in the ductwork on fan startup. To use the De-clutch lever, press and hold the lever in the direction of the arrow (this disengages the motor). Turn the damper shaft until the damper is open and release the lever. When power is restored to the W7751H controller, the controller synchronizes the damper actuator so that the damper is in the correct position upon startup.
When a range stop pin is used with a field-added auxiliary switch, the tab on top of the range stop pin must point inward toward the VAV damper box shaft. See Fig. 11. This allows clearance for the auxiliary switch housing. To remove the pin, pry it up with a flathead screwdriver. See Fig. 8.
95-7553—04 4
EXCEL 10 W7751H SMART VAV ACTUATOR
IMPORTANT
The minimum position set screw on the actuator is not available on the W7751H device.
SCREWDRIVER
M2065
Fig. 8. Lifting a range stop pin out of its slot.

Piping

Air flow Pickup
Connect the air flow pickup to the two connectors on the controller of the W7751H. See Fig. 9.
CW
AIRFLOW DP PICKUP
CCW
– LO
+ HI
60
CW
45
45
CCW
60
AIRFLOW DIRECTION
To prevent VAV air flow connector breakage, use
caution when removing tubing from it. Always pull straight away from connector; never remove by pulling at an angle.

Wiring

All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams.
NOTES:
For multiple controllers operating from a single
transformer, the same side of the transformer secondary must be connected to the same input terminal in each controller and the ground terminals (3 on the W7751H, 28 on the W7751B, and 32 on the W7751D,F) must be connected to a verified earth ground for each controller in the group. See Fig. 10. (Controller configurations are not necessarily limited to three devices, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer. See System Engineering form 74-2949 for power wiring recommendations.)
All loads on an Excel 10 Controller must be
powered by a single transformer.
Keep the earth ground connection (terminal 3)
wire run as short as possible. Refer to Fig. 16.
—Do not connect the analog ground terminal (5) to
earth ground. Refer to Fig. 16.
Power
The 24 Vac power from an energy limited Class II Power Source must be provided to each Smart VAV Actuator. To conform to Class II restrictions, transformers must not be larger than 100 VA. The maximum current draw at 24 Vac is
1.25A.
M10003
Fig. 9. Smart VAV Actuator air flow pickup connections.
NOTES:
Use 1/4 in. (6 mm) outside diameter with 0.040 in.
(1 mm) wall thickness plenum rated 1219 FR (94V-2) pneumatic tubing.
Always use a fresh cut on the end of the tubing
that connects to the air flow pickups and the connectors on the VAV controllers.
Connect the high pressure or upstream tube to the plastic restrictor labeled (+ HI) or P1 and the low pressure or downstream tube to the restrictor labeled (- LO) or P2. See labeling in Fig. 9.
NOTES:
If controllers are mounted in unusually dusty or
dirty environments, a 5-micron disposable air filter is recommended for the high pressure line (marked as +) connected to the air flow pickup.
When using twin tubing from pickup, split pickup
tubing a short length to accommodate connections.
Tubing from air flow pickup to VAV controller
should not exceed three feet (0.914m). Lengths longer than this can degrade flow sensing accuracy.
IMPORTANT
— Power must be off prior to connecting to or removing
connections from output terminals 9 and 10.
— Use the heaviest gauge wire available, up to
14 AWG (2.0 mm (1.0 mm
2
), for all power and earth ground wiring. For
2
) with a minimum of 18 AWG
nonplenum, open areas, run cables exposed (or in conduit, if required).
— If the W7751H Smart VAV Actuator is used on
Heating and Cooling Equipment (UL 1995, US only) and the transformer primary power is more
than 150 volts, connect the transformer secondary to earth ground, see Fig. 10.
NOTE: Maintain a three-inch (76 millimeter) separation
between Triac outputs and L
ONWORKS® Bus wiring
throughout installation.
Auxiliary Switches
The 201052A,B,C Auxiliary Switch can be used with the W7751H. It allows for control of equipment external to the actuator (for example, electric reheat coils or fan) at an adjustable point in the stroke (from 0 to 90 degrees) of the actuator. The 201052 Switch is field-added. Self-tapping Phillips head screws are included with the switch. The switch can be mounted only one way (see Fig. 11) with the switch contacts pointed to the top of the actuator.
5 95-7553—04
EXCEL 10 W7751H SMART VAV ACTUATOR
W7751B
28
EARTH GROUND
9
10
W7751D,F
32
EARTH GROUND
PROCEDURE
1. Determine desired switching action (i.e, if switch energizing is to occur during CW or CCW rotation). With switch cam as shown in Fig. 12, the normally closed contact opens in CCW rotation. The normally open contact closes. Conversely, with switch cam as shown in Fig. 13, the normally closed contact opens during CW rotation and the normally open contact closes.
W7751H OR J
COM
NO NC
CCW
24V
COM
24V
24 VAC
COM
EARTH GROUND
24V
COM
123
EARTH GROUND
1
1234
120/240
VAC
TRANSFORMER
1 IF THE W7751 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND ONE SIDE OF TRANSFORMER SECONDARY.
Fig. 10. Power wiring for multiple controllers.
RANGE STOP PIN POINTED TOWARD SHAFT
90
75
60
45
30
15
0
201052 AUXILARY SWITCH
N C
COM
N O
M2160
Fig. 12. Switching configuration for CCW rotation
(top view).
COM
NO NC
CW
M10524A
M2161
Fig. 13. Switching configuration for CW rotation
(top view).
2. Align switch hub with actuator set screws. Mount switch
on actuator and tighten the three captive screws.
3. Connect controller with laptop PC. To do this, the controller on the W7751H must be wired, powered, and connected to the portable PC via the SLTA. The SLTA connects to the controller on the W7751H via Network Access Jack on the T7770 Wall Module or by B-Port on the Q7750A Zone Manager. From E-Vision Software, drive the W7751H actuator and halt the motion at the desired position for switch operation.
M10005
Fig. 11. 201052 Auxiliary Switch mounted on W7751H.
NOTES:
If a range stop pin is used, it must be pointing
inward toward the shaft (see Fig. 11) to allow clearance for the auxiliary switch.
Each switch is independently adjustable in two-
degree increments to any point within the travel of the actuator. Switches have a fixed differential of approximately three angular degrees.
95-7553—04 6
NOTE: When installed, angular position indicator on
the switch face moves from 90 to 0 degrees during CCW motion and from 0 to 90 degrees during CW motion.
4. Once finished programming, disconnect the portable PC.
5. With a screwdriver, move the cam inside the switch assembly to the appropriate position, remembering cam travel direction for switching purposes (see Fig. 14) when turning switch on or off. Monitor switch closure with ohmmeter for a continuity check. Normally closed contact should measure zero ohms and normally open contact should measure infinite ohms when switch is not activated. The opposite is true when switch is activated.
EXCEL 10 W7751H SMART VAV ACTUATOR
SWITCH CAMS
M2076A
Fig. 14. Auxiliary switch cam adjustment.
NOTE: For 2 or 3 switch models, cams align with their
respective switches and are individually set using the same procedure described above.
6. Ensure switch activation at the desired degree of stroke by commanding the actuator to both fully open and fully closed; see step 3.
NOTE: Switches can also be preset prior to actuator
installation if angular switch position is known.
Communications
Refer to LONWORKS® Bus Wiring Guidelines, form 74-8565, for complete description of L rules.f
If a longer L
ONWORKS® Bus network is required, a Q7740A
2-way or Q7740B 4-way Repeater can be added to extend L
ONWORKS® Bus length, only if this is an Energy
Management (PAZX) Bus.
IMPORTANT
The Q7740A,B Repeaters cannot be used in smoke control applications.
ONWORKS® Bus network topology
• Approved cable type is Level IV 22 AWG (0.34 mm
2
) plenum or non-plenum rated unshielded, twisted pair, solid conductor wire: — For nonplenum areas, use CMP listed cable. — In plenum areas, use CMP listed cable.
• Do not bundle output wires with sensor, digital input or L
ONWORKS® Bus wires.
• Ensure that neither L
ONWORKS® Bus wire is grounded.
• In noisy (high EMI) environments, avoid wire runs parallel to noisy power cables, motor control centers, or lines containing lighting dimmer switches. Keep at least 3 in. (76 mm) of separation between noisy lines and L
ONWORKS® Bus cable.
• Do not use different wire types or gauges on the same LONWORKS® Bus segment: — Step changes in line impedance characteristics cause
unpredictable reflections on the L
ONWORKS® Bus.
Wiring Details
Wire to the terminal blocks as follows:
1. Strip 3/16 in. (5 mm) insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
NOTE: With the exception of 14 AWG (2.0 mm
inserting two or more wires into one terminal location, twist wires together before inserting them. See Fig. 15. Deviation from this rule can result in improper electrical contact.
The controller on the W7751H has the terminal arrangement shown in Fig. 16. Fig. 16 through 21 provide detailed wiring diagrams for the W7751H. Refer to installation diagrams for specific wiring.
NOTE: Ensure Configuration DIP Switch is set as shown in
Fig. 19. Switches 1 through 3 set ML7984B Valve Actuator timing to match W7751H outputs (0.1 sec. minimum with maximum time of 25.6 sec.). Switch 4 determines actuator action (Off = Direct Acting, On = Reverse Acting).
2
), if
A Q7751A Router can only be added to an Energy Management Bus to partition system into two segments (effectively doubling L
ONWORKS® Bus length). Only one
router is allowed with each Excel 10 Zone Manager (or Excel 15 Building Manager), and each network segment can have a maximum of one repeater.
Pull the cable to each device on the L
ONWORKS® Bus and
connect to communication terminals 11 and 12 (W7751H).
IMPORTANT
Screw type terminal blocks are designed to accept no more than one 14 AWG (2.0 mm Multiple 14 AWG (2.0 mm
2
) wires can be connected
2
) conductor.
with a wire nut. Include a pigtail with this wire group and attach the pigtail to the individual terminal block.
Notes on LonWorks® Bus Communications Wiring:
• All field wiring must conform to local codes and ordinances (or as specified on the installation drawings).
1.
1/2
(13)
STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
2.
TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
CONTROLLER OR WALL MODULE E-BUS CONNECTOR TERMINALS
3.
CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
M11413
Fig. 15. Attaching two or more wires at terminal blocks.
7 95-7553—04
EXCEL 10 W7751H SMART VAV ACTUATOR
7 69 8 54321
LED
SET PT
GND
BYPASS
SENSOR
AIR FLOW DP PICKUP
T7770C WALL MODULE
AIR FLOW DIRECTION
LOW
MICROBRIDGE
HI
24 VAC
DP SENSOR
NOT EARTH GROUND
BYPASS
SENSOR
GND
SET PT
COM
24 VAC
EARTH
12345678 9101112
2
WALL MODULE
E-BUS
E-BUS
W7751H
TRIAC EQUIVALENT CIRCUIT
LED
OUT 1
COMM OUT
2
JACK FOR E-BUS NETWORK ACCESS
E-BUS
OUT 2
COMM IN
COMM OUT
2
7 69 8 54321
LED
SET PT
GND
BYPASS
SENSOR
E-BUS
E-BUS
JACK FOR
T7770C WALL
AIR FLOW DP PICKUP
LOW
MICROBRIDGE
HI
2
24 VAC
DP SENSOR
COM
24 VAC
12345678 9101112
2
MODULE
AIR FLOW DIRECTION
NOT EARTH GROUND
SENSOR
GND
SET PT
EARTH
WALL MODULE
BYPASS
W7751H
LED
E-BUS NETWORK ACCESS
TRIAC EQUIVALENT CIRCUIT
E-BUS
OUT 2
OUT 1
2
COMM IN
1 EARTH GROUND
NOTE: LOAD POWER WIRE IS CONNECTED TO TERMINAL 1.
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.0 MM WITH A MINIMUM OF 18 AWG (1.0 MM
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK.
OPEN SIGNAL
COM
STEM UP
M6410 SERIES 60 VALVE ACTUATOR
TWO OR THREE-WAY VALVE
2
), FOR EARTH GROUND WIRE.
STEM DOWN
CLOSED SIGNAL
2
)
M10525
Fig. 16. W7751H modulating reheat valve wiring diagram.
(For Note 2 instructions, refer to Fig. 15.)
95-7553—04 8
1
EARTH GROUND
NOTE: LOAD POWER WIRE IS CONNECTED TO TERMINAL 1.
LINE POWER
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.0 MM WITH A MINIMUM OF 18 AWG (1.0 MM
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK.
STAGE 1
2
), FOR EARTH GROUND WIRE.
STAGE 2
CONTACTORS 24 VAC ONLY
Fig. 17. W7751H 2-stage reheat wiring diagram.
(For Note 2 instructions, refer to Fig. 15.)
2
)
M10526
EXCEL 10 W7751H SMART VAV ACTUATOR
AIR FLOW DP PICKUP
LOW
HI
T7770D WALL MODULE
AIR FLOW DIRECTION
MICROBRIDGE DP SENSOR
NOT EARTH GROUND
7 69 8 54321
LED
SET PT
GND
BYPASS
SENSOR
E-BUS
W7751H
2
E-BUS
JACK FOR E-BUS NETWORK ACCESS
TRIAC EQUIVALENT CIRCUIT
COMM OUT

CHECKOUT

W7751H Checkout

Step 1. Wiring Connections
Inspect all wiring connections at the W7751H and the T7770 terminals, and verify compliance with installation diagrams. If any wiring changes are required, first be sure to remove power from the controller before starting work. Pay particular attention to: — 24 Vac power connections. Verify multiple controllers being
powered by the same transformer are wired with the transformer secondary connected to the same input terminal numbers on each W7751. See Fig. 10. (Controller configurations are not necessarily limited to three devices, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer. See System Engineering form 74-2949 for power wiring recommendations.)
— Controller wiring. Be sure that each controller is wired
(terminal 3 on the W7751H, 28 on the W7751B, and 32 on the W7751D,F) to a verified earth ground using a wire run as short as possible with the heaviest gauge wire available, up to 14 AWG (2.0 mm (1.0 mm
2
) for each controller in the group. See Fig. 10.
— Verify Triac wiring to external devices uses the proper load
power/24 Vac Hot terminal (terminal 1 on the W7751H).
2
) with a minimum of 18 AWG
BYPASS
SENSOR
GND
SET PT
COM
24 VAC
EARTH
12345678 9101112
2
24 VAC
1
EARTH
GROUND
WALL MODULE
2
LED
WIRED FOR MODULATING OR STAGED REHEAT. SEE FIG. 17 OR FIG. 18.
OUT 2
OUT 1
C7770A AIR TEMPERATURE SENSOR
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.0 MM WITH A MINIMUM OF 18 AWG (1.0 MM
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK.
3
NOTE: AIR TEMPERATURE SENSOR CANNOT BE USED WITH EITHER THE T7750B OR C WALL MODULE.
Fig. 18. W7751H discharge air sensing
(For Note 2 instructions, refer to Fig. 15.)
2
), FOR EARTH GROUND WIRE.
E-BUS
COMM IN
2
)
2
M10527A
NOTE: All wiring must comply with applicable electrical
codes and ordinances. Refer to installation diagrams for specific wiring.
Verify Termination Module Placement
The installation wiring diagrams should indicate the locations for placement of Termination Module(s). Refer to the
LONWORKS® Bus Wiring Guidelines, form 74-2865, and the Excel 10 FTT Termination Module Installation Instructions, form 95-7554. Correct placement of the termination module(s)
is required for proper L
ONWORKS® Bus communications.
Step 2. Startup
Broadcasting the Service Message
The Service Message allows a device on the LONWORKS® Bus to be positively identified. The Service Message contains the controller neuron ID number and, therefore, can be used to confirm the physical location of a particular Excel 10 in building.
There are three methods of broadcasting the Service Message from an Excel 10 W7751H Controller:
1. Physical service pin on controller: a. Remove the plastic cover and the white button is
located next to the terminal strip.
b. Momentarily pressing this service pin broadcasts
the Service Message on the network.
2. Using the wall module bypass pushbutton: a. By pressing the wall module bypass/override button
for more than four seconds, the controller sends the Service Message.
b. This functionality is supported in firmware version
1.2.15 or higher.
9 95-7553—04
EXCEL 10 W7751H SMART VAV ACTUATOR
NOTE: During item 2, the occupancy override state of
the controller changes based on how long the bypass/override button is depressed. For example, if the button is pressed for 6 sec., the node sends the Service Pin Message, AND the node enters Continuous Unocc mode. To clear Continuous Unocc mode, the button must be pressed momentarily.
3. The following method is only supported on E-Vision and L
ONSPEC™:
a. When an Assign ID command is issued from the
Honeywell Software listed, the node enters the SERVICE_MESSAGE mode for five minutes.
b. In this mode, pressing the bypass/override button
causes the Service Message to be broadcast on the
network. c. All other functions are normal in this mode. d. If the bypass/override button is not available, short-
ing the controller Bypass Input terminals (on
W7751H short terminals 5 and 7) broadcasts the
Service Message.
Alarms
The commissioning tool is used to perform the ID Assignment task. Once the ID Assignment and commissioning has been done, check the controller status LED to determine if there are any alarms.
W7751 Controller Status LED
The LED on the front of a W7751H Controller (located just under the plastic cover), provides a visual indication of the status of the device. When the W7751H receives power, the LED appears in one of the following allowable states:
1. Off—no power to the processor.
2. Continuous on—processor is in initialized state.
3. Slow blink—controlling, normal state.
4. Fast blink—when the Excel 10 VAV Controller has an
alarm condition. When an Excel 10 has an alarm condition, it reports it to the central node on the L Controller variables, AlarmLogX, where X is 1 through 5, that store the last five alarms to occur in the controller, are available. These points can be viewed through workstation software. Refer to the VAV System Engineering Guide form, 74-2949 Table 12 for a description of the Excel 10 Alarms.
NOTE: The node can be reset by switching the node to
MANUAL and then to the normal operating mode.
ONWORKS® Bus. Also, the Excel 10 VAV
1
24 VAC
REHEAT VALVE
ACTUATOR
W7751H
NOT EARTH GROUND
BYPASS
SENSOR
GND
SET PT
COM
24 VAC
EARTH
12345678 9101112
1
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN; REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK.
WALL MODULE
LED
TRIAC EQUIVALENT CIRCUIT
E-BUS
OUT 2
OUT 1
Fig. 19. W7751H to PWM Valve Actuator.
PWM VALVE ACTUATOR
PWM OUTPUT
24 (N)
24 (H)
T6 T5 C B W R
2
FROM CNTRL
PWM (H 24 VAC)
PWM VALVE ACTUATOR
24 (N)
24 (H)
T6 T5 C B W R
2
CONFIGURATION DIP SWITCHES
LOCATED ADJACENT TO THE INPUT
ML7984B
ML7984B
PWM OUTPUT
FROM CNTRL
PWM (H 24 VAC)
PERIPHERAL REHEAT
VALVE ACTUATOR
1234
ON
OFF
TERMINAL BLOCK ON ML7948B
M10528
95-7553—04 10
EXCEL 10 W7751H SMART VAV ACTUATOR
SERIES OR
W7751H
TRIAC
NOT EARTH GROUND
BYPASS
SENSOR
GND
SET PT
COM
24 VAC
EARTH
12345678 9101112
1
24 VAC
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN; REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.
1
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK.
WALL MODULE
LED
EQUIVALENT CIRCUIT
E-BUS
OUT 2
OUT 1
CONTACTOR
(24 VAC)
PARALLEL
FAN
PWM VALVE ACTUATOR
24 (N)
?24 (H)
T6 T5 C B W R
2
Fig. 20. W7751H to PWM Valve Actuator and series or parallel fan.
ML7984B
PWM OUTPUT
FROM CNTRL
PWM (H 24 VAC)
REHEAT
VALV E
ACTUATOR
M10529
W7751H
NOT EARTH GROUND
BYPASS
SENSOR
GND
SET PT
COM
24 VAC
EARTH
12345678 9101112
24 VAC
1
REVERSE WIRES (INCREASE/DECREASE) TO REVERSE ACTION (DIRECT/REVERSE).
2
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN; REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.
3
OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER.
4
USE 1/4 IN. (6 MM) MINIMUM PNEUMATIC TUBING. BRANCH LINE MUST BE 6 FT (1.8M) OR LONGER.
WALL MODULE
LED
TRIAC EQUIVALENT CIRCUIT
E-BUS
OUT 2
OUT 1
MMC325 PNEUMATIC TRANSDUCER
24 (N)
24 (N)
2
?24 (H)
24 (H)
INCREASE
3
Fig. 21. W7751H to pneumatic transducer.
M
B
DECREASE
1
PNEUMATIC VALV E
M
4
M10530
11 95-7553—04
EXCEL 10 W7751H SMART VAV ACTUATOR
T7770C or D Wall Module Override LED
The remote override LED, located on either the T7770C or T7770D Wall Module will display the Manual Override mode of the controller. The modes are:
1. LED = Off. No override active.
2. LED = Continuously On. Bypass mode (timed Occupied
override).
3. LED = One flash per second. Continuous Unoccupied override.
4. LED = Two flashes per second. Remote only, continuous Occupied override.
Step 3. I/O Tests
The controller can be configured using the LONSPEC™, or E-Vision PC configuration tool. Once this is done, the W7751H can be commanded to MANUAL mode, and each output and input can be exercised/viewed to verify proper wiring connections and equipment operation.
W7751H Actuator Checkout
To check out the actuator on the W7751H, determine the direction the damper shaft moves to open the damper (CW or CCW). See Fig. 5.
NOTE: Devices for use only if used for Energy Management:
Q7740A,B and Q7751A.
Devices for use on an Energy Management and/or Smoke Control: — 14507287 Series Power Supplies, — W7751B2010, W7751D2016, W7751F2011,
— W7751H2025 Series 9, — W7761A2010, — Q7750, — Q9200, — XFL521, XFL522, XFL523, XFL524, — XL500, —XLINK.
Connect the controller with the laptop PC. To do this, the controller on the W7751H must be wired, powered, and connected to the portable PC via the SLTA. The SLTA connects to the controller on the W7751H via the Jack for Network Access on T7770 Wall Modules or by the B-Port on the Q7750A Zone Manager. From L Software, drive the actuator on the W7751H open and then closed. Observe the operation of the actuator; if the damper is closed, it should begin to open. If the damper is open, it should begin to close.
NOTE: Once finished programming, disconnect the portable
PC.
If no movement is observed, check to see if 24 Vac is present at the controller on the W7751H. With proper wiring, 24 Vac present, and proper commands from the software, the actuator should operate properly. If not, the W7751H Smart VAV Actuator may need to be replaced.
ONSPEC™, or E-Vision
Step 4. Verify Sequences of Operation
For the detailed descriptions of the sequences of operation, see the Excel 10 VAV System Engineering form 74-2949.
LONWORKS® and LONTALK® are registered trademarks of Echelon® Corporation.
LONSPEC™ is a trademark of Echelon® Corporation.