LonTalk, LonUsers, LonPoint, Neuron, 3120, 3150, the Echelon logo, the LONMARK
logo, and the LonUsers logo are trademarks of Echelon Corporation registered in
the United States and other countries. LonLink, LonResponse, LonSupport, and
LonMaker are trademarks of Echelon Corporation.
DEVICE ASSEMBLY AND SYSTEM INSTALLATION................................................................................................................... 7
Assembly of Controller Housing................................................................................ 7
Control Cabinet Installation....................................................................................... 8
Meaning of Control Lamp ......................................................................................... 9
Terminal Assignment Overview for Excel 100C ...................................................... 10
General Remarks about Electrical Connections ......................................................11
U.S. SPECIFICATIONS ................................................................................................................................................................36
Electrical Connection of Sensors.............................................................................36
EUROPEAN SPECIFICATIONS ...................................................................................................................................................40
Electrical Connection of Sensors.............................................................................40
The changes listed below show the revisions that have been made in comparison to the previous revision.
Page
Changes
26
44
NOTE: The Excel 100 has been developed to meet control requirements worldwide. Some referenced applications /
accessories have been developed to meet specific regional requirements and may not be available or applicable in all
locations.
The adapter cables have been changed.
The ordering information for repeaters with/without housing has been changed.
5 EN1R-0144GE51 R1109
EXCEL 100C INSTALLATION INSTRUCTIONS
INTRODUCTION
General Safety Instructions
Assembly by trained personnel
CAUTION
Assembly must be completed by trained personnel.
Persons who are not trained and authorized to carry out heating and electrical
installation may not carry out assembly work even if this appears possible on the
basis of the instructions.
Install with power off
CAUTION
All assembly work must be completed with power off.
If some parts of the system are nonfunctional or have not yet been received,
assembly may proceed only if power is disconnected from those assemblies. Simply
switching off the unit is insufficient.
Observe regulations
IMPORTANT
The regulations VDE 0800, VDE 0100, U.S. National Electric Code NEC or
others that replace them, absolutely must be observed.
Follow instructions step by step Follow instructions in accordance with the progress of the assembly step by step.
Skip sections only when requested to do so in the text.
Technical Requirements
All devices ready? Assembly can start only if all system components have been installed and are ready
to be operated and the control and measuring sensor cables have been connected
to the control cabinet.
All cables laid? All cables must be clearly marked and laid with appropriate auxiliary accessories
(cable ducts, cable ties).
Delivery complete? The delivery of all system parts must be complete.
Auxiliary Devices
Use documentation
IMPORTANT
Install all devices according to the documentation supplied with the
equipment.
The instructions are designed in such a way that they provide a suggestion for all
foreseeable situations. Should you be confronted with problem during assembly,
please contact your appropriate dealership (see last page). If there is no one to deal
with your query at that particular moment, please contact technical sales support at
the factory.
EN1R-0144GE51 R1109 6
EXCEL 100C INSTALLATION INSTRUCTIONS
DEVICE ASSEMBLY AND SYSTEM INSTALLATION
1
3
5
7
2
4
6
8
Assembly of Controller
Housing
1Open cover
2 Remove tool
3 Remove screw
4 Loosen housing cover from
base
5 Loosen front right
6Loosen rear
7Loosen left
8Lift housing off base
CB-0700-Mb
7 EN1R-0144GE51 R1109
EXCEL 100C INSTALLATION INSTRUCTIONS
Control Cabinet Installation
XD505
XD508
middle
XD508
beg./end
IMPORTANT
The maximum ambient temperature
for the Excel 100C depends on the
mounting orientation:
switch on the back of the
housing according to the
system configuration
(see page 14 for details).
6Fit housing
Make sure it is straight
EN1R-0144GE51 R1109 8
7Connect operating device
(see pages 24 and up)
IMPORTANT
Set the port selector switch (left to the
sub-D port) according to whether the
front port or the rear terminals should
be active (see page 30 for details).
Front port Rear terminals
active active
b
1
0
7
0
8 Close cover
B
C
NOTE: Cover cannot be mounted
with front connector plugged.
Meaning of Control Lamp
T
L4 L5 L6 L7
RESET
BUTTON
PORT
SELECTOR
SWITCH
FRONT
SERIAL
POR
EXCEL 100C INSTALLATION INSTRUCTIONS
Table 1. Control Lamps and their meanings
LED color status/meaning
L1 YELLOW Lit: Main voltage is present
L2 GREEN Lit: Program is running
Dark: Program is stopped
L3 RED Lit continuously: ALARM; program is stopped
L4 YELLOW Lit : Controller is transmitting via B-port
L5 YELLOW Lit: Controller is receiving via B-port
L6 YELLOW Lit: Transmission via C-bus to system bus interface
L7 YELLOW Lit: Reception via C-bus from system bus interface
L8, L9, L10, and L11 are for future use
NOTE: L4 to L11 are visible only if the cover plate has been removed.
IMPORTANT
The RESET button reboots the controller’s CPU. All plantspecific data held in the controller will be lost after a reboot.
CB-0603-E1
See section "Setting the Port Selector Switch" on page 30 for details on
setting the port selector switch and serial port.
Before rebooting, it is highly recommended that you save the
current application to the flash EPROM.
9 EN1R-0144GE51 R1109
EXCEL 100C INSTALLATION INSTRUCTIONS
{
{
Terminal Assignment Overview for Excel 100C
ANALOG
INPUTS
DIGITAL
INPUTS
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
1
2
3
4
5
6
7
8
9
AI 1 xx0101
AI 2 xx0102
AI 3 xx0103
AI 4 xx0104
AI 5 xx0105
AI 6 xx0106
AI 7 xx0107
AI 8 xx0108
AI 9 xx0201
AI 10 xx0202
AI 11 xx0203
AI 12 xx0204
DI 1 xx0301
DI 2 xx0302
DI 3 xx0303
DI 4 xx0304
DI 5 xx0305
DI 5 xx0305
shield
T x D
R x D
+5 V (Xi582), RTS (modem)
CTS
not used
GND
DTR
DCD
not used
Output voltage 24 V / 300 mA is
protected against short-circuiting.
After short-circuiting, it takes time
(approx. 60 sec.) for voltage to
recover.
24V relay module
(MCD3/MCE3, only!)
reserved
C+
system bus
C-
IMPORTANT
Do not connect system bus shield to earth. Use terminals 33 and 36.
NOTE: Use terminals 65 and 66 for relay modules MCD 3 or MCE 3 only.
Terminals 65 and 66 provide a pulsed 24 Vdc output which is not suitable
to connect direct relays.
Do not use reference voltage 10 V (terminal 67, 68) to supply other
devices.
AO 1 xx0401
AO 2 xx0402
AO 3 xx0403
AO 4 xx0404
AO 5 xx0405
AO 6 xx0406
AO 7 xx0407
AO 8 xx0408
AO 9 xx0501
AO 10 xx0502
AO 11 xx0503
AO 12 xx0504
DI 7 xx0307
DI 8 xx0308
DI 9 xx0309
DI 10 xx0310
DI 11 xx0311
DI 12 xx0312
alarm
(not used)
transformer
REF.
common
37
38
39
40
41
42
OUTPUTS
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
-
65
+
66
+
67
+
68
69
70
71
72
21-28 Vdc
ANALOG
DIGITAL
INPUTS
24 V_
300 mA
10 V
10 mA
24 Vac
+/-20%
or
EN1R-0144GE51 R1109 10
General Remarks about Electrical Connections
Observe all general VDE, NEC and local wiring regulations when making electrical
connections.
CAUTION
Electrical connection work is to be carried out by a qualified technician.
CAUTION
Using free terminals as support terminals can cause system damage.
Free terminals in the base plate must not be used as wiring support points under
any circumstances (danger of damage)! The electrical connection is to be made at
the base plate. The appropriate connection diagrams are on pages 10 and 11.
Further wiring diagrams are contained in the circuit diagrams.
IMPORTANT
Do not disconnect the Excel 100C controller from power supply for more
than 72 hours.
The Excel 100C is equipped with a gold capacitor buffer that holds the
RAM data and supplies the real-time clock for 72 hours in case of a power
outage. Beyond this period of time, all RAM data and time information are
lost.
EXCEL 100C INSTALLATION INSTRUCTIONS
Cable Routing
Minimum distance to mains cables:
10 mm (0.4 in.) All signal and output cables (low voltage) should be regarded as communication
circuits in accordance with VDE 0100, VDE 0800 and NEC, it should therefore be
routed separately from line voltage. Minimum distance 10 cm (4 in.) for unshielded
cable. Minimum distance 10 mm (0.4 in.) for shielded cable. Joining sensor cables
should be avoided.
Shielding of Sensor and Actuator Cables
Shielding of sensor and actuator cables with low protective voltages is not
necessary if the general guidelines on cable routing are observed (see "Cable
Routing" on page 11). If, under certain circumstances, the routing guidelines cannot
be observed, shielded cable must always be used.
IMPORTANT
Shielded cables must be grounded on one side only.
The grounding of the shielded cable must be as shown in the diagram.
Shielding on one sideat the control cabinet ground: Shielding of I/O cables
connected to peripherals such as
sensors and actuators must be
grounded at the control cabinet side,
only; this to avoid ground loops.
11 EN1R-0144GE51 R1109
EXCEL 100C INSTALLATION INSTRUCTIONS
Shielding of Data Transmitting Cables (System Bus and Operator Interface)
IMPORTANT
Data transmitting cables must always be shielded to prevent radio
interference.
1. System Bus Cables
Connect shield of system bus cable
on both sides System bus cables must be shielded on both sides at the base plate terminal 33
and 36 of the controller device. Connection to the control cabinet ground or other
ground points is not permitted (see WARNING below)!
To connect remote operators units, ready-made cables are available (XW582,
XW584, XW585) with the shield already connected to the computer module plug
end.
For detailed information on cable types to be used in accordance with regional
requirements, please refer to the U.S. and European Specifications chapters.
System Ground
Primary: Secondary:
RFI Suppression
CB-0236b
WARNING
High voltage
Risk of electrical shock or equipment damage
The controller's system ground must have no connection with the control cabinet
ground!
NOTE: A document providing additional information on system grounding (if
Honeywell actuators are RFI-suppressed as a standard in accordance with
EN 50 081-1/EN 55 022.
demanded) is available via the Honeywell Technical Assistance Center
(TAC) or, for Honeywell employees, on the Docu Server under:
http://web.ge51.honeywell.de/dep/mc/TAC_Tips.
EN1R-0144GE51 R1109 12
Cable Lengths and Cross Sectional Areas
SFO
Cross sectional areas related to cable length
Table 2. Signal types and cross-sectional areas
EXCEL 100C INSTALLATION INSTRUCTIONS
Cabling of Actuator with 24 Vac
Supply and max. 550 ft (170 m)
IMPORTANT
For detailed information on cable types to be used in accordance to regional
requirements, please refer to the U.S. and European Specifications chapters.
PRIMARY
VOLTAGE
TRANSFORMER
type of signal
cross sectional area
300 ft (100 m) 550 ft (170 m) 1300 ft (400 m)
power supply
(24 Vac)
low-current
16 AWG
( 1.5 mm
2
)
14 AWG
( 2.5 mm2)
20 AWG ( 0.5 mm2)
-
signals*
*E.g. for 0-10 V sensors, totalizers, digital inputs, 0…10 V signals for actuators.
The max. length of a signal cable with 24 Vac supply is 550 ft (170 m).
The max. length of a two-wire, 0 to 10 Vdc signal cable is 1,300 ft (400 m).
The secondary side of the transformer must not be connected to earth
ground.
0000056c
24 Vac
24 V
Y
GND
MAX. 550 ft (170 m)
MIN. 14 AWG (2.5 mm )
2
Cabling of Actuator with 24 Vac Supply
from External Transformer and
max. 1,300 ft (400 m) If the distance between the controller and actuator or sensor with 24 Vac supply is
greater than 550 ft (170 m), a separate external transformer for the actuator or
sensor is necessary.
PRIMARY
VOLTAGE
230 Vac
120 Vac
TRANSFORMER
24 Vac
MAX. 1300 ft (400 m)
MIN.20 AWG (0.5 mm )
0 TO 10 Vdc
GND
24 Vac
2
EXTERNAL
TRAN
230 Vac
120 Vac
PRIMARY
VOLTAGE
RMER
00000057c
NOTE: The transformer must be chosen in accordance with specifications listed in
the U.S. and European Specifications chapters.
13 EN1R-0144GE51 R1109
EXCEL 100C INSTALLATION INSTRUCTIONS
a
IMPORTANT
Line Power Supply
The Excel 100C Controller is powered by an external transformer.
PRIMARY:SECONDARY:
230 Vac
120 Vac
24 Vac
+ 2 0 %
- 20 %
9
6
0
0
0
0
0
Transformer requirements for one Excel 100C Controller:
Secondary
Voltage 24 Vac 20% or 21-28 Vdc
Current 1.1 A
Power 15 VA (Excel 100C, only; no MCE/MCD)
25 VA (if fully equipped with MCE/MCD)
The transformer, already installed in the cabinet, can be used to supply several controllers, communication devices, or peripherals (e.g. actuators, etc.) – provided it
delivers sufficient power.
RIN-APU24 is supported.
For detailed information on transformers to be used in accordance to regional
requirements, please refer to the U.S. and European Specifications chapters.
We recommend installing a fuse on the secondary side of the transformer
in order to protect the devices against miswiring.
Standard Transformers
Requirements for standard transformers
Communication
EBI/SymmetrE
XL-ONLINE
C-BUS
Table 3. Requirements for standard transformers
output voltage impedance AC current
24.5 Vac to 25.5 Vac 1.15 Ω max. 2 A
24.5 Vac to 25.5 Vac 0.40 Ω max. 6 A
24.5 Vac to 25.5 Vac 0.17 Ω max. 12 A
Excel devices may communicate in different modes and lines. The principal
communication scheme is shown in the accompanying figure.
EBI/SymmetrE
Excel 100C
OTHER
CONTROLLERS
Modem/ISDN
COMMUNICATION
Modem/ISDN
Excel 500Excel 600
Modem
XI581/582
(providing bus-wide
access to all devices
connected to C-Bus)
EN1R-0144GE51 R1109 14
Excel 100CExcel 100C
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.