LonTalk, LonUsers, LonPoint, Neuron, 3120, 3150, the Echelon logo, the LONMARK
logo, and the LonUsers logo are trademarks of Echelon Corporation registered in
the United States and other countries. LonLink, LonResponse, LonSupport, and
LonMaker are trademarks of Echelon Corporation.
System Overview.......................................................................................................................................................................... 6
List of Datapoint Attributes ......................................................................................39
Time Programs ............................................................................................................................................................................42
Point Alarms ............................................................................................................46
System Alarms ........................................................................................................47
System Alarms Suppression (V. 2.04.xx or higher).............................................51
User Program Alarms ..............................................................................................52
Data Storage ...........................................................................................................52
Alarms Sent across the System Bus...................................................................52
Test Mode (V2.03.x).....................................................................................................................................................................53
Communication ...........................................................................................................................................................................53
System Bus .............................................................................................................53
The following pages have been changed from the previous issue of this document:
page change
2
21 Table 10 “Pull-up resistor handling” revised
22
27
52 Fig. 1. “Remote Modem Connection” revised
Fig. 1 “Controllers and their supported firmware versions”
revised
Section “LED Mode (XF823x, XFL823x, and XFx830x
modules) revised
Section “Safety Position (XFx822x, XFx824x, and XFx830x
modules)” revised
5 EN2B-0092GE51 R0709
EXCEL 50/100/500/600/800
SYSTEM OVERVIEW
GeneralExcel 50/500/800 controllers support both LONWORKS communication and the
Honeywell proprietary C-Bus communication.
ONWORKS-related information is described in the LONWORKS Mechanism
All L
document (EN0B-0270GE51).
Excel 50/100/500/600/800 is a control and monitoring system specially designed for
use in buildings. These Excel controllers use the latest Direct Digital Control (DDC)
technology. Excel 50/500/800 controllers are also capable of communicating on an
open Echelon® L
particularly well-suited to controlling buildings such as schools, hotels, offices, and
hospitals. Excel 50/100 controllers differ from Excel 500/600/800 controllers in
having a fixed input/output configuration.
Excel 50 controllers have a smaller fixed input/output configuration, and are designed for smaller buildings such as restaurants, shops, banks, and offices.
Excel 50/100/500/600/800 functions are:
• Heating control
• Air conditioning control
• Energy management
• Energy optimization
• Other building management functionality
SoftwareThe Excel 50/100/500/600/800 system includes a comprehensive software package
specially designed to meet the requirements of application engineers. It comprises
the following:
• Datapoint description
• Time program
• Alarm handling
• Password protection
The software package comes with all the files listed. The menu-driven format allows
quick and easy operation.
ONWORKS® network. Excel 50/100/500/600/800 controllers are
Firmware version numberAll information appearing in this Software Description is valid for firmware versions
V1.3.xx and earlier. All information, functions, and attributes valid for newer
firmware versions (V1.5.xx or higher) are marked by the corresponding version
number for which they are valid. Fig. 2 shows various controllers and the firmware
version numbers that they
support.
6 EN2B-0092GE51 R0709
Excel 50/100/500/600/800 OVERVIEW
Fig. 2. Controllers and their supported firmware versions
Excel 50 firmware compatibility Please always make sure that your firmware and the bootstrap loader match; if in
doubt, consult Software Release Bulletin(s). Special care must be taken in particular
in the case of the combinations of firmware and bootstrap loader with XD50B-xxx
modules as set forth in Table 1.
Table 1. Firmw
are / bootstrap loader compatibility with XD50B-xxx modules
firmware ≤ 2.06.07 firmware ≥ 2.06.08
bootstrap loader ≤ 1.01.07 NO* OK
bootstrap loader ≥ 1.01.08 OK OK
*Problems may occur when LONWORKS bus is in use.
Table 2. Firmware / bootstrap loader compatibility with XD50-xxx modules
firmware ≤ 2.06.07 firmware ≥ 2.06.08
bootstrap loader ≤ 1.01.07 OK OK
bootstrap loader ≥ 1.01.08 OK OK
*Problems may occur when LONWORKS bus is in use.
Datapoint descriptionDatapoints are the basis of the Excel 50/100/500/600/800 system. Datapoints
contain system-specific information such as values, status, limit values, and default
settings. The user has easy access to datapoints and the information they contain.
The user can recall and modify information in the datapoints.
Time programsWhenever you want, you can use time programs to enter the setpoint or status for
any datapoint.
The following time programs are available:
• Daily programs
EN2B-0092GE51 R0709
7
OVERVIEW EXCEL 50/100/500/600/800
• Weekly programs
• Annual programs
• The "TODAY" function
• Special day list
Daily programs are used to create a weekly program. The annual program is
created automatically by multiplying the weekly program and then incorporating
additional daily programs.
The "TODAY" function enables you to have a direct influence on the switching
program. This function enables you to allocate a setpoint or status to the selected
datapoints for a defined time period. This action does not depend on the current
daily program.
Alarm handling The alarm handling facility offers system security. Alarm signals can, for example,
alert the operator to maintenance work that is due. All alarms that occur are stored
in data files and reported immediately. If your system configuration allows, you can
also list alarms on a printer or transmit alarms to higher-level front-ends.
There are two kinds of alarm: Critical and Non-critical. Critical alarms have priority
over non-critical alarms. System alarms, caused by a fault in a controller, are always
critical alarms.
To distinguish between alarm types, you can generate your own alarm messages or
select appropriate messages already in the system.
The following events all generate alarm messages:
• Exceeding limit values
• Overdue maintenance work
• Totalizer readings
• Digital datapoint changes of state
Application programYou can use the Honeywell CARE engineering tool to create application programs
for your system. A particular advantage offered by Honeywell CARE is the ability to
create a fully functional control program without having to be familiar with the
programming language.
CARE stands for Computer Aided Regulation Engineering.
PasswordsYour control system is also protected by passwords. This ensures that only
authorized persons have access to the system data. There are four operator levels,
each protected by its own password.
• Operator level 1: Read only; the operator can display information about
setpoints, switching points, and operating hours.
• Operator level 2: Read and make limited changes; the operator can display
system information and modify certain preset values.
• Operator level 3: Read and make changes; system information can be displayed
and modified.
• Operator level 4: Programming.
Password protection prevents unauthorized access system information and ensures
permanent, secure system operation.
EN2B-0092GE51 R0709 8
EXCEL 50/100/500/600/800
DATAPOINTS
An Excel 50/100/500/600/800 system can have the following number of datapoints:
Excel 50: 22 physical (onboard I/Os) plus up to 46 physical LON I/Os
Excel 100: 36 physical (onboard I/Os)
Excel 500: 128 physical I/Os, extendable via L
Excel 600: 128 physical I/Os
Furthermore, Excel 50/100/500/600 support an additional 256 pseudo datapoints.
Excel 800: 381 datapoints (random mix of physical and pseudo datapoints)
A datapoint has different attributes according to its type. Attributes are displayed
and modified on the XI581 (not with XCL5010, Excel 100C), XI582, and the PCbased XL-Online operator interfaces or on the Excel 50 MMI. Attributes contain
information about the given datapoint. This information could be:
• Input limits values
• Operating status
• Current temperature
• Elapsed run time
The following sections provide more-detailed information about the different kinds of
datapoints and datapoint attributes and explain which attributes are assigned to
which datapoints.
ONWORKS I/Os
Physical Datapoints
Physical datapoints are inputs and outputs attached to hardware devices like
sensors and actuators.
Fig. 3. Physical datapoint symbols
The following are examples of physical datapoints
Analog inputsNTC, PT 1000, PT 3000, BALCO Sensors (PT 3000/BALCO not with Excel 100C),
standard 0 (2)...10 V and 0 (4)...20 mA input, to connect e.g. outside air
temperature sensors.
Analog outputsOutputs with a continuous 0...10 V output signal for controlling continuous actuators
(Excel 100C supplies up to 20 mA on the analog outputs).
Digital inputsInputs for processing voltage-free signals (switches, contacts).
Digital outputs (not Excel 100C)Outputs for driving three-position actuators, for example, a damper motor; two
position devices, for example, a circulation pump; 0...10 V and pulsed outputs
Totalizer inputsDigital inputs for processing pulsed signals up to 20 Hz (depending on Distributed
I/O module specifications), for example, metered energy consumption.
EN2B-0092GE51 R0709 9
DATAPOINTS EXCEL 50/100/500/600/800
Flexible Datapoints
Flexible datapoints allow the control of more than one physical output with one
datapoint. There are three subordinate types of flexible datapoints:
1. Pulse 2
2. Multi-stage
3. Feedback.
Pulse 2 flexible datapoint A pulse 2 datapoint allows to pulse two digital outputs (e.g. relays). When activated
(e.g. set to “on”), Pulse 2 triggers one of the digital outputs, and when deactivated,
Pulse 2 triggers the other digital output.
Pulse 2 “on” Pulse 2 “off”
Relay 1
Relay 2
Fig. 4. Pulse 2 flexible datapoint switching
Multistage flexible datapointMultistage flexible datapoints allow to switch up to six physical digital outputs via
one datapoint. A typical example would be a multi-stage electric heater or a multistage fan.
A multistage flexible datapoint provides up to six editable stage texts, e.g., stage 1,
stage 2, stage 3, etc, to be edited in CARE.
Feedback flexible datapointFeedback flexible datapoints, also called “DO feedback DI” combine up to three
pairs of digital outputs/digital inputs to form up to three-stage switching with
feedback. The digital inputs of each pair act as the feedback point.
If the digital input does not feedback the actual equipment status within a predefined
time “Off Phase”, then the software will switch down this point type until a "nonalarm" state is reached. In extreme cases, the point may be switched to the off
position. See also “Off Phase”.
Increased support (V2.04.xx or higher) Excel 500 controllers now support up to 60 flexible datapoints. In case of Feedback
flexible points, the maximum number is 128.
Previous firmware versions supported only up to 20 flexible datapoints.
Pseudo Datapoints
Excel 50/100/500/600 support 256 pseudo datapoints, while Excel 800 supports 381
datapoints (consisting of a random mix of physical and pseudo datapoints)
Pseudo datapoints are values (intermediate results and parameters) computed
while the application program is running. In contrast to physical datapoints, pseudo
datapoints are not directly connected to hardware devices.
EN2B-0092GE51 R0709 10
EXCEL 50/100/500/600/800 DATA POINTS
Access via the user addressDuring system operation, you may need to access these values. To simplify this
process, you can include pseudo datapoints in the datapoint list, where you can
access them directly via their user addresses.
Like physical datapoints, pseudo datapoints, too, can have different attributes; for
example, they can specify a manual value, set minimum and maximum values, or
log trends.
The following are types of pseudo datapoints:
• Pseudo analog points
• Pseudo digital points
• Pseudo totalizer inputs
• Pseudo point multistage
Pseudo analog pointsPseudo analog points are software points containing an analog value in the user
program.
A pseudo analog point could, for example, contain a flow temperature setpoint calculated from the room setpoint and the outside air temperature via the heating
curve.
Pseudo digital pointsPseudo digital points are software points containing a digital value in the user
program.
For example, logical AND operation.
The AND operation provides a logical 1 output when all input conditions are also
logical 1. Otherwise the output is a logical 0. If the user program contains such an
AND operation on different input conditions, then the output could be available as a
pseudo digital datapoint.
Pseudo totalizer inputsPseudo totalizer inputs are digital software points from the user program, where a
totalizer counter input is recorded.
Pseudo point multistagePseudo point multistage datapoints are identical to flexible datapoint of the type
"multistage" except that they allow for 16 stages (including the “off stage“) and the
attribute "Status Text" allows for 16 status texts to be attached. The attribute "Technical Address" is not required.
Global Datapoints
If your control and monitoring system contains more than one controller, the controllers communicate with one another via the system bus. Any given controller can
thus both receive (read) datapoints from other controllers and transmit datapoints to
other controllers. Such datapoints are referred to as global datapoints.
NOTE: The term “global” as used here encompasses more than just those points
explicitly labeled as “global” in the CARE engineering tool.
Global datapoints which a controller receives (reads) from other controllers are
referred to as local global datapoints, and global datapoints which a controller
transmits to other controllers are referred to as remote global datapoints.
During CARE engineering, the program engineer must take care that he does not
exceed the maximum allowed 256 global datapoints (remote and local) per
controller.
EN2B-0092GE51 R0709
11
DATAPOINTS EXCEL 50/100/500/600/800
SYS
S
TEM BU
C
LON
Fig. 5. Global datapoints are available to all controllers on the system bus
Mapped Datapoints (V2.04.xx or higher)
With firmware version V2.04.xx or higher, those Excel 50/500 controllers which
feature free programmability on L
chip, i.e. date code 0044 or higher) may have I/O devices connected via the
L
ONWORKS network. LONWORKS network variables (or individual fields of structured
network variables) can be mapped to the attribute "Value" of physical datapoints
(AI/DI/AO/DO). Pseudo analog, pseudo digital, and pseudo multistage points are
also supported for NV mapping.
Each datapoint type has associated with it various parameters which allow the user
to set, e.g., the user address, the level of access protection, alarm behavior, and
other options. These parameters are called attributes. Each attribute performs a
specific function related to the datapoint.
A complete list of datapoint types and their attributes appears in Table 17 through
Table 19. Not all attributes are available for every
Point refreshing (V1.5.x)Four attributes ("Value", "Manual Value", "Operating Mode", and "Alarm Status") will
be simultaneously refreshed to an XL-Online operator interface.
NOTE: A complete list of attributes associated with the various datapoint types can
be found in the section "List of Datapoint Attributes" on page 39.
Access Level
Four levels of protection The attribute "Access Level" protects datapoints against unauthorized changes on
the basis of the password level needed to modify a datapoint.
"Access Level" attributes between "1" and "4" are assigned to a point. These
attributes correspond to the four password levels found in the XI581 (not with
XCL5010, Excel 100C), XI582, and XL-Online operator interfaces and the Excel 50
MMI:
• Operator level 1: Read only.
• Operator level 2: Read and make limited changes.
• Operator level 3: Read and make changes.
• Operator level 4: Programming.
For example, setting the "Access Level" attribute for the datapoint with the user
address "room temp floor 1" to "2" means that all attributes for this datapoint can
now only be edited or modified at password level 2 or higher.
datapoint type.
Acknowledge Alarm (V2.04.xx or higher)
The attribute "Acknowledge Alarm" allows a controller to acknowledge an alarm for
a flexible datapoint of the type "feedback" without changing the operating mode. The
controller takes the point out of alarm as soon as a rising edge is detected on the
input of the WIA statement writing to the attribute "Acknowledge Alarm".
Fig. 6. The "Acknowledge Alarm" attribute for WIA statement
This attribute is a virtual attribute and can be accessed only by a WIA statement in
CARE. It is not part of the datapoint description and therefore cannot be displayed
on an MMI or building supervisor.
EN2B-0092GE51 R0709 13
ATTRIBUTES EXCEL 50/100/500/600/800
Active State (prior to V2.04.x)
The attribute "Active State" defines when a digital input/output is active.
NOTE: The "Active State" attribute does not reflect the current condition of a digital
datapoint.
NOTE: This is not applicable to digital inputs in applications designed for con-
trollers using V2.04.xx firmware or higher. In such applications, this
attribute is fixed at 1, and the new attribute "Normally Open/Normally
Closed" (NO/NC) is active (see section "Normally Open/Normally Closed
(V2.04.xx or higher)" on page 28 for more details).
T
he following values are possible:
• 0 = digital input/output is active when a "logical 0 signal" is present
• 1 = digital input/output is active when a "logical 1 signal" is present
Table 3 indicates the active state for various conditions of the XF523 and XFL523
modules.
Table 3. Active state for the digital input of XF523 and XFL523 modules
digital input
contact status open closed
CARE definition (NC/NO system
diagram)
definition - in XL-Online DP-Editor
attribute "Active State"
(change Active/Passive State text)
NOTE: XFL523 Module is applicable only for V2.0.xx software.
OFF/
trouble:
alarm
ON/
operating
RTN*
ON/
operating
RTN*
OFF/
trouble:
alarm
ON/
operating
RTN*
OFF/
trouble:
alarm
Active State (Excel 800)
The attribute "Active State" defines when a digital input/output is active.
1 means, that a digital input/output is active when a "logical 1 signal" is present
NOTE: "Active State" = 0 is not allowed/possible.
NOTE: The "Active State" attribute does not reflect the current condition of a digital
datapoint.
EN2B-0092GE51 R0709 14
EXCEL 50/100/500/600/800 ATTRIBUTES
Table 4. Active State for the digital input of XF823 and XFL823 modules
digital input
contact status open closed
CARE definition (NC/NO system
diagram)
definition - in XL-Online DP-Editor
attribute "Active State"
(change Active/Passive State text)
CARE interpretation (control table) 1 0 0 1
display at operator interface
(status text)
trouble:
NC NO NC NO
1 1 1 1
OFF/
alarm
* RTN = Return To Normal
OFF/
trouble:
alarm
ON/
operating
RTN*
ON/
operating
RTN*
Alarm Delay
Delaying alarm outputsThe alarm delay time (in seconds) is entered in the attribute "Alarm Delay". The
alarm delay time determines how long an alarm condition must exist before an
alarm is generated. Entering an alarm delay time of 10 seconds means that the limit
value must be exceeded for at least 10 seconds before this datapoint generates an
alarm. If the limit value lasts for only 7 second, then no alarm occurs.
Alarm Suppression
The attribute “Suppress Alarm” establishes whether or not alarm messages from the
following alarm attributes should be suppressed:
• Operational status
• Min/Max. limit
• Maintenance alarm
• Interval counter
• Alarm Status
The following entries are possible:
• Off = Alarms not suppressed
• On = Alarms suppressed
Example: digital inputIn addition to a variety of other attributes, a digital input also has the "Operating
Mode", "Alarm Status", and "Maintenance Alarm" attributes. If alarm suppression is
activated for this datapoint, then no message is displayed during an operating mode
change-over, or when changing into the alarm condition, or when reaching the
maintenance alarm.
Suppression of system The controller will not issue a system alarm when the alarm’s system alarm text
alarms (V2.04.xx or higher) starts with an @ character.
Alarm Status (prior to V2.04.x)
Alarm monitoringIn the case of a digital input or a pseudo digital point, the attribute "Alarm Status"
specifies whether or not alarm monitoring is required.
The following entries are possible:
• Yes Alarm monitoring is required
• No Alarm monitoring is not required
EN2B-0092GE51 R0709
15
ATTRIBUTES EXCEL 50/100/500/600/800
When alarm monitoring is required, the alarm message occurs when the digital point
changes from the active state to the passive state (alarm reached). An additional
message is generated (alarm going) when the digital point returns to the active state
(see Fig. 7).
Alarm
reached
Alarm
ending
DI in
“Active State”
DI in
“Passive State”
Fig. 7. Alarm status messaging
NOTE: The active state and passive state are defined in the "Active State"
datapoint attribute.
Alarm Status (V2.04.xx or higher)
Alarm monitoring In the case of a digital input or a pseudo digital point, the attribute "Alarm Status"
specifies whether or not alarm monitoring is required.
The following entries are possible:
• Yes Alarm monitoring is required
• No Alarm monitoring is not required
When alarm monitoring is required, the alarm message occurs depending on the
physical contact status and on the logical status as defined in the online attribute
“Normally Open/Normally Closed”.
Alarm Type
The attributes listed in Table 5 are capable not only of generating alarms, but also of
writing them to the internal alarm memory and sending them to the PC front-end or
to the modem module (when connected).
Table 5. Alarm attributes
attribute always critical optional critical or non-critical
Operating Mode X
Min. Limit X
Max. Limit X
Maintenance AlarmX
Interval Counter X
Alarm Status X
Changing over the attribute "Operating Mode" always results in a critical alarm, but
the attribute "Alarm Type" offers a choice for the alarm attributes "Min. Limit", "Max.
Limit", "Maintenance Alarm", "Totalizer", and "Alarm Status" whether an alarm is
classified as critical or non-critical.
EN2B-0092GE51 R0709 16
EXCEL 50/100/500/600/800 ATTRIBUTES
Distinguishing between critical and non-critical alarms is significant for the subsequent reporting of the alarms to the PC front-end or to the modem module. Compared to non-critical alarms, critical alarms are given priority on the bus when
several alarms are in the alarm queue.
When the type of alarm for a datapoint has been decided, e.g. "critical" alarm type, it
refers to all alarm attributes for this datapoint.
Alarm Definition
In the datapoint description, the alarms can be influenced using the functions
described below (see also Table 6 on page 18).
A
Alarm delayAn alarm signal can be delayed by entering an alarm delay time. An alarm signal will
Suppress alarm If an alarm signal is not desired from a particular datapoint, this can be fixed in the
larm typeFor each datapoint in the datapoint description, the user can determine whether the
signals generated are to be treated as critical or non-critical alarm.
be generated only if an alarm continues uninterrupted during the alarm delay time.
datapoint description. Thus, all the alarm signals relevant to the particular datapoint
and the "Operating Mode" alarm types are suppressed.
Fig. 8. Alarm condition depending on point value and Suppress Alarm status
Fig. 8 shows an example of a changing point value that rises above and falls below
the limit Max 2. If Suppress Alarm is not active, then the alarm condition switches
between normal to alarm, according to the limit Max 2. If Suppress Alarm is active,
then the alarm condition remains normal unless Suppress Alarm is switched off
before the point value falls below the limit Max 2. Regardless of the setting of the
Alarm suppression flag, an alarm is entered into the controller's history buffer and is
also available in the EBI alarm report.
Point alarmIt is possible to view all datapoints at the operator interfaces for which the limit value
(analog point) or the alarm status (digital point) is currently exceeded.
Driven by a menu, the user address and the accompanying alarm text are displayed
on the XI581 (not with XCL5010, Excel 100C) or XI582 operator interfaces or Excel
50 MMI.
On the XL-Online operator interface, a datapoint within the framework of the
datapoint description can be seen in all four password levels. If a current alarm is
present for the point in question, the attribute “Point in Alarm” produces the display
“Yes”, otherwise “No”.
Within the framework of the datapoint description, it is possible, under the attribute
“Alarm text”, to enter an alarm text of up to 18 characters in addition to the preprogrammed text. There are 256 alarm texts in total.
Table 6 presents a summary of various alarm types and attributes.
EN2B-0092GE51 R0709
17
ATTRIBUTES EXCEL 50/100/500/600/800
Table 6. Alarm summary
alarm type/attributes alarm status
Limit Values selection in DPD* possible possible X 8 possible
Alarm Status selection in DPD* possible possible X 2 possible
Maintenance Alarm selection in DPD* - possible - 1 -
Totalizer selection in DPD* - possible - 1 -
Operating Mode always critical - possible - 2 -
System Alarms always critical - - - approx. 110 -
user program reports always non-critical - - - - -
*DPD = datapoint description
enter alarm
delay time
NOTE: A point is still seen as “in alarm” even when alarm suppression is enabled.
alarm
suppression
point in
alarm
no. of prepro-
grammed texts
supplementary
text
Cycle Count
The attribute "Cycle Count" contains the value indicating the number of transitions
to the active state (see "Active State (prior to V2.04.x)" on page 14).
Delay Time Switching Up
Fig. 9. Delay time switching up
Delay Time Switching Down
Fig. 10. Delay time switching down
This attribute is used in conjunction with flexible points of
the type "feedback". It defines the delay time between
switching upwards from one stage to another. The delay
time affects every stage. The delay time also takes effect
when switching, e.g. from manual value 0 to 2. In this case,
it is switched from stage 0 to stage 1, then to stage 2 with
the delay time between the switching processes.
• Range: 0 to 255s
• Default value : 10s
• Resolution: 1s
This attribute is used in conjunction with flexible points of
the type "feedback". It defines the delay time between
switching downwards from one stage to another. The delay
time affects every stage.
• Range: 0 to 255s
• Default value: 10s
• Resolution: 1s
The feedback delay time starts to count after termination of
delay time switching up/delay time switching down.
Descriptors
Informative descriptorsA controller contains up to 128 physical datapoints and up to 256 pseudo
datapoints. The Excel 100C provides 36 physical datapoints. An individual user
address can be assigned to each of these 384 datapoints.
EN2B-0092GE51 R0709 18
EXCEL 50/100/500/600/800 ATTRIBUTES
255 plain-language descriptors can be created with a maximum of 32 characters
each. These descriptors are then assigned to datapoints in the datapoint description
via the attribute "Descriptor".
Descriptors complete the information concealed behind the user address. They can
contain, for instance, a reference to a section of a building.
The following list is an example of the relationship between user addresses and
descriptors:
User Address Descriptor
Room temp floor 1 Heating circuit, West wing
Room temp floor 3 Heating circuit, West wing
Room temp floor 10 Heating circuit, East
Room temp corridor Heating circuit, East
Flow temp floor 1 Heating circuit, West wing
Lights floor 1 Building section V
Lights corridor Building section V
Engineering Unit
The attribute "Engineering Unit" contains a list for selecting different engineering
units for both analog datapoints (physical and pseudo), totalizer inputs (physical and
pseudo), and digital datapoints.
If, for instance, the external temperature is measured by an analog datapoint, the
engineering unit of this datapoint must be set to "°C" or "°F". If the electrical load is
detected by a totalizer input, the engineering unit must be set to "kWh" for kilowatthours.
Feedback Delay
The attribute "Feedback Delay" determines the time delay between, e.g. when a
pump switched on (and detected) and when this status is made available to a
program.
High/Low Alarm/Warning Limits
Specifying limit valuesIn the case of analog inputs (e.g. inputs for sensing room temperature) and pseudo
analog points (for instance, internally computed datapoints for the heating flow
setpoint), two minimum and two maximum monitored limit values may be entered.
The following four limit value attributes exist:
• Low Warning Limit
• Low Alarm Limit
• High Warning Limit
• High Alarm Limit
Exceeding the limit values generates an alarm.
Example: Monitoring supply air temperature limits (see Fig. 11).
EN2B-0092GE51 R0709
19
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.