Honeywell EW535 DATASHEET

Honeywell EW535 DATASHEET

EW535 Series

Hydro-Center

M-BUS MASTER AND SYSTEM COMPONENTS

PRODUCT DATA

Design

All system components consist of:

Rail-mount housing with fuse profile, width 71mm or 157.5mm

Materials

• Housing made of dark-grey heat resistant plastic

Application

EW535 Series M-Bus System Components enable remote recording and reading out of M-Bus capable meters, e.g. Honeywell EW773 Series Ultrasonic Heat Meters.

The M-Bus system is used to connect various meters, typically M-Bus ca-pable heat meters and water meters but also gas or electricity meters to a central M-Bus master unit. Values recorded by the meter are stored in the master unit and can be read out directly by connecting a PC or remotely, e.g. by telephone line or LAN converter.

Many non M-Bus capable meters can be connected to the M- Bus system by using a converter.

Features

M-Bus master and level converter in one device

Hydro-Center 60/250 can also be used as M-Bus repeater (amplifier)

25, 60 or 250 M-Bus devices maximum

Memory versions

2MB flash memory (for approx. 20,000 readings)

Real time clock with date and time, max. deviation +/-1 minute per month, 10 years battery life time without external power supply

Programmable automatic meter readout

Device list for 1,000 devices

Comfortable Windows® software included for easy onsite or remote configuration

Honeywell y Subject to change

EN0H-2606GE25 R0807

EW535 SERIES HYDRO-CENTER

Specifications

Ambient temperature

0…60°C (32…140°F)

Humidity rating

10…70% RH

M-Bus transmission

Hydro-Center 25: 300 and 2400 baud

speeds

Hydro-Center 60/250: 300, 600, 1200, 2400, 4800 and 9600 baud

 

automatic baudrate detection

Power supply

Hydro-Center 25: 230V 50…60Hz AC

 

Hydro-Center 25 Solar: 12V DC from solar power supply with 1A max. power

 

Hydro-Center 60: 11…38V DC or 15…38V 50…60Hz AC

 

Hydro-Center 250: 20…38V DC or 24…38V 50…60Hz AC

Interfaces

RS232 PC interface

 

RS232 modem interface

 

M-Bus output

 

Hydro-Center 60/250 only:

M-Bus repeater interface

Optical IrDA interface

Hydro-Radio transceiver interface

Dimensions and Ordering Informations

Table 1. Dimensions and OS-Nos (OS=Ordering System)

Item

Description

Dimensions

OS-No.

 

 

Width

 

Height

 

Depth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Center 25

M-Bus level converter for max. 25 M-Bus devices,

71

 

90

 

62

EW535M0093

 

230V 50Hz power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Center 25 Memory

M-Bus master for max. 25 M-Bus devices, 2MB data

71

 

90

 

62

EW535M0094

 

logger memory, 230V 50Hz power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Center 25 Solar

M-Bus master for max. 25 M-Bus devices, 2MB data

71

 

90

 

62

EW535M0055

 

logger memory, battery charger for 12V power supply,

 

 

 

 

 

 

 

max. 1A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Center 60

M-Bus level converter/repeater for max. 60 M-Bus

157.5

 

90

 

62

EW535M0050

 

devices, 24V AC/DC power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Center 60 Memory

M-Bus master for max. 60 M-Bus devices, 2MB data

157.5

 

90

 

62

EW535M0051

 

logger memory, 24V AC/DC power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Center 250

M-Bus level converter/repeater for max. 250 M-Bus

157.5

 

90

 

62

EW535M0052

 

devices, 24V AC/DC power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Center 250 Memory

M-Bus master for max. 250 M-Bus devices, 2MB data

157.5

 

90

 

62

EW535M0053

 

logger memory, 24V AC/DC power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Center Power

Power supply module for Hydro-Center 60/250, 230V

71

 

90

 

62

EW535M0054

 

50Hz AC input, 24V / 1A 50Hz AC output (24W), 12V

 

 

 

 

 

 

 

DC output for GSM modem

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Port Pulse

Pulse meter to M-Bus converter, 2 pulse inputs

71

 

90

 

62

EW535M0056

 

 

 

 

 

 

 

 

Hydro-Port Analog

Converter for meters with analogue 4…20mA output to

71

 

90

 

62

EW535M0057

 

M-Bus, 2 analogue inputs, 1 analogue output, 1 input

 

 

 

 

 

 

 

for PT temperature sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro-Port Housing

Heavy-duty housing IP66 for Hydro-Port modules

71

 

90

 

62

EW535M0058

 

 

 

 

 

 

 

 

Hydro-Port Control

M-Bus relay module with 2 digital state inputs and 2

71

 

90

 

62

EW535M0059

 

bistable relay outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All dimensions in mm unless stated otherwise.