EW535 Series
Hydro-Center
M-BUS MASTER AND SYSTEM COMPONENTS
PRODUCT DATA
Design |
All system components consist of:
•Rail-mount housing with fuse profile, width 71mm or 157.5mm
Materials
• Housing made of dark-grey heat resistant plastic
Application
EW535 Series M-Bus System Components enable remote recording and reading out of M-Bus capable meters, e.g. Honeywell EW773 Series Ultrasonic Heat Meters.
The M-Bus system is used to connect various meters, typically M-Bus ca-pable heat meters and water meters but also gas or electricity meters to a central M-Bus master unit. Values recorded by the meter are stored in the master unit and can be read out directly by connecting a PC or remotely, e.g. by telephone line or LAN converter.
Many non M-Bus capable meters can be connected to the M- Bus system by using a converter.
Features
•M-Bus master and level converter in one device
•Hydro-Center 60/250 can also be used as M-Bus repeater (amplifier)
•25, 60 or 250 M-Bus devices maximum
Memory versions
•2MB flash memory (for approx. 20,000 readings)
•Real time clock with date and time, max. deviation +/-1 minute per month, 10 years battery life time without external power supply
•Programmable automatic meter readout
•Device list for 1,000 devices
•Comfortable Windows® software included for easy onsite or remote configuration
Honeywell y Subject to change |
EN0H-2606GE25 R0807 |
EW535 SERIES HYDRO-CENTER
Specifications
Ambient temperature |
0…60°C (32…140°F) |
Humidity rating |
10…70% RH |
M-Bus transmission |
Hydro-Center 25: 300 and 2400 baud |
speeds |
Hydro-Center 60/250: 300, 600, 1200, 2400, 4800 and 9600 baud |
|
automatic baudrate detection |
Power supply |
Hydro-Center 25: 230V 50…60Hz AC |
|
Hydro-Center 25 Solar: 12V DC from solar power supply with 1A max. power |
|
Hydro-Center 60: 11…38V DC or 15…38V 50…60Hz AC |
|
Hydro-Center 250: 20…38V DC or 24…38V 50…60Hz AC |
Interfaces |
RS232 PC interface |
|
RS232 modem interface |
|
M-Bus output |
|
Hydro-Center 60/250 only: |
M-Bus repeater interface
Optical IrDA interface
Hydro-Radio transceiver interface
Dimensions and Ordering Informations
Table 1. Dimensions and OS-Nos (OS=Ordering System)
Item |
Description |
Dimensions |
OS-No. |
||||
|
|
Width |
|
Height |
|
Depth |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
Hydro-Center 25 |
M-Bus level converter for max. 25 M-Bus devices, |
71 |
|
90 |
|
62 |
EW535M0093 |
|
230V 50Hz power supply |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hydro-Center 25 Memory |
M-Bus master for max. 25 M-Bus devices, 2MB data |
71 |
|
90 |
|
62 |
EW535M0094 |
|
logger memory, 230V 50Hz power supply |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hydro-Center 25 Solar |
M-Bus master for max. 25 M-Bus devices, 2MB data |
71 |
|
90 |
|
62 |
EW535M0055 |
|
logger memory, battery charger for 12V power supply, |
|
|
|
|
|
|
|
max. 1A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hydro-Center 60 |
M-Bus level converter/repeater for max. 60 M-Bus |
157.5 |
|
90 |
|
62 |
EW535M0050 |
|
devices, 24V AC/DC power supply |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hydro-Center 60 Memory |
M-Bus master for max. 60 M-Bus devices, 2MB data |
157.5 |
|
90 |
|
62 |
EW535M0051 |
|
logger memory, 24V AC/DC power supply |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hydro-Center 250 |
M-Bus level converter/repeater for max. 250 M-Bus |
157.5 |
|
90 |
|
62 |
EW535M0052 |
|
devices, 24V AC/DC power supply |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hydro-Center 250 Memory |
M-Bus master for max. 250 M-Bus devices, 2MB data |
157.5 |
|
90 |
|
62 |
EW535M0053 |
|
logger memory, 24V AC/DC power supply |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hydro-Center Power |
Power supply module for Hydro-Center 60/250, 230V |
71 |
|
90 |
|
62 |
EW535M0054 |
|
50Hz AC input, 24V / 1A 50Hz AC output (24W), 12V |
|
|
|
|
|
|
|
DC output for GSM modem |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hydro-Port Pulse |
Pulse meter to M-Bus converter, 2 pulse inputs |
71 |
|
90 |
|
62 |
EW535M0056 |
|
|
|
|
|
|
|
|
Hydro-Port Analog |
Converter for meters with analogue 4…20mA output to |
71 |
|
90 |
|
62 |
EW535M0057 |
|
M-Bus, 2 analogue inputs, 1 analogue output, 1 input |
|
|
|
|
|
|
|
for PT temperature sensor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hydro-Port Housing |
Heavy-duty housing IP66 for Hydro-Port modules |
71 |
|
90 |
|
62 |
EW535M0058 |
|
|
|
|
|
|
|
|
Hydro-Port Control |
M-Bus relay module with 2 digital state inputs and 2 |
71 |
|
90 |
|
62 |
EW535M0059 |
|
bistable relay outputs |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: All dimensions in mm unless stated otherwise.
EN0H-2606GE25 R0807 |
2 |
Honeywell y Subject to change |