Honeywell EW535 DATASHEET

EW535 Series
Hydro-Center
M-BUS MASTER AND SYSTEM COMPONENTS
PRODUCT DATA
Application
EW535 Series M-Bus System Components enable remote recording and reading out of M-Bus capable meters, e.g. Honeywell EW773 Series Ultrasonic Heat Meters.
The M-Bus system is used to connect various meters, typically M-Bus ca-pable heat meters and water meters but also gas or electricity meters to a central M-Bus master unit. Values recorded by the meter are stored in the master unit and can be read out directly by connecting a PC or remotely, e.g. by tele­phone line or LAN converter.
Many non M-Bus capable meters can be connected to the M­Bus system by using a converter.
Features
• M-Bus master and level converter in one device
• Hydro-Center 60/250 can also be used as M-Bus repeater (amplifier)
• 25, 60 or 250 M-Bus devices maximum
Design
All system components consist of:
• Rail-mount housing with fuse profile, width 71mm or
Materials
• Housing made of dark-grey heat resistant plastic
Memory versions
• 2MB flash memory (for approx. 20,000 readings)
• Real time clock with date and time, max. deviation +/-1 minute per month, 10 years battery life time without external power supply
• Programmable automatic meter readout
• Device list for 1,000 devices
• Comfortable Windows® software included for easy on­site or remote configuration
Honeywell y Subject to change EN0H-2606GE25 R0807
EW535 SERIES HYDRO-CENTER
Specifications
Ambient temperature 0…60°C (32…140°F)
Humidity rating 10…70% RH
M-Bus transmission speeds
Power supply Hydro-Center 25: 230V 50…60Hz AC
Interfaces RS232 PC interface
Hydro-Center 25: 300 and 2400 baud
Hydro-Center 60/250: 300, 600, 1200, 2400, 4800 and 9600 baud
automatic baudrate detection
Hydro-Center 25 Solar: 12V DC from solar power supply with 1A max. power
Hydro-Center 60: 11…38V DC or 15…38V 50…60Hz AC
Hydro-Center 250: 20…38V DC or 24…38V 50…60Hz AC
RS232 modem interface
M-Bus output
Hydro-Center 60/250 only:
M-Bus repeater interface
Optical IrDA interface
Hydro-Radio transceiver interface
Dimensions and Ordering Informations
Table 1. Dimensions and OS-Nos (OS=Ordering System)
Item Description Dimensions OS-No.
Width Height Depth
Hydro-Center 25 M-Bus level converter for max. 25 M-Bus devices,
230V 50Hz power supply
Hydro-Center 25 Memory M-Bus master for max. 25 M-Bus devices, 2MB data
logger memory, 230V 50Hz power supply
Hydro-Center 25 Solar M-Bus master for max. 25 M-Bus devices, 2MB data
logger memory, battery charger for 12V power supply, max. 1A
Hydro-Center 60 M-Bus level converter/repeater for max. 60 M-Bus
devices, 24V AC/DC power supply
Hydro-Center 60 Memory M-Bus master for max. 60 M-Bus devices, 2MB data
logger memory, 24V AC/DC power supply
Hydro-Center 250 M-Bus level converter/repeater for max. 250 M-Bus
devices, 24V AC/DC power supply
Hydro-Center 250 Memory M-Bus master for max. 250 M-Bus devices, 2MB data
logger memory, 24V AC/DC power supply
71 90 62 EW535M0093
71 90 62 EW535M0094
71 90 62 EW535M0055
157.5 90 62 EW535M0050
157.5 90 62 EW535M0051
157.5 90 62 EW535M0052
157.5 90 62 EW535M0053
Hydro-Center Power Power supply module for Hydro-Center 60/250, 230V
50Hz AC input, 24V / 1A 50Hz AC output (24W), 12V DC output for GSM modem
Hydro-Port Pulse Pulse meter to M-Bus converter, 2 pulse inputs 71 90 62 EW535M0056
Hydro-Port Analog Converter for meters with analogue 4…20mA output to
M-Bus, 2 analogue inputs, 1 analogue output, 1 input for PT temperature sensor
Hydro-Port Housing Heavy-duty housing IP66 for Hydro-Port modules 71 90 62 EW535M0058
Hydro-Port Control M-Bus relay module with 2 digital state inputs and 2
bistable relay outputs
NOTE: All dimensions in mm unless stated otherwise.
EN0H-2606GE25 R0807 2 Honeywell y Subject to change
71 90 62 EW535M0054
71 90 62 EW535M0057
71 90 62 EW535M0059
Loading...
+ 2 hidden pages