Honeywell COMP230-P37-20, COMP230-P75-20, COMP230-1P1-20, COMP230-1P5-20, COMP230-2P2-20 PRODUCT DATA

...
COMP230-xxx-20 / COMP400-xxx-20
These variable frequency drives provide step less speed control for various applications:
Pumps Fans Compressors Conveyors, etc.
FEATURES
Compact size Flexible side-by-side mounting with screws or DIN-rail
as standard
Single rating suitable for both pump and fan or
machine applications
Maximum ambient temperature: +50 Integrated RFI-filters Wide Input and Output connection possibilities Configurable inputs and outputs 30s Start-Up Wizard Easy “keypad – remote” change with 1 button Parameter upload/download even without powering
the inverter with COMP-LOADER accessory
Silent motor operation with 4 kHz switching
frequency
Overtemperature ride-through Power ride-through Automatic restart Integrated PI controller
°
C
SMARTDRIVE COMPACT INVERTERS
PRODUCT DATA
SPECIFICATIONS
Mains Connection
Input voltage U
380…480 Vac (-15…+10%), 3~
Input frequency 45…66 Hz Connection to mains Once per minute or less
Brake chopper Integrated as standard in
Motor Connection
Output voltage 0 - U Output current I
Starting current 2 x I Output frequency 0…320 Hz Frequency resolution 0.01 Hz
Control Characteristics
Control method Frequency Control U/f
Switching frequency 1.5...16 kHz;
Field weakening point 30…320 Hz Acceleration time 0.1…3000 sec Deceleration time 0.1…3000 sec Braking torque DC-brake: 30%*TN (without
Ambient Conditions
Operating temperature -10 °C (no frost)…+50 °C
NOTE: Two models with max.
Storage temperature -40 °C…+70 °C
208…240 Vac (-15…+10%), 1~
in
380…480 Vac products from
1.5 kW and up
3~
in,
: Continuous output current
N
with max. +50 °C ambient temperature, overloadability
(1min/10min)
1.5 x I
N
2s/20s
N
Open Loop Sensorless Vector Control
default 4 kHz
brake resistor)
ambient: rated loadability I
operating temperature of +40 °C. See table on page 3.
N
® U.S. Registered Trademark EN0B-0638GE51 R1009 Copyright © 2009 Honeywell Inc. • All rights reserved
SmartDrive COMPACT VARIABLE FREQUENCY DRIVES
Air quality
Chemical vapors IEC 721-3-3, unit in operation,
class 3C2
Mechanical particles IEC 721-3-3, unit in operation,
class 3S2
Altitude 100% load capacity (no derating)
up to 1000 m
1% derating for each 100 m
above 1000 m; max. 2000 m
Relative humidity 0…95% RH, non-condensing,
non-corrosive, no dripping water
Vibration 3...150 Hz EN50178, EN60068-2-6 Displacement amplitude 1(peak)
mm at 3...15.8 Hz
Max acceleration amplitude 1 g
at 15.8...150 Hz
Shock UPS Drop Test (for applicable EN50178, IEC 68-2-27 UPS weights) Storage and shipping: max 15 g,
11 ms (in package)
Enclosure class IP20
Electro Magnetic Compatibility (EMC)
Immunity Complies with EN50082-1, -2,
EN61800-3
Emissions
Standard product EN 61800-3 Category C2 (EMC-
level H)
With external RFI-filter EN 61800-3 Category C1 (EMC-
level C)
Safety
EN60204-1, EN 61800-5 CE UL508C UL, cUL
(see unit nameplate for more detailed approvals)
Control connections
Analog input voltage 0...+10V, Ri = 200k (min),
Resolution 10 bit, accuracy ±1%, electrically isolated
Analog input current 0(4)…20 mA, Ri = 200
differential resolution 0.1%, accuracy ±1%, electrically isolated
Digital inputs 6 positive logic; 0…+30 VDC
Voltage output for +24V, ±20%, max. load 50 mA digital inputs
Output reference voltage +10V, +3%, max. load 10 mA
Analog output 0(4)…20 mA; RL max. 500 Ω;
Digital outputs
Relays 2 programmable relay outputs (1
Open collector 1 open collector output with max.
resolution 16 bit; accuracy ±1%
NO/NC and 1 NO), Max.switching load: 250 Vac/2 A or 250 Vdc/0.4 A
load 48 V/50 mA
Protections
Overvoltage protection 875VDC in COMP400-xxx-20 437VDC in COMP230-xxx-20
Undervoltage protection 333VDC in COMP400-xxx-20 160VDC in COMP230-xxx-20
Earth-fault protection In case of earth fault in motor or
Unit overtemperature YES
protection Motor overload YES
protection
Motor stall protection
(fan/pump blocked)
Motor underload YES
protection (pump dry /
belt broken detection)
Short-circuit protection YES
of +24V and +10V
reference voltages Overcurrent protection Trip limit 4,0*I
motor cable, only the frequency converter is protected
YES
instantaneously
N
EN0B-0638GE51 R1009 2
SmartDrive COMPACT VARIABLE FREQUENCY DRIVES
MODELS
Mains voltage 230 V (208-240 V), 50/60 Hz, 1~in/3~out
Motor nominal
Inverter type
COMP230-P37-20 0.37 COMP230-P75-20 0.75 COMP230-1P1-20 1.1 COMP230-1P5-20 1.5 COMP230-2P2-20 *) 2.2 *) The unit has max. +40 °C ambient temperature
power 230V supply 50 °C P[kW]
Loadability
Rated
continuous
current I
[A]
2.4 3.6 IP20 MI1 66x157x98 0.55
3.7 5.6 IP20 MI2 90x195x102 0.7
4.8 7.2 IP20 MI2 90x195x102 0.7
7.0 10.5 IP20 MI2 90x195x102 0.7
9.6 14.4 IP20 MI3 100x251x109 1
50% overload
N
current
[A]
Enclosure
class
Mechanical
size
Mains voltage 400 V (380- 480 V), 50/60 Hz, 3~
Motor nominal
Inverter type
COMP400-P55-20 0.55 COMP400-P75-20 0.75 COMP400-1P1-20 1.1 COMP400-1P5-20 1,5 COMP400-2P2-20 2.2 COMP400-3P0-20 3.0 COMP400-4P0-20 4.0 COMP400-5P5-20 *) 5.5 *) The unit has max. +40 °C ambient temperature
power 400V supply 50 °C P[kW]
Loadability
Rated
continuous
current I
[A]
1.9 2.9 IP20 MI1 66x157x98 0.55
2.4 3.6 IP20 MI1 66x157x98 0.55
3.3 5.0 IP20 MI2 90x195x102 0.7
4.3 6.5 IP20 MI2 90x195x102 0.7
5.6 8.4 IP20 MI2 90x195x102 0.7
7.6 11.4 IP20 MI3 100x251x109 1
9.0 13.5 IP20 MI3 100x251x109 1
12.0 18.0 IP20 MI3 100x251x109 1
50% overload
N
current
[A]
Enclosure
class
Mechanical
size
PRODUCT IDENTIFICATION CODE
Dimensions
WxHxD
[mm]
Dimensions
WxHxD
[mm]
Weight
[kg]
Weight
[kg]
COMP 400 -1P1 -20
Enclosure classification 20 = IP20
Nominal power P75 = 0.75 kW 1P1 = 1.1 kW etc.
Supply voltage 230 = 230 Vac 1~ (208-240 Vac) 400 = 400 Vac 3~ (380-480 Vac)
Product range: COMP = SmartDrive Compact
Fig. 1. Product Identification Code
3 EN0B-0638GE51 R1009
Loading...