Honeywell CM67RFMV PRODUCT SPECIFICATION SHEET

CM67RFMV
WIREFREE CHRONOTHERM
PRODUCT DATA
I
FEATURES
CM67RF MV can be installed without disrupting your
room décor – no wired connection required between the room unit and the boiler
Reliable RF communication utilising 868,3 MHz band
with 1 % duty cycle limit to minimise communication disturbance
CM67RF MV can be used to control directly mixing
valves depending on the room setpoint temperature
Maximum system efficiency and extended boiler life
due to unique zoning system synchronisation
Up to 4 CM67RF MV can be bound with one HC60NG
for boiler feedback heat on demand
Suitable for any room décor due to subtle styling
Easy to program – user friendly interface allowing 7-
day programming to match variety of lifestyles
Armchair programmed
Non volatile memory holds the user program
permanently even when batteries being replaced
Party button to temporarily maintain (or adjust) the
current temperature for 1-23 hours
Day Off button copies Sunday’s program into
tomorrow or today to allow a rest day program without having to re-program the CM67RF MV
Holiday button provides energy savings by
reducing the temperature for 1 to 99 days when homeowner is on holiday, returning to normal operation (AUTO or MANUAL) on the day of return.
GENERAL
The CM67RFMV Chronotherm is designed to provide automatic time and temperature control of heating or cooling applications. It can be used to control directly mixing valves for individual zoning control. The Chronrotherm is communicating with the universal mixing valve controller HM80 depending on the deviation of the room temperature and room temperature setpoint the mixing valve will be closed or opened.
In combination with other CM67RFMV Chronotherms and one HC60NG receiver it can be used to control the boiler depending on the heat demand (up to 4 CM67RFMV ).
No wiring to the room unit is required. The installer needs to wire the universal mixing valve controller HM80 only to the controlled device mixing valve and mount the room unit in a suitable location where RF communication is reliable.
The CM67RFMV uses reliable RF communication technology in the 868,3 MHz band.
The unit is ideal for consumers who want reliable and precise temperature control from an easy-to-use product.
FEATURES continued
When used with the table top stan d the room unit can
be positioned anywhere in the room where RF communication is reliable
Installer Set-Up Mode allows extra functions to be set
at the discretion of the installer to match the application :
Pump after running time
Mixing valve running time
Upper / Lower Flow Temperature Limit Adjust
Upper / Lower Setpoint Limit Adjust
Forced operation pump
Forced operation mixing valve
Temperature offset
Heat / Cool Operation
Fail-safe mode for communication loss
Frost protection is ensured when the slider is in the
OFF position.
CM67RFMV can be used with Automatic Time Setting
module (Q6667B1007)
EN0H0551GE51 R0905
CM 67 RFMV
y
CM67RFMV
CONTROLS/DISPLAY LAYOUT
Battery Low Indicator
Day Button
Copy Day
Button
Time Change
Buttons
Setting
Slider
Party Button Day Off Button Holiday Button
Day Marker
Time Display
Heat Demand Indicator
Temperature Display
Information Enquir
Temperature Change Buttons
=
increase
= decrease
Battery Compartment
Programming Buttons
Button
SPECIFICATIONS
ELECTRICAL
Room unit power : 2 x 1.5 V IEC LR6 (AA) Alkaline cells supply Battery life : 3 years typical Battery : Program retained in EEPROM replacement Receiver power : 230 V AC + 10% - 15%, 50Hz supply Switch type : SPDT potential free Output rating : 24-230 V AC, 10 A resistive, 3 A inductive 0.6
p.f.
Wiring (receiver : Cable terminals for mains and relay wiring for only) max 2.5 mm Wire access : from the rear (wall box mounting), right and
bottom
RF Communication
RF operation band : ISM (868.0-868.6) MHz, 1% duty cycle RF communication : 30 m in a residential building environment range RF communication : short, high rate transmissions to minimise air technology time and avoid collisions Blocking immunity : Receiver class 2 (ETSI EN300 220-1 version
1.3.1) RF binding method : Factory pre-bound with the room unit. For multi-zone application receiver can be bound to 4 different room units via simple binding procedure)
ENVIRONMENTAL & STANDARDS
Operating : 0 to 40 °C when relay load < 8 A temperature : 0 to 30 °C when relay load > 8 A Shipping & storage : -20 to 55 °C temperature Humidity : Humidity range 0 to 90 %, non-condensing IP class : 30 Meeting the : EN60730-1(1995), EN55014-1(1997), following EN55014-2(1996), ETSI EN300 220-3(2000), standards ETSI EN301 489-3(2000)
2
wire
TEMPERATURE CONTROL
Sensing element : 100K (@ 25 oC ) NTC thermistor
TIME SETTING / PROGRAMMING
Time display : 24 hour or 12 hour AM/PM format Time keeping
accuracy Program : 7-day with 6 daily time and temperature
Time setting resolution
Temperature setting range
Room Temperature display range
: Typically better than 10 minutes per
year
level changes
: Time of day - 1 minute
Program – 10 minute steps
o
: Program : 5 to 30
Frost : 5 to 16
: From 0
0.5
o
C or equal to lower limit (5 oC
o
C).
o
C to 40 oC (Display resolution
o
C)
C in 0.5 oC steps
EN0H0551GE51 R0905
CM 67 RFMV
APPLICATION A
Mixing Valve Application for UFH without boiler feedback
Mixing Valve Application for UFH without boiler feedback
Mixing Valve Application for UFH without boiler feedback
CM67RFMV with parameter
CM67RFMV with parameter
M67RFMV with parameter
C
ttings
se
ttings
se
ttings
se
mp after runnin g time 099 min
Pu
mp after runnin g time 0…99 min
Pu
mp after runnin g time 0…99 min
Pu
ctuator running time 0…240 s
A
ctuator running time 0…240 s
A
ctuator running time 0…240 s
A
in flow tempera ture setpoint 0…50°C
M
in flow tempera ture setpoint 0…50°C
M
in flow tempera ture setpoint 0…50°C
M
x flow temperature setpoint 0…99°C
Ma
x flow temperature setpoint 0…99°C
Ma
x flow temperature setpoint 0…99°C
Ma
CM67RFMV
CM67RFMV
CM67RFMV
Tshe HM80 controls the mixing valve depending on the room temperature
Tshe HM80 controls the mixing valve depending on the room temperature
Tshe HM80 controls the mixing valve depending on the room temperature
etpoint and communicates with the CM67RFMV. In addition the controller
etpoint and communicates with the CM67RFMV. In addition the controller
etpoint and communicates with the CM67RFMV. In addition the controller as a relay output for pump control and connection for the flow sensor.
h
as a relay output for pump control and connection for the flow sensor.
h
as a relay output for pump control and connection for the flow sensor.
h
t using the flow sensor the mixing valve position is adjusted in accordance with
Withou
t using the flow sensor the mixing valve position is adjusted in accordance with
Withou
t using the flow sensor the mixing valve position is adjusted in accordance with
Withou
he room setpoint t emperature and the actual room temperature.
t
he room setpoint t emperature and the actual room temperature.
t
he room setpoint t emperature and the actual room temperature.
t
f the flow sensor is used the mixing valve position is adjusted in accordance with the
I
f the flow sensor is used the mixing valve position is adjusted in accordance with the
I
f the flow sensor is used the mixing valve position is adjusted in accordance with the
I
alculated flow temperature setpoint and the measured flow temperature. The flow
c
alculated flow temperature setpoint and the measured flow temperature. The flow
c
alculated flow temperature setpoint and the measured flow temperature. The flow
c
emperature setpoint is calculated from the room temperature setpoint and the act ual
t
emperature setpoint is calculated from the room temperature setpoint and the act ual
t
emperature setpoint is calculated from the room temperature setpoint and the act ual
t
m temperature deviation.
roo
m temperature deviation.
roo
m temperature deviation.
roo
APPLICATION B
Set-up specific applications parameters Enable special features
Establish support for ATS module
Special Features Description Setting Pump after running time
Mixing valve running time Adjust mixing valve running time (default 150s) Flow temperature max. Maximum flow temperature limit. Flow temperature min. Minimum flow temperature limit.
If the mixing valve is closed the pump continuous run for to the set run time
Flow temperature sensor
Flow temperature sensor
Flow temperature sensor
Flow temperature sensor T7414C1012 (optional)
T7414C1012 (optional)
T7414C1012 (optional)
T7414C1012 (optional)
HM80
HM80
HM80
HM80
Pump
Pump
Pump
Pump
M
M
M
M
Mixing Valve
Mixing Valve
Mixing Valve
Mixing Valve
0…….99 minutes
0…...240s 0……99°C
0…....50°C
EN0H0551GE51 R0905
CM 67 RFMV
Mixing Valve Application for UFH with boiler feedback
Mixing Valve Application for UFH with boiler feedback
CM67RFMV with parameter
CM67RFMV with parameter settings
settings
Pump after running time 099 min
Pump after running time 0…99 min Actuator running time 0…240 s
Actuator running time 0…240 s Min flow temperature setpoint 050°C
Min flow temperature setpoint 0…50°C Max flow temperature set point 0…99°C
Max flow temperature set point 0…99°C
CM67RFMV
CM67RFMV
Flow temperature sensor
Flow temperature sensor T7414C1012 (optional)
T7414C1012 (optional)
HM80
HM80
M
M
Pump
Pump
Mixing Valve
Mixing Valve
HC60NG
HC60NG R6660D
R6660D
Boiler feedback
Boiler feedback
Boiler
Boiler
Automation and Control Solutions
Honeywell GmbH Boeblinger Strasse 17 D-71101 Schoenaich Phone: (49) 7031 63701 Fax: (49) 7031 637493
http://europe.hbc.honeywell.com
Subject to change without notice. Printed in Germany Manufacturing location certified to
EN0H0551GE51 R0905
Loading...