Honeywell CM67 User Manual

T
6
FEATURES
CM67
CHRONOTHERM
PRODUCTSPECIFICATION SHEET
he
M
7 Chronotherm is designed to provide automatic
time and temperature control of heating or cooling systems in villas and apartments. It can be used as part of a system in conjunction with combi boilers, oil- burners and gas fired boilers, circulation pumps, thermal actuators, zone valves and electric heat systems (<8A).
CM67 is designed with the installer in mind and includes
The a moulded backplate with trunking guides and wiring breakouts to make installation quick and easy.
CM67 display, buttons and slider layout are based on
The the same simple programming philosophy used on the acclaimed CM51 product. The unit is ideal for consumers who want reliable precise temperature control from a simple to program easy to use product.
Attractive slim styling makes it ideal for location in
any home.
7-day program
6 daily independent time and temperature level
changes let you set 6 time and temperatures pairs to suit your life style.
Temporary programmed temperature override to
temporarily override the programmed temperature till the next switch point.
Party button to temporarily maintain (or adjust)
the current temperature for 1-23 hours.
Day Off button copies Sunday’s program into
tomorrow or today to allow a rest day program without having to re-program the CM
67.
Holiday button provides energy savings by
reducing the temperature for 1 to 99 days when people are on holiday, returning to normal operation (AUTO or MANUAL) on the day of return.
EEPROM memory holds the user program
indefinitely.
Telephone Interface (optional) can be fitted to the
67 to allow switching between programmed mode
CM
(slider position) and fixed set-point of 21
o
C.
24...230V 8A resistive, 3A inductive SPDT relay
provides compatibility with most domestic central heating systems without stocking many different models.
urface or wallbox mounting options, trunking
guides and wiring breakouts simplify installation.
OFF position on the slider has an integral fixed frost
protection setting at minimum of 5°°°°C (installer adjustable) so that pipes in the house will never freeze in winter.
Installer Set-Up Mode allows extra functions to be
set at the discretion of the installer to match the consumers applications :
Optimisation
Pump Exercise
Upper / Lower Setpoint Limit Adjust
Temperature offset
Minimum ON time
Cycle rate
Heat / Cool Operation
Proportional Band Width
CM67 has provision for add-on modules to allow the
installer to sell additional features during or after the first CM additional sale.
67 installation, giving the installer an
Outside Temperature Sensor accessory (optional)
can be fitted to the CM temperature.
67 to display the external
Remote Temperature Sensor (optional) can be fitted
to the CM room.
67 to control the temperature from another
EN0R 8498 R2 11/98
CM67 CHRONOTHERM
T
c
±
a
CM67 CONTROLS/DISPLAY LAYOUT
SPECIFICATIONS
Batteries : 2 x 1.5 V IEC LR6 (AA) Alkaline cells Battery life : 4 years typical (Duracell MN1500) for
applications with loads <3A
: 3 years typical for electric heat
applications (>3A, <8A)
Battery replacement
Switch type : SPDT (potential free) Electrical rating : 230 V~, 50...60 Hz, 0.5 A to 8 A resistive
Time display : 24 hour or 12 hour AM/PM format Time keeping
accuracy Program : 7-day with 6 daily time and temperature
Time setting resolution
Sensing element : 100K (@ 25 Temperature
setting range
: Program retained in EEPROM
0.5 A to 3 A inductive (0.6 pf) 24 V~, 50...60 Hz, 0.5 A to 8 A resistive
0.5 A to 3 A inductive (0.6 pf)
: Typically better than 10 minutes per year
level changes
: Time of day - 1 minute
Program - 10 minute steps
o
C)NTCthermistor
o
: Program : 5 to 30
Frost : 5
o
Cto16oC). Frost protection does not
(5
Cin0.5oCsteps
o
C or equal to lower limit
work in cooling mode
emperature
ontrol accuracy
Room
:
0.5 K (nominal) @ 20oC, 50% load
3K/hour
: From 0
o
Cto40oC Temperature display range
Control form Minimum ON
time
: P + I (Proportional + Integral) : 10% of cycle time (min one minute),
adjustable to 2 to 5 min (see installer set up)
Cycle rate
: 3, 6( default), 9, 12. Selectable through
the installer set up mode.
Wiring
: Terminal block capable of accepting
wiresupto2.5mm
2
Wire access : Mains wiring - rear, left or below
Low voltage wiring - rear, left or below
Dimensions
: 130 x 87R(82L) x 29 mm (w x h x d)
130 x 172 x 29 mm (w x h x d) (flap open)
Environmental
: Operating temperature range 0 to 40
Shipping and storage temperature range
-20to55
o
C Humidity range 0 to 90% rh, non­condensing
Approvals
: Designed to meet European EN
pprovals EN60730-1(1995), EN55014-1
(1997), EN55014-2 (1996)
o
C
EN0R 8498 R2 11/98 2
INSTALLER SET-UP
To enter the installer set-up mode : a) Set the program slider to OFF.
b) Press and hold Info
together.
c) The unit will display the first parameter of the installer
parameter group category 1 (from n.1 to n.5).
d) Press TEMP
display will flash indicating that a change has been made.
e) Press INFO
i button to confirm the change. The display
will stop flashing.
f) Press
+or-togotonextparameter.
g) Press PROG 2 button to go to Installer parameter group
category 2 (from parameter n.6 to parameter n.16).
h) To exit installer mode move the slider in MAN or AUTO
position.
i button and press PROG 3,4
or to change factory setting. The
Installer Set-upNumber
(Press + or - to change)
e.g. 1 = Optimisation
Installer Set-UpMode
Selected
CM67 CHRONOTHERM
Abbreviated Set-Up Description
e.g. OP = Optimisation
1
In Installer set up we can :
Set-up specific applicationsEnable special featuresEstablish support for Optional Accessories
Specific Applications Setting What do you need to change ?
Heating Gas Boilers
(<30KW) Oil Boiler 3 4 1. Set Minimum ON Time to 4 m inutes.
Thermal Actuator
Zone valve 6 1 No action required. Electric heating
(for applications <8A)
Cycle/ Hour
Minimum ON time
(in minutes)
6 1 No action required
12 1 Set Cycle/Hour to 12.
12 1 1. Configure the Chronotherm for electric heating (set parameter
Note :
a. To change Cycle/Hour, please go to parameter n. 9 in the
installer set-up mode.
b. To change Minimum ON Time, please go to parameter n. 2 in
the installer set-up mode.
2. Set Cycle/Hour to 3.
n.7 in the installer set up mode to 1).
2. Set Cycle/Hour to 12.
Factory Setting or New Choice
Press TEMP or to change
e.g. O = Optimisation disabled
1 = Optimisation enabled
Air conditioning
Heat Pump/ Air conditioner
1. For cooling application only, set the Chronotherm to cooling (set parameter n.6 in the installer set-up mode to 0)
2. For heat/ cool application, set the Chronotherm accordingly to required mode of operation
winter = heating
summer = cooling by changing parameter n.6 in the installer set-up mode. Explain to the end-user how to implement the change-over.
3 4 1. Set Minimum ON Time to 4 minutes .
2. Set Cycle/Hour to 3.
3 EN0R 8498 R2 11/98