Honeywell CLLYUL4024S, CLLYVL4022AS, CLLYUL1012S, CLLYUL6438S, CLLYVL0000AS Product Data

...
LYNX LON Programmable
A
v
VAV/Unitary Controllers
Table 1. Controller configurations
model type
CLLYUL1012S unitary 1* 0 1 2 NO NO CLLYUL4024S unitary 4* 0 2 4 NO NO CLLYUL6438S unitary 6 4 3 8 NO NO CLLYVL0000AS VAV 0 0 0 0 YES YES CLLYVL4022AS VAV 4* 0 2 2 YES YES CLLYVL4024NS VAV 4* 0 2 4 YES NO CLLYVL6436AS VAV 6 4 3 6 YES YES
CLLYVL6438NS VAV 6 4 3 8 YES NO *One Universal Input (UI-1) is user-selectable as a fast digital pulse meter. All eight LYNX controllers communicate via the 78 kbps Echelon® L
interface, and are L The LYNX controllers are field-mountable to either a panel or a DIN rail.
ONMARK®-compliant.
Universal
Inputs (UI)
Digital
Inputs (DI)
Product Data
GENERAL
ONMARK®-compliant devices designed to control
HVAC equipment. LYNX controllers provide many options and advanced system
features that allow state-of-the-art commercial building control. Each LYNX controller is programmable and con­figurable through software.
LYNX controllers are designed for use in VAV (Variable Air Volume) and Unitary HVAC control applications. Each con­troller contains a host microcontroller to run the main HVAC application and a second microcontroller for L network communications. Each controller has flexible, uni­versal inputs for external sensors, digital inputs, and a mix of analog and digital triac outputs (see Table 1). The accom­panying image is of the model CLLYVL6436AS, which includes an actuator.
nalog Out-
puts (AO)
ONWORKS® Network, using the FTT-10A LONWORKS®
Digital Out-
puts (DO)
elocity pressure
sensor (Microbridge)
ONWORKS®
floating
actuator
Copyright © 2015 Honeywell GmbH All Rights Reserved EN0Z-0957GE51 R0615
LYNX LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
TECHNICAL DATA
GENERAL SPECIFICATIONS
Rated voltage: 20 … 30 VAC; 50/60 Hz Power consumption: 100 VA for controller and all connected
Controller-only load: 5 VA max. (CLLYUL1012S,
Controller + actuator load: 9 VA max. (CLLYVL0000AS,
External sensors power output:
VAV OPERATING & STORAGE TEMPERATURE AMBIENT RATING
CLLYVL0000AS, CLLYVL4022AS, CLLYVL6436AS, CLLYVL4024NS, and CLLYVL6438NS:
CLLYUL1012S, CLLYUL4024S, and CLLYUL6438S:
Relative humidity: 5 … 95%, non-condensing LED: Provides status for normal operation, con-
VELOCITY PRESSURE SENSOR (CLLYVL0000AS, CLLYVL4022AS, CLLYVL6436AS & CLLYVL6438NS, ONLY)
Operating range: 0 … 374 Pa
FLOATING ACTUATOR (CLLYVL0000AS, CLLYVL4022AS, AND CLLYVL6436AS)
Rotation stroke: 95° ± 3° for CW/CCW-opening dampers Torque rating: 5 Nm Runtime for 90° rotation: 90 sec at 60 Hz Operating temperature: -20 … +60 °C
REAL-TIME CLOCK
Operating range: 24-hr, 365-day, multi-year calendar, incl.
Power failure back-up: 24 hrs at 0 … +38 °C,
Accuracy: ±1 minute per month at 25 °C
DIGITAL INPUT (DI) CIRCUITS
Voltage rating: 0 … 30 Vdc open circuit Input type: Dry contact to detect open / closed circuit Operating range: Open circuit = FALSE,
Resistance: Open circuit > 3k Ω,
DIGITAL TRIAC OUTPUT (DO) CIRCUITS
Voltage rating: 20 … 30 VAC at 50/60 Hz Current rating: 25 … 500 mA continuous, and 800 mA
loads (incl. actuator on CLLYVL0000AS, CLLYVL4022AS, and CLLYVL6436AS)
CLLYUL4024S, and CLLYUL6438S and CLLYVL6438NS)
CLLYVL4022AS, and CLLYVL6436AS) 20 Vdc ± 10% at 75 mA, max.
0 … +50 °C
-40 … +65.5 °C
troller download process, alarms, manual mode, and error conditions
day of week and configuration for auto­matic daylight savings time adjustment to occur at 2:00 a.m. local times on configured start and stop dates
22 hrs at 38 … 50 °C
closed circuit = TRUE
closed circuit < 500
(AC rms) for 60 ms.
ANALOG OUTPUT (AO) CIRCUIT
Configuration for current / voltage:
Configuration as digital outputs:
Analog current outputs
Current output range: 4 … 20 mA Output load resistance: 550 , max.
Analog voltage outputs
Voltage output range: 0 … 10 Vdc Max. output current: 10.0 mA
UNIVERSAL INPUT (UI) CIRCUITS
See
All 3 analog outputs can be individually configured for current or voltage.
FALSE (0%) -> 0 Vdc (0 mA) TRUE (100%) -> max., 11 Vdc (22 mA)
Table
2 for UI circuit specifications.
Table 2. Universal input circuit specifications
input type sensor type operating range
room/zone discharge air
20k NTC -40 … +93 °C
outdoor air temperature resistive input generic 100 … 100k voltage input transducer,
0 … 10 Vdc
controller
discrete input dry contact
closure
open circuit > 3k Ω; closed circuit < 3k
BEFORE INSTALLATION
The controller is available in eight models (see Table 1). Before installing the controller, review the power, input, and
output specifications in section “Technical Data”. Hardware driven by Triac outputs must have a min.
current draw, when energized, of 25 mA and a max. current draw of 500 mA.
Hardware driven by the analog current outputs must have
a max. resistance of 550 , resulting in a max. voltage of 11 V when driven at 20 mA. If resistance exceeds 550 Ω, voltages up to 18 Vdc are possible at the analog output terminal.
WARNING
Electrical Shock Hazard. Can cause severe injury, death or property damage.
To prevent electrical shock or equipment damage, disconnect power supply before beginning wiring or making wiring connections.
INSTALLATION
The controller must be mounted in a position that allows clearance for wiring, servicing, removal, connection of the L
ONWORKS® Bus Jack and access to the Neuron® Service
Pin (see Fig. 13). The controller may be mounted in any orientation.
EN0Z-0957GE51 R0615 2
LYNX LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
IMPORTANT
Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller, or in areas where escaping gas or other explosive vapors are present. See Fig. 4 and Fig. 7 for mounting dimensions.
In the case of the CLLYVL0000AS, CLLYVL4022AS, and CLLYVL6436AS models, first the actuator and then the controller is mounted. For the other models, see section “Mount Controller” on page 4 to begin the installation.
Mounting Actuator onto Damper Shaft (Models with Actuator)
The CLLYVL0000AS, CLLYVL4022AS, and CLLYVL6436AS controllers include the direct-coupled actuator with DECLUTCH button, which is shipped hard-wired to the controller.
The actuator mounts directly onto the VAV box damper shaft and has up to 5 Nm torque, 90° stroke, and 90-sec timing at 60 Hz. The actuator is suitable for mounting onto a 10 to 13 mm square or round VAV box damper shaft. The min. VAV box damper shaft length is 40 mm.
The two mechanical end-limit set screws control the amount of rotation from 12° to 95°. These set screws must be securely fastened in place. To ensure tight closing of the damper, the shaft adapter has a total rotation stroke of 95° (see Fig. 1).
NOTE 1: The actuator is shipped with the mechanical end
NOTE 2: The DECLUTCH button, when pressed, allows you
LIMIT SET SCREWS (2)
limit set screws set to 95° of rotation. Adjust the two set screws closer together to reduce the rotation travel. Each “hash mark” indicator on the bracket represents approximately 6.5° of rotation per side.
to rotate the universal shaft adapter (see Fig. 1).
UNIVERSAL SHAFT
UNIVERSAL SHAFT
ADAPTER
MECHANICAL END
CLAMPING BOLTS (2)
IMPORTANT
Determine the damper rotation and opening angle prior to installation. See Fig. 2 and Fig. 3 for examples.
DAMPER
DAMPER SHAFT
ROTATES CW
TO OPEN
Fig. 2. Damper with 90° clockwise rotation to open
IMPORTANT
Mount actuator flush with damper housing or add a spacer between the actuator mounting surface and damper box housing.
Before Mounting Actuator onto Damper Shaft (Models with Actuator)
Tools required:
Phillips #2 screwdriver - end-limit set screw adjustment 8 mm wrench - centering clamp
Before mounting the actuator onto the VAV box damper shaft, determine the following:
1. Determine the damper shaft diameter. It must be
10…13 mm.
2. Determine the length of the damper shaft. If the length of
the VAV box damper shaft is less than 40 mm, the actuator cannot be used.
3. Determine the direction the damper shaft rotates to open
the damper (CW or CCW) (see Fig. 3). Typically, there is an etched line on the end of the damper shaft indicating the position of the damper. In Fig. 2, the indicator shows the damper open in a CW direction.
4. Determine the damper full opening angle (45, 60, or 90°).
In Fig. 2, the damper is open to its full open position of 90°.
DECLUTCH
BUTTON
Fig. 1. Floating actuator
EN0Z-0957GE51 R0615
3
LYNX LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
TYPE A DAMPER
AIR
FLOW
CW TO OPEN, CCW TO CLOSE
TYPE B DAMPER
AIR
FLOW
CCW TO OPEN, CW TO CLOSE
Fig. 3. Determining rotation direction (CW or CCW) for
damper opening
Mounting Actuator Onto Damper Shaft (Models with Actuator)
The unit is shipped with the actuator set to rotate open in the clockwise (CW) direction to a full 95°. The extra 5° ensures a full opening range for a 90° damper.
The installation procedure varies depending on the damper opening direction and angle:
1) If the damper rotates CW to open, and the angle of the damper open-to-closed is 90°:
a) Manually open the damper fully (rotate CW). b) Using the DECLUTCH button, rotate the universal
shaft adapter fully CW. c) Mount the actuator to the VAV damper box and shaft. d) Tighten the two bolts on the centering clamp (8 mm
wrench; 8...10 Nm torque). When the actuator closes,
the damper rotates CCW 90° to fully close.
2) If the damper rotates CW to open, and the angle of the damper open-to-closed is 45 or 60°:
a) Manually open the damper fully (rotate CW). b) The actuator is shipped with the mechanical end-limits
set at 95°. Adjust the two mechanical end-limit set screws to provide the desired amount of rotation. Adjust the two set screws closer together to reduce the rotation travel.
c) Tighten the two mechanical end-limit screws (Phillips
#2 screwdriver; (3.0-3.5 Nm torque).
d) Using the DECLUTCH button, rotate the universal
shaft adapter fully CW. e) Mount the actuator to the VAV damper box and shaft. f) Tighten the two bolts on the centering clamp (8 mm
wrench; 8...10 Nm torque). g) When the actuator closes, the damper rotates CCW
either 45 or 60° to fully close.
3) If the damper rotates CCW to open, and the angle of the damper open-to-closed is 90°:
a) Manually open the damper fully (rotate CCW).
b) Using the DECLUTCH button, rotate the universal
shaft adapter fully CCW. c) Mount the actuator to the damper box and shaft. d) Tighten the two bolts on the centering clamp (8 mm
wrench; 8...10 Nm torque). When the actuator closes,
the damper rotates CW 90° to fully close.
4) If the damper rotates CCW to open, and the angle of the damper open-to-closed is 45 or 60°:
a) Manually open the damper fully (rotate CCW). b) The actuator is shipped with the mechanical end-limits
set at 95°. Adjust the two mechanical end-limit set screws to provide the desired amount of rotation. Adjust the two set screws closer together to reduce the rotation travel.
c) Tighten the two mechanical end-limit screws (Phillips
#2 screwdriver; (3.0-3.5 Nm torque).
d) Using the DECLUTCH button, rotate the universal
shaft adapter fully CCW. e) Mount the actuator to the VAV damper box and shaft. f) Tighten the two bolts on the centering clamp (8 mm
wrench; 8...10 Nm torque). g) When the actuator closes, the damper rotates CW
either 45 or 60° to fully close.
IMPORTANT
Special precautions must be taken for dampers that
open in a CCW direction. The actuator is shipped with
its rotation direction set to CW to open, which applies
to the damper direction in steps 1 and 2 above. If the
damper shaft rotates in the CCW direction to open, the
controller software must be programmed to change the
rotation to “Reverse to Open,” which applies to the
damper direction in steps 3 and 4 above.
IMPORTANT
To avoid the possibility of over-pressurizing the duct
work on fan start-up, it is advisable to leave the
dampers in an open position after installation. To
prevent over-pressurization in the duct work on fan
start-up, use the DECLUTCH button (see Fig. 1) to
open the box damper on powered-down controllers. To
declutch, press and hold the DECLUTCH button, thus
disengaging the motor. Turn the damper shaft until the
damper is open and then release the DECLUTCH
button. When power is restored to the controller, the
controller synchronizes the damper actuator, so that
the damper is in the correct position upon start-up.
Mount Controller
NOTE: The controller may be wired before mounting to a
Terminal blocks are used to make all wiring connections to the controller. Attach all wiring to the appropriate terminal blocks (see section “Wiring” on page 7).
See Fig. 4 and Fig. 7 for panel mounting dimensions. See Fig. 8 for DIN rail mounting.
panel or DIN rail.
EN0Z-0957GE51 R0615 4
LYNX LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
159 149
11111111121
56789009
1234
12345678
PANEL MOUNTING
HOLE (4 X 4.5)
211
49105
DEPTH = 57
21
159
Fig. 4. Duct mounting, dimensions in mm
(CLLYVL0000AS, CLLYVL4022AS, and CLLYVL6436AS)
262
211
146
128
PANEL MOUNTING
HOLE (4 X 4.5)
12345678 1
164
2222222222 12345678901234567890
333333333
11111111
23456709
4
47
DEPTH = 57
11
159
Fig. 5. Duct mounting – controller and actuator,
dimensions in mm (CLLYVL6436AS, only)
122 122
105 105
11111 2222211
33
5678900
12
44
159 159149 149
11
34567890
11
22
PANEL MOUNTING
HOLE (4 X 4.5)
11111 2222211
33
5678900
12
44
DEPTH = 57DEPTH = 57
11
34567890
11
22
PANEL MOUNTING
HOLE (4 X 4.5)
Fig. 6. Panel mounting, dimensions in mm
(CLLYUL1012S, CLLYUL4024S, and CLLYVL4024NS,
only; CLLYUL4024S, and CLLYVL4024NS shown)
Panel Mounting
The controller enclosure is constructed of a plastic base plate and a plastic factory-snap-on cover.
22222222223333333334
5678901234567890
1234
CLLYVL6438NS
146
139
128
DEPTH = 57
1234
5678
11111111 1
234
164 174
164
22222222223333333334 12345678901234567890
CLLYUL6438S
139
128
Fig. 7. Panel mounting, dimensions in mm
NOTE: The controller is designed so that the cover does
The controller mounts using four screws inserted through the corners of the base plate. Fasten securely with four screws.
The controller can be mounted in any orientation. Ventilation openings are designed into the cover to allow proper heat dissipation, regardless of the mounting orientation.
DIN Rail Mounting (Models without Actuator)
To mount the CLLYUL1012S, CLLYUL4024S, and CLLYUL6438S or CLLYVL6438NS controller onto a DIN rail, see Fig. 8 and perform the following steps:
1. Holding the controller with its top tilted in towards the DIN rail, hook the two top tabs on the back of the controller onto the top of the DIN rail.
2. Push down and in to snap the two bottom flex connectors of the controller onto the DIN rail.
DEPTH = 57
12345678
11111111 1
23456709
(CLLYVL6438NS and CLLYUL6438S)
not need to be removed from the base plate for either mounting or wiring.
56709
EN0Z-0957GE51 R0615