Honeywell CLLYVB4024NS, CLLYUB1012S, CLLYUB6438S, CLLYVB4022AS, CLLYVB6436AS Product Data

...
LYNX BACnet® Programmable
A
(A
VAV/Unitary Controllers
Product Data
GENERAL
LYNX controllers provide many options and advanced system features that allow state-of-the-art commercial building control. Each LYNX controller is programmable and con­figurable using the COACH
LYNX BACnet controllers require the LYNX BACnet Pro­grammable Feature to be licensed in COACH
LYNX controllers are designed for use in VAV (Variable Air Volume) and Unitary HVAC control applications. Each con­troller contains a host microcontroller to run the main HVAC application and a second microcontroller for BACnet MS/TP network communications. Each controller has flexible, universal inputs for wall modules, digital inputs, and a mix of analog and digital triac outputs (see Table 1). The models CLLYVB6436AS, CLLYVB0000AS, and CLLYVB4022AS include an actuator.
AX
software.
AX
.
Table 1. Controller configurations
model type
CLLYUB1012S unitary 1(A 0 1 2 NO NO CLLYUB4024S unitary 4(A 0 2 4 NO NO CLLYUB6438S unitary 6 4 3 8 NO NO CLLYVB0000AS VAV 0 0 0 0 YES YES CLLYVB4022AS VAV 4(A 0 2 2 YES YES CLLYVB4024NS VAV 4(A 0 2 4 YES NO CLLYVB6436AS VAV 6 4 3 6 YES YES CLLYVB6438NS VAV 6 4 3 8 YES NO
One Universal Input (UI-1*) is selectable as a fast digital pulse meter.
All of the LYNX controllers communicate via an EIA-485 BACnet MS/TP communication network, capable of baud rates of between 9.6 and 115.2 kbits/sec.
The LYNX controllers are field-mountable to either a panel or a DIN rail.
Universal
Inputs (UI)
Digital
Inputs (DI)
nalog Out-
puts (AO)
Digital Out-
puts (DO)
velocity pressure
sensor (Microbridge)
floating
actuator
Copyright © 2015 Honeywell GmbH All Rights Reserved EN0Z-0959GE51 R0615
LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
TECHNICAL DATA
GENERAL SPECIFICATIONS
Rated voltage: 20 … 30 Vac; 50/60 Hz Power consumption: 100 VA for controller and all connected
Controller-only load: 5 VA max. (S- and NS-models) Controller + actuator load: 9 VA max. (AS-models) Wall modules
output:
VAV OPERATING & STORAGE TEMPERATURE AMBIENT RATING
VAV models: 0 … +50 °C Unitary models: -40 … +65.5 °C Relative humidity: 5 … 95%, non-condensing LED: Provides status for normal operation, con-
VELOCITY PRESSURE SENSOR (VAV MODELS)
Operating range: 0 … 374 Pa
FLOATING ACTUATOR (AS-models)
Rotation stroke: 95° ± 3° for CW/CCW-opening dampers Torque rating: 5 Nm Runtime for 90° rotation: 90 sec at 60 Hz Operating temperature: -20 … +60 °C
REAL-TIME CLOCK
Operating range: 24-hr, 365-day, multi-year calendar, incl.
Power failure back-up: 24 hrs at 0 … +38 °C,
Accuracy: ±1 minute per month at 25 °C
DIGITAL INPUT (DI) CIRCUITS
Voltage rating: 0 … 30 Vdc open circuit Input type: Dry contact to detect open / closed circuit Operating range: Open circuit = FALSE,
Resistance: Open circuit > 3k ,
DIGITAL TRIAC OUTPUT (DO) CIRCUITS
Voltage rating: 20 … 30 Vac at 50/60 Hz Current rating: 25 … 500 mA continuous, and 800 mA
ANALOG OUTPUT (AO) CIRCUIT
Configuration for current / voltage:
Configuration as digital outputs:
Analog current outputs
Current output range: 4 … 20 mA Output load resistance: 550 , max.
Analog voltage outputs
Voltage output range: 0 … 10 Vdc Max. output current: 10.0 mA
UNIVERSAL INPUT (UI) CIRCUITS
See Table 2 for UI circuit specifications.
power
loads (incl. actuator on AS-models)
20 Vdc ± 10% at 75 mA, max.
troller download process, alarms, manual mode, and error conditions
day of week and configuration for auto­matic daylight savings time adjustment to occur at 2:00 a.m. local times on configured start and stop dates
22 hrs at 38 … 50 °C
closed circuit = TRUE
closed circuit < 500
(AC rms) for 60 ms.
Up to 3 analog outputs can be individually configured for current or voltage.
FALSE (0%) -> 0 Vdc (0 mA) TRUE (100%) -> max., 11 Vdc (22 mA)
Table 2. Universal input circuit specifications
input type sensor type operating range
Room/Zone Discharge Air Outdoor Air Temp.
Outdoor Air Temperature
Resistive Input Generic 100 …100 k
Voltage Input Transducer,
Discrete Input Dry Contact
Pulse Input(A Counter/Meter Max. frequency: 15 Hz
(A
One Universal Input (UI-1*) is selectable as a fast digital pulse
meter.
NTC 20kOhm -40 ... +93 °C
PT1000 (IEC751 3850)
Controller
closure
-40 ... +93 °C
0 … 10 Vdc
OpenCircuit 3000 ClosedCircuit < 3000
Min. pulse width: 20 ms
NTC 20kOhm are recommended for use with these con­trollers, due to improved resolution and accuracy when compared to the PT1000.
BEFORE INSTALLATION
The controller is available in eight models (see Table 1). Before installing the controller, review the power, input, and
output specifications in section “Technical Data”. Hardware driven by Triac outputs must have a min.
current draw, when energized, of 25 mA and a max. current draw of 500 mA.
Hardware driven by the analog current outputs must have
a max. resistance of 550 , resulting in a max. voltage of 11 V when driven at 20 mA. If resistance exceeds 550 , voltages up to 18 Vdc are possible at the analog output terminal.
WARNING
Electrical Shock Hazard. Can cause severe injury, death or property damage.
To prevent electrical shock or equipment damage, disconnect power supply before beginning wiring or making wiring connections.
INSTALLATION
The controller must be mounted in a position that allows clearance for wiring, servicing, removal, connection of the BACnet MS/TP Molex connector and access to the MS/TP MAC address DIP switches (see Fig. 12).
The controller may be mounted in any orientation.
IMPORTANT
Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller, or in areas where escaping gas or other explosive vapors are present. See Fig. 4 and Fig. 6 for mounting dimensions.
EN0Z-0959GE51 R0615 2
LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
In the case of the AS-models, first the actuator and then the controller is mounted. For the other models, see section “Mount Controller” on page 4 to begin the installation.
Mounting Actuator onto Damper Shaft (AS­Models)
The AS-models include the direct-coupled actuator with DECLUTCH button, which is shipped hard-wired to the controller.
The actuator mounts directly onto the VAV box damper shaft and has up to 5 Nm torque, 90° stroke, and 90-sec timing at 60 Hz. The actuator is suitable for mounting onto a 10 to 13 mm square or round VAV box damper shaft. The min. VAV box damper shaft length is 40 mm.
The two mechanical end-limit set screws control the amount of rotation from 12° to 95°. These set screws must be securely fastened in place. To ensure tight closing of the damper, the shaft adapter has a total rotation stroke of 95° (see Fig. 1).
NOTE 1: The actuator is shipped with the mechanical end
NOTE 2: The DECLUTCH button, when pressed, allows you
LIMIT SET SCREWS (2)
limit set screws set to 95° of rotation. Adjust the two set screws closer together to reduce the rotation travel. Each “hash mark” indicator on the bracket represents approximately 6.5° of rotation per side.
to rotate the universal shaft adapter (see Fig. 1).
UNIVERSAL SHAFT
UNIVERSAL SHAFT
ADAPTER
MECHANICAL END
DECLUTCH
BUTTON
CLAMPING BOLTS (2)
DAMPER
DAMPER SHAFT
ROTATES CW
TO OPEN
Fig. 2. Damper with 90° clockwise rotation to open
IMPORTANT
Mount actuator flush with damper housing or add a spacer between the actuator mounting surface and damper box housing.
Before Mounting Actuator onto Damper Shaft (AS-Models)
Tools required:
Phillips #2 screwdriver - end-limit set screw adjustment 8 mm wrench - centering clamp
Before mounting the actuator onto the VAV box damper shaft, determine the following:
1. Determine the damper shaft diameter. It must be 10…13 mm.
2. Determine the length of the damper shaft. If the length of the VAV box damper shaft is less than 40 mm, the actuator cannot be used.
3. Determine the direction the damper shaft rotates to open the damper (CW or CCW) (see Fig. 3). Typically, there is an etched line on the end of the damper shaft indicating the position of the damper. In Fig. 2, the indicator shows the damper open in a CW direction.
4. Determine the damper full opening angle (45, 60, or 90°). In Fig. 2, the damper is open to its full open position of 90°.
TYPE A DAMPER
AIR
FLOW
CW TO OPEN, CCW TO CLOSE
TYPE B DAMPER
Fig. 1. Floating actuator
IMPORTANT
Determine the damper rotation and opening angle prior to installation. See Fig. 2 and Fig. 3 for examples.
Fig. 3. Determining rotation direction (CW or CCW) for
AIR
FLOW
CCW TO OPEN, CW TO CLOSE
damper opening
EN0Z-0959GE51 R0615
3
LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
A
A V A
V
V A
V
Mounting Actuator Onto Damper Shaft (AS­Models)
The unit is shipped with the actuator set to rotate open in the clockwise (CW) direction to a full 95°. The extra 5° ensures a full opening range for a 90° damper.
The installation procedure varies depending on the damper opening direction and angle:
1) If the damper rotates CW to open, and the angle of the damper open-to-closed is 90°:
a) Manually open the damper fully (rotate CW). b) Using the DECLUTCH button, rotate the universal
shaft adapter fully CW. c) Mount the actuator to the VAV damper box and shaft. d) Tighten the two bolts on the centering clamp (8 mm
wrench; 8...10 Nm torque). When the actuator closes,
the damper rotates CCW 90° to fully close.
2) If the damper rotates CW to open, and the angle of the damper open-to-closed is 45 or 60°:
a) Manually open the damper fully (rotate CW). b) The actuator is shipped with the mechanical end-limits
set at 95°. Adjust the two mechanical end-limit set screws to provide the desired amount of rotation. Adjust the two set screws closer together to reduce the rotation travel.
c) Tighten the two mechanical end-limit screws (Phillips
#2 screwdriver; (3.0-3.5 Nm torque).
d) Using the DECLUTCH button, rotate the universal
shaft adapter fully CW. e) Mount the actuator to the VAV damper box and shaft. f) Tighten the two bolts on the centering clamp (8 mm
wrench; 8...10 Nm torque). g) When the actuator closes, the damper rotates CCW
either 45 or 60° to fully close.
3) If the damper rotates CCW to open, and the angle of the damper open-to-closed is 90°:
a) Manually open the damper fully (rotate CCW). b) Using the DECLUTCH button, rotate the universal
shaft adapter fully CCW. c) Mount the actuator to the damper box and shaft. d) Tighten the two bolts on the centering clamp (8 mm
wrench; 8...10 Nm torque). When the actuator closes,
the damper rotates CW 90° to fully close.
4) If the damper rotates CCW to open, and the angle of the damper open-to-closed is 45 or 60°:
a) Manually open the damper fully (rotate CCW). b) The actuator is shipped with the mechanical end-limits
set at 95°. Adjust the two mechanical end-limit set screws to provide the desired amount of rotation. Adjust the two set screws closer together to reduce the rotation travel.
c) Tighten the two mechanical end-limit screws (Phillips
#2 screwdriver; (3.0-3.5 Nm torque).
d) Using the DECLUTCH button, rotate the universal
shaft adapter fully CCW. e) Mount the actuator to the VAV damper box and shaft. f) Tighten the two bolts on the centering clamp (8 mm
wrench; 8...10 Nm torque).
g) When the actuator closes, the damper rotates CW
either 45 or 60° to fully close.
IMPORTANT
Special precautions must be taken for dampers that open in a CCW direction. The actuator is shipped with its rotation direction set to CW to open, which applies to the damper direction in steps 1 and 2 above. If the damper shaft rotates in the CCW direction to open, the controller software must be programmed to change the rotation to “Reverse to Open,” which applies to the damper direction in steps 3 and 4 above.
IMPORTANT
To avoid the possibility of over-pressurizing the duct work on fan start-up, it is advisable to leave the dampers in an open position after installation. To prevent over-pressurization in the duct work on fan start-up, use the DECLUTCH button (see Fig. 1) to open the box damper on powered-down controllers. To declutch, press and hold the DECLUTCH button, thus disengaging the motor. Turn the damper shaft until the damper is open and then release the DECLUTCH button. When power is restored to the controller, the controller synchronizes the damper actuator, so that the damper is in the correct position upon start-up.
Mount Controller
NOTE: The controller may be wired before mounting to a
Terminal blocks are used to make all wiring connections to the controller. Attach all wiring to the appropriate terminal blocks (see section “Wiring” on page 6).
See Fig. 4 and Fig. 6 for panel mounting dimensions. See Fig. 7 for DIN rail mounting.
146
Fig. 4. Duct mounting, dimensions in mm (AS-models)
panel or DIN rail.
2122 23 24 2526 27 28 29 30 3132 33 34 35 36 37 38 39 40 AO-1
AO-2
AO-3
COM
PANEL MOUNTING
HOLE (4 X 4.5)
128
AS MODELS
BACnet MS/TP MAC
ADDRESS DIP SWITCHES
B
B
24
20
EGND
S-BUS
S-BUS
24
C+
C-
DC
C
C
COM
1 3 4 5 62 7 8 9 10 11 12 13 1415 16 17 18 19 20
211
164
DI-1
DI-2
COM
COM
DI-3
DI-4
20
UI-1
COM
DC
HOST
STATUS
LED
LOCAL BACnet MS/TP
MOLEX CONNECTOR PINS
DO-1
DO-2
DO-4
COM
DO-3
UI-2
COM
262
211
UI-3
COM
UI-4
UI-5
COM
UI-6
DEPTH = 57
DO-6
DO-8
COM
COM
DO-5
DO-7
11
159
Panel Mounting
The controller enclosure is constructed of a plastic base plate and a plastic factory-snap-on cover.
EN0Z-0959GE51 R0615 4
LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
V
V
V
V
A
A V A
V
V A
122 122
105 105
13 14 15 16 17 18 19 2021 22 23 24 1314 15 16 17 18 19 20 21 22 23 24 DO-2
COM
DO-1
COM
AO-1
UI-4
AO-2
COM
UI-3
UI-2
COM
UI-1*
HOST
STATUS
159 159149 149
CLLYUB4024S CLLYVB4024NS
BACnet MS/TP MAC
ADDRESS DIP SWITCHES
24
20
EGND
S-BUS
S-BUS
24VAC COM
AC
DC
1 3 4 5 62 7 8 9 10 1112 1 3 4 5 62 7 8 9 10 11 12
PANEL MOUNTING
HOLE (4 X 4.5)
LED
LOCAL BACnet MS/TP
MOLEX CONNECTOR PINS
BAC+
BAC-
SHIELD
DO-3
COM
DO-4
DO-2
COM
DO-1
COM
AO-1
AO-2
BACnet MS/TP MAC
ADDRESS DIP SWITCHES
24
20
EGND
S-BUS
S-BUS
24VAC COM
AC
DC
PANEL MOUNTING
HOLE (4 X 4.5)
UI-4
COM
UI-3
UI-2
COM
UI-1*
DEPTH = 57DEPTH = 57
LOCAL BACnet MS/TP
MOLEX CONNECTOR PINS
HOST
STATUS
LED
BAC+
BAC-
SHIELD
DO-3
COM
DO-4
Fig. 5. Panel mounting – dimensions (mm) for
CLLYUB1012S, CLLYUB4024S, and CLLYVB4024NS, only
(CLLYUB4024S and CLLYVB4024NS shown)
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
AO-1 AO-1
DI-1 DI-1
DI-2 DI-2
AO-2 AO-2
AO-3 AO-3
COM COM
COM COM
COM COM
DI-3 DI-3
DI-4 DI-4
20VDC 20VDC
UI-1 UI-1
UI-2 UI-2
UI-3 UI-3
UI-4 UI-4
UI-5 UI-5
UI-6 UI-6
COM COM
COM COM
DO-6 DO-6
DO-8 DO-8
COM COM
COM COM
DO-5 DO-5
DO-7 DO-7
146
139
128
DEPTH = 57
NS MODELS
BACnet MS/TP MAC
ADDRESS DIP SWITCHES
24VAC
BAC+
20VDC
EGND
S-BUS
S-BUS
24VAC COM
BAC-
COM COM
HOST
STATUS
LED
LOCAL BACnet MS/TP
MOLEX CONNECTOR PINS
DO-1 DO-1
DO-2 DO-2
DO-4 DO-4
COM COM
COM COM
DO-3 DO-3
The controller can be mounted in any orientation. Ventilation openings are designed into the cover to allow proper heat dissipation, regardless of the mounting orientation.
DIN Rail Mounting (S- and NS-models)
To mount the S- and NS-models onto a DIN rail, see Fig. 7 and perform the following steps:
1. Holding the controller with its top tilted in towards the DIN rail, hook the two top tabs on the back of the controller onto the top of the DIN rail.
2. Push down and in to snap the two bottom flex connectors of the controller onto the DIN rail.
IMPORTANT
To remove the controller from the DIN rail, perform the following:
1. Push straight up from bottom to release top tabs.
2. Rotate the top of the controller out towards you and pull the controller down and away from the DIN rail to release the bottom flex connectors.
TOP TABS
DIN RAIL
1 3 4562
7
8
9 10 11 12 13 14 15 16 17 18 19 20
164 174
164
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
139
128
DEPTH = 57
S MODELS
BACnet MS/TP MAC
ADDRESS DIP SWITCHES
24
C
134
B
20
EGND
S-BUS
S-BUS
24
C+
DC
C COM
5 627 8
B C-
LOCAL BACnet MS/TP
MOLEX CONNECTOR PINS
9 10
HOST
STATUS
11 121314
LED
15 161718 19 20
Fig. 6. Panel mounting, dimensions in mm (S- and NS-
models)
NOTE: The controller is designed so that the cover does
not need to be removed from the base plate for either mounting or wiring.
The controller mounts using four screws inserted through the corners of the base plate. Fasten securely with four screws.
BOTTOM FLEX CONNECTORS
Fig. 7. Controller DIN rail mounting (S- and NS-models)
Piping (AS- and NS-models)
Air Flow Pick-Up
For AS- and NS-models, connect the air flow pickup to the two restrictor ports on the controller (see Fig. 8).
NOTE 1: Use tubing with 6 mm outside diameter and 1 mm
NOTE 2: Always use a fresh cut on the end of the tubing that
Connect the high-pressure or upstream tube to the plastic restrictor port labeled (+), and the low-pressure or down­stream tube to the restrictor port labeled (-). See labeling in Fig. 8. When twin tubing is used from the pickup, split the pickup tubing a short length to accommodate the connections.
wall thickness.
connects to the air flow pickups and the restrictor ports on the controller.
EN0Z-0959GE51 R0615
5
Loading...
+ 11 hidden pages