Honeywell BK V2, BK V12 Operating Instructions Manual

Page 1
GB
F
NL
I
SK
1000243906-002-04
D GB I
www.docuthek.com
Operating instructions
White meters BK V to BK V (component of a diaphragm gas meter)
© 2017 Elster GmbH · Edition 06.17
Translation from the German

Contents

Contents
White meters BK V to BK V
(component of a diaphragm gas meter) ....
Contents ..............................
Safety.................................
Checking the usage .....................
White meters BK V2 to BK V12 .............2
Type code .............................2
Part designations ........................2
Type label/Marking .......................2
Integrated pressure and temperature
sensor (optional) .......................
Integrated valve (optional)................
Installation ............................
Temperature test point ..................4
Pressure test point on housing (optional) ...4
Connecting the piping ....................4
Pressure test point on outlet connector
(optional) ..............................5
Opening the test nipple ...................5
Closing the test nipple ....................5
Tightness test ..........................5
Commissioning.........................5
Maintenance/Removal...................5
Technical data .........................6
Declaration of conformity ................7
White meters BK V2 – V12 with explosion
protection ............................. 7
White meters BK V2 with explosion
protection and integrated valve Ve...........8
ATEX legend ...........................9
Contact ..............................0
Logistics ..............................9

Safety

Safety
Please read and keep in a safe place
carefully before installing or operating. Following the installation, pass the instructions on to the opera­tor. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com.
Explanation of symbols
• ,  ,  ,  ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from non-observance of the instructions and non-com­pliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
Please read through these instructions
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Changes to edition 0.6
The following chapters have been changed: – Checking the usage – Integrated valve – Technical data – Declaration of conformity
GB-1
Page 2
GB
F
NL
I
SK

Checking the usage

White meters BK V to BK V
White meters are components of diaphragm gas meters and cannot be operated independently. They are suitable for recording gas consumption values for natural gas, town gas, propane and butane, as gases of the first to third families pursuant to DINEN437:2003 (DVGWCode of PracticeG260), and can be extended to form complete diaphragm gas meters by installing an index.
The following sizes of gas meter can be assembled
from the listed white meters:
Meter Size
BK V G4 BK VS G4, G6 BK V6 G6, G10, G16 BK V G25
Potentially explosive atmosphere
White meters that are marked with and (see sticker on the base plate) are suitable for operation in potentially explosive atmospheres, see page7 (Declaration of conformity).
If a pressure/temperature sensor is integrated in the white meter, this must be included in the ATEX assessment of the control electronics.

Part designations

7
5
3
1
White meter BK V
Base plate with type label Connectors
4 Pressure test point to BS4161 (optional)
5 Protective caps 6 2 x thermowells (optional)
7 Pressure test point with sealing sleeve (optional)
8 Connection cable for internal pressure and tem-
perature sensor (optional)
9 Index drive (inner part of the magnetic coupling)

Type label/Marking

6
4
2
8
9
The meter function is only guaranteed when used
under the specified operating conditions– see page 6 (Technical data). Any other use is con­sidered as non-compliant.

Type code

Code Description
BK V Meter
 6 
S Increased flow cross-sections
Cyclic volume:
2 dm3 6 dm
12 dm
BK V..
DE–13–EC–PTB001
S/N:0025....
3 3
– Device designation BK V.. – Evaluation certificate No. DE-13... – Serial number S/N... – Manufacturer’s address – Year of construction
White meters with no integrated valve
– CE marking and ATEX identification
ATEX-compliant use is as follows:
Category: internal: none, external: Category 2 (Zone1).
Type of atmosphere: gases, hazes and vapours.
Elster GmbH Strotheweg 1 D-49504 Lotte Germany
II -/2 G c IIB TX
TÜV 11 ATEX 090370 X
2017
Valve Ve
GB-2
Page 3
GB
F
NL
I
SK
White meters with integrated valveVe
– CE marking and ATEX identification
II 3 G IIB T4
from the operating instructions for the control electronics.
▷ Technical data, see page 6 (Technical data).
17 ATEX 1431X
– Valve marking

Installation

Ve = bi-stable valve for electronic flow rate
testing ATEX-compliant use is as follows: Category: 3 (Zone2).
Type of atmosphere: gases, hazes and vapours.
WARNING
Please observe the following to ensure that neither persons nor the meter are damaged during instal­lation and operation:
– Note the max. allowable operating pres-

Integrated pressure and temperature sensor (optional)

As an option, a combined pressure/temperature sensor of type KP089 made by elgass.r.o. (Czech Republic) can be integrated in the meter. In this case, the conductors of the connection cable are assigned as follows:
surep page6 (Technical data).
– Note the permitted ambient temperaturetm and
gas temperaturetg, see page6 (Technical data).
– The white meters are certified for mechanical ambi-
ent conditions pursuant to Class M1 of Directive 2014/32/EU. When installed, the meters must
and measuring rangeQ
max
max
, see
not be subject to permanent vibration such as
1 2 3 4
VCC (voltage supply 2.8 to 3.6V)
SDA (data signal of the I²Cbus) GND (system ground) 4 SCL (clock signal of the I²Cbus)

Integrated valve (optional)

A valve of type Ve may be integrated in the meter as an option. This is marked on the type label below the year of construction with the note “Valve Ve”.
WARNING
Risk of explosion in explosion-hazard areas!
– The intrinsic safety of the control electronics
must be proven.
– When working on electrical equipment in an
explosion-hazard area, only design-approved electrical operating equipment may be used.
– Check that the electrical system complies with
the special electrical explosion protection re­quirements.
– Note the permitted connection ratings of the
interfaces. See page 6 (Technical data), White meters BK V with explosion protection and integrated valveVe.
A connection cable leads out of the meter.
There is a detailed specification for actuating the
valve and using the interface. Please contact the manufacturer.
The manufacturer of the control electronics is
responsible for creating the conditions required
commissioning and operation are to be taken
for safe operation of the valve. Instructions on
that caused by machines in the vicinity. In case of doubt, vibration isolation must be provided.
– When installing meters with integrated valves,
make sure that no dirt particles get into the meter and thus into the valve.
– The yellow sealing sleeve protects the pressure
test point on the meter. It may only be opened for connecting a pressure measuring line.
– Use seals made from tested materials. Elasto-
mer seals or asbestos-free flat seals from Elster
are recommended. – Only use the seals once. – For meters resistant to high temperatures, only use
seals tested to be resistant to high temperatures. – For installation and operation, note the applica-
ble national regulations and the directives of the
gas supply company. For Germany, the valid
DVGW Code of Practice G600 (DVGW-TRGI)
applies. –
Work on meters and the installation of meters which
are marked with and are installed in potentially
explosive atmospheres may only be carried out by
persons with appropriate qualifications. – The meter marked with must be included in
the equipotential bond when being installed in a
potentially explosive atmosphere, e.g. by connect-
ing it to a grounded pipeline. Installation must be
carried out in accordance with EN60079-14. – The meter marked with must be protected
from falling parts. – Avoid subjecting the unit to mechanical stress
and prevent damage. Gas meters must be in-
stalled without any mechanical stress, preferably
only by suspending them on the connectors.
When using additional clamps, it must be en-
sured that no lateral forces act on the gas meter.
These can be avoided by using flexible or supple
connection lines, for instance.
GB-3
Page 4
GB
F
NL
I
SK
If the meter is stored outdoors, protect the site
1 2
1
2
3
4
5
against rain.
If the drive area (magnetic coupling) is protected against the ingress of moisture by an index, then the meter is also suitable for outdoor installation.
Remove protective caps.
Installation in the vertical position: connectors must be pointing upwards.
Note direction of flow (arrow).
After installation, the completed gas meter must not be in contact with masonry or other parts.
Ensure that there is sufficient installation space.
The seal faces on the screw unions must be
clean and damage-free.
Ensure that the seal is correctly seated. For the compression of seals and the resulting
tightening torques for the screw unions, the seal manufacturers’ specifications must be observed.
Tightening torques for the recommended flat
seals in conjunction with screw connectors pursuant to DIN 3376-1 and 3376-2, see www.docuthek.com → Elster-Instromet Prod- ucts Gas measuring devices Diaphragm meters Ergänzung für Betriebsanleitung BK, Verschraubungen und Anzugsmomente für BK­G1,6 bis BK-G25 (Supplement to BK operating instructions, Screw unions and tightening tor­ques forBK-G1.6 toBK-G25)(D).
Install the meter free of mechanical stress.

Pressure test point on housing (optional)

Connecting the piping

WARNING
In order to ensure that the meter is tight:
– The pressure test nipple must not be twisted,
bent, or otherwise manipulated.
– When installing, always secure the pressure test
nipple using a suitable spanner.
Functional safety and reliability are ensured only if the material combination of the screw connector and the pressure line are inter-matched.
Only use the olive and the attached union nut supplied. The olive is secured to the sealing sleeve.
When re-ordering, use original Parker EO pro­gressive ring fittings PSR/DPR.
1
2
3

Temperature test point

Temperature sensors can be inserted into the
thermowells for measuring the gas temperature in the meter housing.
Secure each of the temperature sensors using
the capstan screw provided.
4
Use corrosion-resistant, seamless precision steel
5
tube pursuant to DINEN10305-4 (external di­ameter 6mm, material E235= 1.0308). For other materials, use a suitable adapter and note the Parker/EO recommendations.
▷ Install pipes free of mechanical stress.
6
7
8 Screw on the union nut by hand as far as it will
go.
At the same time, press the end of the pipe firmly against the stop.
9 Mark the position of the union nut and tighten
with about 1½ turns.
GB-4
Page 5
GB
F
NL
I
SK
1
6
7
2
3
4
5
2
2
2
When reinstalling, the union nut will be turned to the original position and then further tightened through approx. 30°.
0 Once the installation and tightness test are com-
plete, see page5 (Tightness test), protect the pressure test point against external access with the sealing sleeve and the seal.
▷ If a pressure measuring line has been retrofitted
to the meter, check this connection for tightness.

Pressure test point on outlet connector (optional)

BS4161-compliant pressure test nipple
Use a 10 mm spanner to release/tighten the test point screw.
The test nipple is secured to prevent it turning
with the screw.
If the BS4161-compliant test nipple on the meter
has been opened and then closed again, test
this connection for tightness.
After the tightness test, slowly vent the meter. 4 If a pressure measuring line has been retrofitted to
the meter, protect the pressure test point against
external access with a sealing sleeve and a seal.
Opening the test nipple  Remove the screw from the test nipple com-
pletely.
▷ The gas connection is open.
Closing the test nipple  Insert the screw by hand as far as possible.Tighten the screw with a torque of 3 Nm +

Commissioning

Once the tightness test has been successfully com­pleted, the meter is ready for operation. Where ap­plicable, further instructions are required for a fitted index.
▷ Slowly open the manual valve.
0.5Nm.
Check for tightness, see page 5 (Tightness
test).
WARNING
If the test nipple has unexpectedly come loose, the gas meter must be regarded as damaged and must be replaced.

Maintenance/Removal

Meters BKV2 to BKV12 from Elster are mainte­nance-free. Where applicable, further maintenance instructions are to be observed for a fitted index.
If the screw unions are loosened for maintenance
work or retesting, replace the seals.
▷ After the meter has been removed, immediately

Tightness test

Check the pipework for leaks prior to installation of the meter, in case the pipework is tested with a greater test pressure than the max. allowable operating pressure p the installed meter may be damaged.
for the meter. Otherwise,
max
▷ Ensure the customer’s consumers are closed.
Apply the test pressure slowly to the meter.
close the connectors with protective caps in
order to prevent ingress of dirt particles.
WARNING
A certain amount of gas may remain in the meter.
Taking into consideration the risk of explosion, it is
important to adopt safety measures, e.g.:
– Following removal of the meter, purge it thor-
oughly with inert gas. – For transporting the meter with gas residue, use
a vehicle with an open or a ventilated loading
area.
GB-5
Page 6
GB
F
NL
I
SK

Technical data

Gas type: natural gas, town gas, propane and
butane, as gases of the first to third families pursuant to DINEN437:2003 (DVGW Code of
PracticeG260).
– Note the max. allowable operating pres-
sure p
(non-HTR)
▷ HTR: high temperature resistance pursuant to
EN1359:1998+A1:2006, section 6.5.5
– Measuring range (in accordance with Evalua-
tion certificate DE-13-EC-PTB001):
Type Q
BK V2 0.04 / 6 BK V2S 0.04 / 6 BK V2S 0.06 / 10 BK V6 0.06 / 10 BK V6 0.06 / 16 BK V6 0.10 / 16 BK V6 0.10 / 25 BK V6 0.16 / 25 BK V12 0.25 / 40
– Max. allowable ambient temperature range
tm=-25°C to +55°C
– Max. allowable gas temperature range
tg* = -25°C to +55°C
– Cyclic volume V
BK V2, BK V2S: V = 2 dm³ BK V6: V = 6 dm³
BK V12: V = 12 dm³ – Transitional flow rate Qt = 0.1 x Q – Max. allowable storage temperature range:
-25°C to +60°C
– Mechanical environment class: M1
= 0.1 bar (HTR version)/0.5 bar
max
min/Qmax
in m³/h
max
White meters BK V with pressure test point
Pressure test point: 24° olive fitting to ENISO8434-1, L6x M12x1.5-St.
White meters BK V with integrated valve Ve
Max. operating pressure for valve operation:
100mbar.
▷ The operating pressure of the gas meter can be
higher if necessary.
Leakage flow (closed): max. 1 l/h up to 100 mbar.
White meters BK V with explosion protection
and integrated valveVe
For meters of Category3 which are marked with , the ambient temperature t ture t
are limited to a maximum range between
gas
-20°C and +55°C.
and the gas tempera-
amb
In addition, the following interface parameters apply for BKV: Ui = 4.1 V Ci = negligible Li = 3.82 mH
Supplementary notes: * If operated within the gas temperature range,
the measuring error still lies within the required
error limits.
GB-6
Page 7
GB
F
NL
I
SK

Declaration of conformity

Scan of the Declarations of conformity – see www.docuthek.com Elster-Instromet
White meters BK V – V with explosion protection
GB-7
Page 8
GB
F
NL
I
SK
White meters BK V with explosion protection and integrated valve Ve
GB-8
Page 9
GB
F
NL
I
SK

ATEX legend

= Marking of explosion protection
II = Equipment group ll for general industries
(with the exception of mines)
-/2 = Category: internal: none external: Category 2 (Zone 1)
3 = Category 3 (Zone 2) G = Type of atmosphere: gases, hazes and
vapours
c = “Constructional safety” explosion protection
type
IIB = Explosion group for gases TX = No intrinsic heating T4 = Temperature class: maximum allowable
surface temperature 135°C

Logistics

Transport
Diaphragm gas meters are always to be transported
in the upright position. On receipt of the product,
check that the delivery is complete, see page 2
(Part designations). Report any transport damage
immediately.
Storage
Diaphragm gas meters are always to be stored in the
upright position and in a dry place. Ambient tempera-
ture: see page 6 (Technical data).
Disposal
Components are to be disposed of separately.
On request, old units may be returned carriage paid
to the manufacturer, see page 10 (Contact), in
accordance with the relevant waste legislation re-
quirements.
GB-9
Page 10
GB
F
NL
I
SK

Contact

Contact
United Kingdom
Elster Metering Limited Paton Drive
Tollgate Business Park
Beaconside Stafford, ST16 3EF
T +44 1785 275200
F +44 1785 275305
jeavons.info@gb.elster.com
www.elstermetering.co.uk
Germany
Elster GmbH Strotheweg 1
49504 Lotte
T +49 541 1214-0
F +49 541 1214-370 info@elster-instromet.com
www.elster-instromet.com
Ireland
Active Energy Control Ltd. Unit 4, Clare Marts Quin Road Ennis, Co. Clare
T +353 65 6840600
F +353 65 6840610
info@aec.ie
www.aec.ie
GB-10
in the interests of progress.
We reserve the right to make technical modifications
Loading...