Honeywell BCS 3600 Operating Instructions Manual

Burner Control System BCS 3600
CONTENTS
Safety ........................................1
General Information Receiving and Inspection Installation Adjustment
.....................................2
....................................2
Final Checkout Panel Operation Assistance in the event of malfunction Human Machine Interface (HMI) Screens Control motor slidewire calibration UDC3200 Series Controller
Temperature controller configuration record sheet
High Temperature Limit Exhaust Fan Flow Limit Switch Installation Stack Thermocouple Installation Material thermocouple installation Recommended spare parts Converting units
..............................1
.........................2
.................................3
................................3
................4
..............4
...................5
........................6
.......7
...........................8
.............9
...................10
..................11
.......................12
...............................12
OPERATING INSTRUCTIONS
Edition 11.19· ·
SAFETY
32-00248
WARNING
– This equipment is potentially dangerous with the possibility of
serious personal injury and property damage. Hauck Manufac­turing Company recommends the use of flame supervisory equipment and fuel safety shutoff valves. Furthermore, Hauck urges rigid adherence to National Fire Protection Association (NFPA) standards and insurance underwriter’s requirements. Operation and regular preventative maintenance of this equipment should be performed only by properly trained and qualified personnel. Annual review and upgrading of safety equipment is recommended.
– These instructions are intended for use only by experienced,
qualified combustion start-up personnel.
– Adjustment of this equipment and its components, by
unqualified personnel, can result in fire, explosion, severe personal injury, or even death.
GENERAL INFORMATION
The Hauck Burner Control System (BCS) provides burner manage­ment and temperature control of a single pilot ignited burner firing on gas, oil or liquid propane (LP). The spark ignited, gas fired pilot is interrupted after the main burner flame has been established. Flame supervision is provided by a Honeywell RM7890A1056 flame relay combined with a R7849A1023 amplifier module and one or two C7027A1049 UV scanners. A Programmable Logic Controller (PLC) supervises burner operation and is coupled to a Human Machine Interface (HMI) to provide the operator with system status and fault annunciation. A Honeywell UDC3200 series microprocessor based instrument is provided for temperature control. The controller is electronically linked to the burner control motor to automatically adjust the burner firing rate and maintain process temperature near the controller’s setpoint. The Temperature Controller’s thermocouple senses the temperature of the material or exhaust gases as it exits the dryer, depending on where it’s positioned. The controller generates a position proportional output based on the difference between the setpoint and the process temperature input. The control MODE selector switch enables the operator to assign control of the burner. The center, LOW FIRE, position of this switch is used to hold the burner at low fire. The right, MAN (manual) position enables the operator to increase (INC) or decrease (DEC) the burner position via the MANUAL switch. The left, AUTO position uses the Temperature Controller to operate the burner.
GB – www.docuthek.com
The limit contact of the High Temp Limit instrument is used to shut
1
2
3
down the burner if the preset high temperature limit is exceeded. An alarm contact is also used to alert the Operator when the stack temperature nears the limit setting. Refer to HIGH TEMPERATURE LIMIT for entering the desired alarm setpoints. High temperature limits will not prevent baghouse fires. They will, when properly installed and adjusted shut off the burner when the limit’s temperature setpoint is exceeded. Outside factors such as chemicals, bag contamination or other ignition sources are beyond the control of the burner management system.
CAUTION
– The HIGH TEMP LIMIT setpoint is factory set at 400°F
(204°C). If the system is equipped with a fabric dust collector (baghouse), consult the manufacturer for recommended baghouse temperature limitations.
Part designations
1 UDC3200 Temperature Controller 2 High Temperature Limit 3 Human Machine Interface (HMI) Screens
RECEIVING AND INSPECTION
Upon receipt, check each item on the bill of lading and/or invoice to determine that all equipment has been received. Examine all parts to determine if there has been any damage in shipment. If equipment is to be stored prior to installation, provide a dry storage area.
INSTALLATION
For optimum use of the BCS panel, it is suggested that the draw­ings provided by Hauck be referred to for limit switch and valve installation and wiring. In the event that a recommended switch or valve is not used, it may be necessary to connect jumper wire(s) between appropriate terminals in the control panel or burner junction box. Such determination remains the responsibility of the Customer, based upon his application, accepted safe installation and operating procedures, and any applicable insurance guidelines or governmental regulations.
Locate the tabletop panel on a firm support in an area that is protected from the weather and free from vibration. The drop-in version is designed to install in an existing enclosure. Reference the panel assembly drawings for mounting dimensions and re­quired cutouts.
WARNING
– A ground wire is also required between the burner junction
box and the control panel terminal strip.
3
Determine the burner control motor type and install one of the following jumpers:
a. From fuse 5 to Ground for a sinking type motor, Barber-Cole-
man EA57 medium torque.
b. From fuse 5 to 7A for a sourcing type motor, Barber-Coleman
EA71 or EA73 high torque.
➔ If the burner control motor needs to be driven open until purge
time is completed the control needs to be configured. See page 2 (Adjustment) for instructions.
4
Wire the fuel valves, valve position limit switches and fuel pressure limit switches as shown on the external component wiring diagram.
5
Install the exhaust fan flow limit switch in the dryer exhaust duct as shown in page 9 (Exhaust Fan Flow Limit Switch Installa­tion) . Wire the normally open contact of the exhaust flow limit to the appropriate terminals in either the burner junction box or the BCS control panel.
6
Install a limit switch on the exhaust damper set to close when the damper is greater than 50% open.
7
Install the stack temperature thermocouple in the dryer exhaust duct to sense exhaust gas temperature. See page 10 (Stack Thermocouple Installation) for installation instructions.
8
Install a Hauck Rapid Response material temperature thermo­couple in the material discharge chute to sense the temperature of the material leaving the dryer. See page 11 (Material ther­mocouple installation) for recommended installation.
9
Connect the thermocouples to the appropriate terminals in the BCS control panel using thermocouple cable of the same type as the Material and Stack thermocouples.
10
Install the pilot (if applicable) and main flame scanner(s) on the burner and wire them to the appropriate terminals in the burner junction box. Reference burner instructions for scanner installation details.
11
Refer to the external component wiring diagram for interconnec­tion between the burner junction box and the BCS panel terminal strips.
ADJUSTMENT
1
Set the purge timer for the required purge time and whether the control motor needs to be open during the purge cycle.
a
With the control power ON push the F4 (SETUP) button on the HMI.
WARNING
– Operating specifications of 32 to 130°F (0 to 54°C), 30 to
95% relative humidity (non-condensing) should be considered in selecting a suitable location for the control panel.
1
Provide 120Vac single phase grounded neutral power to the burner control panel. It is recommended that the customer provide a master disconnect switch to interrupt power service to the panel. Maintain polarity as indicated on the drawings provided when connecting the main power source to the panel.
2
Install a heavy gauge (No. 12 AWG minimum) ground wire between the panel ground connector and "Earth" ground.
b
Push the SERVICE button on the HMI screen.
2
BCS 3600 · Edition 11.19 · EN
c
Enter the service password using the keypad on the HMI.
WARNING
– Before igniting the burner, the dryer must be purged to remove
possible accumulation of combustible gases. A minimum of four complete air changes must be supplied. Multiply the total system volume (dryer, baghouse and exhaust ducts) in cubic feet by four. Divide this value by the low fire air flow in cubic feet per minute. The result will be the required purge time in minutes
2
Perform the fuel motor calibration procedure described in page 5 (Control motor slidewire calibration).
➔ Recalibrate annually or whenever a control motor is serviced or
replaced.
3
Verify that all low fire limit switch contacts are closed when the burner is at 0% and open when the burner leaves low fire. Ref­erence the burner operating instructions for switch adjustment.
4
Verify that all purge permissive contacts are closed after the burn­er control motor drives open for purge (Sealed-in burners only).
FINAL CHECKOUT
1
Ensure sure that all equipment and components have been in­stalled in accordance with the manufacturer's instructions.
2
Verify all wiring and tighten connections.
3
Confirm all linkage adjustments and insure that control arms and linkage rods are tight.
4
Clean all traps and filters.
5
Check all fuel and air supply lines for leaks.
6
Verify all pressure settings.
d
Enter the amount of time needed to complete the purge cycle, in seconds, into the purge timer window by selecting the PURGE TIMER field and entering the time using the keypad on the HMI.
e
If the control motor needs to be open during the purge cycle turn on the HIGH FIRE PURGE by touch the switch symbol.
f
Push the MAIN soft key to exit the SERVICE screen.
BCS 3600 · Edition 11.19 · EN
PANEL OPERATION
1
Open applicable manual shutoff valves to supply air and fuel to the system.
2
Twist to release the EMERGENCY STOP button and verify that the FUEL selector switch is in the desired position.
a
The Temperature Controller, High Temperature Limit and flame relay will perform their self-test procedures.
b
The burner control motor will drive to its low fire position.
c
The RESET indicator will come on.
d
A “BURNER STOPPED” message will appear
3
Start the combustion air and exhaust fans and all other equipment required for plant operation. After all safety limits have closed, a “PRESS RESET TO START PURGE” message will appear.
4
Place the control MODE selector in the desired position and verify setpoints of both the Temperature Controller and High Tem­perature Limit(s).
5
Momentarily press the RESET button to initiate the system purge sequence.
a
Run Relay, CR102, will be energized.
b
The RESET indicator will go out.
c
If HIGH FIRE PURGE was setup in the SERVICE screen the burn­er control motor will drive open to prepare for system purge and a “WAITING FOR PURGE LIMITS” message may appear (Sealed­in burners only).
6
Provided that all purge permissive contacts are closed:
a
The Purge Timer will begin its timed delay, and a “PURGING … SECONDS” message will appear.
7
After the purge delay, has been completed:
a
The PURGE COMPLETE relay, CR228, will be energized.
b
The burner control motor will drive closed to prepare for pilot ignition (Sealed-in burners only).
c
A “WAITING FOR LOW FIRE LIMITS” message may appear.
8
When the motor has reached its low fire start position and the burner low fire limit switches have closed:
a
“READY to START” will be displayed.
b
The START pushbutton will flash indicating that the burner is ready to start.
9
Momentarily press the START pushbutton to begin the burner ignition sequence
3
a
Start Relay, CR320, will be energized.
b
The RM7890A flame relay will be energized and perform its safe start check.
c
“IGNITING PILOT” will be displayed and the ignition transformer and pilot solenoid valves will be energized.
10
If a satisfactory pilot flame is detected by the UV scanner:
a
Flame signal strength will be displayed on the HMI
b
A “PILOT ON” message will appear.
c
The ignition transformer will be de-energized.
d
Power will be supplied to the main fuel valves.
e
“MAIN VALVES ON” followed by “MAIN FLAME TRIAL” will be displayed as the flame relay performs a 10 second main flame trial for ignition.
11
After the ignition trial, has completed, the pilot solenoids will be de-energized and the pilot will go out.
12
When a 10 second internal timer has been completed:
a
The pilot scanner will be de-energized, (If applicable).
b
The burner control motor will be released from low fire, and re­spond to the motor positioning outputs of the temperature con­troller.
13
Start material flow to the dryer. Use the and keys of the Temperature Controller to manually control the burner firing rate, or press the MANUAL/AUTO key on the controller to begin au­tomatic temperature control.
➔ The center, LOW FIRE, position of the MODE switch will return
the burner to its low fire position.
In the event of a Temperature Controller failure, the MAN. (MANU­AL) position of the control MODE selector will enable the Operator to increase (INC) or decrease (DEC) the burner via the MANUAL INC/DEC switch.
14
To terminate burner operation, press the STOP pushbutton.
a
Run Relay, CR102, will be de-energized and the RESET indicator will come on.
b
Purge Complete relay, CR228, and Start Relay, CR320, will be de-energized and a “BURNER STOPPED” message will appear.
c
The Honeywell RM7890 flame relay will be de-energized.
d
All fuel valves will be de-energized.
e
The burner control motor will drive closed.
ASSISTANCE IN THE EVENT OF MALFUNCTION
?
No power to instruments or indicators.
• Check for 120Vac between L1 and L2. Reset circuit breaker.
?
“WAITING FOR PURGE LIMITS”
• Check purge limits series: 120Vac on terminals 19, 24C, 24B, 24A and 24.
?
“WAITING FOR LOW FIRE LIMITS”
• Check low fire series: 120Vac on terminals 19, 21B, 21A and
21.
?
"IGNITION FAILURE RESET REQUIRED”
• Verify operation of pilot solenoids and ignition transformer. Check pilot adjustment and fuel supply.
• Check for 120Vac on terminals 8 and 9.
• Replace flame relay.
?
FLAME RELAY FAULT RESET REQUIRED
• Verify pilot and main burner setup.
• Clean UV scanner lens and verify operation.
?
“EXHAUST FAN FAULT”
• Monitor module 1 input 2. Check exhaust flow switch (termi­nal 12) and exhaust fan interlock (terminal 13)
?
“COMBUSTION AIR FAULT”
• Monitor module 1 input 3. Check combustion air interlock (terminal 14) and air pressure switch (terminal 16)
?
“LOW GAS PRESSURE”
• Monitor module 1 input 4. Verify that the manual gas valve is open and that the low gas pressure switch is made (120Vac on terminal16A)
?
“HIGH GAS PRESSURE”
• Monitor module 1 input 7 and the high gas pressure switch is made (120Vac on terminal18)
?
“OIL PRESSURE FAULT”
• Monitor module 1 input 5. Verify that the manual valve is open and that the low and high pressure switches are made (120Vac on terminal17A)
?
“ATOMIZING AIR FAULT”
• Monitor module 1 input 6. Verify that compressed air is avail­able and that the supply pressure switch is made (120Vac on terminal17C)
?
“OIL TEMPERATURE FAULT”
• Monitor module 1 input 7. For heavy oil systems, verify that oil heater is operating and that both the low and high oil temperature switches are made (120Vac on terminal18)
?
“COMPRESSED AIR FAULT”
• Monitor module 2 input 3. For oil firing with compressed air atomization, the compressed air pressure switch must close within 5 seconds after the compressed air solenoid is ener­gized (120Vac on terminal 30A)
?
“HIGH LIMIT FAULT”
• Monitor module 2 input 2. (120Vac on terminal 26) Observe the display and OUT indicator of the High Temp Limit instru­ment. “OPEN” indicates an open TC or broken wire. The instrument must be manually reset by pressing the RESET key.
?
“STACK TEMP NEAR LIMIT”
• Warns the Operator that the High Limit instrument is nearing the High Limit setpoint (factory set at 380 F). Manually de­crease the burner firing rate or increase material feed rate to avoid burner shutdown.
?
PURGE TIMER NOT SET
• Warns the operator that the internal purge timer has not been set in the PLC.
HUMAN MACHINE INTERFACE (HMI) SCREENS
Main
F1 Displays limits and system status along with flame signal strength.
BCS 3600 · Edition 11.19 · EN
4
Loading...
+ 8 hidden pages