Honeywell BacNet protocol Installation And User Manual

Honeywell
Installation and
User Manual
BacNet protocol
for Variable Frequency Drives
Honeywell • 0
Document: DPD00546B
Version release date: 6.9.11
1. Safety ..................................................................................................................2
1.1 Danger ............................................................................................................................ 2
1.2 Warnings......................................................................................................................... 3
1.3 Grounding and ground fault protection ........................................................................... 3
1.4 Electro-magnetic compatibility (EMC)............................................................................. 4
2. BACnet - general info........................................................................................6
3. BACnet technical data.......................................................................................8
3.1 BACnet MS/TP protocol.................................................................................................. 8
3.2 BACnet IP protocol ......................................................................................................... 8
4. BACnet installation..........................................................................................10
4.1 Prepare for use through Ethernet ................................................................................. 11
4.2 Prepare for use through MS/TP .................................................................................... 13
5. Programming ...................................................................................................16
5.1 BACnet MS/TP parameters and monitoring values (M5.7.3)........................................ 16
5.2 BACnet IP parameters and monitoring values.............................................................. 18
5.2.1 Ethernet common settings (M5.8.1).............................................................................. 18
5.2.2 BACnet IP settings........................................................................................................ 18
5.3 BACnet MS/TP parameter descriptions ........................................................................ 20
5.3.1 BACnet MS/TP Parameters .......................................................................................... 20
5.3.2 BACnet MS/TP monitoring values ................................................................................ 21
5.4 BACnet IP parameter descriptions................................................................................ 23
5.4.1 Ethernet common settings ............................................................................................ 23
5.4.2 BACnet IP settings........................................................................................................ 24
5.4.3 BACnet IP monitoring values ........................................................................................ 24
6. Communications..............................................................................................26
6.1 Object types and properties supported ......................................................................... 26
6.1.1 Binary Value Object ...................................................................................................... 27
6.1.2 Analog Value Object ..................................................................................................... 29
6.2 Control word bits ........................................................................................................... 31
6.3 Status word bits ............................................................................................................ 31
7. Fault tracing .....................................................................................................32
7.1 Typical fault conditions.................................................................................................. 32
7.2 Other fault conditions .................................................................................................... 33
8. Quick setup ......................................................................................................36
9. Appendix - additional information .................................................................37
9.1 Max master ...................................................................................................................37
10. Annex - Protocol implementation conformance statement.........................38
Honeywell • 1
Safety Honeywell • 2
1. Safety
This manual contains clearly marked cautions and warnings which are intended for your per­sonal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
Table 1. Warning signs
1.1 Danger
= DANGEROUS VOLTAGE!
= WARNING or CAUTION
The components of the power unit of the SmartDrive are live when the VFD is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when the drive is connected to mains, even if the motor is not running.
After disconnecting the VFD from the mains, wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes before doing any work on the connections of the drive. Do not open the cover before this time has expired. After expiration of this time, use a measur­ing equipment to absolutely ensure that no
voltage is present.
Always ensure
absence of voltage before starting any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have a dangerous control voltage present even when the drive is disconnected from mains.
Before connecting the VFD to mains make sure that the front and cable covers of the drive are closed.
During a ramp stop (see the Application Manual), the motor is still generating voltage to the drive. Therefore, do not touch the components of the VFD before the motor has completely stopped. Wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait additional 5 min­utes before starting any work on the drive.
Honeywell • 3 Safety
1.2 Warnings
1.3 Grounding and ground fault protection
The Honeywell SmartDrive must always be grounded with a ground conductor to the ground terminal marked with .
The earth leakage current of the drive exceeds 3.5mA AC. According to EN61800-5-1, one or more of the following conditions for the associated protective circuit shall be satisfied:A fixed connection and
a) the protective earthing conductor shall have a cross-sectional area of at least 10
mm
2
Cu or 16 mm2 Al.
The Honeywell SmartDrive is meant for fixed installations only.
Do not perform any measurements when the VFD is connected to the mains.
The ground leakage current of the Honeywell SmartDrive exceeds 3.5mA AC. According to standard EN61800-5-1, a reinforced protective ground connec- tion must be ensured. See chapter 1.3.
Corner grounding is allowed for the drive types with the ratings from 72 A to 310 A at 380…480 V supply and from 75 A to 310 A at 208…240 V supply.
If the VFD is used as a part of a machine, the machine manufacturer is respon- sible for providing the machine with a supply disconnecting device (EN 60204-1).
Only spare parts delivered by Honeywell can be used.
At power-up, power brake or fault reset the motor will start immediately if the start signal is active, unless the pulse control for
Start/Stop logic has been selected. Futhermore, the I/O functionalities (including start inputs) may change if parame­ters, applications or software are changed.Disconnect, therefore, the motor if an unexpected start can cause danger.
The motor starts automatically after automatic fault reset if the autoreset func- tion is activated. See the Application Manual for more detailed information.
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the VFD.
Do not touch the components on the circuit boards. Static voltage discharge may damage the components.
Check that the EMC level of the VFD corresponds to the requirements of your supply network.
In a domestic environment, this product may cause radio interference in which case supplementary mitigation measures may be required.
CAUTION!
Safety Honeywell • 4
or
b) an automatic disconnection of the supply in case of discontinuity of the protective
earthing conductor.
or
c) provision of an additional terminal for a second protective earthing conductor of the
same cross-sectional area as the original protective earthing conductor.
Table 2. Protective earthing conductor cross-section
The cross-sectional area of every protective grounding conductor which does not form part of the supply cable or cable enclosure shall, in any case, be not less than:
-2.5mm
2
if mechanical protection is provided or
-4mm
2
if mechanical protection is not provided. For cord-connected equipment, provi­sions shall be made so that the protective earthing conductor in the cord shall, in the case of failure of the strain-relief mechanism, be the last conductor to be interrupted.
NOTE! Due to the high capacitive currents present in the VFD, fault current protective switches may not function properly.
1.4 Electro-magnetic compatibility (EMC)
This equipment complies with IEC 61000-3-12 provided that the short-circuit power SSC is greater than or equal to 120 at the interface point between the user’s supply and the public sys­tem. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power S
SC
greater than or equal to 120.
Cross-sectional area of phase conductors (S)
[mm
2
]
Minimum cross-sectional area of the corre­sponding protective earthing conductor
[mm
2
]
S 16
16 
S 35
35 <
S
S
16
S/2
The values above are valid only if the protective earthing conductor is made of the same metal as the phase conductors. If this is not so, the cross-sectional area of the protective earthing conductor shall be determined in a manner which produces a conductance equivalent to that which results from the application of this table.
Do not perform any voltage withstand tests on any part of the drive. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.
Honeywell • 5 Safety
BACnet - general info Honeywell • 6
2. BACnet - general info
BACnet stands for ‘Building Automation and Control Networks’. It is the common name for the communication standard ISO 16484-5 which defines the methods and the protocol for cooper­ating building automation devices to communicate. Devices can be designed to operate using BACnet communication protocol as well as utilising BACnet protocol to communicate between systems. BACnet is an internationally accepted protocol for building automation (e.g. lightning control, air conditioning and heating automation) and control over a communications network.
BACnet provides a method by which computer-based control equipment, from different manu­facturers can work together, or 'interoperate'. For this to be achieved, components must be able to exchange and understand BACnet data messages.
Your Honeywell SmartDrive is equipped with BACnet support as standard.
Figure 1.Principal example diagram of BACnet
BACnet IP - Ethernet
Ethernet to MS/TP Router
Switch
BACnet IP
BACnet MS/TP
Honeywell • 7 BACnet - general info
BACnet technical data Honeywell • 8
3. BACnet technical data
3.1 BACnet MS/TP protocol
Table 3.
3.2 BACnet IP protocol
Table 4.
Connections and communications
Interface RS-485 Data transfer method RS-485 MS/TP, half-duplex
Transfer cable
STP (Shielded Twisted Pair), type Belden 9841 or similar
Connector
2.5 mm
2
Electrical isolation Functional
BACnet MS/TP
As described in ANSI/ASHRAE Stan­dards 135-2004
Baud rate
9600, 19200, 38400 and 76800 baud(supports autobaud detection)
Connections and communications
Interface 100BaseTX, IEEE 802.3 compatible Data transfer method Ethernet half/full -duplex Data transfer speed 10/100 MBit/s, autosensing Protocol BACnet over UDP/IP
Connector
Shielded RJ45 connector; NOTE: Max length of the non-bending part 40 mm.
Cable type CAT5e STP
BACnet IP
As described in ANSI/ASHRAE Stan­dards 135-2004
Default IP Selectable: Fixed or DHCP (AutoIP)
Honeywell • 9 BACnet technical data
BACnet installation Honeywell • 10
4. BACnet installation
Figure 2.
1
Open the cover of the VFD.
The relay outputs and other I/O-terminals may have a dangerous control voltage present even when the drive is disconnected from mains.
2
Locate the components that you will need on the VFD to connect and run the BACnet cables.
Be sure not to plug the Ethernet/BACnet IP cable to the terminal under the key­pad! This might harm your personal computer.
M4x55
Honeywell • 11 BACnet installation
Figure 3.
You can use the BACnet communication protocol through Ethernet and RS485.
4.1 Prepare for use through Ethernet
Figure 4.
3
Connect the Ethernet cable (see specification on page 8) to its terminal and run the cable through the conduit as shown in Figure 4. NOTE: Pay attention that the non-bending part of the connector does not exceed 40 mm in length.
Ethernet connector
Ethernet cable run conduit
I/O terminal (see larger picture)
Grounding bar
DIP switches
32 33
12 13 14 15 16 17 18 19 30
BA
RS485 terminals
21 22 23 24 25 26
1234567891011
max. 40 mm
Ethernet cable
Loading...
+ 29 hidden pages