Honeywell BACnet Installation Instructions

BACnet® Fixed Function Thermostat
MERCURY NOTICE
CAUTION
FOR FAN COIL/HEAT PUMP/CONVENTIONAL SYSTEMS
INSTALLATION INSTRUCTIONS

APPLICATION

Honeywell’s BACnet® Fixed Function Thermostat, BACnet FF, is a configurable device with 19 pre-loaded applications. The thermostat is a communicating, intelligent sensor-controller combination with built-in temperature and humidity sensors used to control systems such as roof top units, fan-coil units and heat pumps. The thermostat communicates over an MS/TP LAN so it operates as a fully-functioning BACnet controller and easily integrates with the building automation system. The two available models are TB3026B and TB3026B-W, which includes a wireless sensor option.

INSTALLATION

Dimensions

The Fixed Function Thermostat consists of a mounting plate and a circuit board with a plastic cover.

When Installing this Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for the application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control. If you have questions, contact Honeywell Customer Care Center.
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
31-00093-03
BACNET® FIXED FUNCTION THERMOSTAT
CAUTION
4 FEET
(1.2 METERS)
YES
NO
NO
NO
M36229
20 19 18 17 16 15 14 13 12
11
M36230
10
9
8
7
6
5
4
3
BO-5
BO-4
BO-3
BO-2
GND
AO-0
COM
AO-1
MS TP
+
MS TP
24VAC = HOT
RELAY 24VAC
BO-0
BO-1
GND = NEUTRAL
AI/BI-0
COM
AI/BI-1
COM
AI/BI-2

Location

Do not install the thermostat where it can be affected by: — drafts or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
IMPORTANT
To avoid electrical interference, which can cause erratic performances, keep wiring runs as short as possible and do not run thermostat wires adjacent to the line voltage electrical distribution systems. Use shielded cable. The cable shield must be grounded only at the controlled equipment case.
WHEN USED TO SENSE ROOM TEMPERATURE
Install the thermostat about 4 ft. (1.2m) above the floor in an area with good air circulation at average temperature. (See Fig. 2.) Confirm mounting height meets Americans with Disabilities Act requirements.
WHEN NOT USED TO SENSE ROOM TEMPERATURE
When using the remote-mounted temperature (and humidity) sensor(s) to sense ambient conditions, install the thermostat in an area that is accessible for setting and adjusting the temperature and settings.
Fig. 3. Wallplate dimensions.

Wiring the Wallplate

IMPORTANT
All wiring must comply with local electrical codes and ordinances.
NOTE: Maximum (and recommended) wire size is 18-
gauge. Do not use wire smaller than 22-gauge.
Follow equipment manufacturer wiring instructions when available. A letter code is located near each terminal for identification.
Power must not be connected while wiring.
Wiring a unit that is powered may result in electrical shock and/or equipment damage.

Mounting Wallplate

The thermostat can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
1.
2. Use a pencil to mark the mounting holes (see Fig. 3).
3.
4. Pull the wires through the wiring opening, and posi-
5. Insert the screws into the holes and tighten.
31-00093—03 2
Fig. 2. Typical location of thermostat
or remote-mounted sensor.
Position and level the wallplate (for appearance only).
Drill two pilot holes in the wall, on the marks. For dry­wall, drill 3/16-in. holes. For firmer material such as plaster, drill 7/32-in. holes. Gently tap anchors (pro­vided) into the pilot holes until flush with the wall.
tion the wallplate over the mounting holes.
1. Connect wires to the terminal blocks. See Fig. 4 for terminal assignments and Table 1 for terminal descriptions.
2. Securely tighten each screw.
3. Push excess wire back into the hole.
4. Plug the hole with non-flammable insulation to pre-
vent drafts from affecting the Fixed Function Ther­mostat.
5.
Check for loose or frayed wire that may cause a short.
Fig. 4. Fixed Function Thermostat terminal
assignments.
BACNET® FIXED FUNCTION THERMOSTAT
WARNING
Do not apply line voltage to source pins.
A jumper is pre-installed between pins 1 and 2. The jumper supplies 24 VAC to BO-1, BO-3, and BO-4 relays. It can be removed if those BOs are powered from an external source. (Note: BO-0, BO-2, and BO-5 relays are powered from terminal 1.)
See BACnet Fixed Function Thermostat System Engineering Guide (31-00098) for typical wiring examples.
Table 1. Terminal Identification.
Terminal Label Connection
1 24VAC 24 VAC Power
2 RELAY 24VAC 24 VAC Power
3 BO0 Relay Output
4 BO1 Relay Output
5 GND Ground
6 AI0 Universal Input
7 COM Common
8 AI1 Universal Input
9 COM Common
10 AI2 Universal Input
11 MS/TP - BACnet ® Communications
12 MS/TP + BACnet ® Communications
13 AO1 Analog Output
14 COM Common
15 AO0 Analog Output
16 GND Ground
17 BO2 Relay Output
18 BO3 Relay Output
19 BO4 Relay Output
20 BO5 Relay Output
Table 2. MS/TP LAN Facts.
Tra nsm ission speed
Layout Bus (daisy chain).
Cabling BACnet specifies the following. Shielded,
Segment length
Maximum devices overall
Maximum devices per segment
Repeaters Required when making runs longer than
Ter min ating resistors
Shield grounding
9.6, 19.2, 38.4, 76.8Kbps (configured at global controller).
twisted-pair cabling with characteristic impedance between 100 and 130W. Distributed capacitance between conductors must be less than 30 pF/foot (100 pF/m). Distributed capacitance between conductor and shield must be less than 60 pF/foot (200 pF/m). Foil or braided shield acceptable.
4000 ft. (1071 m.) per segment using recommended wire.
Depends on classification of devices as master or slave. Maximum number of master devices is 128. Maximum number of slave devices or devices overall (mixed master and slave) is 255. This includes BACnet FFs, BACnet global controllers (all are considered masters) and any other devices, regardless of their relative unit loads.
Depends on relative unit load of devices (see “Terminating MS/TP LAN Cabling” on page 3).
4000 ft. Three repeaters maximum between any two devices.
Matched resistors required at each end of segment bus wired across (+) and (–). Use matched precision resistors rated | 1/4 W ±1% / 80 - 130 Ohms.
Ground shield drain wire at single point earth (panel) ground, not BACnet FF ground. Tape off shield drain wire at other end. Tie shield drain wire through at each BACnet FF.

MS/TP LAN Wiring

The BACnet FF communicates on the site-wide BACnet system over a twisted-pair MS/TP LAN, which uses the EIA–485 signaling standard. The BACnet FFs are master devices on the MS/TP LAN.
Each BACnet FF employs a high-quality EIA–485 transceiver and exerts 1/4 unit load on the MS/TP LAN.
Terminating MS/TP LAN Cabling
MS/TP terminations are located on the lower left of the BACnet FF wallplate.
Maintain polarity of the MS/TP wire run throughout the MS/TP LAN.
Grounding the MS/TP LAN Shield
Proper shield grounding of the MS/TP cabling can help minimize the risk of communications problems and damage to equipment because of transient voltage spikes (for example, lightning strikes).
Follow these guidelines for grounding MS/TP cable shields:
• Each MS/TP segment should have a single point of shield ground, preferably as close to the middle of the cabling run as possible.
• Do not ground the MS/TP shield using a BACnet FF terminal.
3 31-00093—03
BACNET® FIXED FUNCTION THERMOSTAT
CAUTION
• Never ground both ends of a shield; differences in potential between the grounds may induce current on the shield, causing interference.
• At termination connecting points, tie the shield through with a wire nut.
• At ungrounded, exposed shield points (the end of a segment), tape back the shield to the wire jacket or, for optimum transient shunting, use 100V gas discharge tubes or 120V MOVs between shield and ground.
Terminating Resistors
Matched terminating resistors wired across MS/TP+ and MS/TP– are required at the last device on each end of the MS/TP segment for signal integrity (Fig. 5).
Optimum segment performance typically requires “tuning,” a process by which the value of the terminating resistors is selected based on the wave form of signals on the segment. View wave forms using an industrial scope meter. The goal is to have as square a wave form as possible with an amplitude greater than 200 mV. Resistors affect the wave form as follows:
• When the resistance value decreases, the amplitude of the wave form decreases and becomes more square.
• When the resistance value increases, the amplitude of the wave form increases and becomes less square.
WALL
INSTALLATION
REMOVE DURING
Fig. 6. Thermostat mounting.
M19919
Typically, precision resistors in the range 80-130 Ohms (+1%) yield acceptable results. Ideally, the value of the terminating resistors should match the rated characteristic impedance of the installed cable. For example, if the installed MS/TP cable has a listed characteristic impedance of 100 Ohm, install 100 Ohm matched precision resistors.
Do not mismatch terminating resistors.
Ensure that both resistors on a segment have the same value.
NOTE: Typically, White is Data - and Black is Data +.
Fig. 5. Terminating resistor detail.

Mounting Thermostat to Wallplate

1. Align the terminal screw blocks with the pins on the
back of the thermostat.
2. Push the thermostat straight onto the wallplate.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; then remove the top.

CONFIGURATION

Once the BACnet FF is mounted and wired, it can be configured using the local touchscreen and a configuration wizard using Niagara Framework® software. When using the software, BACnet data is transmitted to and from the device and building management system using analog values (AVs) and binary values (BVs). Listings of these AVs and BVs can be found in their entirety in the BACnet Fixed Function Thermostat System Engineering Guide (31-00098) and a limited listing can be found on page 6.

Adjusting the Date and Time

When the controller is first powered up, the date and time might need to be set. These are set at the factory, but the on-board power supply may have run down. If this happens, adjust the date and time.
TO ADJUST THE TIME
1. Touch Clock at the bottom of the screen.
2. Use the arrows to adjust the year, month, and day.
3. Press DONE.
4. Adjust the time and press DONE.

Setting the MAC Address and Device Instance

The MS/TP MAC address for each device must be set to a unique value in the range of 0-127 on an MS/TP network segment. The MAC address is set using the installer setup menu through the device’s display. The factory default MAC address is 0.
31-00093—03 4
Loading...
+ 8 hidden pages