Honeywell BA300, BA300-80ZVDS, BA300-...A Product Specification Sheet

EN0H-1242GE23 R1117
Backflow Preventers
BA300
Backflow Preventer
with flanged connections

APPLICATION

Backflow preventers of this type are suitable for the protection of drinking water systems against back pressure, back flow and back syphonage.
Fluids up to and including liquid category 4 to EN 1717 are protected.
They can be used for residential buildings, industrial and commercial purposes within the scope of their specification.

APPROVALS

DVGW
BELGAQUA
NF
KIWA
WRAS
SVGW
VdS (BA300-80ZVDS)
VA-ETA

SPECIAL FEATURES

Optimal protection of the drinking water supply system
Easy access to all internal components
Powder-coated inside and outside - Powder used is
physiologically and toxicologically safe
Easy Maintenance due to optimized construction
Triple security - two check valves and a discharge valve
separate the backflow preventer into three pressure zones
Few individual parts
Light weight
Standardised discharge connection
All materials are ACS approved
All materials are KTW approved
Approved by OTH (Hungary)

TECHNICAL DATA

Media
Medium: Drinking water
Connections/Sizes
Connection size: DN65 - DN200
Discharge pipe connection: DN150
Pressure values
Min. inlet pressure: 1.5 bar
Max. operating pressure: 10.0 bar
Operating temperatures
Max. operating temperature medium:
Specifications
Installation position: Horizontal with discharge
65 °C (WRAS 60 °C)
valve downwards
Product Specification Sheet • EN0H-1242GE23 R1117 • Subject to change 1
BA300 - Backflow Preventer

CONSTRUCTION

Overview Components Materials
1 Three ball valves for the
connection of a differential pressure gauge
2 Inlet/Outlet check valves Stainless Steel 3 Housing Ductile iron, powder-coated
4 Discharge valve CW626N with stainless steel
5 Pressure control line Polyethylene with stainless
Not depicted components:
Diaphragm EPDM
Sealing washers EPDM
Brass
with polyamide
seat
steel braid
(BA300-80ZVDS stainless steel)

METHOD OF OPERATION

BA type backflow preventers are divided into three pressure zones. The pressure in zoneis higher than in zone , which in turn is higher than in zone . A discharge valve is connected to zone which opens at the latest when the differential pressure between zones and drops to
0.14 bar. The water from zone discharges to atmosphere, both check valves close and therefore separate zone  from zone and . In this way the danger of back pressure or back syphonage into the supply network is prevented. The pipework connection is interrupted and the drinking water network is protected.

TRANSPORTATION AND STORAGE

Keep parts in their original packaging and unpack them shortly before use.
The following parameters apply during transportation and storage:
Parameter Value
Environment: clean, dry and dust free
Min. ambient temperature: 5 °C
Max. ambient temperature: 55 °C
Min. ambient relative humidity:
Max. ambient relative humidity:
*non condensing
25 % *
85 % *

INSTALLATION GUIDELINES

Setup requirements

Install shut-off valves before and after backflow
preventer
Install backflow preventer downstream of the filter or
strainer
This protects the appliance against dirt
Install in horizontal pipework with the discharge valve
downwards
Ensure good access
Simplifies maintenance and inspection
a permanent, professionally dimensioned wastewater connection
The installation environment should be protected
against frost and ventilated well
Install discharge pipework which has adequate capacity
These armatures need to be maintained regularly
2 Product Specification Sheet • EN0H-1242GE23 R1117 • Subject to change