EN0H-1242GE23 R1117
Backflow Preventers
BA300
Backflow Preventer
with flanged connections
APPLICATION
Backflow preventers of this type are suitable for the
protection of drinking water systems against back pressure,
back flow and back syphonage.
Fluids up to and including liquid category 4 to EN 1717 are
protected.
They can be used for residential buildings, industrial and
commercial purposes within the scope of their specification.
The powder-coated ductile iron housing provides increased
corrosion protection.
APPROVALS
• DVGW
• BELGAQUA
• NF
• KIWA
• WRAS
• SVGW
• VdS (BA300-80ZVDS)
• VA-ETA
SPECIAL FEATURES
• Optimal protection of the drinking water supply system
• Easy access to all internal components
• Powder-coated inside and outside - Powder used is
physiologically and toxicologically safe
• Easy Maintenance due to optimized construction
• Triple security - two check valves and a discharge valve
separate the backflow preventer into three pressure
zones
• Few individual parts
• Light weight
• Standardised discharge connection
• All materials are ACS approved
• All materials are KTW approved
• Approved by OTH (Hungary)
TECHNICAL DATA
Media
Medium: Drinking water
Connections/Sizes
Connection size: DN65 - DN200
Discharge pipe connection: DN150
Pressure values
Min. inlet pressure: 1.5 bar
Max. operating pressure: 10.0 bar
Operating temperatures
Max. operating temperature
medium:
Specifications
Installation position: Horizontal with discharge
65 °C (WRAS 60 °C)
valve downwards
Product Specification Sheet • EN0H-1242GE23 R1117 • Subject to change 1

BA300 - Backflow Preventer
CONSTRUCTION
Overview Components Materials
1 Three ball valves for the
connection of a differential
pressure gauge
2 Inlet/Outlet check valves Stainless Steel
3 Housing Ductile iron, powder-coated
4 Discharge valve CW626N with stainless steel
5 Pressure control line Polyethylene with stainless
Not depicted components:
Diaphragm EPDM
Sealing washers EPDM
Brass
with polyamide
seat
steel braid
(BA300-80ZVDS stainless
steel)
METHOD OF OPERATION
BA type backflow preventers are divided into three pressure
zones. The pressure in zone is higher than in zone ,
which in turn is higher than in zone . A discharge valve is
connected to zone which opens at the latest when the
differential pressure between zones and drops to
0.14 bar. The water from zone discharges to atmosphere,
both check valves close and therefore separate zone from
zone and . In this way the danger of back pressure or
back syphonage into the supply network is prevented. The
pipework connection is interrupted and the drinking water
network is protected.
TRANSPORTATION AND STORAGE
Keep parts in their original packaging and unpack them
shortly before use.
The following parameters apply during transportation and
storage:
Parameter Value
Environment: clean, dry and dust free
Min. ambient temperature: 5 °C
Max. ambient temperature: 55 °C
Min. ambient relative
humidity:
Max. ambient relative
humidity:
*non condensing
25 % *
85 % *
INSTALLATION GUIDELINES
Setup requirements
• Install shut-off valves before and after backflow
preventer
• Install backflow preventer downstream of the filter or
strainer
– This protects the appliance against dirt
• Install in horizontal pipework with the discharge valve
downwards
• Ensure good access
– Simplifies maintenance and inspection
• In order to avoid flooding, it is recommended to arrange
a permanent, professionally dimensioned wastewater
connection
• The installation environment should be protected
against frost and ventilated well
• Install discharge pipework which has adequate capacity
• These armatures need to be maintained regularly