Honeywell 32004629-001, 32004629-002, 32004629-003, 32004629-004 Installation Instructions

32004629-001, -002, -003, -004 Bonnet Adapter Kits

FOR Q5020 GLOBE VALVE LINKAGES

INSTALLATION INSTRUCTIONS

DESCRIPTION

The Bonnet Adapter Kits allow you to mount a Q5020 Globe Valve Linkage on some Seimens, Johnson, and Siebe globe valves. Each kit consists of a bonnet adapter and stem adapter.

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

Table 1. Valve/Adapter/Linkage Compatibility.

Valve

Size (in.)

Kit

See

Linkage

Series

Fig.

Siemens

1/2 to 3

32004629-001

1

Q5020A,B

Flowrite

 

 

 

 

599

 

 

 

 

Johnson

1/2 and

32004629-002

2

Q5020D

Controls

3/4

 

 

 

VG7000

 

 

 

 

1 to 2

32004629-003

3

Q5020A,B,D

 

 

 

 

 

 

Siebe

1/2 to 2

32004629-004

4

Q5020D

VB-7000

 

 

 

 

32004629-001 Installation

Once the old actuator is removed, proceed as follows:

1.Place stem adapter on the valve stem.

2.Tighten the set screws.

3.Place the bonnet adapter on the existing valve bonnet.

4.Tighten the set screw.

5.Install the Q5020 according to the instructions provided with the linkage.

STEM ADAPTER

SET SCREW (2)

BONNET ADAPTER

SET SCREW

VALVE STEM

M17575

Fig. 1. 32004629-001 Installation.

® U.S. Registered Trademark

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62-0167

Copyright © 2000 Honeywell Inc. • All Rights Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Honeywell 32004629-001, 32004629-002, 32004629-003, 32004629-004 Installation Instructions

32004629-001, -002, -003, -004 BONNET ADAPTER KITS

32004629-002 and -004 Installation

Once the old actuator is removed, proceed as follows:

1.Thread the bonnet adapter onto the valve until it bottoms out on the valve.

2.Thread the stem adapter onto the valve stem until it bottoms out.

3.Install the Q5020 according to the instructions provided with the linkage.

STEM ADAPTER

BONNET ADAPTER

VALVE STEM

M17576

Fig. 2. 32004629-002 Installation.

32004629-003 Installation

Once the old actuator is removed, proceed as follows:

1.Thread the stem adapter onto the valve stem until it bottoms out.

2.Place the bonnet adapter on the existing valve bonnet.

3.Tighten the set screw.

4.Install the Q5020 according to the instructions provided with the linkage.

STEM ADAPTER

BONNET ADAPTER

SET SCREW

VALVE STEM

M17578

Fig. 3. 32004629-003 Installation.

STEM ADAPTER

BONNET ADAPTER

VALVE STEM

M17577

Fig. 4. 32004629-004 Installation.

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.

Home and Building Control

Home and Building Control

Honeywell Inc.

Honeywell Limited-Honeywell Limitée

 

M2H 3N7