32004629-001, -002, -003, -004
Bonnet Adapter Kits
FOR Q5020 GLOBE VALVE LINKAGES
INSTALLATION INSTRUCTIONS
DESCRIPTION
The Bonnet Adapter Kits allow you to mount a Q5020
Globe Valve Linkage on some Seimens, Johnson, and
Siebe globe valves. Each kit consists of a bonnet adapter
and stem adapter.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
Table 1. Valve/Adapter/Linkage Compatibility.
Val ve
Series
Siemens
Flowrite
599
Johnson
Controls
VG7000
Siebe
VB-7000
Size (in.) Kit
1/2 to 3 32004629-001 1 Q5020A,B
1/2 and
3/4
1 to 2 32004629-003 3 Q5020A,B,D
1/2 to 2 32004629-004 4 Q5020D
32004629-002 2 Q5020D
See
Fig.
Linkage
32004629-001 Installation
Once the old actuator is removed, proceed as follows:
1. Place stem adapter on the valve stem.
2. Tighten the set screws.
3. Place the bonnet adapter on the existing valve
bonnet.
4. Tighten the set screw.
5. Install the Q5020 according to the instructions
provided with the linkage.
STEM ADAPTER
SET SCREW (2)
BONNET ADAPTER
SET SCREW
VALVE STEM
M17575
Fig. 1. 32004629-001 Installation.
® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved
62-0167
32004629-001, -002, -003, -004 BONNET ADAPTER KITS
32004629-002 and -004 Installation
Once the old actuator is removed, proceed as follows:
1. Thread the bonnet adapter onto the valve until it
bo
ttoms out on the valve.
2. Thread the stem adapter onto the valve stem until
it b
ottoms out.
3. Install the Q5020 according to the instructions
provided with the linkage.
STEM ADAPTER
BONNET ADAPTER
VALVE STEM
STEM ADAPTER
BONNET ADAPTER
VALVE STEM
M17576
Fi
g. 2. 32004629-002 Installation.
32004629-003 Installation
Once the old actuator is removed, proceed as follows:
1. Thread the stem adapter onto the valve stem until
it b
ottoms out.
2. Place the bonnet adapter on the existing valve
bo
nnet.
3. Tighten the set screw.
4. Install the Q5020 according to the instructions
provided with the linkage.
STEM ADAPTER
BONNET ADAPTER
SET SCREW
VALVE STEM
M17577
Fig. 4. 32004629-004 Installation.
M17578
Fi
g. 3. 32004629-003 Installation.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or
modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any
liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Home and Building Control Home and Building Control
Honeywell Inc. Honeywell Limited-Honeywell Limitée
M2H 3N7
62-0167 B.B. 5-00 www.honeywell.com