32004629-001, -002, -003, -004 Bonnet Adapter Kits
FOR Q5020 GLOBE VALVE LINKAGES
INSTALLATION INSTRUCTIONS
The Bonnet Adapter Kits allow you to mount a Q5020 Globe Valve Linkage on some Seimens, Johnson, and Siebe globe valves. Each kit consists of a bonnet adapter and stem adapter.
1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3.Installer must be a trained, experienced service technician.
Table 1. Valve/Adapter/Linkage Compatibility.
Valve |
Size (in.) |
Kit |
See |
Linkage |
|
Series |
Fig. |
||||
Siemens |
1/2 to 3 |
32004629-001 |
1 |
Q5020A,B |
|
Flowrite |
|
|
|
|
|
599 |
|
|
|
|
|
Johnson |
1/2 and |
32004629-002 |
2 |
Q5020D |
|
Controls |
3/4 |
|
|
|
|
VG7000 |
|
|
|
|
|
1 to 2 |
32004629-003 |
3 |
Q5020A,B,D |
||
|
|||||
|
|
|
|
|
|
Siebe |
1/2 to 2 |
32004629-004 |
4 |
Q5020D |
|
VB-7000 |
|
|
|
|
Once the old actuator is removed, proceed as follows:
1.Place stem adapter on the valve stem.
2.Tighten the set screws.
3.Place the bonnet adapter on the existing valve bonnet.
4.Tighten the set screw.
5.Install the Q5020 according to the instructions provided with the linkage.
STEM ADAPTER
SET SCREW (2)
BONNET ADAPTER
SET SCREW
VALVE STEM
M17575
Fig. 1. 32004629-001 Installation.
® U.S. Registered Trademark |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
62-0167 |
||||||||||||||||||
Copyright © 2000 Honeywell Inc. • All Rights Reserved |
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
32004629-001, -002, -003, -004 BONNET ADAPTER KITS
Once the old actuator is removed, proceed as follows:
1.Thread the bonnet adapter onto the valve until it bottoms out on the valve.
2.Thread the stem adapter onto the valve stem until it bottoms out.
3.Install the Q5020 according to the instructions provided with the linkage.
STEM ADAPTER
BONNET ADAPTER
VALVE STEM
M17576
Fig. 2. 32004629-002 Installation.
Once the old actuator is removed, proceed as follows:
1.Thread the stem adapter onto the valve stem until it bottoms out.
2.Place the bonnet adapter on the existing valve bonnet.
3.Tighten the set screw.
4.Install the Q5020 according to the instructions provided with the linkage.
STEM ADAPTER
BONNET ADAPTER
SET SCREW
VALVE STEM
M17578
Fig. 3. 32004629-003 Installation.
STEM ADAPTER
BONNET ADAPTER
VALVE STEM
M17577
Fig. 4. 32004629-004 Installation.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.