Honeywell 301c User Manual

Centrale
Controller
Manuel de l’utilisateur
301C
User Manual
M-510324
7/10
Controller Unit
301C
User Manual
M-510324
7/10
Notices and Trademarks
Copyright by Honeywell International Inc.
July 2010
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
This manual covers software version 3.086.
Honeywell Analytics
405 Barclay Boulevard
Lincolnshire, Illinois 60069
Symbol Definitions
The following table lists the symbols used in this document to denote certain conditions:
Symbol Definition
ATTENTI ON: Identifies information that requires
special consideration
TIP: Identifies advice or hints for the user, often in terms of performing a task
REFERENCE _ INTERNAL: Identifies an additional source of information within the bookset.
Indicates a situation which, if not avoided, may
CAUTION
result in equipment or work (data) on the system being damaged or lost, or may result in the inability to properly operate the process.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. CAUTION: Symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in serious injury or death. WARNING symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
M-510324 301C User Manual v 7/10 Honeywell
INTRODUCTION ............................................................11
Intended Use ......................................................................................... 11
Receiving and Unpacking ...................................................................... 11
Installation Instructions ...................................................................... 12
Basic Guidelines .................................................................................... 12
Surface Mount Installation..................................................................... 13
Wiring Details .................................................................................... 14
Power Connections ...........................................................................16
Communication Connections ............................................................ 16
Settings for Specific Transmitters ...................................................... 16
Relay Output ..................................................................................... 17
Jumper Use Instructions ........................................................................ 18
GETTING STARTED ......................................................19
Initial Startup ......................................................................................... 19
Datalogger (SDcard) ............................................................................. 19
Programming Interface...................................................................... 20
Keypad Functions .................................................................................. 20
LED Definitions ...................................................................................... 21
System Operation .................................................................................. 21
SYSTEM PROGRAMMING ............................................22
Tx Info Menu ..................................................................................... 25
Ident Menu ............................................................................................ 26
Product and Sensor Types ..................................................... 27
COM Menu ............................................................................................ 29
Scale Menus (1 and 2) .......................................................................... 30
Detection Menu ..................................................................................... 31
Display Menu ......................................................................................... 32
Alarm A, B and C Menus ....................................................................... 33
Servicing and Operating Menus ............................................................ 34
Status Code ........................................................................................... 35
Erase Current Tx ................................................................................... 35
Change Tx Address ............................................................................... 36
Groups Menu ..................................................................................... 37
Creating Groups .................................................................................... 38
Deleting Groups .................................................................................... 39
M-510324 301C User Manual vii 7/10 Honeywell
Event Menu .......................................................................................40
Action Menu ...........................................................................................42
Delays Menu.......................................................................................... 43
Latch Mode............................................................................. 44
Conditions ..............................................................................................45
Status .....................................................................................................49
Database................................................................................................ 49
Acquisition Menu ...............................................................................50
Starting and Stopping Tx Logging ..........................................51
Starting and Stopping Event Logging .....................................52
Copy Menu ........................................................................................53
Configuration .....................................................................................53
Parameters ............................................................................................54
System Log Menu ..................................................................................55
Config Menu ......................................................................................56
Network Menu ...................................................................................61
Remote Calibration ................................................................................63
Tests Menu ........................................................................................65
Test Sequence .......................................................................................67
Normal Mode .........................................................................................69
Single Tx Mode ......................................................................................69
Debug Mode ..........................................................................................69
Simulation Mode ....................................................................................70
Bacnet Menu ..........................................................................................72
Changing BACNet values .......................................................75
Wireless Network Menu .....................................................................77
Parameters Menu ..................................................................................78
Changing PAN ID or RF Channel ...........................................80
Diagnostics Menu ..................................................................................82
Nodes Menu ...........................................................................................83
New Node Menu ....................................................................................87
Hibernate Menu .....................................................................................88
Reset Network Menu .............................................................................88
Status Log Menu ....................................................................................89
Consolidate Route Menu .......................................................................89
BACnet/IP MODULE .........................................................................91
Specifications .........................................................................................91
BACnet Objects .....................................................................................91
Analog Input ........................................................................... 92
viii 301C User Manual M-510324
Honeywell 7/10
Analog Value .......................................................................... 92
Binary Input ............................................................................ 92
Binary Output ......................................................................... 93
Binary Value ...........................................................................93
Device .................................................................................... 93
Object Names ......................................................................... 94
Protocol Implementation Conformance Statement ............................ 99
BACnet Protocol Implementation Conformance Statement .................. 99
Specifications .................................................................................. 105
LIMITED WARRANTY .................................................107
Limited Warranty ................................................................................. 107
Re-Stocking Policy .............................................................................. 107
Exclusions ........................................................................................... 108
Warranty Limitation and Exclusion ..................................................... 108
Disclaimer of Unstated Warranties ...................................................... 109
Limitation of Liability ............................................................................ 109
M-510324 301C User Manual ix 7/10 Honeywell
Introduction
Introduction
The 301C controllers act as nerve centers for gas detection networks, providing continuous monitoring for up to 96 connected units (plus 1 301ADI). Since the controllers are factory programmed to the owner’s specifications, installation is limited simply to mounting and connecting them. Once installed and connected, the controllers allow the user to monitor, adjust, or reconfigure an entire network of units.
The 301C has a supplementary option of the wireless coordinator that enables this controller to communicate with and manage up to 25 wireless gas detection devices in addition to its regular capabilities.
Intended Use
The controller is intended to monitor an entire gas detection network around the clock. The unit offers logging capabilities, creating log files of all transmitter concentrations and alarms for analysis. The unit is also equipped with grouping or zoning capabilities that allow users to query and monitor specific groups of transmitters or specific transmitter zones.
Receiving and Unpacking
Upon receiving the controller unit:
Check that the package is undamaged
Carefully open the package.
Locate the packing slip or purchase order and verify that all items on the order are present and undamaged
Note: If the package or any of its contents are damaged, please refer to
the Warranty section at the back of the manual for instructions.
M-510324 301C User Manual 11 7/10 Honeywell
Introduction
Installation Instructions
Installation Instructions
Basic Guidelines
Follow these instructions to the letter to ensure that the equipment will function properly. Failure to respect these guidelines will release Honeywell Analytics from any responsibility in the event of improper functioning:
Locate all units in areas easily accessible for service.
Avoid locations where instruments are subject to vibrations
Avoid locating units near sources of electromagnetic interference
Avoid locating units in areas subject to significant temperature swings
Verify local requirements and existing codes that may impact choice of location.
12 301C User Manual M-510324
Honeywell 7/10
Introduction
17.4 cm 6
13/32
26.8 cm 10
9/16
1.5m 5’
Ø .5cm
¼”
Installation Instructions
Surface Mount Installation
It is recommended that controllers be installed 5 feet (1.5 m) above the floor, at approximate eye level.
Mark the holes as shown:
Height markers 6 13/32” apart
Width markers 10 9/16” apart
Pre-drill 1/4” mounting holes as needed
Securely mount the 301C using the appropriate screws
Wiring for the unit must be passed through the knock-outs provided at the bottom of the unit.
M-510324 301C User Manual 13 7/10 Honeywell
Introduction
COMMUNICATION
Communication Wire Gauge: 2-24 AWG (Belden 9841) Twisted and shielded cable 2000 feet (600 m) per channel T-tap: 65 feet (20 m) / T-tap 130 feet (40 m) total
Channel Specifications :
Channel 1-2: Modbus,Vulbus protocol Channel 3: Modbus protocol only Communicates only with Vulcain transmitters Channel 4: Modbus output Communicates only with VA301 BDCM
Channel 4 (not used)
Channel 3
A 4
B 4
A 3
B 3
Channel 2
Channel 1
B 2
A 2
A 1
B 1
V-
NEXT
V+
PREVIOUS
V-
V+

5(6(7
3&%&:5$
6+,(/'
6+,(/'
6+'1
9
%$%$
%$
5,*+7
/()7
5;
7;
$/$50B$
%
$
9
$/$50B%
$/$50B&
32:(5
)$8/7
'2:1
(17(5
(6&
6,/(1&(
1&
12
12 1&
83
0$'(,1&$1$'$
5&
5&
5&
5&
5
5
5
5
5(/$<
5(/$<
5(/$<
5(/$<
9LQ 9RXW
(7+(51(702'8/(
99
-
-
-
-
-
5
/('
/('
/('
/('
/('
&
6:
6:
6:
6:
6:
6:
/('
/('
/('
/('
/('
/('
/('
.
-
-
-
(2/
(2/
(2/
(2/
%=
-
-
-
-
-
-
-
.
.
/
5
-
6:
-
.
0DGHLQ&DQDGD
9XOFDLQ,QF

9$&:35%
5(6(7
-
-
'
'
-3
/
1&
12
12
Ethernet: 10/100-compa tible with 10Base-T interface, RJ-45
Visual Indicators: Green LED LINK Yellow LED ACT
BacNet/IP MODULE (-BIP option)
Always respect minimum voltage requirements at device
LCD screen
Wireless communication module
Wireless Communication : ISM worldwide Indoor range 30m
RELAY OUTPUTS
3+5 4+6
1+3 2+4
Normally open
Normally closed
5
31
642
RISK OF ELECTRIC SHOCK
RISK OF ELECTRIC SHOCK
End-of-line specification : The E.O.L. jumper for channels 1-2-3-4 must always be in E.O.L. position.
End-of-line jumper
position
5&
5
SD Card
Grounding screw
Wiring Details
Wiring Details
The diagram below provides the details required to connect the 301C with the wireless communication module (coordinator). This module allows the controller to communicate with and manage the 301W wireless gas detectors.
Details concerning power supply, cables, capacities, etc., are provided in the Specifications section at the back of this manual.
14 301C User Manual M-510324
Honeywell 7/10
Introduction
Wiring Details
The connectors, or ports, on the PCB allow various wiring to be connected to the controller. The wiring includes power, communication, BACNet and relays, each with an assigned position (and number) on the board:
J22 Power Input: Connect the power supply to the controller
(see Wiring Details for cabling diagrams) J23, J24 Communication inputs: Connect communication cables to channels 1
through 3. Relay Outputs 1-4: Depending on the desired configuration,
connect the relay cables to either N.O. or N.C. SHDN jumper Place the jumper over the Shutdown header
pins to reset or restart the system. EOL Resistors 1-4: Place the jumper over the header pins to
create the connection to attenuate
communication echoes.
M-510324 301C User Manual 15 7/10 Honeywell
Introduction
Power Connections
Power Connections
The 301C requires a power range of 17-27 Vac, 50/60 Hz (8.64 VA), 18-36 Vdc, 350 mA @24 Vdc (8.4 VA). Polarization is not important in either AC or DC mode. The system must be grounded on the transformer and a dedicated circuit breaker must be used.
Communication Connections
Communication cables must be grounded using the shield terminal, using twisted and shielded pair Belden 2-24 AWG #9841 cable (or equivalent).
The network cabling can extend up to a limit of 2000 feet (609 m) per channel.
The length of a T-tap can reach 65 feet (20 m), up to a maximum of 130 feet (40 m) for all T-taps.
All wireless devices associated to the controller will automatically be detected and communicate with the controller using wireless communication protocols.
Settings for Specific Transmitters
Honeywell Sensepoint XCD Transmitters must be configured for 9600 baud, no parity, and a unique address. Honeywell XNX Universal Transmitters must be configured for 9600 baud and a unique address. Information on configuring each transmitter is in the associated
technical manual.
16 301C User Manual M-510324
Honeywell 7/10
Introduction
RELAY OUTPUTS
N.O.
N.C.
COMM
Normally closed
Normally open
Relay Output
Relay Output
The relay output can withstand up to 5A at 30Vdc or 250Vac (resistive load only). Relays can be used to activate horns and strobes. Although each relay is programmed with a default setting (below), they can be configured using the controller programming menu.
If relays are set to Normally closed, the relay is powered up with the controller and the device linked to the relay is functioning. The relay will shut down when the specified alarm condition is reached.
If the relay is set to normally open, the relay will remain off when the controller is powered up and the device connected to the relay will only be activated when the specified alarm condition is reached.
Note: These functions are reversed if the controller Failsafe mode has
been activated.
M-510324 301C User Manual 17 7/10 Honeywell
Relay Output
Jumper Use Instructions
The jumpers on the controller PCB allow a variety of operations to be performed manually:
EOL 1-4: Enables the user to add End-Of-Line jumpers that improve
communication signals. Put the jumper in R position (as shown on wiring diagram) to activate the End-of-Line termination. (R provides a resistance termination and RC provides resistance and condensator termination.)
SHDN: Enables the microcontroller to be reset or temporarily shut
down. This function is used mainly when system wiring
adjustments are needed (power off for safety). Relays These jumpers allow the relay to be tested by activating it J29-J32 without having any effect on Events.
18 301C User Manual M-510324
Honeywell 7/10
Getting Started
Relay Output
Getting Started
The controller units are customized to the purchaser’s specifications but they can be further programmed using the following menu options.
Initial Startup
Make sure that all wiring has been completed according to specifications in the wiring details before powering up the unit. When all is secure, remove the SHDN jumper to power-up the unit. It should only take a few seconds until the unit is fully operative.
Datalogger (SDcard)
The DLC (Data Logger Card) option for the controller collects data and stores it on a digital Flash memory card (SDCard). In the event that the card memory becomes full:
Information logging is stopped
No SDcard flag is displayed on-screen
The SDcard LED blinks
See the Acquisition section for more details on starting and stopping the datalogging function.
CAUTION
M-510324 301C User Manual 19 7/10 Honeywell
Always deactivate datalogging function before removing the SDcard. Never remove the card when its LED is on.
Getting Started
Programming Interface
Programming Interface
The front panel of the 301C provides a programming keypad (buttons) and LEDs.
301C front panel Keypad
Keypad Functions
Each unit has 7 keypad keys, or buttons:
Arrows: Used to move the cursor through the various programming
fields (Up, Down, Left and Right), or to adjust the display
contrast (press and hold the up or down arrow until desired
contrast is reached and release). ESC: Used to exit the programming menu or to cancel a change or
input. Enter: Used to access the programming menu and to modify
programming fields. Silence: Turns off the controller’s buzzer.
20 301C User Manual M-510324
Honeywell 7/10
Getting Started
Programming Interface
LED Definitions
The controller is equipped with 7 LEDs that provide a status for each function related to that indicator:
Alarm A: A blinking red light indicates that an event has been
activated. A constant red light indicates that one or more transmitters has reached Alarm A or Alarm 1.
Alarm B When the red indicator is on, one or more transmitters has
reached Alarm B or Alarm 2.
Alarm C When the red indicator is on, one or more transmitters has
reached Alarm C. Power: Green indicates that the unit is powered up and functional Fault: When the amber LED is on, it indicates a fault (i.e. a
communication, maintenance or device problem) Tx: When the amber LED is blinking, it indicates that the
controller is sending information or requests on the
communication channel. Rx: When the green LED is blinking, it indicates that the
controller is receiving information.
Each of these functions is linked to parameters programmed in the control unit, which we will discuss in the following section.
System Operation
The system operates in four different modes that allow it to use, analyze, debug, and simulate the actions that the system can perform. These modes are: Normal, Single Tx, Debug and Simulate. The default system operation mode is Normal. The other modes are available through the Tests menu (option 8 from the Main Menu).
Note: Systems services may be disrupted by some menu operations.
M-510324 301C User Manual 21 7/10 Honeywell
System Programming
VA301C Ver. 3.00
Ad: 1 Gr:0 Ev:0
2007-01-17 13:18:18
Programming Interface
System Programming
The system’s Normal programming mode offers several menu options that are accessible from the main menu screen:
Tx Info: Allows transmitter parameters to be programmed Groups: Allows groups of transmitters to be set up Events: Allows events and event behavior to be programmed Acqui: Allows the datalogging feature to be activated or deactivated Copy: Allows data or parameters to be copied from the (controller)
configuration to parameters Config: Allows system parameters and password to be set Network: Allows actions on the network to be performed,
communication statistics to be consulted, and remote
calibrations to be performed Tests: Allows each device to be tested sequentially (inputs, outputs,
communications, events, etc.) and operation of various
parameters to be validated BACNet: Allows a device’s BACNet parameters to be set Wireless: Allows a network of wireless gas detection devices to be
configured, monitored, and modified.
Note: Access to the programming functions is password protected.
The default password is 2967.
The screen display shown below appears initially. This display can be configured to scroll among the information screens for each device connected to the controller.
If one or more of the connected devices is in an alarm mode, the controller will only scroll between the main information screen and the screens for device(s) in alarm mode. In this case, you must scroll manually to view screens for other devices.
22 301C User Manual M-510324
Honeywell 7/10
System Programming
Programming Interface
The information screen also displays icons representing certain system functions. Here is a list of possible icons and their meaning:
Icon Description
BACNet: Indicates that there is a BACNet module present and that it is communicating with the controller.
BACNet error: Indicates that a BACNet module is present but communication with the controller has failed (error)
Debug: Indicates whether the controller is in debug mode (Single TX, Debug or Simulation modes). When in simulation mode, SIM appears next to this icon.
Log: Indicates that either “Tx Logging” or “Event logging” is enabled.
Log error: Indicates that an error occured during TX or Event logging. All logging functions are stopped.
SDC: Indicates that an SDcard is present and functionning. The icon “fills” (from white to black) progressively as memory is used. A white icon indicates empty memory and black indicates full memory.
SDC error: If this symbol persists for more than 5 seconds, an SD card card is present but not functioning properly.
Wireless network: Indicates that the wireless network coordinator (wireless communication module) is present and communicating with the controller.
Wireless network error: Indicates that the wireless network coordinator (wireless communication module) is present but is not communicating with the controller.
M-510324 301C User Manual 23 7/10 Honeywell
System Programming
PASSWORD
_ _ _ _
MENU
1. Tx Info 3. Events
2. Groups 4. Aqui
MENU
5. Copy 7. Network
6. Config 8. Tests
MENU
9. BACNet
10. Wireless
Programming Interface
Since the controller’s programming functions are password protected, it is necessary to access the login screen:
Press Enter to access the programming options. The password
screen appears:
Use the keypad Up or Down arrows to increase or decrease the
value, one digit at a time, starting with the first digit
When all the digits of the password are correct, press Enter to
access the programming functions.
The first MENU options screen appears. Use the keypad arrows to navigate through multiple screens to the desired function and press Enter to access it.
24 301C User Manual M-510324
Honeywell 7/10
System Programming
Tx Info Menu
Tx Info Menu
Tx Info is the menu option that is dedicated to transmitter information and contains several sub-menu options. The exact list of screens will vary depending on the transmitter type. A summary is presented below with details on the following pages
Ident: Allows the network component’s
identification information to be viewed.
COM: Allows the communication
protocol to be viewed or changed
Detection Allows the detection range and or Scale(1) the unit of measurement and parameters to be viewed and Scale(2): changed
Display: Allows the label (or name) of a
specific component to be changed
Alarms: Allow alarm thresholds to be
viewed and sometimes changed. There can be significant variations in this screen depending on transmitter type.
Status Transmitter and node status Displays: (in hexadecimal values)
Erase or Erases or changes the Current Tx: Tx address
M-510324 301C User Manual 25 7/10 Honeywell
System Programming
1. Tx Info 001
-Ident­NotVul CO2 (IR)
Tx Info Menu
Ident Menu
The Ident, or identification menu allows a component’s network ID to be consulted:
The upper right corner of the screen shows the component’s address. If the address of the device whose information must be viewed is known:
Use the arrows to move the cursor arrow to the on-screen address
Press Enter (the value can be edited while the number is flashing)
Use the up or down arrows to increase or decrease the value
Press Enter again to validate the entry and display the information for the desired device.
The bottom left corner of the display shows the transmitter name (ex.: 301D2 - product name) and the sensor type (ex.: CH4 - methane sensor). These values can also be changed for Group or Vulbus product types. The procedure is identical for both fields:
Programming or changing a product or sensor type
Use the arrows to move the cursor to the product type field.
Press Enter to select the field (the value can be modified when flashing)
Use the arrows to scroll through the list of product types and press Enter when the desired product or sensor appears
26 301C User Manual M-510324
Honeywell 7/10
System Programming
1. Tx Info 121
-Ident­301W CO2 (IR)
Tx Info Menu
Product and Sensor Types
This is a list of all the (preprogrammed) product types available from the Identification option in the Tx Info menu.
The order of the products below is not necessarily the order in which they will appear in the controller
Product Types
Addresses 1-96
VA301D2 VA301AP XNX 90DM3R VASQN8X XCD VA301IRF VA301EM VA201R IRT100 VA301EMRP VA201T EC-F9 GsPnt2 90DM2 VA201T2 S301RLC VA201D VA301T (Std.Device)* VA301D GsPnt VA901T NotVul RgRt3
Product Types
Addresses 97-120 Addresses 121-170
301ADI (?) (?) 301W
301RW 301RPT
* E3Point and 420MDBS are examples of standard devices.
Note: When Group is selected as a product type, the remaining Tx
INFO screens are not accessible (because each product in the group has already been individually programmed). Only the Ident and Erase current Tx screens will be available.
M-510324 301C User Manual 27 7/10 Honeywell
System Programming
Tx Info Menu
The sensor type list applies to address ranges 1-96 and is not dependent on the type of product selected. Devices in the address range from 97-170 will display a BACNet object identifier, rather than a sensor type.
*An additional Product Type, simply called “Group”, represents a group created in the Groups Menu in the controller. When scrolling through the available product type list, this name will appear as many times as there are groups created in the controller (example: Group 1, Group 2, Group 3, etc.). If a group is selected as the product type, then the sensor type options are limited to MIN, MAX and MEAN.
28 301C User Manual M-510324
Honeywell 7/10
System Programming
1. Tx Info 001
-COM- Mdbs RTU 8D 1S EP 9600 bauds
1. Tx Info 001
-COM­Mdbs RTU 8D 1S EP 9600 bauds
Tx Info Menu
COM Menu
This screen displays the selected communication protocol for device addresses from 1 to 96. Each transmitter’s protocol is defined by the controller (see Network Auto-configuration section)
.
If a transmitter is compatible with several different protocols, it can be modified using to one of the following options:
•Vulbus
Mdbs ASCII 7D 2S NP 9600 bauds
Mdbs RTU 8D 2S NP 9600 bauds
Mdbs RTU 8D 1S NP 9600 bauds
Mdbs RTU 8D 1S OP 9600 bauds
When a transmitter is configured with the Modbus communication protocol, the transmitters automatically sends the programmable parameters to the controller.
Note: Vulbus transmitter parameters must be programmed manually.
M-510324 301C User Manual 29 7/10 Honeywell
System Programming
1. Tx Info 001
-Scale(1)-
Max 00250
Min 00000
1. Tx Info 001
-Scale(2)-
Factor 00010
Units %
Tx Info Menu
Scale Menus (1 and 2)
These menus appear only for certain devices. Scale(1) allows the detection range, minimum and maximum, to be defined for the selected device. Whatever value is specified is the value that will appear at the device display (if applicable). The Minimum value is generally left at 0. Parameters for the XNX and XCD gas detectors can be viewed here but can be changed only at the transmitter.
Scale(2) allows the factor by which to divide the scale (between 0 and
65535) and the unit of measurement for the selected scale to be determined.
The factor allows precise scale limits for detection to be set. By dividing the maximum scale value in the first Scale screen (250 in this example) by 10, a scale value of 25.0 can then be displayed.
The “Units” allow the unit of measurement for the device to be selected:
°F: Sets degree Farenheit as the unit of measurement °C Sets degree Centigrade as the unit of measurement %RH Sets Relative Humidity as the unit of measurement mV Sets millivolts as the unit of measurement V Sets volts as the unit of measurement mA Sets milliamps as the unit of measurement % Sets the percentage of gas as the point unit of measurement ppm Sets parts per million of gas as the point unit of
measurement
30 301C User Manual M-510324
Honeywell 7/10
System Programming
1. Tx Info 001
-Detection­scale: 0-0.00 unit: %
Tx Info Menu
Detection Menu
The detection menu (available only for devices with addresses between 1 and 96) displays the detection range (scale: 0-100.0) and the unit of measurement (unit: %) for the selected component. If a transmitter uses the Modbus protocol, the detection parameters are automatically defined during network configuration and are not editable. Vulbus protocols must be manually defined by the programmer.
The detection scale is between 0 and the maximum value (0.00) and the unit of measurement is either ppm or percent (% for oxygen and % LEL for combustibles).
The detection menu is not available for the VA301R or VA301AP.
Programming or modifying the scale range or unit:
Use the arrows to move the cursor to the scale or unit option
Press Enter and use the arrow to increase or decrease the value
Press Enter when the desired value is obtained
M-510324 301C User Manual 31 7/10 Honeywell
System Programming
1. Tx Info 001
-Display-
edit (20 char.max)
301D2 CH4 Ad001
Tx Info Menu
Display Menu
This option allows a specific label or name to be assigned to the selected component (transmitters, relay modules, annunciators). Up to 20 characters, including spaces, can be used in the label (example: BOILER ROOM). The default Modbus transmitter labels are composed of the component (or transmitter) name, sensor type and address.
Vulbus transmitter labels contain 20 blank characters (spaces).
32 301C User Manual M-510324
Honeywell 7/10
System Programming
Tx Info Menu
Alarm A, B and C Menus
The screens for viewing alarm thresholds are combined in this manual. There will be either two or three levels, depending on transmitter type.
If present, separate “MIN” and “MAX”levels permit manual control of the hysteresis of each alarm. Normally, the “MAX” level is set greater than “MIN.” However, alarms can be made to trigger on falling concentration (as with oxygen) by setting the “MAX” threshold smaller than the “MIN” threshold.
With certain transmitters, only one threshold will be displayed.
Additionally, with certain transmitters, the alarm thresholds are read­only at the controller. These thresholds can be set only at the transmitter.
These are typical screens:
Typical screen for viewing alarms A or B on XCD and XNX transmitters
Typical screen for viewing or changing alarm A, B, or C thresholds on other transmitters.
M-510324 301C User Manual 33 7/10 Honeywell
System Programming
Tx Info Menu
Servicing and Operating Menus
These functions vary depending on the transmitter type. These displays show the total time the device has been in service and the amount of time remaining until the next required calibration or replacement.
34 301C User Manual M-510324
Honeywell 7/10
System Programming
1. Tx Info 001
erase current Tx Change Tx Address
Tx Info Menu
Status Code
These screens display transmission or node status and sensor status for the selected transmitter. This read-only information can assist service personnel in troubleshooting.
The XNX and XCD gas detectors will report the warning or fault number (iFaultWarnNumber) in hexidecimal on the third line. These transmitters will also report the monitoring state (iMonitoringState) in the fourth line. See the transmitter documentation for interpretation of fault numbers and monitoring states.
Typical display for XNX or XCD
Typical display for other transmitters
Erase Current Tx
This function allows the configuration to be erased or the Tx address for the displayed component to be changed.
Note: Selecting erase current Tx only erases the current device entry
Tx Info configuration. No other data is erased.
M-510324 301C User Manual 35 7/10 Honeywell
System Programming
1. Tx Info 001
erase current Tx Change Tx Address
1. Tx Info 001
To address: 001
1. Tx Info 001
Processing...
Tx Info Menu
Change Tx Address
Selecting Change Tx Address allows users to move a device from one TX address to another:
Use the arrows to scroll to Change Tx Address and press Enter to select
In the next screen, scroll to the address number and press Enter to select
Use the up or down arrows to increase or decrease the address value and press Enter to validate the new address.
The Change Tx address option is only available (active) for device address 1 to 96 and if there is a Modbus device connected.
If the address is valid, the screen will display “Processing”.
If the address is invalid, the screen will display “Invalid Tx” and return to the Change Tx Address screen (the address for GasPoint devices cannot be changed)
A final screen will display either “Error” or “Success” (re-start procedure if Error is displayed).
Note: If a device address is changed to one already associated with
another device, the existing data will be overwritten. Customers should know their network’s address assignments and be careful when changing a Tx address. Delete the original Tx address to avoid duplicate entries.This feature is not supported with XNX and XCD transmitters.
36 301C User Manual M-510324
Honeywell 7/10
System Programming
MENU
1. TxInfo 3. Events
2. Groups 4. Acqui
2. Groups 001 <end> [----] [----] [----] [----] [----] [----] [----]
empty all groups
Groups Menu
Groups Menu
Programming groups of transmitters allows several units to be combined which then enables actions (events) to be taken based on a series of units rather than each unit, individually.
A group is a stack containing the addresses from each of the transmitters included in the group.
Groups are displayed in a single line; if a group contains more than four components, the arrows must be used to scroll left and right of the display window to view all members of a group.
The cursor in the Group screen is represented by the blinking brackets (<end>). Any information between the brackets can be edited.
M-510324 301C User Manual 37 7/10 Honeywell
System Programming
Groups Menu
Creating Groups
Use the arrows to move the cursor to a group line and press Enter
The field can be edited when the brackets stop blinking and the word “end” blinks
Use the up or down arrows to scroll through the list of all units connected to the 301C, until the desired address is displayed .
Press Enter again to validate the address.
The address is added to the group and the <end> bracket is shifted one position to the right.
The process can be repeated until all the desired transmitters in the group (up to 126) have been added. The address for each transmitter added in the Tx Info menu is available when creating groups.
Note: Groups created in the Groups menu will appear in the product
type list (Tx Info - Ident screen) as “Group xx” (the number assigned to the group when it was created).
38 301C User Manual M-510324
Honeywell 7/10
System Programming
Groups Menu
Deleting Groups
Use the empty all groups command to delete all groups previously programmed in the controller.
Single groups can be deleted with a simple procedure:
Scroll to the first transmitter in the group list,
Select the transmitter (its address blinks) and scroll to <del> (<del> erases the entry and <end> marks the end of the stack)
Press enter and the group is emptied.
This procedure makes it possible to delete one, several or all entries previously included in a group.
Note: Up to 126 groups, with a maximum of 128 members each, can be
created.
7/10 Honeywell
39
System Programming
Event Menu
Event Menu
Though the controller has a default setting for Event configuration (as shown below), the Event menu is programmable. Event programming lets specific actions to be defined:
Action: What will be done if programmed criteria are reached Delay: Defines the length of time to wait before taking an
action on an event and time to wait after an event has returned to normal before the action output is returned to normal state.
Conditions: AND, OR or none (---); equations that allow more
detailed control of an event Coverage Determines the period during which the event is period: applicable Status: Disables or enables a programmed Event disabled: Database: Erases the selected event or all events
40 301C User Manual M-510324
Honeywell 7/10
3. Events 001
-Delays­Before: 99min After: 01min
3. Events 001
-Action-
Target: Ctrl Relay: #01
3. Events 001
1/3 Gr036 =2.01% AND
3. Events 001
-Coverage Period­All day All week
3. Events 001
-Database­Erase current event Erase all events
3. EVENEMENT 001
-Status : disabled­Enable event .
System Programming
Event Menu
M-510324 301C User Manual 41 7/10 Honeywell
System Programming
3. Events 001
-Action­Target: Ctrl Relay: #01
Event Menu
Action Menu
Actions are comprised of two parameters:
Target Indicates which component is responsible for the action to
be taken; Tx (transmitter) Re (Relay/Annunciator) Ctrl (Controller)
Relay Indicates which of three possible outputs will be activated
when the event is true; #XX (activates the component’s #xx relay), Buzzer (activates the component’s audible alarm) ALL (activates the relays and audible alarms)
Example: Tx 007 detects a concentration exceeding the set values. The target (controller) triggers relay 1 connected to that event (a fan perhaps).
42 301C User Manual M-510324
Honeywell 7/10
System Programming
3. Events 001
-Delays-
Before: 99min After: 01min
Event Menu
Delays Menu
This option allows Before and After settings that will delay the activation or deactivation of an action to be programmed.
Before Delays the action for the specified length of time. If the
condition persists beyond this delay, the defined action is executed.
After The time to wait after an event has returned to normal before
returning action output to normal state. The after delay also offers a Latch option, described below.
Before and After delays can be configured at either 30 or 45 seconds or from 1 to 99 minutes, in one minute increments. Five dashes (-----) indicates that no delay has been programmed.
Use the keypad arrows to scroll to the desire option
Press Enter to select the option
Use the keypad arrows to scroll through the second or minute settings
Press Enter at the desired setting. The delay is set.
M-510324 301C User Manual 43 7/10 Honeywell
System Programming
Event Menu
Latch Mode
The Latch function is executed on an Event state
It is possible to select the Latch mode by changing the after delay to “
The Event stays active until the Silence keypad button is pressed
The Silence keypad button has two functions: Silence the buzzer and unlatch the event.
When the Silence keypad button is pressed, events in Latch mode are unlatched and reevaluated. If the Event condition persists, the Event remains active and returns to Latch mode. If the condition does not persist, the event is deactivated.
Note: If the Event has a Before delay and the Silence button is pressed
while the Event conditions are still true, the buzzer will be silenced only for the length of the programmed delay.
44 301C User Manual M-510324
Honeywell 7/10
Event Menu
3. Events 001 1/3 Gr036 >2.01% AND
3. Events 001 all Gr003
AND > 2.99%
Conditions
Conditions are the parameters that define what makes an Event true. Each condition is defined by four elements and can be combined with other conditions to provide greater flexibility. A condition, as in the example provided below, defines:
IF at least 1/3 of group 36 detects concentrations greater than 2.01% of specified gas AND all of group 03 detects a concentration greater than
2.99% of gas, then the specified action (Actions were set at the first Event screen) for that Event will be triggered.
Since the display screens offer limited space, scroll left and right to view and edit further information.
Condition programming screens
The portion of the Events condition screen that is within the brackets is divided into four editable list fields:
7/10 Honeywell
45
System Programming
Event Menu
The top left portion contains the statistic quantifier (available only for Groups) that take only the specified part of the group into the equation. Options available in this field are:
all: includes all transmitters in the group mean: includes the average concentration for the group’s transmitters max: includes the group’s maximum concentration min: includes the group’s minimum concentration 1/4: includes at least a quarter of the group’s transmitters that
meets set conditions
1/3: includes at least a third of the group’s transmitters that meets
set conditions
1/2: includes at least half of the group’s transmitters that meets set
conditions
2/3: includes at least two thirds of the group’s transmitters that
meets set conditions
3/4: includes at least three quarters of the group’s transmitters that
meets set conditions
1 or +: at least one or more than one of the group’s transmitters that
meets set conditions
46 301C User Manual M-510324
Honeywell 7/10
System Programming
Event Menu
The bottom left portion contains the logic, or operator, quantifier that determines how conditions are calculated. Options available in this field are:
Operator
Symbol
--- No operator
= Equal to <= Equal to or smaller than < Smaller than >= Equal to or larger than > Larger than != Not equal to
max
min
When the maximum value is reached, an action is triggered. It will not be deactivated until levels fall below minimum value
When concentrations fall below minimum value, an action is triggered. It will not be deactivated until concentrations rise above set maximum value
Meaning
The top right portion contains the source, which defines what device or group of devices the Event will be based on. The list provides the following options:
GrAll: Includes all transmitters (see note) Gr_ _ _: Includes only the devices in the specified group (see note) Tx000: Includes only the specified transmitter (connected to the con-
troller)
Clock: Includes only information gathered between the specified
times. Selecting clock sets a condition that is applied only between the start and end time frame. It is possible to set one condition screen to specific parameters and the second to clock, which means that the specified condition will trigger an event only if it occurs during the set time period.
Note: Clicking on the magnifying glass to the right of a Group number
on the display opens a view of the Group for consultation or editing. Press Esc to close the group view and return to the Event condition screen.
M-510324 301C User Manual 47 7/10 Honeywell
System Programming
3. Events 001
-Coverage Period­All day All week
Event Menu
The bottom right portion contains the operand, which defines what device or group of devices on which the Event will be based. The list provides the following options:
OFF Used for status on binary inputs (ex.: used with 301ADI) ON: Used for status on binary inputs (ex.: used with 301ADI) Fault: Bases trigger on maintenance alarm, communication failure or
device failure
Alrm A: If the chosen device or group has an Alarm A or Alarm 1, an
event will be triggered.
Alrm B: If the chosen device or group has an Alarm B or Alarm 2, an
event will be triggered
Alrm C: If the chosen device or group has an Alarm C, an event will be
triggered.
The Coverage Period screen allows the period that will be covered by the Event to be defined. (The time frames for each of these periods can be defined in the controller Config menu.) This option provides two further selection fields:
Day definition field: allows All day, Daytime, or Nighttime to be selected
Week definition field: Weekend, Working Days, All week
1. Use the keypad up or down arrows to scroll to either All day or All
week
2. Press Enter to select. The value can now be changed
3. Use the keypad up ro down arrows to scroll through options (see
above)
4. Press Enter to select.
48 301C User Manual M-510324
Honeywell 8/10
System Programming
3. EVENT 001
-Status : disabled­Enable event .
3. Events 001
-Database­Erase current event Erase all events
Event Menu
Status
This screen displays the current event status and allows it to be either enabled or disabled, depending on the current status.
Enable event:This is a “toggle” switch; press Enter to change the value
from Enable to Disable and vice versa
After going through all the steps and programming an event, this screen will display “Enable event”. Press Enter to activate all the parameters and enable the Event.
If an existing Event is being consulted, this screen would display “Disable event”. Press Enter to disable an Event (it will not be deleted but will not function). The programming of this Event is always present, which means that it easily can be reactivated by scrolling to this screen and pressing Enter.
Database
This screens displays the options linked to the database:
Erase current event:Lets user erase the current event Erase all events:Lets user erase all events
M-510324 301C User Manual 49 7/10 Honeywell
System Programming
4. Acquisition 10% threshold mode Start Tx logging Start event logging
2005-04-27 11:05:20;1_CO2_ppm;574;-normal-: 2005-04-27 11:06:02;1_CO2_ppm;503;-normal-: 2005-04-27 11:06:15;1_CO2_ppm;562;-normal-: 2005-04-27 11:06:28;1_CO2_ppm;645;-normal-: 2005-04-27 11:06:39;1_CO2_ppm;557;-normal-: 2005-04-27 11:30:45;1_CO2_ppm;715;-normal-:
Acquisition Menu
Acquisition Menu
The Acquisition mode is only accessible when there is an SD card present (controllers with the Data Logging, or DLC function). It is used to enable or disable the logging of system Events or transmitter information. The information is logged (or recorded) on an SD card. Intervals or conditions must be defined before using this option.
The first line of the Acquisition screen offers either :
Delay mode: Allows for delay intervals of 10 to 59 seconds
or 1 to 60 minutes.
Threshold mode: Allows log values to be set according to set
variation thresholds (based on last reading) of 3% or more, 5% or more or 10% or more of last detected concentration.
If a 3% threshhold is selected, the system will not log a value at 3% but will log a value of 3.1%. Remember that the sampling rate (system refresh rate) may have an impact on logging.
Here is an example of threshold logging. The logs a semi-colon delineated text files.
50 301C User Manual M-510324
Honeywell 7/10
System Programming
2004-01-23 17;54;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.5;-normal-;003_CO_ppm;0;-normal­2004-01-23 17;55;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;0.5;-normal-;003_CO_ppm;0;-normal­2004-01-23 17;56;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;0.5;-normal-;003_CO_ppm;0;-normal­2004-01-23 17;57;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.0;-normal-;003_CO_ppm;0;-normal­2004-01-23 17;58;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.5;-normal-;003_CO_ppm;0;-normal-
Acquisition Menu
Starting and Stopping Tx Logging
In the previous step, “Acquisition”, the frequency at which Tx logs would be recorded can be configured. To start the logging function:
When “Start Tx logging” appears on the display, it indicates that the acquisition, or logging, mode is inactive. When “Stop Tx logging” appears, it indicates that Tx data is being logged. The log message is displayed on the screen according to the chosen mode and LED 1 will light up.
Press the Enter keypad button to stop or start Tx logging.
When Tx data is logged, the system creates files named tayymmdd.log, tbyymmdd.log and tcyymmdd.log, each representing one third of the network. The record includes the transmitter’s date, time and address, the sensor type, the concentration read, as well as the alarm status. Here is a sample of what a Tx log looks like:
The first column of the Tx log displays the date (yyyy-mm-dd) and the time (hh:mm:ss) of the log. In this example, the “Delay mode” was set to one minute intervals.
The third column of the Tx log displays the transmitter address and the fourth displays the gas type, gas concentration and unit of measurement.
The display then lists the next transmitter address with its gas type, concentration and unit of measurement, and so on until all the transmitters have been listed.
M-510324 301C User Manual 51 7/10 Honeywell
System Programming
2004-01-23 17:54:25: Event logging enable 2004-01-23 17:55:25: Event logging enabled 2004-01-23 19:05:47; Simulation sequence activated 2004-01-23 19:05:48; Tx 6 communication no more in fault 2004-01-23 19:05:48; Tx 8 communication no more in fault
Acquisition Menu
Starting and Stopping Event Logging
The Acquisition menu offers an event logging option. Event Logging records controller transactions, events, Tx and alarm flags and relay status.
When “Start Event logging” appears on the display, it indicates that the acquisition, or logging, mode is inactive. When “Stop Event logging” appears, it indicates that Event data is being logged.
Press the Enter keypad button to stop or start Event logging.
When Event data is logged, the system creates a file named evyymmdd.log. The record includes the date, time and the event. Here is a sample of what an Event log looks like:
The first column of the Event log displays the date (yyyy-mm-dd) and time (hh:mm:ss) of the log. Column A displays the date and time of the log. In this example, the event’s “Delay mode” was set to one minute intervals.
The system logs the following types of events:
Event Log
Event status changed
Alarm A, B, C, Fault, and X status changed
Note: New log files are created when the existing files reach 32 000
lines or at the start of a new week (0h00 Sunday)
52 301C User Manual M-510324
Honeywell 7/10
System Programming
5. Copy
-Configuration­Config to SDcard SDcard to Config
Copy Menu
Copy Menu
The Copy menu allows programmed parameters to be copied and transferred. Data from the SD card can be transferred to a controller or from a controller to the SD card or copy parameters from one device to the next. The Copy option offers three screens: Configuration, Parameters and System Log.
Configuration
If the controller is equipped with an SD card, the configuration function allows data to be transferred either from the 301C to the SD card or the reverse. This makes it possible to transfer the controller’s programming to a computer or from a computer to the controller.
The first option in the configuration screen is 301C to SDcard. Selecting this option copies the controller’s configuration and
parameters into a “config.ini” file
1
.
The second option is SDcard to 301C allows the configuration and parameters of the “config.ini” file on an SDcard to be copied to the controller.
Note: The “config.ini” file contents can be modified at any time and from
any computer.
1. When transferring data, the system will automatically search for an existing “config.ini” file before proceeding. If one exists, the system searches for a “config.bak” file. If found, the file is deleted. Then, t he pre-existing “con fig.ini” file is r enamed “confi g.bak”, making it possible to save the new “config.ini” fi le and keep a backup copy of the previ­ous one.
After inserting an SD card into the controller, the controller’s system looks for an exist-
ing “config.ini” file that contains an “autoload” tag equal to 1 (yes). If the tag is found, the system loads the contents of the file and reset s “autoloa d” to 0 (no). This is a useful feature for editing the file on a computer without having any impact on the controller (such as recorded Events).
M-510324 301C User Manual 53 7/10 Honeywell
System Programming
5. Copy
-parameters­TxInfo to TxInfo Event to Event
TxInfo to TxInfo source tx001 target tx113 COPY
Event to Event source #001 target #013 COPY
Configuration
Parameters
The “parameters” function allows one transmitter’s configuration to be
copied to another or one event’s parameters to be copied to another
event. This allows several devices that share identical or similar
parameters to be quickly configured.
The options within this screen are:
Tx Info to Tx Info copies transmitter parameters from one device to
another.
Event to Event copies parameters from Event to Event.
The process is identical for both options:
Select source, (the data to be copied) using the up/down keypad arrows and press Enter.
When the transmitter address is flashing, use the up/down keypad buttons to search for the desired device address.
Press Enter to select the new address
Select the target address (where the data is to be copied to) in exactly the same way as source
Select COPY and press Enter. The parameters have been copied.
54 301C User Manual M-510324
Honeywell 7/10
System Programming
5. Copy
-System Log-
SysLog to SDcard
--- START of system log dump : 2007-04-18 13:19:05 --­2007-04-04 18:42:06;Accessing menu; 2007-04-04 18:43:47;Event 1 definition modified; 2007-04-04 18:48:12;Exiting menu; 2007-04-04 18:54:49;System power-down; 2007-04-04 18:56:40;System power-up; 2007-04-04 19:02:44;Accessing menu; 2007-04-04 19:03:07;Event 6 definition modified; 2007-04-04 19:03:21;Exiting menu; 2007-04-05 10:51:28;Accessing menu; 2007-04-05 10:54:59;Database reset; 2007-04-05 10:55:18;Tx 25 parameters modified; 2007-04-05 10:55:29;Group 0 definition modified; 2007-04-05 10:55:36;Group 0 definition modified; 2007-04-05 10:55:46;Group 0 definition modified; 2007-04-05 10:55:55;Group 4 definition modified; 2007-04-05 10:55:57;Exiting menu; 2007-04-05 10:56:02;Accessing menu; 2007-04-05 10:56:19;Tx 24 parameters modified;
Configuration
System Log Menu
The controller will record log information to its internal memory. If the controller is equipped with an SD card, the system log function allows users to save system log information to the memory card in text format.
When this option is selected, a log of all the last actions performed on the controller is copied to the SDcard, with the filename slyymmdd.log. This file can contain up to a maximum of 64Kb of information in text format. Once the memory card is full, the oldest log entries are erased and replaced by new entries.
Here is an example of a system log:
M-510324 301C User Manual 55 7/10 Honeywell
System Programming
MENU
5. Copy 7. Network
6. Config 8. Tests
6. Config
Set User Password
- 2967 -
Slave Port Cnfg
6. Config Relay Configuration AP Brdcst: auto Honeywell
6. Config Day definition Week definition
6. Config Manual scroll mode Set Date and Time Menu français
Slave Port Cnfg Address: 001 38400 bauds Mdbs RTU 8D 2S NP
Relay Configuration
-Failsafe­All relays Inactive
Relay Configuration
-Silence­1234 dis ena dis dis
Day definition
-Daytime­sta: 08:00 end: 17:00
Week definition
-Working Days­sta: Monday end: Friday
Date and Time
2005-11-21 11:47:36 (ISO 8601 standard)
Config Menu
Config Menu
The Config menu contains several main configuration screens and is used to program the controller display mode, adjust the date and time, select the display language, change the controller access password, modify the Slave Port configuration, set the Relay Configuration, and select the AP Broadcast mode.
Each main screen offers further programming options, as shown.
56 301C User Manual M-510324
Honeywell 7/10
Config Menu
6. Config Manual scroll mode Set Date and Time Menu français
Date and Time
2005-11-21 11:47:36 (ISO 8601 standard)
Selecting the first line of the first screen allows selection from three display modes: Manual scroll, 3-second scroll, 5-second scroll. If Manual scroll mode is chosen, the screen will only advance if you press on the arrow keypad buttons. If either 3 or 5 second scroll mode is chosen, the screens will automatically scroll display readings for all devices connected to the controller after 3 or 5 seconds.
3 or 5 second scroll modes do not prevent the keypad arrows to be used to return to a previous screen or move ahead through the screens manually.
Selecting the second line allows the date and time in a new screen to be adjusted; Date and Time. When a number is flashing, the value can be changed using the up/down keypad arrows. The year, month, day and the hour, minute and second values can be changed.
The controller does not manage Daylight Savings Time, therefore, users must manually adjust any time changes.
Selecting the third line allows the display language to be changed. If the display is already in English, it will then display the Menu français option (and vice-versa). Simply scroll to the line and press Enter to change the language.
M-510324 301C User Manual 57 7/10 Honeywell
Config Menu
6. Config
Set User Password
- 2967 -
Slave Port Cnfg
The second main screen in the Config menu allows a new user password to be set and the slave port configuration to be modified.
The default password is 2967. Select Set User Password to change the password:
When the first digit blinks, change the value by using the up/down keypad arrows to increase or decrease the number
Use the left/right keypad arrows to move from one digit to the next.
When the desired password has been set, press Enter to validate it and exit the editing mode.
Note: Contact Honeywell technical support for help with lost passwords
at 1-800-563-2967.
58 301C User Manual M-510324
Honeywell 7/10
System Programming
6. Config Relay Configuration AP Brdcst: auto Honeywell
Relay Configuration
-Failsafe­All relays Inactive
Relay Configuration
-Silence-
1234 dis ena dis dis
Config Menu
Scroll through the main Config menu screens using the left (previous) or right (next) keypad arrows.
The third main screen in the Config menu allows the relay configuration to be set, the AP broadcast mode and to select from four separate manufacturers for the given controller.
When Relay Configuration is selected, two further options to configure the relays are available: The first screen, Failsafe, appears allowing the failsafe to be activated for all relays using the Enter keypad button. This function is used in case of a power failure: if power is cut, the relay will activate the connected device (ex. a light) to signal the problem.
Scrolling to the right displays the “Silence” screen that enables or disables the silence option for each relay, using the Enter keypad button.
M-510324 301C User Manual 59 7/10 Honeywell
System Programming
6. Config Day definition Week definition
Day definition
-Daytime­sta: 08:00 end: 17:00
Week definition
-Working Days­sta: Monday end: Friday
Config Menu
The fourth screen in the Config menu allows a definition of a day and a week to be programmed.
Day and Week definition allows hours (time frames) to be defined for either Daytime and Working Days respectively.
Note: Remember, the controller uses a 24 hour clock (0:00 to 23:59).
Any time changes (DST) must be made manually or through BACNet time synchronisation (BACNet module required).
60 301C User Manual M-510324
Honeywell 7/10
System Programming
7. Network
Reset Database Scan Network Reset and Scan
Network Menu
Network Menu
The Network menu allows network device information to be either scanned or reset.
This menu offers four options, divided into two screens; the first screen contains three options:
Reset Database: Resets all network device Tx information in the
database. This only resets the Tx infomation for the network device. It does not affect programmed Groups or Events.
Network Scan: Begins an auto-detect of all network devices
that allows the system to configure the Tx database for network devices (i.e. it will scan and add new devices but will not overwrite or erase the old database)
Reset and Scan: Performs both previous functions
simultaneously.
Note: Once one of these options has been set, wait until the controller
completes the process. Do not interrupt or stop the process once it has begun.
M-510324 301C User Manual 61 7/10 Honeywell
System Programming
7. Network
Statistics
Calibration
Statistics 001
Valid 16 100% Errors 0 0% Timeouts 0 0%
Network Menu
The second Network screen offers the Statistics and Calibration options.
Selecting Statistics from the Network menu displays a screen containing the statistics for the selected device address.
Valid: Indicates the number of valid responses for the last 16
requests
Errors: Indicates the number of errors in the response for the last 16
requests
Timeouts: Indicates the number of timeouts (no response) for the last
16 requests
62 301C User Manual M-510324
Honeywell 7/10
System Programming
7. Network
Statistics Calibration
Calib 007 S301M Status: Normal Set Zero Set Span 246 PPM
Calib 007 S301M Status: Normal Set Zero Set Span 246 PPM
Network Menu
Remote Calibration
The network menu also offers a Calibration option for use with devices that support network calibration.
The Calibration screen contains four (4) lines of information:
Line 1: Indicates the mode (Calib, meaning calibration), the
(Modbus) address of the device to calibrate (001) and the type of device to calibrate (301D2)
Line 2: Indicates the status (Normal or In calib…) of the specified
device Line 3: Displays the function to perform (Set Zero) Line 4: Displays the function to perform (Set Span) and the span
gas concentration value (246 ppm)
5. On the first line, scroll to the device address and press Enter
6. Scroll through the devices to display the desired device* and press
Enter to select.
7. The second line displays the device’s status
8. Scroll to select the desired function, Set Zero to set the device's
zero, and press Enter to select.
9. Upon pressing Set Zero, the controller requests confirmation.
*The device must be configured in the 301C’s database in order to be included in the device addresses displayed on screen.
M-510324 301C User Manual 63 7/10 Honeywell
System Programming
Calib 001 : 301D2 Status : Normal Set Zero Set Span 2.60 ppm
Calib 001 : 301D2 Status : In calib... Set Zero Set Span 2.60 ppm
Network Menu
10. Press Enter to confirm or Esc to cancel. If confirmed, the controller calibrates the sensor’s Zero. This takes only a few moments and the display returns to the default calibration screen.
Note: Never calibrate any unit’s Zero with ambient air. Always use
Nitrogen (N
) at the calibration port to calibrate the Zero.
2
11. To calibrate the device, scroll to Set Span** and change the span gas calibration value using this procedure;
a. Using the right arrow, move the cursor to xxx PPM (span
value field). Press Enter to select the field (it is editable when flashing).
b. Use the up or down arrows to increase or decrease the
value, press Enter to validate the new value.
c. Move the cursor back to Set Span and press Enter to start
the calibration.
The device Span is being calibrated. The screen will display the device’s status as “In calib...” until the calibration is complete.
**When selecting Set Span, make sure that the device has been supplied with the appropriate calibration gas before and during the calibration process.
64 301C User Manual M-510324
Honeywell 7/10
System Programming
MENU
5. Copy 7. Network
6. Config 8. Tests
8. Tests
Oprt Mode: normal
8. Tests Test sequence Start Sim Sequence Maximum load
Simulation Sequence Start with Tx001 Confirm
Test sequence Relays activated Any key to continue Esc to quit
Test sequence BUZZER activated Any key to continue Esc to quit
2
Test sequence LEDs activated Any key to continue Esc to quit
Test sequence Press ‘left’
Esc to quit
Test sequence Display test Any key to continue Esc to quit
Test sequence Test Network comm. 9600 bauds Channel 1 PASSED
Test sequence Test done Any key to continue
7
6
5
4
3
1
Tests Menu
The Tests menu allows a variety of tests to be performed on components and on the network communications. It also allows the system to be operated in four different modes which, in turn, provide different functionalities.
Tests Menu
M-510324 301C User Manual 65 7/10 Honeywell
System Programming
8. Tests Test sequence Start Sim Sequence Maximum load
8. Tests Oprt Mode: normal
Tests Menu
The Tests menu provides four main options, divided between two screens. Each of these options offers different capabilities.
The first screen presents three options:
Test sequence: Enables each output to be activated and validates
operation of each controller keypad buttons, display
pixels, and various communication protocols. Start Sim Sequence: This options starts or stops the Simulation mode,
which allows a simulation of a gas concentration
over an associated scale range on all transmitters.
The simulated gas concentration values are local (on
the controller) and do not affect logging functions.
(Events will be activated for the simulation but
detection devices are not affected.) Maximum load: Activates all controller components
The second screen option is “Oprt Mode”, which offers three separate operation settings: Normal, Single Tx or Debug.
Normal Normal controller operation mode Single Tx: Activates the polling mode on a single transmitter. Debug: Activates the service mode to perform a calibration
and to test Events without triggering actions.
66 301C User Manual M-510324
Honeywell 7/10
System Programming
Test sequence
Relays activated Any key to continue Esc to quit
Test sequence
BUZZER activated Any key to continue Esc to quit
Test sequence
Press ‘left’ Esc to quit
Tests Menu
Test Sequence
When test sequence is selected from the main Tests menu, the controller will display the Test sequence screen.
If Esc is pressed on the keypad, the main Tests menu screen will be displayed. However, to perform system tests, press any key to proceed to the first test screen.
This screen tests each component individually and will advance only to the next component when a key is pressed. This option will display 13 screens. Screens 1, 2 and 3 test Relays, BUZZER and LEDs.
The following six screens prompt the user to press the keypad buttons, in turn: left, right, up, down, Silence, Enter and Esc. The system will not advance until a key is pressed.
M-510324 301C User Manual 67 7/10 Honeywell
System Programming
Test sequence
Display test Any key to continue Esc to quit
Test sequence
Test Network comm. 9600 bauds Channel 1 PASSED
Test sequence
Test done Any key to continue
Tests Menu
The system then moves to the Display test. When the blank screen is displayed, it is testing for display pixels. Press any key to proceed to the next step.
The final test that the system performs is a network communication test:
Once these tests have begun, do not interrupt or stop them. The system tests all five bauds (communication speed: 9600, 19200, 38400, 57600, 115200) and each of the 4 channels per baud.
When the system has completed the test, it displays the final Tests screen. Press any key to return to the main Tests menu.
68 301C User Manual M-510324
Honeywell 7/10
System Programming
Tests Menu
Normal Mode
This is the system’s normal (default) operation mode. When the system is in normal mode, some values can be changed without interrupting services. When a value has been changed in any of the menu fields, the change will take effect upon returning to the main menu screen.
Single Tx Mode
This mode allows transmitters to be analyzed one at a time. The controller polls only the selected device, which subsequently has its information updated. This mode does not interfere with Event Evaluation functions.
Debug Mode
This mode allows complete system operation to be evaluated and tested without affecting operations (outside of debug mode). Events
are evaluated and displayed as necessary but no action is triggered.
M-510324 301C User Manual 69 7/10 Honeywell
System Programming
Tests Menu
Simulation Mode
This mode deactivates network communication Information Updates. It can be combined with any of the three previous modes (example: using the Simulation mode when in Debug mode allows the user to test the entire system [groups, events, etc] without triggering any actions or using any additional material such as gases). It allows gas concentrations to be simulated over an associated scale for each transmitter, sequentially:
Alarm levels A, B and C are evaluated according to the simulated gas concentration and events are evaluated and actions are taken.
This type of alarm simulation at the controller does not work with certain transmitters with falling alarms. In these cases, an alarm can be simulated at the transmitter.
While in simulation mode, the controller is unaware of the device’s actual network status. This mode can be stopped at any time in the Test menu (see Normal System Operation).
If one of these modes has been activated, the system will automatically return to Normal Mode after 12 hours of inactivity. (No changes will be lost.)
70 301C User Manual M-510324
Honeywell 7/10
System Programming
BACnet Menu
BACnet Menu
The BACNet menu offers several main menu screens to configure the BACNET IP connection, DHCP, server, time zone information and more.
M-510324 301C User Manual 71 8/10 Honeywell
System Programming
9. BACNet
-Device­BACnet ID : 1 Static IP address
-IP address-
192.168. 1.254
-Network mask-
255.255.255. 0
Bacnet Menu
The first of these screens allows the identification and address to be configured:
BACnet ID: (B
uilding Automation and Control Networks) is the device ID number assigned to this particular controller on a network.
Static IP address: This is an address that is used when DHCP is
disabled.
Changing BACNet values
Use the keypad arrows to scroll down to select the desired line and press Enter to select it.
Selecting BACnet ID activates the field. The ID value (0-4194303) can be increased or decreased using the up or down keypad arrows
If the Static IP address option is selected, the following screen appears. All controllers are shipped with a preset IP address as shown in the example below.
72 301C User Manual M-510324
Honeywell 7/10
System Programming
9. BACNet
-DHCP : disabled-
Enable DHCP
Bacnet Menu
The next screen allows the device DHCP (Dynamic Host Configuration Protocol) to be enabled or disabled.
Simply press Enter to change the field value. Consult the IT
department for details concerning this option.
M-510324 301C User Manual 73 7/10 Honeywell
System Programming
9. BACNet
- SNTP Client ­SNTP server SNTP request : 1min
SNTP server
10. 4. 1. 12
Bacnet Menu
The next main BACNet screen allows modification of the SNTP (Simple Network Time Protocol) server IP address and configure the frequency at which the system will make SNTP server requests. Honeywell has made these options available to better adapt to the building’s network protocol, however Honeywell does not provide configuration or support for these options.
Selecting Server request activate the minute The SNTP server option opens another screen that allows the SNTP server IP address to be changed
The SNTP server option opens a secondary screen that allows the SNTP server’s IP address to be modified
. Consult the IT
department for details concerning these settings
scrolling through 0 to 60 minutes to set the frequency at which the system will perform SNTP server synchronizations.
74 301C User Manual M-510324
Honeywell 7/10
Bacnet Menu
9. BACNet
-Time Zone­Time Zone : 0:00 DST: OFF
9. BACNet
-Device Name­edit (20 char.max) 301C:1
The next main menu screen is the Date and Time screen. This screen allows the system’s time zone to be defined (if it differs from universal time) and whether daylight savings time is applicable.
If the Time Zone field is selected, use the keypad arrows to scroll through the available times (from 0:00 to +13:00 and -12:00 to 0:00)
The Device Name screen allows a specific name to be assigned to the BACNet device.
The next screens allow users to configure BACNet communication between different systems on a network (subnets), specifically with Foreign Device Registration and BBMD.
M-510324 301C User Manual 75 7/10 Honeywell
Bacnet Menu
9. BACNet
-ForeignDevReg:dis­Enable FDR TTL: 43200 sec
9. BACNet
-BBMD Info­IP: 192.168. 1.100 Port: 0xBAC0
The Foreign Device Registration (FDR) allows users to enable the FDR and to set a specific Time To Live (in seconds).
A Foreign Device is a BACNet device that has an IP subnet address different from those on the BACNet/IP network it seeks to join.
The TTL (Time-To-Live) parameter is the registration duration supplied to the BBMD at the time of registration. Devices must re-register within this specified interval to remain connected.
The BBMD Info screen lets users specify the address for the BBMD to which the device will try to connect (or register).
For more information on this subject, please consult the ASHRAE standard number 135-2001, Annex J, section J5.
76 301C User Manual M-510324
Honeywell 7/10
System Programming
Wireless Network
1. Parameters
2. Diagnostics
3. Nodes
Hibernate
Enter to confirm
Esc to cancel
Parameters
1. 7B7177EFACE0049
2. WC Version
3. PAN ID
System Menu Invalid Option
Log Mode
Log
PAN ID VAL : 1B05 MAX : FFFF MIN : 0001
Diagnostics
1. Weak Link Report
2. Lost Link Report
Nodes
1. ID 121 (79h)
2. 7B7177EFACE0049
3. Product VA301W
Nodes
1. ID 121 (79h)
2. 7B7177EFACE0049
3. Product VA301W
System Menu Invalid Option
4. RF channel
5. Log Mode No Log
6. Association Ina
7. Nodes 0
8. Max nodes 0
9. Max hops 0
10. Power 0
11. AHFO 0
12. BO 0
13. SUO 0
14. LCO 18
15. LTO 0
16. MMO 0
17. BMO 0
18. KNSRO 0
19. FNSRO 0
20. Clone WC
4. Link Quality 1
5. Op Mode Log
6. Net Addr 9
7. SWU slot 1
8. # of parents 1
9. DP Id 0
10. DP Net Addr 0
11. DP LQ1 2
12. DP Retries (?)
13. DP BM 0
14. DP LC 256
15. AP1 ID (?)
16. AP1 Net Addr (?)
17. AP1 LQ1 16
18. AP1 Retries 128
19. AP1 BM (?)
20. AP1 LC 27132032
21. AP2 ID 2
22. AP2 Net Addr 31756
23. AP2 LQ1 198
24. AP2 Retries 190
25. AP2 BM 0
26. AP2 LC 56320
27. LSU 661
28. Status Alive
29. Freshness 2
30. Version A14
31. Hibernate
32. Replace
33. Remove
34. Consolidate Route
35. Failsafe ON
The “ Nodes” menu appearing under both Weak and Lost link reports is identical to the “Nodes” (option 3) in the Wireless Network menu
Association
Ina
System Menu
No Node Found
or
MAC 1st part VAL : 00155F00 MAX : FFFFFFFF MIN : 00000000
New Node VAL : 121 MAX : 180 MIN : 121
Hibernate
Enter to confirm
Esc to cancel
4. New Node
5. Hibernate
6. Reset Network
7. Status Log NoLog
8. Consolidate route
Status Log No Log
Status Log
Enter to confirm
Esc to cancel
Conslidate Route Enter to confirm Esc to cancel
Consolidate Route VAL : 00060 MAX : 65535 MIN : 00000
Wireless Network Menu
Wireless Network Menu
The wireless menu allows wireless communication parameters to be set, wireless network diagnostics to be consulted, and the various aspects of the wireless nodes (sensors) to be accessed.
M-510324 301C User Manual 77 7/10 Honeywell
System Programming
Parameters
1. 7B7177EFACE0049
2. WC Version
3. PAN ID
System Menu Invalid Option
Log Mode
Log
PAN ID VAL : 00000 MAX : 65535 MIN : 00001
4. RF channel
5. Log Mode No Log
6. Association Ina
7. Nodes 0
8. Max nodes 0
9. Max hops 0
10. Power 0
11. AHFO 0
12. BO 0
13. SUO 0
14. LCO 18
15. LTO 0
16. MMO 0
17. BMO 0
18. KNSRO 0
19. FNSRO 0
20. Clone WC
Association
Ina
MAC 1st part VAL : 00155F00 MAX : FFFFFFFF MIN : 00000000
Wireless Network Menu
Parameters Menu
When Parameters is selected from the Wireless Network main menu options, all the coordinator parameters are displayed in order.
The screen can only display three items at one time. Use the up or down arrows to scroll through the list of parameters.
Note: When data is provided for information purposes only, it is not
editable. When an item that is not editable is selected, the screen will briefly display the “System Menu - Invalid Option” screen (as shown above).
78 301C User Manual M-510324
Honeywell 7/10
System Programming
Parameters
1. 7B7177EFACE0049
2. WC Version
3. PAN ID
PAN ID VAL : FF07 MAX : FFFF MIN : 0001
PAN ID
Enter to confirm
Esc to cancel
RF Channel
Enter to confirm
Esc to cancel
RF channel VAL : 011 MAX : 255 MIN : 001
Wireless Network Menu
Changing PAN ID or RF Channel
When the PAN ID or the RF channel is changed, using the Parameters menu option within the Wireless Network menu, the system needs confirmation at more than one option, as described below:
To change the PAN ID:
Select Parameters from the Wireless Network menu
Scroll down (using the arrows) to hightlight option 3, PAN ID
Press Enter to select
Change the PAN ID values, as desired and press Enter
The next screen requests either confirmation or cancellation. Press Enter to confirm (If Esc is pressed, no changes will be made and the screen returns to the main Wireless Network menu)
The system displays the RF channel screen; press Enter to proceed (or to record changed values)
The next screen requests confirmation or cancellation. Press Enter to confirm. If Esc is pressed at this point, the changes to the
PAN ID will not be made.
Note: Whenever changes are made to the PAN ID or the RF channel,
M-510324 301C User Manual 79 7/10 Honeywell
the network must rebuild itself. Losing the network (entire network in Fault mode) during this process is normal and should only last approximately 10 minutes.
System Programming
Wireless Network Menu
The following table provides the list of parameters displayed for the coordinator (wireless communication module). Use the up or down keypad arrows to navigate the entire list.
# Title Value Description
1. 7B177A7EFACE0049 Coordinator MAC address
2. WC Version A10 Wireless coordinator firmware version
3. PAN ID FF07 The hexadecimal ID number assigned to the coordinator
4. RF channel 11 Radio frequency channel
5. Log Mode No
Log
6. Association Ina Defines whether new nodes can join the
7. Nodes 0 Displays the number of nodes
8. Max nodes 0 Defines the maximum nodes that can
9. Max hops 0 Defines the maximum number of hops a
10. Power 0 Sets the transmission power amplifier
11. AHFO 0 Defines the time between wake-up
12. BO 0 Sets the time between transmission of
13. SUO 0 Defines the status update period; time
14. LCO 18 Packet sent from the coordinator to the
15. LTO 0 The number of status update packets
Displays whether debug mode is activated
network
associated to the wireless coordinator.
reside in the network (1-60)
node can make on a communication route to the wireless coordinator
value
cycles
two consecutive beacons by a node to establish and maintain synchronization
between 2 consecutive status update packets sent from node to coordinator
node, confirming to the node that it is registered on the network at the coordinator
that can be missed before a “leave indication” is triggered
80 301C User Manual M-510324
Honeywell 7/10
System Programming
Wireless Network Menu
# Title Value Description
16. MMO 0 Defines the bandwidth of the message retry measurement
17. BMO 0 Defines the bandwidth of the missed beacons measurement
18. KNSRO 0 Defines the frequency at which a node updates information from known neighbors
19. FNSRO 0 Defines the frequency at which a node will scan for new neighbors
20. Clone WC Although accessible, this option is not available (will be used for future advanced use features).
M-510324 301C User Manual 81 7/10 Honeywell
System Programming
Diagnostics
1. Weak Link Report
2. Lost Link Report Nodes
1. ID 121 (79h)
2. 7B7177EFACE0049
3. Product VA301W
Wireless Network Menu
Diagnostics Menu
The diagnostics menu allows both Weak Link and Lost Link reports to be consulted. These reports consist of the multiple-item node information list (as it appears in the Nodes menu). If there are no weak or lost links, the system will return the message “System Menu No Node Found”.
If more than one node appears in this section, use the left or right keypad arrows to scroll through nodes.
82 301C User Manual M-510324
Honeywell 7/10
System Programming
Nodes
1. ID 121 (79h)
2. 7B7177EFACE0049
3. Product VA301W
Wireless Network Menu
Nodes Menu
The Nodes menu displays a multiple-item node information list. Use the left and right keypad arrows to scroll between nodes and then use the up or down keypad arrows to scroll through the information list for each node.
Each line represents specific information, as shown in the screen (above):
Line 1 displays the device’s network identification (the last two digits of
a hexadecimal ID, example 79) and controller reference number
(121) for the specific transmitter. Line 2 displays the device’s MAC address Line 3 displays the type of product (VA301W).
The screen can display only three items at one time, so the up or down arrows must be used to scroll through the list
M-510324 301C User Manual 83 7/10 Honeywell
System Programming
Wireless Network Menu
The following table provides the list of data displayed for each node. Use the right or left keypad arrows to navigate the possible nodes, then use the up or down keypad arrows to navigate the entire list of data for the selected node.
# Title Value Description
4. Link Quality 1 Percentage of signal strength (0-100%) for a node, relative to parent signal quality
5. Log Mod Log Indicates whether the node is in debug mode
6. Net Addr 0009 Displays the node’s (hexadecimal) network address (seen in 1st screen)
7. SWU slot 1 Displays the SWU slot used to transmit beacon
8. # of Parents 1 Displays the number of current parents for a given node, from 0 - 3.
9. DP Id 0 Displays the ID associated to the default parent
10. DP Net Addr 0 Displays the default parent network address
11. DP LQI 2 Displays the link quality with the default parent: 0 = no useful link/1 = weak link/2 = strong link
12. DP Retries (?) Displays the number of default parent retries
13. DP BM 0 Displays the number of parent beacons missed over last beacon period
14. DP LC 256 Displays the time since lasct communication to default parent (in milliseconds)
15. AP1 ID (?) Displays the ID associated to the alternative parent 1
16. AP1 Net Addr (?) Displays the alternative parent 1 network address
17. AP1 LQI 16 Displays the link quality with alternative parent 1: 0 = no useful link/1 = weak link/2 = strong link
84 301C User Manual M-510324
Honeywell 7/10
System Programming
Wireless Network Menu
# Title Value Description
18. AP1 Retries 128 Displays the number of alternative parent 1 retries
19. AP1 BM (?) Displays the number of alternative parent 1 beacons missed over last beacon period
20. AP1 LC 27132
032
Displays the time since last communication to alternative parent 1 (in milliseconds)
21. AP2 ID 2 Displays the ID associated to alternative parent 2
22. AP2 Net Addr 31756 Displays the alternative parent 2 network address
23. AP2 LQI 198 Displays the link quality with alternative parent 2: 0 = no useful link/1 = weak link/2 = strong link
24. AP2 Retries 190 Displays the number of alternative parent 2 retries
25. AP2 BM 0 Displays the number of alternative parent 2 beacons missed over last beacon period
26. AP2 LC 56320 Displays the time since last communication to alternative parent 2 (in milliseconds)
27. LSU 661 Displays the time at which the system was last updated
28. Status Alive Displays whether the node is activated or off
29. Freshness 2 Displays the number of status updates that can be missed before a “leave indication” is triggered
30. Version A14 Node (device) firmware version
31. Hibernate Selecting these options displays a
32. Replace
33. Remove
confirmation screen. If confirmed, the selected function will be executed (see descriptions below).
34. Consolidate Route Enabling this option forces the node to take the best route to the controller using an alternate parent.
35. Failsafe ON This option is only available only when there is a relay module in the network. It allows users to specify relay failsafe settings for a wireless relay module.
M-510324 301C User Manual 85 7/10 Honeywell
System Programming
Wireless Network Menu
Options 1 through 29 are for information purposes only and cannot be modified.
Options 16 through 21 are only displayed if the selected node has a second parent (a parent is any other node to which a node may connect to create a link to the controller).
Option 22 through 27 are only displayed if the node has a third parent.
Options 31 through 33 allow the Hibernate, Replace, or Remove nodes to be selected:
Hibernate Places the node in hibernation (power down). This mode is
used for maintenance or to change the battery.
Replace Allows a node to be replaced by another without changing
the MAC address or node ID (enables a free node with a different [or same] MAC address to be mapped to the current node ID).
Remove Removes the node from the network and erases the node
data from the coordinator memory and from the 301C database.
Option 34, Consolidate Route, allows the user to force the node to find the best route to the controller using an alternate parent.
86 301C User Manual M-510324
Honeywell 7/10
System Programming
Wireless Network
4. New Node
5. Hibernate
6. Reset Network MAC 1st part
VAL : 00155F00 MAX : FFFFFFFF MIN : 00000000
MAC 2nd part
VAL : 80000024 MAX : FFFFFFFF MIN : 00000000
New Node
VAL : 121 MAX : 180 MIN : 121
Wireless Network Menu
New Node Menu
The New Node menu allows users to add new nodes to the existing network, assigning a specific ID number to its MAC address.
Scroll to highlight New Node and press Enter to select
In the New Node window, enter the desired ID value in the VAL field and press Enter
Press Enter to confirm
When the MAC 1st part screen appears, enter the first 8 digits of the new node’s MAC address* and press Enter
Press Enter to confirm
When the MAC 2nd part screen appears, enter the last 8 digits of the new node’s MAC address and press Enter
Press Enter to confirm
*The node’s MAC address is printed on the node’s housing.
Note: If an ID number that already exists is assigned, this function will
M-510324 301C User Manual 87 7/10 Honeywell
not be completed.
System Programming
Hibernate
Enter to confirm
Esc to cancel
Wireless Network
4. New Node
5. Hibernate
6. Reset Network
Wireless Network
4. New Node
5. Hibernate
6. Reset Network
Reset Network
Enter to confirm
Esc to cancel
Wireless Network Menu
Hibernate Menu
The hibernate menu allows users to shut down the entire network of wireless nodes, to prevent any damage when maintenance is needed.
Reset Network Menu
This function, which should only be used by authorized, fully qualified technicians, resets the wireless network parameters to zero,
enabling nodes to look for a new controller in Association mode.
CAUTION
This function resets the nodes; once reset, nodes may change IDs, and thus render controller Events and Groups inoperable.
88 301C User Manual M-510324
Honeywell 7/10
System Programming
Wireless Network
5. Hibernate
6. Reset Network
7. Status Log NoLog
Status Log
Enter to confirm
Esc to cancel
Status Log
Log
Wireless Network
6. Reset Network
7. Status Log NoLog
8. Consolidate Route
Consolidate Route
Enter to confirm
Esc to cancel
Consolidate Route VAL : 00060 MAX : 65535 MIN : 00000
Wireless Network Menu
Status Log Menu
The Status Log file, named wyymmddq.log, that will be recorded on the SD card contains 27 columns of information (as in the sample above) that correspond to each of the first 27 fields in the Nodes Menu.
The resulting file can then be copied to a computer and consulted or printed, as needed.
Consolidate Route Menu
Although nodes will always look for the best route to the controller, this command forces all nodes to search for the shortest communication route, with the least hops, to the controller using an alternate parent.
M-510324 301C User Manual 89 7/10 Honeywell
System Programming
Wireless Network Menu
90 301C User Manual M-510324
Honeywell 7/10
BACnet/IP MODULE
BACnet/IP MODULE
(BIP option)
Specifications
Ethernet Port : 10/100-compatible with 10 Base-T interface, RJ-45
Visual Indicators : Green LED LINK
Yellow LED ACT
Network Configuration: See 301C BACnet menu section.
BACnet/IP protocol
UDP Port: 47808. This value is not modifiable using the 301C.
The module has been developed as per ANSI/ASHRAE Standard 135­2001 : BACnet®— A Data Communication Protocol for Building Automation and Control Networks. The Data Link Layer option is per BACnet/IP (Annex J).
http://www.ashrae.org/
BACnet Objects
BACnet objects represent any information available through the 301C sub network. Each available value is represented by one object of a specific type. There are currently 6 object types supported :
Analog Input represented by ‘AI’ Analog Value represented by ‘AV’ Binary Input represented by ‘BI’ Binary Output represented by ‘BO’ Binary Value represented by ‘BV’ Device represented by ‘DEV’
M-510324 301C User Manual 91 7/10 Honeywell
BACnet/IP MODULE
Analog Input
The Analog Input object type defines a standardized object whose properties represent the externally visible characteristics of an analog input, such as a gas sensor.
Supported properties for the Analog Input object type are : Object_Identifier, Object_Name, Object_Type, Status_Flags, Event_State, Reliability, Present_Value, Out_of_Service and Units.
Analog Value
The Analog Value object type defines a standardized object whose properties represent the externally visible characteristics of an analog value. An "analog value" is a control system parameter residing in the memory of the BACnet Device, such as a gas alarm level.
Supported properties for the Analog Value object type are : Object_Identifier, Object_Name, Object_Type, Status_Flags, Event_State, Reliability, Present_Value and Units.
Binary Input
The Binary Input object type defines a standardized object whose properties represent the externally visible characteristics of a binary input. A "binary input" is a physical device or hardware input that can be in only one of two distinct states, such as the 301ADI digital inputs.
Supported properties for the Binary Input object type are : Object_Identifier, Object_Name, Object_Type, Status_Flags, Event_State, Reliability, Present_Value, Polarity, Inactive_Text and Active_Text and Out_of_Service.
92 301C User Manual M-510324
Honeywell 7/10
BACnet/IP MODULE
Binary Output
The Binary Output object type defines a standardized object whose properties represent the externally visible characteristics of a binary output. A "binary output" is a physical device or hardware output that can be in only one of two distinct states, such as a relay or a switchable power output.
Supported properties for the Binary Output object type are : Object_Identifier, Object_Name, Object_Type, Status_Flags, Event_State, Reliability, Present_Value, Polarity, Inactive_Text, Active_Text, Priority_Array, Relinquish_Default and Out_of_Service.
Binary Value
The Binary Value object type defines a standardized object whose properties represent the externally visible characteristics of a binary value. A "binary value" is a control system parameter residing in the memory of the BACnet Device.
Supported properties for the Binary Value object type are : Object_Identifier, Object_Name, Object_Type, Status_Flags, Event_State, Reliability, Present_Value, Inactive_Text, Active_Text, Priority_Array, and Relinquish_Default.
Device
The Device object type defines a standardized object whose properties represent the externally visible characteristics of a BACnet Device. There is only one Device object to represent the BACnet Module.
Supported properties for the Device object are : Object_Identifier, Object_Name, Object_Type, System_Status, Vendor_Name, Vendor_Identifier, Model_Name, Firmware_Revision, Application_Software_Version, Protocol_Version, Protocol_Revision, Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_List, Max_APDU_Length_Accepted, Segmentation_Supported, APDU_Timeout, Number_Of_APDU_Retries, Device_Address_Binding, Database_Revision, Local_Time, Local_Date, UTC_Offset, Daylight_Savings_Status and Out_of_Service.
M-510324 301C User Manual 93 7/10 Honeywell
BACnet/IP MODULE
Honeywell Products and BACnet Objects
Object Names
Object names are constructed in two parts, as follows:
Part one: The device display label (product name) for the network in
which the object resides. This value is editable only when using the 301C controller.
Part two: Unique tag label among all the objects for the same device.
Ex : “301D2 CO2 AD:14.CO2” where ‘301D2 CO2 AD:14’ is the device display label and ‘CO2’ is the unique tag label that identifies the object as a CO2 sensor.
Vulcain Object Tag Labels
Table 1:
Tag Labels Description
‘Gas label’ Gas sensor AI .Alrm Simple alarm level AV Amin /Amax Alarm level A and hysteresis AV Bmin /Bmax Alarm level B and hysteresis AV Cmin /Cmax Alarm level C and hysteresis AV relx Relay output X (1 to 8) BO buzz Buzzer output BO .outx Output X (1 to 3) BO or BV .AIx Analog input X (1 to 16) AI .BIx Binary Input X (1 to 12) BI .RH Relative Humidity sensor AI .Temp Temperature sensor AI
94 301C User Manual M-510324
Honeywell 7/10
Object
Type
BACnet/IP MODULE
Object Table For Honeywell Network Devices
Objects residing in Honeywell network devices
Device GP2 301IRF 301EM 201T2/vulbus 90DM3R
.GAZ .GAZ .GAZ .GAZ .GAZ .Amin .Amin .Amin .Amin .Alrm .Amax .Amax .Amax .Amax .Bmin .Bmin .Bmin .Bmin .Bmax .Bmax .Bmax .Bmax .Cmin .Cmin .Cmin .Cmin .Cmax .Cmax .Cmax .Cmax .rel1 .rel1 .rel1 (snsr1) .rel1 .rel2 .rel2 .rel2 (snsr1)
.rel3 .rel3 (snsr1)
.rel4 (snsr1) .out1
(snsr1) .out2
(snsr1) .out3
Objects
(snsr1)
M-510324 301C User Manual 95 7/10 Honeywell
BACnet/IP MODULE
Object Table For Honeywell Network Devices
Objects residing in Honeywell network devices
Device 301AP 301C 301R 301ADI 901T
.rel1 .rel1 .rel1 .AI1 to .AI16 .GAZ .rel2 .rel2 .rel2 .BI1 to .BI12 .Amin .rel3 .rel3 .rel3 .Amax .buzz .rel4 .rel4 .Bmin
.buzz .rel5 .Bmax
.rel6 .Cmin .rel7 .Cmax .rel8
Objects
96 301C User Manual M-510324
Honeywell 7/10
BACnet/IP MODULE
Object Table For Honeywell Network Devices
Objects residing in Honeywell network devices
Device ECF9 S301RLC 301W 301RW S td.Device*
.GAZ .GAZ .GAZ .rel1 .GAZ .Amin .Amin .Amin .rel2 .Amin .Amax .Amax .Amax .rel3 .Amax .Bmin .Bmin .Bmin .rel4 .Bmin .Bmax .Bmax .Bmax .rel5 .Bmax .Cmin .Cmin .Cmin .rel6 .Cmin** .Cmax .Cmax .Cmax .rel7 .Cmax**
.rel8
Objects
* Std.Device refers to the following products: S301M, 420MDBS and 90DM4 ** The values .Cmin and .Cmax apply only to the 90DM4.
M-510324 301C User Manual 97 7/10 Honeywell
BACnet/IP MODULE
Object Examples
In the first example, we see the CO
gas sensor input for a 301D2
2
Vulcain network device:
Name : “301D2 CO2 AD:14.CO2” Value : 600 Units : PPM Object : 1.AI2* Description : Analog Input
* 1 is the 301C unique device instance, AI is the object type and 2 is the unique instance of the object in this device. We identify this object as “Analog Input 2 of BACnet device 1”.
In this example, we can see the output status for relay 2 of the same Vulcain network device, but with a different device display label:
Name : “Floor 01 Sensor 02 .rel2” Value : OFF Units : Object : 1.BO4* Description : Binary Output
*We identify this object as “Binary Output 4 of BACnet device 1”.
Example 3 where we can see the first 24V output status of a 301EM Vulcain network device.
Name : “301EM CO AD:25.out1” Value : OFF Units : Object : 1.BV1 Description : Binary Value*
*We identify this object as “Binary Value 1 of BACnet device 1”.
98 301C User Manual M-510324
Honeywell 7/10
Loading...