APPLICATION
The 272630D auxiliary board is an optional circuit board that is used in conjunction with Series 4000 ML6984 and ML7984 globe valve actuators. This auxiliary board combines the function of an adjustable low voltage SPDT auxiliary switch with a 2-10 Vdc or 4-20 mA position feedback signal. It has a 4-pin keyed connector for communications from the mother circuit board.
SPECIFICATIONS
Feedback: 2-10 Vdc (10-2 V reverse acting)
into minimum impedance 500 Ω. Maximum output current is 20 mA dc.
272630D
For ML6984 and ML7984
INSTALLATION INSTRUCTIONS
Auxiliary Switch: SPDT, 24 V, 50/60Hz, 1 A
2005.04 RJ Printed in Canada Form No. 95C-10941
inductive. Fixed differential (3% of stroke), adjustable operating point from 0 to 100% of stroke.
272630D Auxiliary Board
INSTALLATION
Fingers Bridge
When installing this product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation in complete, check out product operation as provided in these instructions.
!
CAUTION:
1. Disconnect power supply before beginning
installation to prevent electric shock and equipment damage.
2. All wiring must comply with applicable local
electrical codes, ordinances and regulations.
3. DO NOT electrically operate the ML6-7984
actuator before assembly to the valve because damage not apparent to the installer may occur. Mount the actuator to the valve before connecting to power.
Assembly
1. Remove plastic cover from the ML6-7984
by loosening the two screws located on the top. (Note: These screws are captive. Rotate three complete revolutions to remove cover).
2. Slide the auxiliary board into the two slots
at the bottom of the bridge. Push back and snap the board into the fingers. (See Fig. 1)
3. Connect one end of the 4-pin connector to
the main board and the other end to the auxiliary board if it is not already connected. The connectors are keyed and only install one way.
4. Mount the actuator onto the valve body and
connect wiring.
5. Reinstall cover after operational check.
1. Install circuit board
Slots
Fig. 1 - Installation of auxiliary board
OPERATION
The first time the valve is powered, the microprocessor will automatically cycle the valve through a full stoke to calibrate its position. Any stroke between 1/2" (13 mm) and 1" (25 mm) will be divided into 30 equal steps. Run time will be proportional to stroke length. (For example: nominal timing for 3/4" stroke is 63 seconds. For 1/2" stroke this would be 42 seconds). The LED lights up when terminals T5-T6 are powered, and flash when the actuator is in motion.
NOTE: 272630D requires that the actuator be continuously powered, so ML6984 must be wired in "5-wire" configuration.
C-NC contact CLOSED when valve position is below trim pot setting (direct acting).
RLY1
C-NO contact CLOSED when valve position is above trim pot setting (direct acting).
Trim pot
LED
2-10 V, (4-20 mA into 500 ) feedback output COM
+FBNC C NO
-COM
J1
Connect to main board for position feedback.
Fig. 2 - Wiring and operation of auxiliary
board 272630D