Honeywell 15P, Vista-20P, Vista-20PSIA, Vista-15PSIA Installation And Operation Manual

Page 1
ADEMCO VISTA SERIES
VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA
Security Systems
Installation and Operation Guide
K5305-1V8 4/09 Rev. A
Page 2
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection
Devices Help Provide Proper Coverage for the Protected Premises.
Recommendations For Smoke And Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES.
DINING
LIVING ROOM
BEDROOM
LVNG RM
BASEMENT
KITCHEN
BEDROOM
TO BR
BEDROOM
BEDROOM
BEDROOM
KTCHN
BEDROOM
CLOSED
.
DOOR
TV ROOM
BEDROOM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
GARAGE
KITCHEN
LIVING ROOM
DINING
BDRM
BDRM
floor_plan-001-V1
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or commercial premises. This would include any skylights that may be present, and the upper windows in a multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can still be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).
ii
Page 3
Table Of Contents
Features and Installation Highlights............................................................................................................1-1
Capabilities and Functions................................................................................................................................................1-1
Compatible Devices ...........................................................................................................................................................1-2
Important Installation Highlights (Installer Please Read) .............................................................................................1-2
Mounting and Wiring the Control .................................................................................................................2-1
Installing the Control Cabinet and PC Board.................................................................................................................. 2-1
Cabinet and Lock .........................................................................................................................................................2-1
Mounting the PC Board Alone (no RF Receiver)........................................................................................................2-1
Mounting Board with RF Receiver..............................................................................................................................2-1
Auxiliary Device Current Draw Worksheet................................................................................................................2-2
AC Power, Battery, and Ground Connections..................................................................................................................2-3
1321 Transformer.........................................................................................................................................................2-3
1361X10 Transformer..................................................................................................................................................2-3
Battery Connections.....................................................................................................................................................2-3
Battery Saver Feature ................................................................................................................................................. 2-3
Earth Ground ............................................................................................................................................................... 2-3
Sounder (Bell) Connections...............................................................................................................................................2-4
Basic Connections ........................................................................................................................................................2-4
Supervised output........................................................................................................................................................2-4
Connecting the Keypads and Other Addressable Devices...............................................................................................2-4
Connections .................................................................................................................................................................. 2-4
Supplementary Power (optional).................................................................................................................................2-4
Keypad Notes ...............................................................................................................................................................2-5
Communication Device ................................................................................................................................................ 2-5
(Long Range Radio) Connections.................................................................................................................................2-5
Table of Device Addresses.................................................................................................................................................2-5
Hardwire Zones and Zone Expansion...............................................................................................................................2-6
Hardwire Zones............................................................................................................................................................2-6
Double-Balanced Zones................................................................................................................................................2-6
Zone Doubling ..............................................................................................................................................................2-6
Smoke Detectors...........................................................................................................................................................2-6
Smoke Detector Notes.................................................................................................................................................. 2-7
4219/4229 Expansion Zones ........................................................................................................................................2-7
Installing the RF Receiver and Wireless Transmitter Zones ..........................................................................................2-8
Compatible Receivers...................................................................................................................................................2-8
Receiver Connections...................................................................................................................................................2-8
RF Receiver Notes........................................................................................................................................................2-8
Installing a 5800TM Module ....................................................................................................................................... 2-9
Installing the Transmitters.........................................................................................................................................2-9
Transmitter Battery Life.............................................................................................................................................2-9
Installing a Keyswitch.....................................................................................................................................................2-10
Keyswitch Connections..............................................................................................................................................2-10
Keyswitch Notes.........................................................................................................................................................2-10
Connecting Relay Modules, Powerline Carrier Devices and Output Triggers..............................................................2-11
4204/4229 Relay Modules..........................................................................................................................................2-11
Powerline Carrier Devices.........................................................................................................................................2-11
On-Board Triggers .....................................................................................................................................................2-12
Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections............................................................2-13
Phone Line..................................................................................................................................................................2-13
4286 Phone Module....................................................................................................................................................2-13
Phone Module Problems ............................................................................................................................................2-13
Audio Alarm Verification Connections......................................................................................................................2-14
Audio Alarm Verification Connections......................................................................................................................2-15
iii
Page 4
Table Of Contents
System Communication and Operation .......................................................................................................3-1
Panel Communication with Central Station ....................................................................................................................3-1
Report Code Formats......................................................................................................................................................... 3-1
Ademco Contact ID®.........................................................................................................................................................3-3
Uploading/Downloading via the Internet .........................................................................................................................3-4
System Security Codes ......................................................................................................................................................3-5
Panic Keys..........................................................................................................................................................................3-7
Setting the Real-Time Clock .............................................................................................................................................3-7
Various System Trouble Displays.....................................................................................................................................3-8
Testing the System.............................................................................................................................................4-1
About Test Procedures.......................................................................................................................................................4-1
System Test........................................................................................................................................................................4-1
Checking Transmitter Enrollment (Sniffer Mode)...........................................................................................................4-1
Go/No Go Test Mode .......................................................................................................................................................... 4-2
Dialer Communication Test and Periodic Test Reports...................................................................................................4-2
Automatic Standby Battery Tests.....................................................................................................................................4-2
Specifications & Accessories ...........................................................................................................................5-1
Security Control................................................................................................................................................................. 5-1
Compatible Devices ...........................................................................................................................................................5-1
Regulatory Agency Statements ......................................................................................................................6-1
Limitations and Warranty ...............................................................................................................................7-3
iv
Page 5
SECTION 1
Features and Installation Highlights
This manual applies to the following Honeywell security systems:
ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/ADEMCO VISTA-20PCN (collectively referred to as VISTA-20P series), ADEMCO VISTA-15P/ADEMCO VISTA-15PSIA/ADEMCO VISTA-15PCN (collectively referred to as VISTA-15P series) Features and procedures apply to all, except where differences are noted.
SIA Installations: The VISTA-20PSIA and VISTA-15PSIA are certified SIA-compliant controls that meet SIA specifications for False Alarm Reduction. The other controls described in this manual are not certified as SIA compliant, but can be programmed for False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.
Capabilities and Functions
Feature/Function VISTA-20P Series VISTA-15P Series
Partitions
Zones Up to 48 protection zones plus 16 keyfob
Security Codes Up to 48 Security Codes, with separate
One-button arming Dedicated keys can arm the system. Dedicated keys can arm the system. Schedules Up to 32; can control devices and/or auto-
Keypad macros Up to 4; activated by wired keypads Up to 2; activated by wired keypads Paging Up to 4 pagers; certain system conditions
Event Logging 100 events; display via Compass Downloader
Zone descriptors Can assign for all zones (for alpha display keypads and/or 4286 Phone Module). Bell supervision Optional, detects external sounder wiring short (when in alarm) or open (when bell is off);
RF jam detection Optional, for wireless systems detects a condition that may impede proper RF reception
Telephone Line Monitoring Downloading via Phone Line or Internet
2 partitions, can protect two independent areas
Common zone option allows either partition to arm, while leaving a common area (ex. lobby or foyer) disarmed for access into the other partition.
zones (zones 49-64) for total of 64 zones:
8 basic hardwired zones (zones 1-8) with optional zone-doubling feature
Up to 40 additional wired zones (zones 9-
48) using up to 5 4219/4229 modules
Up to 40 wireless transmitter zones (5800 series; zones 9-48)
Up to 4 configurable zone types
authority levels and partition access
arm/disarm
can report to pagers; can use a dedicated key on keypads to send a signal to a pager
software or installer/master code at Keypad
causes a trouble condition, keypad display, and sends a report to the central monitoring station, if enabled.
(i.e., jamming or other RF interference); causes keypad display, and sends a report to the central monitoring station (if trouble reporting is enabled). Built-in option can monitor the telephone line voltage and can cause a local display, or a display and trouble/alarm sound.
Via Standard Phone Line: Use an IBM compatible computer, Compass downloading
software, and a compatible HAYES or CIA modem specified by Honeywell.
Via Internet: supports Upload/Download via the Internet/Intranet when used with an
appropriate communications device (ex. 7845i-GSM) and Compass downloading software. This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet. UL NOTE: Uploading/Downloading via the Internet has not been evaluated by UL.
VISTA-15P is not a partitioned system.
Up to 32 zones plus 8 keyfob zones (zones 49-56) for total of 40 zones:
6 basic hardwired zones (zone 1-6)
Up to 16 additional wired zones (zones 9-
24) using up to 2 4219/4229 modules
Up to 26 wireless transmitter zones (5800 series; zones 9-34)
Up to 2 configurable zone types
Up to 32 Security Codes, with separate authority levels
Up to 8; can control devices and/or auto­arm/disarm
Up to 2 pagers; certain system conditions can report to pagers; can use a dedicated key on keypads to send a signal to a pager 50 events; display via Compass Downloader software or installer/master code at Keypad
1-1
Page 6
Installation and Setup Guide
Compatible Devices
Device VISTA-20P VISTA-15P Notes
Addressable Keypads 8 8 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V
Fixed-Word Display Voice Keypad, 6160V Alpha
Display Voice Keypad, 6150RF Keypad/Transceiver Touch Screen (AUI) Devices 4219, 4229 Zone Expander Modules
5800 Series Wireless Up to 40 RF
Output relays and/or Powerline Carrier Devices (X-10 type) On-Board Triggers 2 2 Can be used to reset 4-wire smoke detectors. Output functions Up to 48 Up to 24 Program output functions via *80 Menu mode. 4286 Phone Module Partition 1
Audio Alarm Verification
Alarm output 12VDC, 2
Auxiliary Power Output See note. See note 12VDC, 600 mA maximum; uses circuit protection. Backup Battery See note. See note. Rechargeable (sealed lead-acid type) 12VDC, 4AH
Long Range Radio (Communication Device)
AC Power Supply See note. See note. Plug-in 120VAC transformer, 1321 (1321CN in
NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.
4 2 Touch Screen (AUI) devices are in addition to the 8
addressable keypads. E.g., Symphony, 6270
Up to 5 for
up to 40
exp. zones
zones
Up to 16 Up to 8 Use any combination of 4204, 4229 and or Powerline
only
Using AAV
module
AMP output
See note. See note. Primary telephone number messages can be reported
Up to 2 for
up to 16
exp. zones
Up to 26 RF
zones
yes Provides access to the system via on premises or off-
Using AAV
module
12VDC, 2
AMP output
Zone numbers are predefined according to the device
addresses used. See Expander Module Addresses table
in Wiring section and set addresses accordingly.
Uses 5881/5883 Series Receivers/Transceivers.
Carrier Devices.
Map output devices via *79 Menu mode.
premises phones for arming, disarming, etc., plus
control of relay outputs and Powerline Carrier devices.
Use ADEMCO UVS or Eagle Model 1250 in
conjunction with an output trigger to permit voice
dialog between an operator at the central station and
a person at the premises. Alternatively, the AVS
system can be used to provide AAV via phone line or
AlarmNet IP/GSM (using a GSMV module).
Can drive the compatible sounders; steady output for
burglary/panic, or temporal pulse (3 pulses – pause –
3 pulses – pause – 3 pulses. . .) for fire. Uses current
limiting circuitry for protection.
minimum.
via ECP connection to various communication devices
(check compatibility/availability of specific models)
Canada) or, if using Powerline Carrier devices,
1361X10 Transformer Module
Important Installation Highlights (Installer Please Read)
This system uses addressable keypads and Zone Expander Modules (see Table of Addresses in
Section 2. Mounting and Wiring – Wiring the Keypads and Other Addressable Devices).
Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from previous controls) and programmed in data fields *190-*196.
Zone Expander Modules must be set for specific addresses (07-11), based on the zone numbers used.
4204 Relay Modules must be set for specific addresses (12-15).
This control will not power-up unless AC power is connected (will not power-up on battery alone).
However, once the system is powered up, it will operate on battery power in the event of AC loss.
Relays have two programming menu modes: Use *79 Menu mode to map module addresses and device (output) numbers. Use *80 Menu mode to define the output functions.
This system supports programmable function keys. Use *57 Menu mode to define the function keys.
1-2
Page 7
Mounting and Wiring the Control
Installing the Control Cabinet and PC Board
Cabinet and Lock
Mounting the PC Board Alone (no RF Receiver)
1. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet mounting holes.
2. Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock.
3. Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, push the lock until the snap tabs hold it securely.
The cabinet can be secured without a lock by using 2 screws in the cover's edge. Before installing the cabinet's contents, remove the metal cabinet knockouts required for wiring entry. Do not remove the knockouts after the circuit board has been installed.
1. Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B).
2. a. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure
that the board rests on the correct row (see Detail A).
b. Swing the base of the board into the mounting clips and secure the board to the
cabinet with the accompanying screws (see Detail B).
SECTION 2
CHECK
POSITION
LOCKED
UNLOCKED
CABINET DOOR
BOTTOM
PUSH
Figure 1. Installing the Cabinet Lock
SNAP
TAB
ADEMCO
SNAP
TAB
CIRCUIT
BOARD
STEP 2STEP 1
ADEMCO
PUSH
ON LOCK
UNTIL IT IS SEATED SECURELY
CABINET
cab_lock_snap-001-V0
Mounting Board with RF Receiver
CIRCUIT
BOARD
DETAIL A
SIDE VIEW
OF BOARD
SUPPORTING
SLOTS
CABINET
+
+
DETAIL B
SIDE VIEW
OF MOUNTING
CLIPS
MOUNTING-001-V0
Figure 2. Mounting the PC Board
Do not mount the cabinet on or near metal objects. This will decrease RF range and/or block RF transmissions from wireless transmitters.
Do not locate the cabinet in an area of high RF interference (revealed by frequent or prolonged lighting of the LED in the receiver (random flicker is OK)
1. a. Remove the receiver board from its case, then insert the top of the board into the
slots at the top of the cabinet, as shown in Detail A in Figure 3 on the next page. Make sure that the board rests on the correct row of tabs.
b. Swing the base of the board into the mounting clips and secure it to the cabinet
with the accompanying screws.
c. Insert the top of the control's board into the slot in the clips and position two clips
at the lower edge of the board.
d. Swing this board into place and secure it with two additional screws.
2. Insert grounding lugs (supplied with the receiver) through the top of the cabinet into
the left-hand terminals of the antenna blocks (at the upper edge of the receiver board) and secure them to the cabinet top with the screws provided (see Detail B).
3. Insert the receiver's antennas through the top of the cabinet, into the blocks' right-
hand terminals, and tighten the screws.
2-1
Page 8
Installation and Setup Guide
CABINET
RECEIVER CIRCUIT BOARD
INSTALLATION WITH RECEIVER CIRCUIT BOARD
WHITE
MOUNTING
CLIP
NOTE A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN INCLUDED IN YOUR INSTALLATION KIT. USE THE APPROPRIATE CLIPS FOR MOUNTING.
IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.
AB
BOARD SUPPORTING
RED
MOUNTING
CLIP
SLOTS
MOUNTING CLIP
MOUNTING CLIP
CIRCUIT
BOARD
DETAIL A
SIDE VIEW
OF BOARD -
SUPPORTING SLOTS
ANTENNA
(2)
SCREW
(2)
GROUNDING
LUG
(2)
ANTENNA
(2 PLACES)
DETAIL B
ANTENNA AND GROUNDING
LUG INSTALLATION
++
CONTROL
CIRCUIT
BOARD
BLACK
MOUNTING
CLIP
Figure 3. Mounting the PC Board and RF Receiver
CABINET
MOUNT
pc_mount-001-V1
Auxiliary Device Current Draw Worksheet
6150 Fixed-Word Keypad 40mA/70mA** 6160 Alpha Keypad 40mA/150mA** 6150V Fixed-Word Display Voice Keypad 60mA/160mA** 6160V Alpha Display Voice Keypad 60mA/190mA** 8132/8142 Series AUI (Symphony) 150mA/400mA** 6270 Touch Screen Keypad 180mA/280mA** 5881/5882 RF Receiver 60mA 5883 Transceiver 80mA 4219 Zone Expander 30mA 4204 Relay Unit
4229 Zone Expander/Relay Unit 4286 Phone Module 300mA
*
(Current available from Aux. terminals = 600 mA max.)
*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw. ** Values are for standby/alarm; alarm for keypads means armed with backlighting on and sounder on †In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Aux. Output). ‡Values are for relays OFF/relays ON.
The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet these requirements without using a supplementary power supply, provided that the panel’s auxiliary power and bell output currents are limited as indicated below.
Output Current Total Maximum Auxiliary Current Battery Capacity
600mA maximum total of
auxiliary power plus bell
output currents
NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the cabinet.)
DEVICE CURRENT No. UNITS TOTAL CURRENT
15/180mA‡ 30/100mA‡
TOTAL =
CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE
24-HOUR BATTERY BACKUP REQUIREMENTS
OUTPUT CURRENT LIMITATIONS BATTERY INFORMATION
OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES
Recommended Battery
45mA 160mA 200mA 425mA 500mA
To Use (Amp/Hrs)
4AH 7AH 8AH
14AH
17.2AH
(Yuasa Model No.)
NP4-12 (or ADEMCO 467)
NP7-12 NP4-12 (two) ‡ NP7-12 (two) ‡ NPG18-12
2-2
Page 9
AC Power, Battery, and Ground Connections
AC AC
SYNC
COM DATA
2
34
5
1
2
1
SA412OXM CABLE
CONTROL
BOARD
TERMS.
1361X10 TRANSFORMER
1 345678
8-PIN TRIGGER CONNECTOR
KEY
+12 AUX.
DATA
COM
SYNC
GND (-)
OUTPUT 17
(RED)
OUTPUT 18
(GREEN)
(ORANGE)
(YELLOW)
(BLUE)
(PURPLE)
(BLACK)
1321 Transformer
1
2
TO
TERMINALS
1 AND 2
1361X10 Transformer (required if using Powerline Carrier devices)
AC
AC
S y n
c
O
u tp
S ig
u
t
n a
C
l
o
m
m
X10 o n
Data
Battery Connections
BLACK
RED
CONNECT FLYING LEADS AFTER AC POWER IS APPLIED
CONNECTOR
TO
TERMINALS
1 AND 2
8-PIN
1
Battery Saver Feature
Earth Ground
CONNECT PROPER EARTH
CONTROL BOARD
25
GROUND IF DESIRED
Connect the 1321 Transformer (1321CN in Canada) to terminals 1 and 2 on the control board. See Wire Run Chart for wire size to use.
Use caution when wiring the transformer to the control to guard against blowing the transformer fuse (the fuse is non-replaceable).
1321X10-001-V0
Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire. The
voltage reading between terminals 1 and 2 of the control must not fall below 16.5VAC or an “AC LOSS” message will be displayed.
Do not plug the transformer into the AC outlet until all wiring connections to the
control are complete. As a safety precaution, always power down the control when making such connections.
1. Splice one end of a 3-conductor cable
to the wire ends of the SA4120XM-1 Cable.
2. Connect the SA4120XM-1 cable plug
to the 8-pin connector on the control (see the Summary of Connections
TO
diagram for location of the 8-pin connector).
3. Connect the other end of the
2
3-conductor cable to the 1361X10
Transformer, as shown in Figure 4. Canadian Installations: See Powerline Carrier Device section for
1361X10-001-V0
connections to the PSC04 X-10 Interface and trigger pins.
1. Place the 12-volt backup battery in the cabinet.
2. After all connections to the control are completed and AC power has been applied,
connect the red and black flying leads on the control board to the battery. Do not
attach these leads to the battery terminals until all connections are completed.
U
L
at left for the correct battery size required to meet the mandatory standby time.
batt_conn-001-V0
The battery will disconnect from the system after its voltage decreases below 9VDC. This assists the control panel in recharging the battery when AC is restored. IMPORTANT: The panel will not power up initially on battery power only. You must plug the transformer in first, and then connect the battery.
This product has been designed and laboratory-tested to ensure its resistance to
damage from generally expected levels of lightning and electrical discharge, and does not normally require an earth ground.
If an earth ground is desired for additional protection in areas of severe electrical
activity, terminal 25 on the control board, or the cabinet, may be used as the ground connection point. The following are examples of good earth grounds available at most installations.
Metal Cold Water Pipe: Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which the ground lead is electrically connected and secured.
AC Power Outlet Ground: Available from 3-prong, 120VAC power outlets only. To test
earth_gnd-001-V0
the integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61-035, or equivalent, available at most electrical supply stores.
Mounting and Wiring the Control
Wire Run Chart
Distance from control Wire Size
Up to 50 feet # 20 50–100 feet # 18 100-250 feet # 16
Figure 4. 1361X10 Transformer Connections
For UL installations and Residential fire installations, refer to the chart on page 2-2
2-3
Page 10
Installation and Setup Guide
Sounder (Bell) Connections
Basic Connections
ALARM OUTPUT
10.5 - 13.5 VDC 2A MAX.
Make sounder connections to alarm output terminals 3 (+) and 4 (–).
The 12VDC sounder output activates when an alarm occurs.
3
4
Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will overload the power supply, or may cause the electronic circuit protecting the sounder output to trip).
You must install a battery, since the battery supplies this current.
Supervised output
1. Cut the red Bell Supervision Jumper located above terminal 5 on the PC board.
2. Connect a 2k ohm resistor across the terminals of the last sounder. See Figure 5.
3. Set field ∗91 Option Selection for Bell Supervision.
spkr_conn-001-V0
This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses – pause – 3 pulses–etc..
U
L
Use only UL Listed sounding devices for UL installations.
Bell supervision is required for fire alarm installations.
The total current drawn from the alarm
ALARM
OUTPUT
TERMINALS
output and the auxiliary power output, combined, cannot exceed 600 mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a 10.2-13.8 VDC voltage range, and must be mounted indoors.
CUT RED JUMPER ON CONTROL BOARD TO ENABLE BELL (SOUNDER) SUPERVISION.
Figure 5. Sounder Wiring (Supervised)
Connecting the Keypads and Other Addressable Devices
Connections
ARM
ED
READ
Y
_
4
+
5
6 IN
BLACK
RED
GREEN
YELLOW
Connect keypads and other addressable devices (4204, 4219, 4229, 4286, 5881, LRR, etc.) to the control’s keypad terminals as shown on the Summary of Connections diagram. The system supports up to 8 keypads, which can be assigned to partitions in
7 OUT
any combination (see program fields *190-*196).
Use the Table of Device Addresses to determine the appropriate address for each device.
Determine wire size using the Wire Run Chart on the following page. For single 4-wire runs, determine the current drawn by all units, then refer to the Wiring Run chart to determine the maximum length that can be safely used for each wire size.
TERMINALS ON
CONTROL BOARD
_
4
+
3
2
EXTERNAL ALARM
SOUNDER
_
OBSERVE POLARITY
+
IF BELL SUPERVISION IS ENABLED (RED JUMPER ON CONTROL BOARD IS CUT) CONNECT A 2000 OHM RESISTOR ACROSS THE EXTERNAL SOUNDER AS SHOWN BY THE DOTTED LINE.
DO NOT CONNECT THE RESISTOR AT THE ALARM OUTPUT TERMINALS THEMSELVES!
2000 OHM EOL RESISTOR
sounder-001-V0
conn-001-V0
Supplementary Power (optional)
U
Use a UL Listed,
L
battery-backed supply for UL installations. The battery supplies power to these keypads in case of AC power loss. The battery-backed power supply should have enough power to supply the keypads with the UL required minimum standby power time.
Use supplementary power if the
control’s aux. power load for all
devices exceeds 600mA (suggested
power supply: AD12612). Connect
as shown in Figure 6. Be sure to
connect the negative (–) terminal
on the power supply unit to
terminal 4 (AUX –) on the control.
IMPORTANT: Keypads powered from supplies that do not have a backup battery will not function if AC power is lost. Make sure to power at least one keypad in each partition from the control’s auxiliary power output.
2-4
SUPPLEMENTARY
POWER SUPPLY
+
TO KEYPAD RED WIRE
TO KEYPAD BLK WIRE
TO KEYPAD GRN WIRE
TO KEYPAD YEL WIRE
CONTROL TERMINAL STRIP
IMPORTANT:
MAKE THESE CONNECTIONS DIRECTLY TO SCREW TERMINALS AS SHOWN.
AUX. DATA
AUX.
IN
+
456 7
TO KEYPAD BLK WIRE
TO KEYPAD RED WIRE
TO KEYPAD GRN WIRE
DATA
OUT
supp_pwr_supply-V0
TO KEYPAD YEL WIRE
Figure 6. Using a Supplementary Power Supply
Page 11
Mounting and Wiring the Control
Keypad Notes
Set device addresses. Refer to the instructions included with the devices and set each address according to the Table of Device Addresses. See Keypad Programming Fields (fields *190-*196) in Section 4. Data Field
ARMED
READY
1
OFF
2
AWAY
4
MAX
3
STAY
5
TEST
7
IN
ST A N
T
6
B Y P
8
A
S S
COD
E
R
E AD Y
9
CHIME
0
#
Programming for details on enabling keypad addresses, assigning keypad partitions and selecting keypad sounding options.
IMPORTANT: Each keypad must be assigned a unique, predefined address, from 16 to
23. The first keypad is address 16 (default = partition 1, all sounds enabled).
TOUCH SCREEN KEYPAD (AUI) NOTES:
•••• Use of AUI devices (e.g., 6270, Symphony) is independent from standard keypads and
does not affect the number of standard keypads the system can support.
•••• AUI devices must be set for address 1, 2, 5**, or 6** depending on which unit is
enabled in field *189. ** VISTA-20P series
•••• To ensure proper AUI device operation, use AUI devices with the following rev levels:
6270 series use version 1.0.9 or higher; 8132/8142 (Symphony) series use version
1.1.175 or higher.
Communication Device (Long Range Radio) Connections
Connect the data in/data out terminals and voltage input terminals of the communication device to the control's keypad connection points. Set the device’s address to “03” following the instructions provided with the device.
Use a compatible communication device (e.g., 7845GSM, 7845i-GSM).
Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)
Wire
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Size 50 mA or less 100 mA 300 mA 500 mA 600 mA
#22 900 ft (274m) 450 ft (137m) 150 ft (46m) 90 ft (27m) 75 ft (23m) #20 1400 ft (427m) 700 ft (213m) 240 ft (73m) 140 ft (43m) 120 ft (37m) #18 1500 ft (457m) 1100 ft (335m) 350 ft (107m) 220 ft (67m) 170 ft (52m) #16 1500 ft (457m) 1500 ft (457m) 550 ft (168m) 350 ft (107m) 270 ft (82m)
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, 4286 Phone Module, and Communication Device.
Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on the current draw of that device alone The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.
.
Table of Device Addresses
††
This Device Uses Address
Reports as
RF Receiver 00 100 *56 zone programming: input device type entry AUI 1 01 automatic if AUI enable field *189 enabled for AUI 1 AUI 2 02 automatic if AUI enable field *189 enabled for AUI 2 AUI 3 (VISTA-20P series) 05 automatic if AUI enable field *189 enabled for AUI 3 AUI 4 (VISTA-20P series) 06 automatic if AUI enable field *189 enabled for AUI 4 Communication Device (LRR) 03 103 automatic if communication device is enabled in field *29 4286 Voice Module 04 104 automatic if phone module access code field *28 enabled Zone Expanders (4219/4229):
module 1 (for zones 09 - 16) module 2 (for zones 17 - 24) module 3 (for zones 25 - 32) module 4 zones 33 - 40 module 5 zones 41 - 48
Relay Modules (4204):
module 1 module 2 module 3 module 4
Keypads:
keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8
5800TM Module 28 n/a automatic
07**
08 09 10 11
12
13 14 15
16
17
18
19
20
21
22
23
107 108 109 110 111
112 113 114 115
n/a n/a n/a n/a n/a n/a n/a n/a
** address 07 not available if zone-doubling enabled † 4219/4229 addresses 9-11 and 4204 addresses 14-15 apply to the VISTA-20P. †† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable
device reporting (default = reports enabled). See field *199 for addressable device 3-digit/2-digit identification keypad display options.
Enabled By…
*56 zone programming: input device type, entry 2, then:
automatic if zone no. 9-16 set as AW type or relay assigned automatic if zone no. 17-24 set as AW type or relay assigned automatic if zone no. 25-32 set as AW type or relay assigned automatic if zone no. 33-40 set as AW type or relay assigned automatic if zone no. 41-48 set as AW type or relay assigned
*79 output device programming: device address prompt:
entered at device address prompt entered at device address prompt entered at device address prompt entered at device address prompt
data field programming as listed below:
always enabled for partition 1, all sounds enabled. data field *190 data field *191 data field *192 data field *193 data field *194 data field *195 data field *196
2-5
Page 12
Installation and Setup Guide
Hardwire Zones and Zone Expansion
Hardwire Zones
HI
LO
Double-Balanced Zones (V20P only)
Zone Doubling (V20P only)
Smoke Detectors
TO ZONE 1
TERMINALS
HI
LO
ZONE 1
8
9
2-WIRE
SMOKE
DETECTOR
2-6
Normally Open Zones/ N.O. EOLR Zones
1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device.
2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.
Normally Closed Zones/ N.C. EOLR Zones
1. Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the EOLR in series following the last device.
2. Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.
zones-001-V0
End of Line Resistor (EOLR) Notes
If the EOLR is not at the end of the loop, the zone is not properly supervised and the
system may not respond to an “open” on the zone.
Zone 1 is intended for EOLR only.
U
For UL commercial burglar alarm installations, use EOLR zones.
L
Connect as shown below (resistor provided for one device).
IMPORTANT: Double-balanced zones provide zone tamper protection, and should be used as burglary zones only.
Do not use double-balanced zones as fire zones.
This feature provides two hardwired normally closed zones for each standard hardwired zone connected to the control’s terminals (but does not increase the total number of zones supported by the control). If enabled (Zone Programming mode, “Hardwire Type” prompt, option “3”), hardwire zones are automatically paired as shown in the table. Connect as shown (resistors provided).
•••• Do not use zone doubling for fire
zones.
NOTE: A short across the EOL (i.e., at
terminal) on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition (displayed as CHECK plus zone numbers).
1. Connect up to 16 (10, if “clean me” option used) 2-wire smoke detectors across zone 1 terminals 8 (+) and 9 (-) as shown in the Summary of Connections diagram at the back this manual. Observe proper polarity when connecting the detectors.
2. Connect an EOL resistor across the loop wires at the last detector.
3.
Connect 4-wire smoke detectors (up to 16, depending on detector current draw) to
any zone from 2-8 as shown in Figure 7 (on next page).
Power Reset: This control does not automatically reset power to 4-wire smoke
detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger to reset
5806-001-V0
power (also required for fire verification). Do this by programming the designated relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for other information.
NOTE: Maximum current on trigger 17 is 100mA.
12 13
TAMPER
2k
CONTACTS
TAMPER
2k
CONTACTS
2k
ZONE 3
Fig. 7. Typical Double Balanced Zones
Fig. 8. Typical Zone Doubling Wiring
10 11
ZONE 2
ZONE 10
2k
2k
2k
ZONE 4
3k
6.2k
14
zone-004-V0
zone-002-V0
Zone Doubling Table
Zone Paired with zone 2 10 3 11 4 12 5 13 6 14 7 15 8 16 NOTE: Zone numbers used for zone doubling cannot be used for anything else (ex. cannot be used for 4219 zones)
Page 13
Smoke Detector Notes
4219/4229 Expansion Zones
Mounting and Wiring the Control
•••• Fire Verification (zone type 16): The control panel will “verify” a fire alarm by
resetting the smoke detectors after the first alarm trigger, and then waiting up to 90 seconds for a second alarm trigger. If the smoke detector or thermostat does not trigger again, the control will disregard the first trigger, and no alarm signal will occur. This feature eliminates false alarms due to electrical or physical transients.
SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm
Listed relay accessories must be used to reset power as described in the Power Reset paragraph above.
The zone 1 alarm current supports only one smoke detector in the alarmed state.
•••• Clean Me Option: If enabled (field *174 = 1; *56 zone programming, response time
prompt = 3), certain ESL smoke detectors send “clean me” reports as appropriate. If used, the maximum number of detectors is reduced to 10 (not standard 16). Refer to the ESL documentation included with the smoke detector for information regarding compatibility with the clean-me option.
Do not use 4-wire smoke detectors on zone 1.
5
+
AUX PWR
OUTPUT
TERMINALS
_
CONTACT OPENS
MOMENTARILY UPON
FIRE ALARM RESET
TO ZONE TERM. ( )
TO ZONE TERM. ( )
PROGRAM
AS ZONE
TYPE 54
(FIRE ZONE
4
+
_
RELAY
RESET)
RELAY
N.C.
OR COMBUSTION
HEAT
DETECTOR
4-WIRE SMOKE
DETECTOR
Figure 9a. 4-Wire Smoke Detector Using Relay for Power Reset
+
( )
_
( )
+
_
5
DETECTOR
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
HEAT
AUX PWR
TO OUTPUT 17
PROGRAM OUTPUT 17
FOR "OUT NORM
LOW" = YES IN 79 MENU
MODE AND AS ZONE
TYPE 54 IN
80 MENU MODE
TO ZONE TERM. ( )
TO ZONE TERM. ( )
Figure 9b. 4-Wire Smoke Detector Using Output 17 for Power Reset
1. Connect each module to the control’s keypad terminals and set the device addresses. See the Table of Device Addresses to select an appropriate address for each module.
VISTA-20P: Up to 40 expansion zones using up to 5 Zone Exp. Modules.
VISTA-15P: Up to 16 expansion zones using up to 2 Zone Exp. Modules.
2. Connect sensors to the module’s loops. See Figure 8 on the following page.
Use 1000 ohm end-of-line resistors at the end of loops connected to the 4219/4229 modules. (EOLRs used on the control terminals are 2000 ohms.)
Expansion zones have normal response time (300–500 msec), except zone connected to each module’s loop “A,” which can be set for fast response (10–15 msec).
3. If using relays with the 4229, connect the desired field wiring to the unit's relay contact terminals.
_
BLK
+
_
2000
OHMS
EOLR
VIOLET
_
BLK
+
_
2000
OHMS
EOLR
N.O.
N.O.
VIOLET
+
+
RED
EOL POWER SUPERVISION RELAY MODULE A77-716B. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED.
RED
EOL POWER SUPERVISION RELAY MODULE A77-716B. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED.
4_wiresmk-007-V0
4_wiresmk-008-V0
2-7
Page 14
Installation and Setup Guide
RELAY
CONNECTOR
VIO
BLK
GRY
WHT
NONCC
RLY
2
RELAYS OFF
YEL
GND
ORG
NONCC
RLY
1
BRN
RELAY
NO C NC
REED
(TAMPER)
SWITCH
ZONESAB
2
DIP SWITCH
FOR SETTING ADDRESS AND ZONE "A" RESPONSE
RELAY
1
TAMPER JUMPER POSITION
4229 IN CABINET (NOT TAMPER)
4229 REMOTE (TAMPER PROTECTED)
2
1
3
4 6
5
C
EITHER OR BOTH CAN BE USED
4-PIN CONSOLE PLUG
TB1
8
9
7
10
E
D
F
12
11
GH
4229
TB2
4
3
4 3
2
2
1
1
TERMINATE EACH PROGRAMMED ZONE WITH 1000 OHM (1K) END-OF-LINE RESISTOR (EACH ZONE'S MAX. LOOP RESISTANCE 300 OHMS + EOL)
Figure 10. Wiring Connections, 4219 & 4229 (4229 shown)
Installing the RF Receiver and Wireless Transmitter Zones
Compatible Receivers
Receiver Connections
WIRELESS ZONE NUMBERS
VISTA-20P: transmitter zones 9-48 button zones 49-64
VISTA-15P: transmitter zones 9-34 button zones 49-56
RF Receiver Notes
These fields must be enabled for Residential Fire, UL Residential Burglar Alarm, and UL Commercial Burglar Alarm installations.
Use any ADEMCO 5800 Series Wireless Receivers, such as:
RF Receiver No. of Zones
5881L/5882L up to 8 5881M/5882M, up to 16 6150RF 5881H/5882H, VISTA-20P = up to 40 plus 16 buttons 5883, 6160RF VISTA-15P = up to 26 plus 8 buttons
1. Set Device Address to “00” (set all switches to the right, “off” position).
2. Mount the receiver, noting that the RF receiver can detect signals from transmitters within a nominal range of 200 feet.
3. Connect the receiver's wire harness to the control's keypad terminals. Plug the connector at the other end of the harness into the receiver. Refer to the installation instructions provided with the receiver for further installation procedures regarding antenna mounting, etc.
NOTE
CIRCUIT BOARD IS MOUNTED IN CONTROL'S CABINET. GROUNDING LUGS (2) PROVIDED IN LEFT-HAND TERMINALS OF ANTENNA BLOCKS AND SECURED TO CABINET. (SEE RECEIVER'S AND CONTROL'S INSTRUCTIONS)
MOUNTING
HOLES
MUST
BE INSERTED
ANTENNAS
(INSERT IN RIGHT-HAND TERMINALS)
INSERT IN
RIGHT- HAND
TERMINALS
MODEL NO. IS INDICATED ON CIRCUIT BOARD
5882
LOCATION
INTERFERENCE
INDICATOR
CIRCUIT BOARD
TO RELEASE CIRCUIT BOARD,
REMOVE SCREWS AND
LED
BEND BACK TABS
DIP SWITCH
Figure 11. 5881/5882 RF Receiver (cover removed)
Set the following options: *22 RF Jam Option† *24 RF House ID Code (if using wireless keypads) for each partition *67 Transmitter Low Battery Report Code† *75 Transmitter Low battery restore report code†
The receiver is supervised and a trouble report is sent (“CHECK 100” displayed) if communication between the panel and receiver is interrupted, or if no valid RF signals from at least one supervised transmitter are received within 12 hours.
If the receiver is mounted remotely:
Place the RF receiver in a high, centrally located area for best reception.
Do not locate the receiver or transmitters on or near metal objects. This will decrease
range and/or block transmissions.
Do not locate the RF receiver in an area of high RF interference (indicated by frequent or prolonged lighting of the LED in the receiver; random flicker is OK).
Do not locate RF receiver closer than 10 feet from any keypads to avoid interference from the microprocessors in those units.
GRN
BLK
RED
YEL
SOCKET
DATA OUT (>) TO CONTROL
(–) GROUND
(+) 12VDC
DATA IN (<) FROM CONTROL
YELLOW RED BLACK GREEN
PLUG
TERMINALS ON
CONTROL PANEL
(TERM 6)
(TERM 4)
(TERM 5)
(TERM 7)
4229-002-V0
TO CONTROL'S REMOTE KEYPAD CONNECTION POINTS.
WIRING OPENING
KNOCKOUT AREA FOR SURFACE WIRING
5881-003-V0
2-8
Page 15
Installing a 5800TM Module
Installing the Transmitters
Transmitter Battery Life
Mounting and Wiring the Control
Use this module only if you are using one or more wireless bi-directional keypads or keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g.,
5883).
The 5800TM must be set to address 28 (cut red-W1 jumper).
The 5800TM can be used in partition 1 only.
For additional information regarding the 5800TM, refer to the 5800TM’s instructions.
1. Mount the 5800TM next to the RF receiver (between one and two feet from the receiver’s antennas) using its accompanying mounting bracket. Do not install within the control cabinet.
2. Connect the 5800TM to the control panel’s keypad connection terminals as shown on the Summary of Connections diagram and set to address 28.
Refer to the table of compatible devices at the back of this manual.
Supervised transmitters† send check-in signals to the receiver at 70-90 minute
intervals. If at least one check-in message is not received from each transmitter within a 12-hour period, the “missing” transmitter number(s) and “CHECK” is displayed. († Hand-held transmitters, e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD, do not send check-in signals.)
To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go Test, described in the Testing the System section.
Install transmitters in accordance with the instructions provided with each.
Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24),
using its DIP switches (5827) or follow the instructions provided with the device.
Use *56 or *58 Zone Programming Menu modes to program zone information and enroll transmitters (VISTA-20P: zones 9-48, buttons 49-64; VISTA-15P: zones 9-34, buttons 49-56).
•••• Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone Programming Menu mode to program zone information and enroll each button of the wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before it becomes active. See Adding/Deleting Security Codes section for procedure.
ULC NOTE: In accordance with ULC standards, the RF supervision period for the VISTA-20PCN
and VISTA-15PCN is three hours for Fire zones (Zone Type 9 and 16) and 12 hours for all other zone types.
U
L
The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804,
5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.
• See Wireless Transmitter paragraph in the Limitations of This Alarm System statement located at the end of this manual for information on transmitter battery life.
• Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable batteries, and no battery installation is required. At the end of their life, the complete unit must be replaced (and a new serial number enrolled by the control).
• Button-type transmitters (such as 5801, 5802, and 5802CP) should be periodically tested for battery life.
• The 5802MN and 5804 Button Transmitters have replaceable batteries.
Do not install batteries in wireless transmitters until you are ready to enroll during system programming. After enrolling, batteries need not be removed.
2-9
Page 16
Installation and Setup Guide
Installing a Keyswitch
Keyswitch Connections
GREEN RED
keyswitch-001-V1
1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8)
2. Using a standard keypad cable as shown:
Connect the Red and Green LED wires to the appropriate output 17/output 18
3. Connect a 2000 ohm EOL resistor across the momentary switch.
4. You can wire an optional closed-circuit tamper switch (model 112) in series with the
If the tamper is opened when the system is armed, an alarm will occur.
terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone.
Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V).
trigger connector pins.
zone. If the switchplate is then removed from the wall, the tamper will open, disabling keyswitch operation until the system is next disarmed from the keypad.
8-PIN TRIGGER CONNECTOR
1345678
KEY
(RED)
(YELLOW)
OUTPUT 17
(GREEN)
+12 AUX.
OUTPUT 18
11
TYPICAL ZONE
ON CONTROL
BOARD
10
STANDARD KEYPAD CABLE
YELLOW
WHITE
BLACK
RED
BROWN
BLUE
(ARMED)
RED
(READY)
GREEN
4146 KEYSWITCH
820
ohms
TAMPER
SWITCH (N. C.)
LOCK
SWITCH (N. O.)
820
ohms
BROWN
BLUE
Keyswitch Notes
EOLR
(use appropriate value)
U
A UL Listed keyswitch is required for fire installations and UL commercial and residential
L
burglar alarm installations. The Ademco 4146 keyswitch is UL Listed. If a keyswitch is used on:
Figure 12. Keyswitch Wiring Connections
00-trigcon-004-V1
an installation that transmits opening and closing signals, the keyswitch zone must be programmed to send opening and closing signals.
a UL commercial burglar alarm installation, the keyswitch’s tamper switch must be connected in to the alarm system. This tamper switch zone must also be programmed for Zone Type 05 – Trouble by Day / Alarm by Night.
a fire alarm installation, the keyswitch must be located next to an alphanumeric display keypad.
Use 4146 keyswitch or any N.O. keyswitch.
Use only one keyswitch per partition.
When using a keyswitch, the zone it is connected to is no longer available for use as a
protective zone.
Use *56 Menu mode to program the keyswitch zone and assign it zone type 77.
Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for
system operation zone type 78 (red LED) and 79 (green LED) as appropriate (see
Output Device Programming section).
2-10
Page 17
Mounting and Wiring the Control
Connecting Relay Modules, Powerline Carrier Devices and Output Triggers
4204/4229 Relay Modules
U
For UL installation
L
requirements, refer to the Installation Instructions for the 4204.
Powerline Carrier Devices
U
Powerline Carrier
L
devices and the 1361X10 Transformer are not UL Listed for fire or burglary functions and are intended for home automation.
1. Mount either remotely or in the control panel.
2. Connect each module to the control’s keypad terminals and set the device addresses as previously described in the Connecting Keypads and Other Addressable Device section. Use the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs.
VISTA-20P: Up to 16 relays (if no powerline carrier devices are used) VISTA-15P: Up to 8 relays (if no powerline carrier devices are used)
3. Connect the desired field wiring to the unit's relay contact terminals.
4204
DIP SWITCH
FOR SETTING DEVICE ADDRESS AND ENABLING/DISABLING TAMPER
COVER TAMPER (REED) SWITCH
4-PIN TOUCHPAD PLUG
EITHER OR BOTH CAN BE USED
TB1
13 14 15 16
Figure 13. 4204 Connections to Control
YEL
BLK
GRN
RED
RELAY
4
TYPICAL
(SHOWN "OFF")
DATA IN FROM CONTROL
(–) GROUND
DATA OUT TO CONTROL
(+) 12V
RELAY
3
RELAY
2
RELAY
1
121110
9
87654321
TB2
4204_conn-1-V0
C
NC
NO
C
NC
NO C
NC
NC
NO
C
NC
NO
Supervision: 4204 and 4229 modules are supervised against removal. The module’s device address is displayed as follows if a module is disconnected from the control’s terminals, or if the module cover is removed and the tamper jumper is installed:
Alpha: CHECK xx Wire Expansion FAULT xx Wire Expansion ALARM xx Wire Expansion
Fixed-Glass: lxx (or 91 if field *199 set for 2-digit display)
where “xx is the module’s address.
If communication/tamper failure occurs on a device with zones wired to it, all zones on the device will be displayed in their respective partitions.
1. Install the powerline carrier devices according to the instructions included with each. VISTA-20P: Up to 16 devices (if no relays are used) VISTA-15P: Up to 8 devices (if no relays are used)
2. Use Programming Mode to enter the device house ID in data field*27, and enter the unit code using *79 Output Device menu Mode.
3. See connections diagram in the AC Wiring section for connecting the 1361X10 transformer to the triggers.
You must use a 1361X10 Transformer instead of the 1321 Transformer.
The 1361X10 Transformer provides AC power to the control panel, and also supplies
signals from the control panel through the premises AC wiring to the Powerline Carrier devices (which are plugged into AC outlets). You can then make devices that are plugged into Powerline Carrier devices perform various functions in response to commands you enter at the security system keypads.
Canada: Use the PSC04 Powerline Interface as shown below.
8-PIN TRIGGER CONNECTOR
1345678
KEY
(RED)
OUTPUT 17
(YELLOW)
(ORANGE)
GND (-)
+12 AUX.
(BLUE)
(GREEN)
OUTPUT 18
DATA
(BLACK)
(PURPLE)
COM
SYNC
SYNC
COM
DATA
SA4120XM-1 CABLE
X-10 PSC04
POWERLINE INTERFACE
1 2 3 4
BLK
GRN
RED
YEL
MODULAR PHONE CORD (not supplied)
1 - BLACK 2 - RED 3 - GREEN 4 - YELLOW
Figure 14. PSC04 Powerline Interface Connections
2-11
Page 18
Installation and Setup Guide
On-Board Triggers
Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip.
If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1
If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied
cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section for transformer connections.
with the control) as shown below.
8-PIN TRIGGER CONNECTOR
1345678
KEY
8-PIN TRIGGER CONNECTOR
1345678
KEY
(RED)
(ORANGE)
+12 AUX.
OUTPUT 17
Figure 15a. On-Board Trigger Connector Figure 15b. On-Board Trigger Connector
(GREEN)
(YELLOW)
GND (-)
OUTPUT 18
(BLUE)
(PURPLE)
COM
DATA
(BLACK)
SYNC
SA412OXM-1 CABLE
00-trigcon-003-V1
(RED)
(YELLOW)
+12 AUX.
OUTPUT 17
(BLACK)
(GREEN)
GND (-)
OUTPUT 18
4-WIRE CABLE
00-trigcon-005-V2
with SA4120XM-1 Cable for Use With with 4-Wire Cable for Trigger Use Only 1361X10 Transformer
Trigger outputs are normally high, and go low upon programmed condition.
The outputs can be programmed for inverted operation (normally low, go high) using
*79 Menu mode.
Program these triggers using *80/*81 Menu modes as you would for any other relay output.
When using these outputs, note: pin 1 = output number 17 (trigger 1): 15 ohms to ground when closed (output low), open when off (output high, normal
default); can be used to reset smoke detector power (must set “output normal low = yes” in *79 Menu mode, and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay module (
e.g., Altronix AX-RBS) that draws less
than 100mA pin 5 = output number 18 (trigger 2): 100 ohms to ground when closed (output low); open when off (output high,
normal default); or can support 12V relay module that draws less than 20mA
U
If on-board triggers are used, the wiring between the control unit and the UL Listed device must
L
be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.
2-12
Page 19
Mounting and Wiring the Control
Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections
Phone Line
4286 Phone Module
Compatibility: 4286 Phone
Modules must have software version WA4286-
15.1 or higher (refer to the label on the square 4286 microprocessor chip).
U
The 4286 modules
L
are UL Listed only for use on residential fire and UL residential burglar alarm installations.
Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual. Wire colors represent the colors of the cable to the RJ31X jack.
1. Make 12V (+) and (–) and data in and data out connections from the phone module to the control, using the connector cable supplied with the phone module, then insert the keyed connector at the other end of the connector cable into the header on the phone module.
2. Connect Phone Module terminals as shown below. Use an RJ31X jack with a direct­connect cord and make all connections exactly as shown.
3. Caller ID Units: If a Caller ID unit is being used, connect the unit directly to the “Handset” terminals (21 & 22) on the control, as shown.
TERMINALS
ON CONTROL
CALLER ID
UNIT
IMPORTANT NOTE FOR EXISTING INSTALLATIONS:
EXISTING WIRES CONNECTED TO THE "HANDSET" TERMINALS ON CONTROL MUST BE MOVED FROM THERE TO TERMINALS 3 AND 4 ON THE 4286.
4286 VIP MODULE
INCOMING
HANDSET
TELCO LINE
{
{
21 22 23 24 25
RED (RING)
(RING)
GREEN (TIP)
GREY (R)
(TIP)
GROUND
DIRECT
CONNECT
CORD
PLUG
BROWN (T)
TO EARTH GROUND (COLD WATER PIPE, ETC.)
INCOMING TELCO LINE
TIP
RING
TIP
RJ31X
RING
JACK
CA38A
IN
CANADA
PREMISES ANSWERING MACHINE AND PHONES
ANSWERING
MACHINE
*
Phone Module Problems
LOUDER
123456 7
*
UNUSED
CONNECTOR WITH FLYING
VOLUME
LEADS
KEYED HEADER
YELLOW: TO DATA OUT (term. 7) NO CONNECTION RED: TO AUX (+) (term. 5) BLACK: TO AUX. GROUND (–) (term.4) GREEN: TO DATA IN (term. 6)
TO CONTROL PANEL TERMINALS USED FOR KEYPAD CONNECTIONS
*
NOTE: IF THE TELEPHONE HAS BUILT-IN CALLER ID,
Figure 16. 4286 Phone Module Wiring Connections
THE CALLER ID FUNCTION MAY NOT WORK
4286 TERMINAL ASSIGNMENTS
1 - TIP
PHONE INPUT
}
2 - RING 3 - TIP
PHONE OUTPUT
}
4 - RING 5 - NO CONNECTION 6 -
AUDIO OUT
}
7 -
.
4286_cntrl-001-V1
Only one phone module can be used and it can only be connected to partition 1.
The phone lines must be in service for the phone module to function, even when
accessing the system from an on-premises phone.
If you are also using an Audio Alarm Verification (AAV) unit, refer to Audio Alarm Verification (AAV) section for special wiring connections.
CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord for phone line connections.
If no touch tones are produced following access to the security system from on-premises (this problem may arise in rare cases), it may be necessary to reverse the wires connected to terminals 3 and 4 on the phone module and the wires connected to terminals (21) & (22) on the control. The wiring diagram shows the wiring connections that will provide proper operation in most cases. Connection to the incoming telco line via a RJ31X jack and direct-connect cord, as shown, is essential, even if the system is not connected to a central station. The 4286 will not function if this is not done and an error signal (fast busy signal) will occur when trying to access the system via the phone. The house phone lines (gray and brown wires) must be wired to the phone module terminals; not to the control terminals. Otherwise, an error signal (fast busy signal) will occur when trying to access the system from an on-premises phone.
2-13
Page 20
Installation and Setup Guide
Audio Alarm Verification Connections (UVS System)
NOTE:
REFER TO UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE.
SWITCH
BANK 1
1 = OFF 2 = OFF 3 = OFF 4 = OFF 5 = OFF 6 = OFF 7 = OFF 8 = ON
Figure 17a. Connection of AAV Unit When Not Using a 4286 Phone Module
NOTE:
REFER TO UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE.
SWITCH
SWITCH
BANK 2
BANK 1
1 = ON
1 = OFF
2 = ON
2 = OFF
3 = OFF
3 = OFF
4 = ON
4 = OFF
5 = ON
5 = OFF
6 = ON
6 = OFF
7 = ON
7 = OFF
8 = ON
8 = ON
Using the UVS System with UVCM Module
The UVS system provides audio alarm verification via the phone line.
Refer to the connection diagrams below. One diagram shows connections when a 4286
Connections use one of the on-board triggers.
Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80
For voice session monitoring, connect an EOLR zone to UVCM module terminals 6 & 7,
E.g., Using output 18 for the trigger, program an output function in *80 Menu mode as: ZT = 60, P = 0, Action = 1, Device = 18
Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250
SWITCH BANK 2
1 = ON 2 = ON 3 = OFF 4 = ON 5 = ON 6 = ON 7 = ON 8 = ON
UVCM MODULE
Figure 17b. Connection of AAV Unit When Using a 4286 Phone Module
Phone Module is used, the other shows connections when the 4286 is not used.
Menu mode: select zone type 60 and output action 1 (close for 2 seconds).
and program the zone as zone type 81 (*56 Menu mode).
U
UL installations using the AAV feature must use the ADEMCO UVCM module (part of the
L
ADEMCO UVS system).
TRIGGER
5
UVCM MODULE
ON ON
AUXILIARY
AUDIO LEVEL
ADJUSTMENT
TRIM POT
12345678 1 2345678
ON ON
AUXILIARY AUDIO LEVEL ADJUSTMENT
TRIM POT
SWITCH BANK 2
FALLING VOICE TRIG
SWITCH BANK 1
12345678 12345678
SWITCH BANK 2
FALLING VOICE TRIG
SWITCH BANK 1
+12VDC IN
GND
+12VDC IN
RING
TIP
GND
CONTROL
29 30 31 32 33 34
12345 67891011
CONTROL
29 30 31 32 33 34
1234567891011
GND
CONNECTOR
ZONE
TERMINALS
4
GND
+12VDC
4
+12VDC
OUTPUT 18
5
TRIGGER
5
CONNECTOR
ZONE
TERMINALS
5
OUTPUT 18
21
EOL
RING
TIP
OPTIONAL MONITORING ZONE CONNECTION (USE ZONE TYPE 81)
EOL
RING
TIP
OPTIONAL MONITORING ZONE CONNECTION (USE ZONE TYPE 81)
23
22
24
21
22
4286
4
3
2
1
25
RED (R)
GREEN (T)
GREY (R)
BROWN (T)
PREMISES HANDSET
23 24
TO
RED (R)
GREEN (T)
GREY (R)
BROWN (T)
25
PREMISES
HANDSET
EARTH
GROUND
RJ31X
INCOMING
PHONE LINE
TO
aav_uvcm-003-V0
EARTH
GROUND
RJ31X
INCOMING
PHONE LINE
aav_uvcm-004-V1
2-14
Page 21
Audio Alarm Verification Connections (AVS System)
Mounting and Wiring the Control
Using the AVS System with AVS Module and AVST Remote Stations
The AVS system provides audio alarm verification via the phone line or via AlarmNet if
the GSMV module is used as the communication device.
Refer to the instructions included with the AVS system for installation procedures. The
following is a summary.
Mounting the AVS Base Unit
As shipped, the AVS Base unit board comes pre-mounted on its mounting bracket, which is designed to mount inside the control cabinet. Refer to the diagram at right. a. Position the mounting plate/PC
board assembly in the bottom of the control’s cabinet.
b. Slide the mounting plate to the
right so that the plate’s left-hand tang slides under the cabinet’s tie­wrap loop.
c. Secure the assembly to the cabinet
using the two self-tapping screws provided.
SYSTEM
BATTERY
TANG
BENEATH
MOUNTING
PLATE
N O
5
N
O
4 3
2
1
4
3 2 1
SLIDE ASSEMBLY TO RIGHT UNTIL
TANG SLIPS UNDER CABINET LOOP
BATTERY NOTE: When using a 7AH battery, mount the battery vertically on the bottom left-hand side of the cabinet, with the terminals facing down and right (negative terminal closest to the PC board bracket).
Wiring the AVS to the Control
The AVS Base unit board has several terminal blocks for making connections to remote stations, telephone lines, and to the control panel. The AVS base unit connects to the control’s ECP terminals, with all other ECP devices connecting to the AVS base unit ECP terminals. See the diagram on the next page for specific wiring connections.
DIP Switch: Set the AVS DIP switch to the appropriate address (V15P = 08; V20P = 11).
IMPORTANT: The AVS should be the only ECP device connected to the control’s
ECP terminals. Connect all other ECP devices (keypads, expander modules, etc.) to the ECP terminals on the AVS board.
Connecting an Optional GSMV Module
a. If using a GSMV module for 2-way voice operation, install the module according to its
instructions. NOTE: The module must be mounted within three feet of the control.
b. Connect the audio cable from the GSMV module to the Audio connector on the AVS
board. The audio cable is supplied with the GSMV module.
c. Complete all other GSMV wiring following the instructions included with that
module.
The following summarizes the programming steps for AVS operation (refer to the Programming Guide for details of the AVS Quick Command options): a. Install the AVS module according to its instructions. b. Use one of the control’s AVS Quick Program commands as follows :
installer code + [#] + 03: enable AVS operation without panel sounds on the AVST
installer code + [#] + 04: enable AVS operation and enable panel sounds on the AVST speaker
c. Use data field 55 Dynamic Signaling Priority to select the desired reporting paths.
SECURE WITH TWO (2) SELF-TAP SCREWS (SUPPLIED)
CABINET TIE-WRAP LOOP
AVS-003-V0
2-15
Page 22
Installation and Setup Guide
KEYPAD
AVST STATION
SPEAKERS
LED
VOLUME / ID
BUTTON
AAV
YEL
GRN
MIC
BLK RED
KEYPAD
DATA AUDIO
GND
+VDC
ECP TERMINALS
DATAINDATA
GND AUX
BLK
RED
OUT
GRN
TIP
RING
PREMISES
PHONES
VISTA SERIES RESIDENTIAL CONTROL
TRIGGER HEADER
123456
IMPORTANT:
DO NOT CONNECT ANY OTHER
YEL
ECP DEVICES TO PANEL. USE AVS BASE UNIT ECP TERMINALS FOR OTHER ECP DEVICES.
78
5
4
67
RJ31X
8
12 3
DIRECT CONNECT CORD
(TIP)
INCOMING
PHONE LINE
(RING)
HANDSET
SUPPLIED HARNESS
TIP
RING
GRN
(TIP)
RED
(RING)
INCOMING
TELCO
GRY
(EARTH GND
BRN
FOREXTERNAL ANTENNA 50 OHM, MMCXONLY
TB 1
1
Honeywell
2 3 4 5 6 7 8
9 10 11
GSMV
(OPTIONAL)
BASE UNIT
DEVICE ADDRESS
VISTA-15P = 8
ON
23 541
VISTA-20P = 11
ON
23 541
AUDIO CABLE
GSM
GPPS
WEB
MODE 2
MODE 1
RSSI
AVS BASE UNIT
LED
HANDSET
INCOMING
PHONE LINE
RED BLK GRN YELRED BLK GRN YELRED BLK GRN YEL
PHONE
RING
TIP
TIP
RING
GRY
BRN
TO ALL OTHER ECP DEVICES
AVS-001-V0
BATTERY
(200 FT. MAX)
PROGRAM MODE
CALLBACK MODE
PANEL TRIGGER
MODE
NORMAL MODE
DIP SW
ON
ON
DEVICE ADDRESS
NOT USED
23 541
AAV
(ADDRESS 8 SHOWN)
AUDIO CONNECTOR
PANEL ECP
2341
Figure 18. Connections for the AVS System
2-16
Page 23
SECTION 3
System Communication and Operation
Panel Communication with Central Station
This system accommodates several formats for reporting alarms and other system conditions to the Central Station. The process of a successful transmission consists of both the method of communication between the control panel and the Central Station receiver; and the actual way the information is sent and displayed at the Central Station. When the panel calls the Central Station receiver, it waits to hear a “handshake” frequency from the receiver to confirm that the receiver is on-line and ready to receive its message. Once the panel hears the handshake it is programmed to listen for, it sends its message. The panel then waits for a “kissoff” frequency from the receiver acknowledging that the message was received and understood. If the handshake frequency is not given or is not understood by the panel, the panel will not send its message. Once the handshake frequency is received and understood by the panel, the panel sends its message. If there is an error in the transmission (the receiver does not receive a “valid” message), the kissoff frequency is not given by the Central Station receiver. The panel makes a total of eight attempts to the primary telephone number and eight attempts to the secondary telephone number (if programmed) to get a valid message through. If the panel is not successful after its numerous attempts, the keypad displays COMM. FAILURE (on alpha keypads) or FC (on fixed­word keypads).
Report Code Formats
The following chart indicates the types of (handshake/kissoff) frequencies that the panel supports and the different formats that can be sent with each.
FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME
Low Speed 1400 Hz 1900Hz (10PPS) 1400 Hz Under 15 secs 3+1, 4+1, 4+2
Sescoa/Rad 2300 Hz 1800Hz (20PPS) 2300 Hz Under 10 secs 3+1, 4+1, 4+2
Express 1400–2300 Hz DTMF (10 cps) 1400 Hz Under 3 secs 4+2
Contact ID 1400–2300 Hz DTMF (10 cps) 1400 Hz Under 3 secs
The following table describes each format in greater detail.
FORMAT TYPE DESCRIPTION
3+1 and 4+1 Standard Formats 3+1 and 4+1 Expanded Formats
4+2 Format Comprises a 4-digit subscriber number and 2-digit report code. ADEMCO Contact ID Reporting Format
Comprises a 3- (or 4-) digit subscriber number and a single-digit report code (e.g., Alarm, Trouble, Restore, Open, Close, etc). Comprises a 3- (or 4-) digit subscriber number and a two-digit report code. The first digit is displayed on the first line. On the second line, it is repeated 3 (or 4) times and is followed by the second digit. This is the “expanded” digit.
Comprises a 4- or 10-digit subscriber number (depending on format selected), 1-digit event qualifier (“new” or “restore”), 3-digit event code, and 3-digit zone number, user number, or system status number (see the following page).
(Standard report)
(Standard report)
3-1
Page 24
Installation and Setup Guide
The following table lists codes for reports sent in different formats:
Code for Code for
Type of 3+1/4+1 3+1/4+1 Code for Report Standard Expanded 4+2
Alarm SSS(S) A SSS(S) A SSSS AZ AAA(A) Z
Trouble SSS(S) T SSS(S) T SSSS Tt TTT(T) t
Bypass SSS(S) B SSS(S) B SSSS Bb BBB(B) b
AC Loss SSS(S) E SSS(S) E SSSS EAC
EEE(E) A
Low Batt SSS(S) L SSS(S) L SSSS LL
LLL(L) L
Open SSS(S) O SSS(S) O SSSS OU OOO(O) U
Close SSS(S) C SSS(S) C SSSS CU CCC(C) U
Test SSS(S) G SSS(S) G SSSS Gg GGG(G)g
Restore SSS(S) R SSS(S) R SSSS RZ Alarm RRR(R) Z
AC Restore SSS(S) RA SSS(S) RA SSSSRA A
R
LoBat Res. SSS(S) RL SSS(S) RL SSSS RLL
R
Trouble Res. SSS(S) RT SSS(S) RT SSSS RTt
R
Bypass Res. SSS(S) R
R
Where:
SSS or SSSS = Subscriber ID C = Close Code–1st Digit A = Alarm Code–1st digit U = User Number (in hex) Z = Typically Zone Number*–2nd digit Gg = Test Code (1st & 2nd digits) Tt = Trouble Code (1st & 2nd digits) R = Restore Code (Alarm) Bb = Bypass Code (1st & 2nd digits) RTt = Restore Code (Trbl) 1st & 2nd digits
EA
LL
O = Open Code–1st Digit RLL
*Zone numbers for:
AC Loss Code (1st & 2nd digits) RBb = Restore Code (Byps) 1st & 2nd digits
C =
Low Battery Code (1st & 2nd digits) RAAC = Restore Code (AC) 1st & 2nd digits
B =
& #, or B = 99; 1 + ✱, or A = 95; 3 + #, or C = 96; Duress = 92
B
Restore Code (Bat) 1st & 2nd digits
B =
C
B
ARARA(RA)Ac
LRLRL(RL)LB
(RT)t
TRTRT
SSS(S) R
BRBRB
B
(RB)b
B
c
B
SSSS RBb
3-2
Page 25
System Communication
Ademco Contact ID®
The Ademco Contact ID® Reporting Format comprises the following:
4-digit or 10-digit subscriber number (depending on format selected). 1-digit event qualifier (“new” or “restore”). 3-digit event code. 2-digit Partition No. 3-digit zone number, user number, or system status number (see the following page).
Ademco Contact ID® Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ
where: CCCC(CCCCCC) =Customer (subscriber) ID
Q = Event qualifier, where: E = new event , and R = restore EEE = Event code (3 hexadecimal digits) Note: For a complete list of event codes, refer to the central office
GG = Partition Number (system messages show “00”) ZZZ = Zone/contact ID number reporting the alarm, or user number for
(some event codes may not apply to certain control panels)
Code Definition
110 Fire Alarm 121 Duress 122 Alarm, 24-hour Silent 123 Alarm, 24-hour Audible 131 Alarm, Perimeter 132 Alarm, Interior 134 Alarm, Entry/Exit 135 Alarm, Day/Night 143 Alarm, Expansion Module 145 ECP Module cover tamper 146 Silent Burglary 150 Alarm, 24-Hour Auxiliary/Monitor zone 162 Carbon Monoxide 301 AC Power 302 Low System Battery/Battery Test Fail 305 System Reset (Log only) 321 Bell/Siren Trouble 333 Trouble, Expansion Mod. Supervision 341 Trouble, ECP Cover Tamper 344 RF Receiver Jam 351 Telco Line Fault
353 Long Range Radio Trouble 373 Fire Loop Trouble 374 Exit Error Alarm 380 Global Trouble, Trouble Day/Night
receiver manual.
open/close reports. System status messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location.
TABLE OF CONTACT ID EVENT CODES
Code Definition
381 RF Sensor Supervision 382 Supervision Auxiliary Wire Zone 383 RF Sensor Tamper 384 RF Sensor Low-battery 393 Clean Me 401 Disarmed, Armed AWAY, Armed
MAXIMUM 403 Schedule Arm/Disarm AWAY 406 Cancel by User 407 Remote Arm/Disarm (Downloading) 408 Quick Arm AWAY 409 Keyswitch Arm/Disarm AWAY 441 Disarmed/Armed STAY/INSTANT,
Quick-Arm STAY/INSTANT 442 Keyswitch Arm/Disarm STAY 455 Scheduled Arm Fail 459 Recent Closing 570 Bypass 601 Manually Triggered Dialer Test 602 Periodic Test 606 AAV to Follow 607 Walk Test Entered/Exited 623 Event Log 80% Full 625 Real-Time Clock was Changed (log only) 627 Program Mode Entry (log only) 628 Program Mode Exit (log only) 642 Latch Key (log only)
750 ­ 789
Reserved for Configurable Zone Type
report codes (check with central station
when using these codes)
3-3
Page 26
Installation and Setup Guide
Uploading/Downloading via the Internet
UL: Up/downloading via the Internet has not been evaluated by UL.
This control, when used with a compatible Internet/Intranet Communication Device, supports upload/download programming capability via the Internet using the AlarmNet network or, depending on the communication module used, a Private local area network (Intranet). This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet. Depending on the module used, Internet connection from the protected premises is either via high speed (broadband) cable or phone service, or via the GSM/GPRS digital cellular network (GSM modules).
Refer to the instructions provided with the communication module for information regarding its installation, programming, and registration. The System Requirements table below lists two sets of system requirements, depending upon whether you intend to communicate over the Internet or whether you are communicating over a Private LAN (Intranet).
Compatible Communication Modules: The following modules support Internet uploading/downloading, but future modules may also provide Internet upload/download support; refer to the module’s instructions for compatibility. Compatible Modules: 7845i-ent, 7845i-GSM, 7845GSM
System Requirements
Internet Communication
At the Installation Site:
Appropriate Internet Communication Module
7720P Programmer
Broadband Internet Access (for wired modules)
Broadband (Cable/DSL) Modem (for wired modules)
Broadband (Cable/DSL) Router (for wired modules if
connecting more than one device to the Internet)
IP compatible Control Panel
At the Downloading Office:
Broadband Internet Access
Broadband (Cable/DSL) Modem
Broadband (Cable/DSL) Router (optional, if connecting
more than one device to the Internet)
Computer running Compass Downloading Software version that supports Internet upload/download for this control.
To set up the control panel, do the following:
1. Connect the module to the control panel’s ECP (keypad) terminals.
2. Internet Users: For wired modules, connect the module to the Internet via a cable/DSL modem and router. Intranet Users: Connect the module to the Intranet (LAN) via the appropriate Ethernet connection.
3. Enable the module in the control panel (using 29 Menu mode) to enable alarm reporting and module supervision.
4. Using the module’s programming menus (via 29 Menu mode or 7720P programmer), program the communication device module for address 3 and program the module’s other options as required.
5. Register the module with AlarmNet. The module must be registered before downloading or alarm reporting can take place.
To perform upload/download functions:
1. Connect the computer to the Internet and start the Compass downloading software.
2. Open the control’s account, then select the Communications function and click the Connect button.
3. At the Connect screen, check that the control’s MAC address is entered and the TCP/IP checkbox is checked.
4. Click Connect. The Internet connection to the control is made automatically via AlarmNet.
5. Once connected, use the Compass downloading software as normal to perform upload/download functions.
Intranet (Private LAN) Communication, if applicable*
At the Installation Site:
Internet/Intranet Communication Module
7720P Programmer
Ethernet Network Connection
IP compatible Control Panel
At the Downloading Office:
7810iR-ent IP Receiver
Internal Router
Computer(s) running the following software:
- Compass Downloading Software version that supports IP upload/download for this control.
- Compass Connect Data Server Application
- Compass Connect Control Server Application
* see module’s instructions for applicability for LAN usage (ex. 7845i-ent supports LAN)
NOTE: Compass, the Compass Connect Data Server, and the Compass Connect Control Server applications may all be installed on the same computer if desired. If they are installed on one computer, the computer must have a fixed IP Address.
3-4
Page 27
System Operation
System Security Codes
The systems provides one Installer code, one System Master code, plus a set of other user codes intended for other users of the system. These codes can each be assigned one of 5 authority levels, which determine the functions each code can perform as listed in the table below.
VISTA-20P: Provides 48 security codes (plus Installer code), including one System Master code, two
Partition Master codes, and 45 general user codes.
VISTA-15P: Provides 32 security codes (plus Installer code), including one System Master code and 31
general user codes.
Authority Levels (can be assigned to users 03-49 only; users 1 and 2 cannot be changed)
Level User No. Functions
Installer 01
System Master
Partition Master (default)
0-User 03-49 (V20P)
1-Arm Only see “user” arm system only
2-Guest see “user” can disarm the system only if it was used to arm the system
3-Duress see “user”
4-Partition Master
02
P1 = 03 P2 = 33
03-33 (V15P)
see “user”
Refer to the user guide for detailed procedures on adding/deleting security codes and changing user attributes.
The following is a brief description of how to add user codes.
Changing the System Master code...
Using Installer code: Installer code + [8] + 02 + new code
Using current System Master code: System Master code + [8] + 02 + new code + new code again Adding a User Code: Master code + [8] + 2-digit user no. + user’s code Deleting a User Code: Master code + [8] + 2-digit user no. + [#] [0] Assigning Attributes: Master code + [8] + 2-digit user no. + [#] [attribute no.] + value
Attributes: Values
1 = Authority Level 0-4 (see Authority Level table above) 2 = Access Group 0-8 (0 = not assigned to a group) 3 = Active Partition(s) 1, 2, 3 (common) for this user; Enter partitions consecutively if more than one and press [#] to
4 = RF Zone No. Assigns user number to button type zone for arm/disarm
5 = Open/Close Paging 1 for yes, 0 for no
(default=4112) perform all security functions except can disarm only if used to arm; can enter program mode; can change System Master code; cannot assign any other user codes
(default 1234) only one system master code per system; can perform all security functions, add/delete users in either partition, change system master code, view event log, set system clock, program keypad macro, program scheduled events, activate output devices (triggers/relays)
VISTA-20P. Same as Master, except add/delete users limited to assigned partition only, (these users can be assigned different authority levels, if desired; any user can be assigned the partition master authority level)
perform security functions (arm, disarm, etc.) only; cannot add/delete users, view event log, set system clock or program scheduled events
performs security functions, but also silently sends a duress message to the central station; reports as duress code user number.
VISTA-20P. See Partition Master paragraph above; used to assign other user numbers as partition masters
end the entries.
(keyfob must be enrolled in system first; see Wireless Key Templates section).
3-5
Page 28
Installation and Setup Guide
Keypad Functions
The following is a brief list of system commands. For detailed information concerning system functions,
refer to the User's Manual. For Touch Screen style keypad users, refer to the separate Touch Screen keypad (AUI) User’s Guide.
Voice Keypads
The 6150V/6160V Voice Keypads provide the following features:
Message Center, which lets the user record and playback one message.
Voice Status, which can announce system status by using the STATUS key.
Voice Chime, which can alert users to the opening of doors/windows while the system is disarmed.
Refer to the User Guide for specific procedures for activating and using these features.
Keypad Commands
Function Description
Silence Burglary Alarms Silence Fire or Carbon Monoxide Alarms
Quick Arm
Single-Button arming If programmed (*57 Function Key menu mode), lettered keys A-D can be used for arming,
Alarm Memory When the system is disarmed, any zones that were in an alarm condition during the armed
Arming Away Enter code + AWAY [2] or simply press appropriate lettered key on the keypads (see
Arming Stay Enter code + STAY [3] or simply press appropriate key on the keypads (see “Single-Button
Arming Night-Stay Enter code + STAY [3] + STAY [3] or simply press appropriate key on the keypads (see
Arming Instant Enter code + INSTANT [7]. Arming Maximum Enter code + MAXIMUM [4] or simply press appropriate lettered key on the keypads (see
Disarming Enter code + OFF [1]. If entry delay or an alarm is active, you do not need to press OFF. Bypassing Zones Enter code + BYPASS [6] + zone number(s). Forced (Quick) Bypass To automatically bypass all faulted zones, use the “Quick Bypass” method. Enter code +
Chime Mode Enter code + CHIME [9]. To turn chime off, enter code + CHIME again. Activate Output Devices
Pressing any key will silence the keypad sounder for 10 seconds. Disarming the system (security code + OFF) silences both keypad and external sounders. Press the OFF [1] key to silence the keypad sounder and, for fire alarms, the external sounder. The detector sounding stops when the contaminated air is cleared from the detector; see the detector’s instructions for further information. If enabled (field 21), you can press [#] in place of the system's security code, plus the desired arming key (Away, Stay, Instant, Maximum)
using options 3-AWAY, 4-STAY, 5-NIGHT-STAY, or 6-Step-Arming If used, no security code is required to arm the system.
period will be displayed. To clear this display, simply repeat the disarm sequence (enter the security code and press the OFF key) again.
“Single-Button Arming” above). If the “Auto-Stay Arm” feature is enabled (field *84) and the entry/exit door is not opened and closed within the programmed exit delay time, the system will automatically arm in STAY mode if armed from a wired keypad (non-RF device). If the door is opened and closed within the exit delay period, the system arms in AWAY mode.
Arming” above). See “Arming Away” above for Auto-Stay arming feature.
“Single-Button Arming” above).
“Single-Button Arming” above).
BYPASS + [#], then wait for all open zones to be displayed. Arm when display indicates “ZONE BYPASSED” and “READY TO ARM”.
If relay outputs (via a 4204, or 4229), or Powerline Carrier devices are used, two keypad entries available to the user are included. If programmed, these entries can be used to manually activate or deactivate the device(s) for starting or stopping some action, such as turning lights on or off, etc. These keypad entries are: [Security Code] + # + 7 + [2-digit Device #] activates (starts) that device. [Security Code] + # + 8 + [2-digit Device #] deactivates (stops) that device.
3-6
Page 29
System Operation
SUMMARY OF ARMING MODES
Arming Mode
Exit Delay Entry Delay Perimeter Armed Interior Armed
AWAY Yes Yes Yes Yes
STAY Yes Yes Yes No
NIGHT-STAY Yes Yes Yes only those zones
INSTANT Yes No Yes No
MAXIMUM Yes No Yes Yes
Features for Each Arming Mode
listed in Night-
Stay zone list
Panic Keys
There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station.
Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal Emergency responses. The programmed Panic response is activated when the appropriate key is pressed for at least 2 seconds.
The Panic keys are identified by the system as follows:
Keys Displayed as Zone
[A] (∗∗∗/1) [B] (∗∗∗/#)
[C] (3/#)
95 99 96
IMPORTANT: For a Silent panic function (if programmed) to be of practical value, you must program a report code for the zone and the system must be connected to a central station.
Setting the Real-Time Clock
IMPORTANT: The Real-Time Clock must be set before the end of the installation.
NOTE: All partitions must be disarmed before time/date can be set.
Set the time and date by doing the following:
+[#] + [6] [3]
1.
(Master Code)
2. Press [] when the time/date is displayed. A cursor appears under the first digit of the hour.
To move cursor ahead, press [
]. To go back, press [#].
Enter the 2-digit hour setting.
Enter the 2-digit minute setting.
Press [1] for PM or [2] for AM.
Enter the last two digits of the current year.
Enter the 2-digit month setting.
Enter the 2-digit day setting.
3. To exit, press [] when cursor is at the last digit, or wait 30 seconds.
Alpha Display:
DISARMED READY TO ARM
TIME/DATE SAT 04:04PM 10/17/00
Current time display
TIME/DATE SAT 04:04P2000/10/17
Time/date editing display
3-7
Page 30
Installation and Setup Guide
Various System Trouble Displays
Alpha Display Fixed Disp. Meaning
ALARM CANCELED CA
EXIT ALARM EA
CHECK CHECK
ALARM 1xx FAULT 1xx CHECK 1xx
1xx 1xx 1xx 91
SYSTEM LO BAT BAT LO BAT BAT
TELCO FAULT 94
Busy-Standby dl Modem Comm CC
no display no display
Comm. Failure FC Open Circuit 0C Long Rng Trbl bF Bell Failure 70 RCVR Jam 90 KEYPAD LOW BAT 00 BAT Phone Okay Cd Dialer Off d0 Test in Progress dd Upload Completed dC Upload Failed dF
will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay time. The alarm sounder and keypad sound continuously, but stop when the system is disarmed. No message will be transmitted to the central station. appears when Exit Delay ends if an exit or interior zone contained a fault during closing. The alarm sounder and keypad sound continuously until the system is disarmed (or timeout occurs). An “Exit Alarm” message is sent to the central station. Also results if an alarm from an exit or interior zone occurs within 2 minutes after the end of an Exit Delay. indicates that a problem exists with the displayed zone(s) and requires attention. indicates that communication between control and a zone expander or wireless receiver is interrupted, where “xx” is the device address. Check the wiring and DIP switch settings on the units. If field *199 is set to “1,” all ECP module problems are displayed as “91.” If there are wireless sensors in the system, the Check condition may also be caused by some change in the environment that prevents the receiver from receiving signals from a particular sensor. with no zone number indicates that the system's standby battery is weak. with a zone number and a once-per-minute beeping at the keypad indicates that a low-battery condition exists in the wireless sensor displayed (zone “00” indicates a wireless keypad). If the battery is not replaced within 30 days, a “CHECK” display may occur. NOTE: Some wireless sensors contain a non-replaceable long-life battery which requires replacement of the entire unit at the end of battery life (e.g., Nos. 5802, 5802CP). Telephone Line Failure, indicates that a monitored telephone line (if programmed in field *92) has been cut or disconnected. Depending on how the system was programmed, the keypad may also produce a trouble sound, and the external sounder may be activated. Silence by entering installer code + OFF. If this remains displayed for more than 1 minute, the system is disabled. The system is in communication with the central station for change of function or status verification. Power Failure If there is no keypad display at all and the LEDs are unlit, operating power (AC and battery) for the system has stopped and the system is inoperative. If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed-Word display keypads) is displayed, the keypad is operating on battery power only. If the battery standby capacity is used up during a prolonged AC power outage, the control's power will shut down to minimize deep discharge of the battery. A communication failure has occurred. The keypad is not receiving signals from the control; sees an open circuit. Backup LRR communication failure. Bell supervision failure. RF jam detected. Wireless keypad low battery. The dialer test has been successful (CID code 601). The dialer is disabled. Walk test mode is active(CID code 607). The upload or download session was completed. The upload or download session failed before completion.
3-8
Page 31
SECTION 4
Testing the System
About Test Procedures
After the installation is complete, you should perform the following tests:
System Test: Checks that all zones have been installed properly and the system responds to faults. Dialer Test: Checks that the phone connection to the central station is working properly. Go/No Go Test: Checks that transmissions can be received from transmitters. Should be performed
before permanently mounting transmitters.
RF Sniffer Mode: Checks that RF transmitter serial numbers have been properly enrolled. Battery Tests: Automatic battery tests are performed by the system.
System Test
NOTE: Test mode can be entered from any keypad. However, faulted zones appear only on those keypads assigned to the partition to which the zone is assigned (i.e., partition 1 zones appear only on partition 1 keypads, etc.). To see another partition’s faulted zones, view a keypad assigned to that partition or use the GOTO command (code +[] + partition number 0-3, where 0 is the keypad’s home partition).
With the system in the disarmed state, check that all zones are intact (not faulted). Doors and windows with contacts should be closed, PIRs should be covered (use a cloth to mask them temporarily if necessary). If a “NOT READY” message is displayed, press [] to display the faulted zone(s). Restore faulted zone(s) if necessary, so that the “READY” message is displayed.
1. Enter Installer Code + 5 [
1=DIAL, 0=WALK (no special display on Fixed-Word keypads)
The following will be displayed on the initiating keypad and a Contact ID report will be sent (code 607):
TEST IN PROGRESS (“dd” displayed on Fixed-Word Display Keypads)
2. Upon entering the system test mode, the outside sounder should sound for 1 second. If the backup battery is discharged or missing, the sounder may not turn on and a “LOW BATTERY”
report will be transmitted with a “TEST” report. The keypad will beep about every 30 seconds as a reminder that the system is in the Test mode. NOTE: Wireless motion detectors (Passive Infrared units) will send signals out only if they have been
inactive for 3 minutes (conserves battery life).
3. Test all sensors using the procedure described in the User’s Guide “Testing the System” section.
4. After checking sensors, turn off the test mode by entering installer code + OFF.
NOTE: Test mode automatically ends after 4 hours. During the final 5 minutes (after 3 hours 55
minutes of Test mode), the keypad emits a double-beep every 30 seconds to alert that the end of Test
mode is nearing.
Checking Transmitter Enrollment (Sniffer Mode)
Use this mode to verify that all transmitters have been properly programmed. Make sure both partitions are disarmed before trying to enter this mode, since this is a system-wide command.
1. From a keypad in partition 1, press [Installer code] + [#] + 3.
NOTE: If the communicator is in the process of sending a report to the central station, the system will
The keypads in both partitions will display all zone numbers of wireless units (in both partitions)
programmed into the system. Fault each transmitter in turn, causing each one to send a signal. As the
system receives a signal from each of the transmitters, the zone number of that transmitter disappears
from the display.
2. After all transmitters have been checked, exit the sniffer mode by keying [Installer code] + OFF.
IMPORTANT: Sniffer mode does not automatically expire. You must manually exit Sniffer mode (by
entering [Installer code] + OFF) to return to normal operation.
TEST] , then press “0” at the prompt to start Walk Test mode.
not go into the Sniffer mode. If so, wait a few minutes, and try again.
4-1
Page 32
Installation and Setup Guide
NOTES: All BR type units must physically be activated to clear the display.
When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are cleared from the display. This also applies to 5816 and 5817 transmitters, which have multiple loops (zones).
Any transmitter that is not “enrolled” will not turn off its zone number.
Go/No Go Test Mode
The Go/No Go Test verifies adequate RF signal strength from the proposed transmitter location, and allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently. This mode is similar to the Transmitter Test mode, except that the wireless receiver gain is reduced. This will enable you to make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the system is in the normal operating mode.
1. Enter [Installer code] + [#] + 4 from the partition being tested. For multi-partition systems, repeat this test for each partition.
2. After you have placed transmitters in their desired locations and the approximate length of wire to be run to sensors is connected to the transmitter's screw terminals (if used), fault each transmitter. Do not conduct this test with your hand wrapped around the transmitter, as this will cause inaccurate results. a. The keypad will beep three times to indicate signal reception and display the zone number. b. If the keypad does not beep, you should reorient or move the transmitter to another location.
Usually a few inches in either direction is all that is required.
4. If each transmitter produces the proper keypad response when it is faulted, you can then permanently
mount each of the transmitters according to the instructions provided with them.
5. Exit the Go/No Go Test mode by entering: [any user code (partition-specific)] + OFF.
Dialer Communication Test and Periodic Test Reports
1. Enter Installer Code + 5 [TEST], then press “1” at the prompt to start the Dialer Test (checks phone line integrity only; does not confirm report transmissions).
1=DIAL, 0=WALK (no special display on Fixed-Word keypads)
The following will be displayed (accompanied by 2 beeps) if test is successful:
PHONE OKAY (“Cd” displayed on Fixed-Word Display Keypads)
A Contact ID report will also be sent (code 601)
If the dialer test is unsuccessful, “COMM FAILURE” (or FC) is displayed.
2. Enter Installer code + OFF to clear the display and exit.
Automatic Periodic Test Report
The system can be set to automatically send test reports (enabled in field *64; Contact ID code 602) at specified intervals. Frequency of the reports is set in Scheduling mode (event 11) or by the following key commands:
installer code + [#] + 0 + 1 = test report sent once per week installer code + [#] + 0 + 2 = test report sent every 28 days
Each mode sets schedule 32 (VISTA-20P) or schedule 08 (VISTA-15P) to the selected repeat option; the first test report is sent 12 hours after command.
To ensure that test reports are sent at the times expected, set the Real-Time Clock to the proper time before entering the test report schedule command.
Automatic Standby Battery Tests
1. An automatic test is conducted every 3 minutes to ensure that a standby battery is present and
2. A battery capacity test is automatically conducted for 2 minutes every 4 hours, beginning 4 hours after
installer code + [#] + 0 + 0 = test report sent every 24 hours
properly connected. If a battery is not present or is not properly connected, a “LOW BATTERY” message is displayed and, if so programmed, will be reported to the central station.
exiting the Programming mode or after powering up the system. In addition, entry into the Test mode will also cause a battery capacity test to be initiated. If the battery cannot sustain a load, a “Low Battery” message is displayed and, if so programmed, will be reported to the central station.
4-2
Page 33
Security Control
1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm)
2. Electrical:
VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, ADEMCO 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type). Charging
Voltage: 13.8VDC.
ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or can drive one or two
702 (series connected) self-contained 20-watt sirens. Do not connect two 702s in parallel.
AUXILIARY POWER OUTPUT: 12VDC, 600mA max.
NOTE: For UL installations, Alarm Sounder plus Auxiliary Power currents should
not exceed 600mA total.
FUSE (if installed): Battery (3A) No. 90–12 (PC board may have a PTC device instead of
3. Communication: FORMAT SUPPORTED:
ADEMCO Express: 10 characters/sec, DTMF (TouchTone) Data Tones,
ADEMCO Low Speed: 10 pulses/sec, 1900Hz Data Tone, 1400Hz ACK/KISSOFF.
Radionics/SESCOA: 20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF.
Ademco Contact ID 10 characters/sec., DTMF (TouchTone) Data Tones,
LINE SEIZE: Double Pole RINGER EQUIVALENCE: 0.1B FCC REGISTRATION No.: 5GBUSA-44003-AL-E
4. Maximum Zone Resistance: Zones 1–8 = 300 ohms excluding EOLR standard zones
Compatible Devices
Keypads: 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V and
Wireless Receivers: 5881L/5882L: accepts up to 8 transmitters
5881M/5882M: accepts up to 16 transmitters 5881H/5882H: accepts up to system maximum transmitters 5800TM Transmitter Module (used with Wireless 2-Way Keypads) 5883 Transceiver: accepts up to system maximum transmitters 6150RF Keypad/Transceiver: accepts up to system max. transmitters Zone Expansion: 4219 WIRED EXPANSION MODULE 4229 WIRED EXPANSION/RELAY MODULE
Relay Module: 4204 RELAY MODULE Phone Modules: 4286VIP PHONE MODULE Long Range Radio 7845GSM, 7845i-GSM
(Communication Device)
SECTION 5
Specifications & Accessories
a fuse. The PTC serves as an automatically resetting fuse.)
1400/2300Hz ACK, 1400Hz KISSOFF.
Can report 0-9, B-F
1400/2300Hz ACK, 1400Hz KISSOFF.
6160V Voice Keypads, 6270 Touch Screen Keypad, Symphony Advanced User Interface
5-1
Page 34
Installation and Setup Guide
2-Wire Smoke Detector:
Transformers: 1321: 16.5VAC, 25VA Plug-In Transformer (No. 1321CN in Canada)
1361X10: 16.5VAC, 40VA Powerline Carrier device Interface AC Transformer
Sounders: AB12M 10” Motorized Bell & Box 1011BE12M 10” Motorized Bell & Box 702 Outdoor Siren 719 2-Channel Siren 713 High Power Speaker 746 Indoor Speaker 747 Indoor Siren 747PD Two-Tone Piezo Dynamic Indoor Siren 747UL Indoor Siren 748 Dual Tone Siren 749 Speaker/Horn 744 Siren Driver 745X3 Voice Siren Driver 705-820, 5-inch Round Speaker 713 Speaker WAVE Speaker WAVE2 Two-Tone Siren WAVE2PD Two-Tone Piezo Dynamic Siren 5800WAVE Wireless Siren System Sensor PA400B (beige)/; PA400R (red) Indoor Piezo Sounder
Detector Type
System Sensor
Model No.
Photoelectric w/heat sensor, direct wire 2300TB Photoelectric, direct wire 2400 Photoelectric w/heat sensor, direct wire 2400TH Photoelectric 2451 w/B401B base Photoelectric w/heat sensor 2451TH w/B401B base Ionization, direct wire 1400 Ionization 1451 w/B401B base Photoelectric duct detector 2451 w/DH400 base Ionization duct detector 1451D w/DH400 base H Low-profile, Photoelectric, w/135°F thermal 2100T Low-profile, Ionization type, direct wire 1100
5-2
Page 35
SECTION 6
Regulatory Agency Statements
FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
INDUSTRY CANADA (IC) STATEMENTS
This device complies with RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
This Class B digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
TELEPHONE/MODEM INTERFACE
FCC Part 68
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration number and Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs. This equipment is hearing-aid compatible.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications
network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or electrician, as appropriate.
Ringer Equivalence Number Notice:
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may cons ist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
Industrie Canada
AVIS: l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de
protection, d’exploitation et de sécurit é des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences techniques relatives au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur.
Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterprise locale de télécommunication. Le matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier qu’il est possible que la conformité aux conditions énoncées ci-dessus n’empêche pas la dégradation du service dans certaines situations.
Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de télécommunications peut demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de modifications effectuées par l’utilisateur ou à cause de mauvais fonctionnement.
Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électrique, de lignes téléphoniques et des canalisations d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
Avertissement : L’utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir racours à un service d’inspection des installations électriques, ou à un électricien, selon le cas.
AVIS : L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre m aximal de terminaux qui peuvent être raccordés à une interface. La terminaison d’une interface téléphonique peut consister en une combinaison de quelques dispositifs, à la seule condition que la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5.
6-1
Page 36
Installation and Setup Guide
UL NOTICES
1. Entry Delay No. 1 and No. 2 (fields ∗35, ∗36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.
2. For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60 seconds.
3. The maximum number of reports per armed period (field ∗93) must be set to “0” (unlimited) for UL installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA max.).
6. All partitions must be owned and managed by the same person(s).
7. All partitions must be part of one building at one street address.
8. If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9. For UL commercial burglar alarm installations the control unit must be protected from unauthorized access. The tamper switch installed to protect the control unit enclosure door is suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended downloading) is not permissible for UL installations.
11. Auto-disarming is not a UL Listed feature.
12. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to
a remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security, b) 120 seconds for a system without standard line security or encrypted line security, or c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
13. This control is not intended for bank safe and vault applications.
SIA Quick Reference Guide
1. *31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the same as the “number of reports in armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).
2. *34 Exit Delay: Minimum exit delay is 45 seconds.
3. *35/*36 Entry Delay 1 and 2: Minimum entry delay is 30 seconds.
4. *37 Audible Exit Warning: Feature always enabled; field does not exist.
5. *39 Power Up in Previous State: Must be “1,” power up in previous state.
6. *40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option in field *91 must be set.
7. *50 Burglary Dial Delay: Delay must be a minimum of 30 seconds.
8. *59 Exit Error Alarm Report Code: Always enabled.
9 *68 Cancel Report Code: Default is “code enabled.”
10. *69 Recent Closing Report Code: Always enabled.
11. *91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting Disable must be set to “1” (enabled).
12. *93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.
13. Cross zone timer programming is set in field 85; cross zone pairs are assigned in zone list 4 using 81 Zone List mode.
14. Duress code is assigned by using the “add a user code” procedure found in the User Guide. Enable Duress code reporting by programming zone 92 using 56 Zone Programming mode.
15. Fire alarm verification is a built-in system feature when a zone is programmed for zone type 16.
6-2
Page 37
SECTION 7
Limitations and Warranty
WARNING
THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example:
• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device.
• Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work without power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
• A user may not be able to reach a panic or emergency button quickly enough.
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending on the nature of the fire and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death.
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of the protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the detection performance can decrease.
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people.
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately.
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and remote keypad) should be tested as well. Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life in a given installation. This wireless system, however, can identify a true low-battery situation, thus allowing time to arrange a change of battery to maintain protection for that given point within the system. Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property. We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to learn about these developments.
7-3
Page 38
Installation and Setup Guide
1321 ......................................... 1-2, 2-3
1321 AC Transformer .................... 2-11
1361X10................. 2-3, 2-11, 2-12, 5-2
3+1 and 4+1 Standard Formats ....... 3-1
4204 ....1-2, 2-2, 2-5, 2-6, 2-11, 3-6, 5-1
4219 ......1-1, 1-2, 2-2, 2-5, 2-7, 2-8, 5-1
4229 .1-1, 1-2, 2-2, 2-5, 2-6, 2-7, 2-8, 2-
11, 3-6, 5-1
4285 .............................................. 2-14
4286 .............................................. 2-14
5800 Series Transmitters................. 2-9
5800TM .................................... 2-9, 5-1
5801 ................................................ 2-9
5802 ......................................... 2-9, 3-8
5802CP ....................................2-9, 3-8
5827 ................................................ 2-9
5827BD ...........................................2-9
5881 ......................................... 2-2, 2-8
7720PLUS or 7820 .......................... 1-2
AC Power Supply ............................1-2
AC Transformer............... 2-3, 2-12, 5-2
Ademco Contact ID.......................... 3-3
Alarm Output ............................ 2-2, 2-4
Arming Away ................................... 3-6
Arming Instant ................................. 3-6
Arming Modes .................................3-7
Arming Stay..................................... 3-6
Audio Alarm Verification (AAV) ...... 2-13
AUI .................................................. 2-5
Authority Levels............................... 3-5
Auxiliary Output ............................... 2-2
Backup Battery................................1-2
Battery Life...................................... 2-9
Battery Tests ............................ 4-1, 4-2
Bell Supervision............................... 2-4
Bell Supervision Jumper .................. 2-4
Bypassing Zones .............................3-6
INDEX
Cabinet............................................ 2-1
CALIFORNIA STATE FIRE
MARSHALL.................................2-2
Caller ID Unit .................................2-13
Charging Voltage............................. 5-1
Chime Mode....................................3-6
Clean Me Option..............................2-7
Communication.........................3-1, 5-1
Contact ID Reporting ....................... 5-1
CSFM .............................................. 2-2
Device Address ...............2-5, 2-11, 3-8
Dialer Communication Test..............4-2
DIP Switches...................................2-9
Disarming ........................................ 3-6
Double-Balanced ............................. 2-6
Enrolling ..........................................2-9
Entry Delay...............................3-7, 3-8
EOLR .......................................2-6, 5-1
Exit Delay ................................. 3-7, 3-8
Exit Error Alarm ...............................3-8
Expansion Zones.............................2-7
Fast Busy Signal............................2-13
FCC................................................. 6-1
Go/No Go Test Mode.......................4-2
Handshake ......................................3-1
Hardwired Zones .............................1-1
HAYES Modem ...............................1-1
House ID .........................................2-9
Ideal Model 61–035 ......................... 2-3
Installer Code ........................... 4-1, 4-2
Keypad Addresses...........................2-5
Keyswitch .................................. 2-10, 3
Kissoff..............................................3-1
Lock.................................................2-1
Long Range Radio................ 2-5, 3, 5-1
Low Battery Message ...................... 4-2
MODel 112 ....................................2-10
Modem ............................................3-8
Momentary Switch .........................2-10
On-Board Triggers .........................2-14
Output Relays..................................1-2
Panic Keys.......................................3-7
Periodic Test Reports ......................4-2
Phone Line ....................................2-13
Phone Module.1-1, 2-2, 2-5, 2-13, 2-14,
5-1
Power Failure...................................3-8
Power Supply.....................2-2, 2-4, 7-6
Powerline Carrier Devices1-2, 2-11, 3-6
PSC04 Powerline Interface............ 2-11
Relay Modules........................1-2, 2-11
Report Code ....................................3-1
Report Code Formats ......................3-1
Response Time
RF House ID Code...........................2-8
RF Interference................................2-8
RF jam detection..............................1-1
RF Jam Option.................................2-8
RF Receiver............2-1, 2-2, 2-5, 2-8, 3
RJ31X Jack ................................... 2-13
SA4120XM-1 Cable .........................2-3
Security Codes .........................1-1, 3-5
Silent Burglary .................................... 3
Silent Panic......................................3-7
Sniffer Mode ....................................4-1
Sounder Connections ......................2-4
Supplementary Power......................2-4
System Communication...................3-1
System Test.....................................4-1
Tamper Switch........................2-10, 6-2
Telco Line.................................. 2-13, 3
Telephone Line Monitoring...............1-1
Test Mode.................................4-1, 4-2
Trigger outputs...............................2-12
Trouble Displays.......................3-7, 3-8
UL.............................2-2, 2-4, 2-11, 5-1
Verify Operation...............................2-7
Wire Run Chart.........................2-4, 2-5
Worksheet .......................................2-2
Zone Doubling .................................2-6
................................
2-7
7-4
Page 39
SEE
EARTH
HI
LO
LO
HI
HI
LO
LO
HI
HI
LO
LO
HI
HI
LO
LO
HI
RING
(RED)
TIP
(GREEN)
RING
(GRAY)
TIP
(BROWN)
} }
GROUND
INCOMING
PHONE LINE
TELEPHONE WIRING
HANDSET
+
}
OUTPUT
AUX. POWER
GROUNDING
FOR PROPER
INSTRUCTIONS
DOC LOAD NO.: 3
CONNECT CORD)
(VIA RJ31X* JACK AND DIRECT
FOR CONNECTION OF OPTIONAL 4286 VIP MODULE
TO PHONE TERMINALS, SEE INSTRUCTIONS.
*CA38A IN CANADA
VISTA-20P ONLY
ZONE 8
ZONE 7
ZONE 6
ZONE 5
ZONE 4
ZONE 3
ZONE 2
ZONE 1
FOR UL
600mA MAX.
(500mA MAX.
10.5-13.8VDC INSTALLATIONS)
TO 110VAC
UNSWITCHED
OUTLET (24HR)
TO PREVENT RISK OF SHOCK,
DISCONNECT TELEPHONE LINE AT TELCO
JACK BEFORE SERVICING THIS UNIT.
WARNING:
2000
OHMS
2000
OHMS
2000
OHMS
2000
OHMS
2000
OHMS
2000
OHMS
2000
OHMS
2000
OHMS
LIMITED.
ARE POWER
ALL OUTPUTS
BLACK: KEYPAD GROUND (- ) RETURN
NOTE:
+
ALARM OUTPUT
10.5–13.8VDC, 2A MAX.
EOLR
EOLR
EOLR
EOLR
EOLR
EOLR
EOLR
EOLR
KEYPAD (S)
(600mA MAX. FOR UL
COMPLIES WITH FCC RULES, PART 68. FCC REGISTRATION
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
1312 14
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
YELLOW: KEYPAD DATA OUT
GREEN: DATA IN FROM KEYPAD
REMOTE
RED: KEYPAD PWR ( + )
DEVICES
KEYPADS
AND OTHER
ADDRESSABLE
BLK
CURRENT (IN BOTH
PARTITIONS) AND
ALL OTHER DEVICES
DRAWING POWER
FROM TERMS 4 & 5
MUST BE INCLUDED
IN AUX CURRENT
TEMPORAL PULSE
USAGE, INCLUDING
SIREN, OR 12V BELL).
AUX POWER) STEADY
SOUNDING FOR FIRE.
FOR BURGLARY/PANIC,
CAN USE ADEMCO No. 702
NO. 5GBUSA-44003-AL-E RINGER EQUIVALENCE: 0.1B.
POWER SHUTDOWN NOTE:
SYSTEM SHUTS DOWN
SENSOR DETECTION
PROCESSING IF CONTROL'S
VOLTAGE DROPS BELOW 9.6V.
ZONE
PAIRS
2 / 10
3 / 11
4 / 12
ZONE 2
10 11
2k
2k
4286, LRR,
4219, 4229,
4204, 5881)
(e.g. 5800TM,
REMOTE KEYPADS
DRAIN CALCULATIONS.
PROPER OPERATION OF THIS SYSTEM.
SEE INSTRUCTIONS.
WEEKLY TESTING IS REQUIRED TO ENSURE
USE IN CANADA
ALL DEVICES AND
MUST BE LISTED FOR
CANADIAN INSTALLATION
ACCESSORIES USED IN A
5 / 13
6 / 14
7 / 15
8 / 16
3k
6.2k
TYPICAL WIRING FOR
ZONE 10
2k
2k
ZONE 4
TAMPER CONTACTS
2k
2k
TYPICAL WIRING FOR
ZONE 3
CAN USE 6150 OR 6160
KEYPADS. LOCAL
PROGRAMMING
MUST BE DONE WITH A
6160, BUT NEED NOT
REMAIN IN THE SYSTEM
(SET TO ADDRESS 16).
IN ADDITION, THIS SYSTEM MUST BE
CHECKED BY A QUALIFIED TECHNICIAN
AT LEAST ONCE EVERY THREE (3) YEARS.
V20P_V15P-SOC-V9
ZONE DOUBLING
(VISTA-20P ONLY)
SUMMARY OF CONNECTIONS
(VISTA-20P ONLY)
DOUBLE BALANCED ZONE
ADEMCO VISTA-20P / VISTA-20PSIA SERIES / VISTA-15P / VISTA-15PSIA SERIES
EOL
POWER
RED
+
_
BLK
4-WIRE SMOKE DETECTOR CONNECTIONS
RELAY
5
4
AS ZONE TYPE 54
PROGRAM RELAY
_
+
(FIRE ZONE RESET)
OUTPUT
AUX PWR
TERMINALS
SET UNITS
DIP SWITCH
FOR DEVICE
ADDRESSES
-AND/OR-
ADEMCO No. 4219
ADEMCO No. 4229
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
BLK
K5305-1V5
OR LATER.
(USE SA4120XM-1
INFORMATION,
FOR COMPLETE
SEE INSTRUCTIONS
TRANSFORMER
8-PIN CONNECTOR
USED FOR 1361X10
SEE INSTRUCTIONS.
ON-BOARD TRIGGERS
CONNECTIONS AND FOR
BATTERY FUSE
(IF INSTALLED.)
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
FUSE NOTE
3A
SUPERVISION
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
N.O.
VIOLET
2000
OHMS
EOLR
_
+
DETECTOR
4-WIRE SMOKE
OR COMBUSTION
N.C.
TO OUTPUT 17
CONTACT OPENS MOMENTARILY
UPON FIRE ALARM RESET
MAX. CURRENT = 100 mA
"OUT NORM LOW" = YES IN
PROGRAM OUTPUT 17 FOR
TYPE 54 IN 80 MENU MODE
OR
79 MENU MODE AND AS ZONE
7 - 15
SEE
INSTRUCTIONS.
SET
RECEIVERS
DIP SWITCH
AND/OR
-AND/OR-
(4 OUTPUT RELAYS)
ADEMCO No. 4204 RELAY MODULE
GRN
YEL
OPTIONAL
TO
COM
SYNC
BLACK
RF RECEIVER
ADEMCO 5881* Type
TRANS.
DATA
(TRIG. 2)
GND
+12 AUX
(TRIG. 1)
FLYING LEADS
FOR BATTERY
CONNECTION
+
RED
+
BLK
OUTPUT 18
OUTPUT 17
OUTPUT RELAYS)
RED
CABLE)
78
1234 5 6
MAY HAVE PTC IN
PLACE OF FUSE.
HEAT
DETECTOR
+
_
TO ZONE TERM. ( )
TO ZONE TERM. ( )
FOR DEVICE
ADDRESS
OF 0.
SEE
INSTRUCTIONS.
WIRELESS ZONES
5881L: UP TO 8
5881M: UP TO 16
5881H: UP TO 56
*5882 IN CANADA
RED
GRN
YEL
( FROM EITHER OR BOTH GROUPS)
FOR UP TO 40 ADDITIONAL ZONES
BLK
YEL
RED
GRN
TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7
RED JUMPER
CUT FOR BELL SUPERVISION.
ALSO, CONNECT 2000 OHM RESISTOR
DIRECTLY ACROSS SOUNDER.
21 22 23 24 25
20
19
18
17
16
15
14
13
12
11
10
9
78
6
5
4
3
12
BATTERY
24-HR BATTERY STANDBY REQUIRED FOR
FIRE INSTALLATIONS. USE 12V, 17.2AH
BATTERY FOR 600mA AUX POWER. SEE
INSTRUCTIONS.
CHARGING VOLTAGE
13.8VDC. MAXIMUM
BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4 HRS
12V, 4AH
SEALED LEAD-ACID TYPE.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.
CHARGING CURRENT
650mA.
TO DETERMINE TOTAL STANDBY LOAD
Figure 17. Summary of Connections
ON BATTERY, ADD 100mA TO TOTAL OF
CLASS 2 PLUG-IN TRANSFORMER
AUX. POWER OUTPUT AND REMOTE
KEYPAD CURRENTS.
USE UL LISTED LIMITED ENERGY
CABLE FOR ALL CONNECTIONS
16.5VAC, 25VA
(e.g. ADEMCO No. 1321).
(USE No. 1321CN IN CANADA)
USE 1361X10 TRANSFORMER
INTERFACE IN PLACE OF 1321 OR
1321CN WHEN POWER LINE CARRIER
DEVICES ARE BEING USED. (SEE
INSTRUCTIONS FOR CONNECTIONS)
THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
STANDARD 72, CHAPTER 11 (NATIONAL
FIRE PROTECTION ASSOCIATION,
BATTERY-MARCH PARK, QUINCY,MA
02169).
PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION,
OPERATION,TESTING, MAINTENANCE,
EVACUATION PLANNING AND REPAIR
SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM
HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE
PERMISSION OF THE LOCAL AUTHORITY
HAVING JURISDICTION. THE BURGLAR
ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY
NUMBER.
7-5
Page 40
WARRANTY INFORMATION
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2004 Honeywell International Inc.
www.honeywell.com/security
ÊK5305-1V88Š
K5305-1V8 4/09 Rev. A
Loading...