Honeywell T87F, 137421P, 137421N Installation Instructions Manual

T87F Zone Thermostat and
137421N,P Wallplates; T87F Zone
Thermostat and Q539A,B Subbases
INSTALLATION INSTRUCTIONS

APPLICATION

Table 1. Thermostat/Wallplate and Subbase Applications and Specifications.
Thermostat
/Wallplate
or Subbase Application
T87F3707/ 137421N
T87F3715/ 137421P
T87F3715/ Q539A1436
T87F3707/ Q539A1428
T87F3715/ Q539B1039
T87F3707/ Q539B1021
To control zones other than zone 1 using MM-2 or MM-3 Zone Control Panels. To control zone damper actuators in independent heating-only systems.
To control any zone on TZ-3, EZ-2, EZ-4, EMM-3 or EMM-3U or zone one on MM-2 or MM-3 Zone Control Panels.
To control zone damper actuators in independent zones in heating-cooling systems.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control.
Thermostats. The T87F is used with the 137421N or P Wallplate (provided) or Q539A or B Subbase (ordered separately), depending on application. See Table 1 for thermostat/wallplate and subbase applications and specifications.
Switching
CommentsSystem Fan
None None Wallplate included with
COOL-OFF­HEAT
HEAT__COOL None Q539B ordered
ON-AUTO Q539A ordered
thermostat. Terminals are marked: W, R, Y.
separately. Terminals marked: R,W,Y,G,O,B.
separately. Terminals marked: 4,5,6.

INSTALLATION

When Installing This Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Disconnect the power supply to prevent electrical
shock or equipment damage.
3. Check the rating given in the instructions and on
the product to make sure the product is suitable for your application.
4. Installer must be a trained, experienced service
technician.
5. After completing installation, use these instructions
to check out the product operation.
® U.S. Registered Trademark Copyright © 2002 Honeywell • •All Rights Reserved
69- 0579- 4
T87F ZONE THERMOSTAT AND 137421N,P WALLPLATES; T87F ZONE THERMOSTAT AND Q539A,B SUBBASES
A

Selecting Location

• Install the thermostat about 5 ft (1.5 meters) above the floor in an area with good air circulation at average temperature.
• Do not install the thermostat where it can be affected by: — drafts or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside
wall behind the thermostat.
• Handle this thermostat carefully; it is a precision instrument that was carefully calibrated at the factory.
CAUTION
Electrical Shock Hazard Can cause personal injury or equipment damage.
Disconnect power supply before installation.

Mounting and Wiring

IMPORTANT
To prevent interference with thermostat linkage, keep wire length to a minimum and run wires as close as possible to the subbase.
All wiring must comply with local codes and ordinances.
T87F Zone Thermostat and wallplate or subbase are used in zoned conventional single-stage heating or heating-cooling systems.
137421 Wallplate or Q539 Subbase
REPLACEMENT APPLICATION
1. Remove old equipment. Dispose of properly. See
Mercury Notice.
2. Check the existing wallplate or subbase wires for
cracked or frayed insulation.
3. Replace any wires in poor condition.
4. If the wires are plastered into the wall, make a hole
next to the wires so they can be pushed back into the wall later.
5. Continue with step 3 for New Installation.
NEW INSTALLATIONS
1. Run low voltage thermostat cable (if necessary) to
the thermostat location.
2. Pull about 3 in. (76 mm) of cable through a hole in
the wall.
3. Connect wires to the terminals inside the wallplate
or subbase. See Fig. 1 and 2 or zone control panel installation instructions for wiring diagrams of typi­cal zone systems.
4. Push excess wire back through the hole and plug
any opening with insulation to prevent drafts that can affect thermostat performance.
137421 Wiring Cross Reference
Old Terminal New Terminal
4W 5R 6Y
5. Loosely fasten the thermostat wallplate or subbase
to the wall with a screw through the left mounting hole. See Fig. 3.
6. Adjust the wallplate or subbase so it is approxi-
mately level and start the second screw through the right mounting slot. Do not tighten.
T87F3715/Q539B1039 T87F3707/Q539B1021
ADJUSTABLE HEAT ANTICIPATOR
HEAT COOL HEAT COOL
J
R/5
R C
T140 TRANSFORMER
W
J
TEMPERATUE RISE
TEMPERATUE FALL
Y
W/4
Y/6
ARD CONFIGURED WITH POWER OPEN
M14842
Fig. 1. Wiring single ARD (power open) to thermostat.
T87F3715/Q539B1039 T87F3707/Q539B1021
ADJUSTABLE HEAT ANTICIPATOR
W
HEAT COOL HEAT COOL
J
J
3
R/5
DAMPER ACTUATOR
1
L2
L1
(HOT)
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
NO SYSTEM SWITCHING ON 137421 WALLPLATE.
3
FOR CORRECT SYSTEM OPERATION, DO NOT DISCONNECT FACTORY­INSTALLED J-J JUMPER ON Q539B.
Fig. 2. Wiring T87F Thermostat and Q539B Subbase
or 137421 Wallplate in independent zone.
(COM) (HOT)
TEMPERATUE RISE
TEMPERATUE FALL
Y
2
Y/6W/4
4
5 6 Z
1 2 3
X
M19059
69-0579-4 2
T87F ZONE THERMOSTAT AND 137421N,P WALLPLATES; T87F ZONE THERMOSTAT AND Q539A,B SUBBASES
THERMOSTAT CABLE ENTRANCE HOLE
137421
1
WALLPLATE
1
USE 137421 WALLPLATE FOR HEAT ONLY APPLICATIONS. SEE TABLE 1 APPLICATION INFORMATION.
Fig. 3. Mounting T87F Thermostat and 137421
Wallplate or Q539 Subbase.
IMPORTANT
An incorrectly leveled thermostat causes the temperature control to deviate from setpoint.
7. Level the thermostat wallplate or subbase exactly
using a spirit level as shown in Fig. 4.
IMPORTANT
Do not overtighten thermostat captive mounting screws because damage to subbase threads can result.
T87F
THERMOSTAT COVER RING
Q539 SUBBASE
CAPTIVE MOUNTING SCREWS (3)
THERMOSTAT CABLE ENTRANCE HOLE
1
M19048
8. Tighten mounting screws.
T87 Thermostat
1. Before mounting the thermostat, see Heat Antici-
pator Adjustment in Settings and Adjustments sec­tion.
2. Align the thermostat over the wallplate or subbase
and tighten the three mounting screws.
MOLDED POST
MOUNTING HOLES
HORIZONTAL CENTER LINE
OPENING FOR THERMOSTAT WIRING
Fig. 4. Leveling wallplate or subbase before
[13]
1 2
9
[14]
16
mounting T87F.
VERTICAL GUIDE
SPIRIT LEVEL
MOUNTING SLOTS
MOUNTING SLOTS
M1371B

Settings and Adjustments

Temperature Selection
To select the desired temperature for each zone, turn the transparent dial on the zone thermostat until the desired point on the setting scale (top scale) is aligned with the pointer.
System and Fan Switching
Q539A
The Q539A provides System and Fan switches to control heating-cooling equipment and zone one fan in multi­zone applications:
• The System switch controls the system operation: — Heat: Only the heating system operates. — Off: Both heating and cooling control systems are
disconnected.
— Cool: Only the cooling system operates.
• The Fan switch controls the fan operation: — Auto: The fan operates in response to the plenum
fan control in heating; the fan operates in response to the thermostat in cooling.
— On: The fan runs continuously.
• To change positions, use thumb and index fingers to move the switch lever to the desired position. Place the switch lever directly over the selected function indicator mark.
3 69-0579-4