Honeywell 13270-01LB, 75585-01NMB, 75585-02NMB, 13270-04LB, 75585-04NMB Data, Installation And Commissioning Manual

...
This manual covers a range of conventional fire panel and include system design, installation and configuration information.
The fire panels covered are designed in accordance with the requirements of EN54 Part 2:1997 + AMD 1 (and include optional clauses 7.8, 7.10 & 7.11), plus the requirements of EN54 Part 4:1997 + AMD 1 and AMD 2. This publication covers the Conventional fire alarm panels:
q 1 zone panel:- 13270-01LB and
75585-01NMB
q 2 zone panel:- 13270-02LB and
75585-02NMB
q 4 zone panel:- 13270-04LB and
75585-04NMB
q 8 zone panel:- 13270-08LB and
75585-08NMB
q Fire alarm repeat panel:
13271-08LB and 75586-08NMB.
The panels are supplied without batteries.
This manual is intended for use by installers and commissioning engineers.
A separate Operating instructions and Log book has been supplied along with this booklet which must be forwarded on to the End User.
4188-424 issue 4_Part 1_10-09
Data, Installation and Commissioning guide
Fire Control and Repeat panels
(Conventional 1, 2, 4 and 8 Zone panel range)
Content Page
System design · · . . . . . 2
Cables - · · · · · . . . . . 4
Notes to installers . . . . . 5
Panel fixing· · · · . . . . . 6
Terminals · · · · . . . . . 8
Controls & indicators . . . . 9
Power up tests · · . . . . . 10
Installed system tests . . . 11 Config. considerations . . . 11
Access levels 2 · . . . . . 12
Operating instructions for
Access level 2 functions . . 12 Programming Options . . . 14 Operating instructions for
Access level 3 functions . . 14 Operating instructions for
Access level 4 functions . . 15
Fault indications · . . . . . 16
Fault finding · · · . . . . . 17
Specification for the
Control panel· · · . . . . . 20
Specification for the
Repeat panel· · · . . . . . 22
Parts list · · · · · . . . . . 23
System design
The fire system design should be to
BS 5839:Part 1:2002 + A2:2006 Code of Practice for system design installation and servicing.
Supplemented with customer requirements.
Mains Supply
The control panel mains supply must be via a fused spur unit rated:
5A - 1 & 2 Zone panel/Repeat
panel
7A - 4 & 8 Zone panel
Standby Supply
With the recommended batteries the control panel will provide a standby supply under mains failure conditions. A period of 72 hours followed by 30 minutes of alarm load is possible and is dependent on the system loading.
24V power supply
The power supply terminals ‘24+ and 0’ may drive external ancillary equipment and is designed to be used in conjunction with auxiliary contacts and common fire and fault outputs. The maximum currents are 250mA (1 & 2 zone) and 500mA (4 & 8 zone). The supply is monitored for faulty 24V supply level or fuse blowing.
NOTE: The use of the 24V supply will affect the panel standby capability.
Fire Detection (Zone Circuits)
Each zone circuit can have up to
3.0mA load. An end-of-line capacitor unit or bipolar capacitor is required for zone circuit monitoring, which must be fitted after the last detector or manual call point on the circuit. All
manual call points used must have a 470 ohms series resistor.
Where a zone circuit is not being used, the
end-of-line
capacitor unit or bipolar capacitor must be fitted across its terminals in the panel.
System design Fire Panels
2 4188-424 issue 4_Part 1_10-09
Un-used Zone circuits mus
t
be terminated with an end-of-line Capacitor unit or bipolar capacitor
End-of-line Capacitor unit or bipolar capacitor
RED
BLACK
FIRE DETECTION (ZONE) CIRCUIT
A
fire detector head may be fitted to a diode-base for continuity when a detector head is removed and there can be a maximum of up to 20 diode-bases per zone circuit.
MANUAL CALL POINT
NOTE: Spur wiring is not permitted off zone circuits.
Zone
Circuit
Zone
Circuit
Control panel
Z1+ Z2+Z1- Z2-
BLACK
RED
FIRE DETECTOR
Figure 1 Zone circuit - used and unused
IN
C
OUT
NC/NO
IN
IN
1
1
7
7
6
6
5
5
4
4
3
3
2
2
OUT
OUT
IN
1
7
6
5
4
3
2
OUT
IN
1
7
6
5
4
3
2
OUT
IN
1
7
6
5
4
3
2
OUT
LED unit
Base showing End of Line device fitted
Base with LED connection
Base with Relay connection
Standard base shown. Diode base connection is identical.
Standard base
MCP
Zone Circuit
Zn+
Zn-
1
2
3
NOTE: LED unit is supplied with LED module
NOTE: End of line unit is supplied with panel
Zone
Circuit
Control panel
Zn+ Zn-
Earth continuity
+
-
Control panel
Connection to 17800 range of detector bases are shown here.
Figure 2 Connection to detectors, call points and panel
Alarm (Sounder circuits)
To comply with the requirements of
BS 5839: Part 1:2002 +
A2:2008,
two or more alarm sounder circuits should be used on all installations.
NOTE: All sounder circuits (sectors) will operate together in the event of a fire condition.
NOTE: Each sounder output is
0.5A maximum protected by
0.75A fuse.
1 & 2 Zone Panels
4 & 8 Zone Panels
1A maximum Alarm sounder load per panel
1.5A maximum Alarm sounder load per panel
The load must be shared between the sounder circuits. The alarm sounder circuits are regularly pulse monitored for failure. It is important that the last alarm sounder is fitted with a 10K Ohm end-of-line resistor.
The sounder outputs are monitored in alarm for loss of supply or multiple sounder output overloads
Where a sounder circuit is not being used, the
end-of-line
resistor must be fitted across its terminals in the control panel.
Class Change
A pair of unmonitored terminals allow only the system alarm sounders to be activated from a remote position. It is considered that the major use for these will be for class change functions in schools and colleges.
Auxiliary Contacts
These are normally open (NO) and normally closed (NC) contacts that change over when the panel goes into a fire condition. The contacts are rated at 24V dc 1A for a resistive load and should not be used to switch voltages in excess of 50V. The auxiliary circuits should be powered from an independent power supply.
NOTE:There is no indication given at the panel of class change push button operation.
Fire Panels System design
4188-424 issue 4_Part 1_10-09 3
NOTE: Spur wiring is not permitted off circuits.alarm sounder
Sounder
Sounder
Control panel
Alarm sounders
be polarised
and suppressed.
must
S1+
Sn+S1- Sn-
Alarm sounder
must have a
series blocking
diode
Sounder circuit that is not used is terminated with an end-of line resistor
ALARM SOUNDER CIRCUIT
End ofline Resistor 10k Ohms
Control panel
Sn+
Sn-
Earth continuity
Sounder
Figure 3 Alarm sounder circuit used and unused
Class change
100m max.
Cable
distance
Pushb
utton switc
h
or relay pulsed
at 1 second
interval (minimum)
for class change
application
CC1
C2C
Control panel
Figure 4 Class change circuit
Contacts rated 1A@24Vdc
Contacts change over occur with a fire condition
NC
NC
N0
N0
Auxiliary
contacts
Control panel
100m maximum cable distance
Figure 5 Auxiliary contacts
Common Fire and fault
The common fire output is a normally open electronic switch that closes with a fire condition.
The common fault output is a normally closed electronic switch, which opens with a fault condition, this is for a fail safe operation.
Each electronic switch is current limited, see specification.
Use a relay to provide volt free contacts.
The +24V & 0V is a power supply for use with auxiliary contacts, common fire and common fault circuits, see specification.
Repeat Panel
A Repeat panel can be connected in series to the control panel. A repeat panel duplicates fire and fault indications together with system controls.
Cables Fire Panels
4 4188-424 issue 4_Part 1_10-09
24+
CFT
CFR
0V
Control panel
Current limited
Current limited
Normally closed
electronic switch
Normally open electronic switch
NOTE: The maximum 24V relay load is 280mW (Common Fire) and 500mW (Common Fault). Use a relay to provide volt free contacts.
0V
24V+ - 24V+ supply CFT - Common fault CFR - Common fire 0V - 0V supply
The Indicator and Relay
shown connected here are typical examples of external circuit
Figure 6 Fire fault & 24V outputs
Length per circuit Type of circuit Recommended cables, also see BS5839:Part 1 guidance
2m Mains power supply cord see power supply cord
1Km Zone circuit
See BS5839:Part 1:2002 + A2:2008 for guidance
1Km Sounder circuits
100m Auxiliary circuit
100m Common fire and fault circuit
100m Class change circuit
500m total circuit Repeat panel link Belden type -screened 2-core twisted pair
Cables
The guidance of BS5839:Part 1:2002 + A2:2008, should be followed.
Generally available electrical installation cable may be used, providing the cable is:
q
to
BS6387
q
with no more than 2 - cores
q each core having no less than
1.5mm
2
cross section area
(maximum 2.5mm
2
).
q
with an inherent or through metal conduit screen for earth continuity in order to produce electrical protection and screening.
q
having protection from heat and mechanical damage.
Power supply cord
The mains supply to the panel should be wired in 0.75mm
2
cable with a effective connection to building service earth continuity conductor.
R+
R-
Control panel
Repeat panel
Screen must be connected to panel
R+ R-
Figure 7 Control to repeat panel connections
Notes to installers
Check
q
The power-up and commissioning is done by the servicing organisation.
q
The wires between the termination point and terminals should be short and straight as possible.
q
The cables of the fire detection and alarm system and other systems should usually be separated by at least 160mm, unless dedicated conduit or ducting is used.
q
Do not use any part of building structure for earthing.
q
The cable length between the Repeat LED unit and respective fire detector where used , should not exceed 10m.
q Cable Glands should be used
on the equipment for the mains supply cable.
q Unused knockouts on product
enclosure that have been removed, should not be left open.
Requirements
It is recommended that the installer follow the general requirements of:
q
BS5839:Part 1:2002 + A2:2008
,
which is the
code of practice relating to the fire detection and alarm systems for buildings
.
q
the relevant parts of the
BS 7671 Requirements for Electrical Installation
.
Second fix
To prevent the possibility of damage or dirt degrading the performance or appearance of the System products, the installation of second fix items should be delayed until all major building work in the area is complete.
Fixtures and fittings
It is the installers responsibility to provide:
· adequate fixtures and fittings
for the type of construction surface onto which a product is to be installed.
· as an aid to this decision, the
weight and overall size of each full assembly together with implications on cable entries and routing should be taken into consideration.
NOTE: All these procedures assume that the cable, gland, steel box (BESA box) and other related accessories are provided by the installer.
As fitted wiring drawings
The installer should acquire:
q
site specific information from the interested parties, for details on the location of products for installation
q
the acquired information together with this guide and the relevant standards should be used to assist the work.
Earth continuity
To maintain earth continuity, the cable screen must be continued through each system device, whether the earth is connected to a device or not.
NOTE: The cable from the main panel to repeat panels if fitted must be a screened cable. Refer to Figure 8.
Fire Panels Notes to installers
4188-424 issue 4_Part 1_10-09 5
4-off earth points
Mains input terminal
block c/w mains fuse
Mains supply
to panel
13-back 13-top
cable entry points
Gland
Earth drain
Cable
Zone Cable termination
N
O
TE: Repeat panel link cable entries are located at the opposite end to the mains cable entries, ie on the Right Hand Side.
Panel backbox
Electronic assembly
Figure 8 Panel cable entry and earth points
Panel fixing
a) Remove panel from its
packing.
b) Store the front panel (including
the electronic assembly) and the metal plates in a safe place until later.
c) Check the spare parts supplied
with those listed in
Table 1.
d) Remove the appropriate
knock-in on the panel case for cable entry.
e) Hold the panel on the wall in
the desired mounting position and mark the positions of the fixing holes. See
Figure 9
for
case fixing details.
f) Secure the panel to the wall
using suitable fixings. A top centre keyhole fixing is provided on the case to allow the panel to be hooked whilst the bottom two fixing points are located.
NOTE: For details on flush fixing the panel, see Figure 11.
g) Connect the mains supply
cable to the panel. The cable:
· must be fed through one of the dedicated mains cable entry points into the panel.
·
must be via an unswitched fused spur unit, rated 5A for
the 1&2 Zone Control and Repeat panels and 7A for 4&8 Zone panels.
·
The fused spur isolator cover should be red and marked:
FIRE ALARM - DO NOT SWITCH OFF
·
The fused spur units must be fed from a dedicated isolation switch used for the fire alarm system only.
h) Wire the system. With the
exception of mains cable, all other cables should remain unconnected at the panel. For the unconnected cable leave 300mm tail wire length and mark each core identifying its final point of connection. The system wiring can be tested whilst not connected to the respective terminals at each system device.
CAUTION: DO NOT undertake high voltage insulation tests WITH THE CABLES CONNECTED to their terminals. This may damage the electronic circuitry in the product.
I) Refit the front panel
(including
the electronic assembly
) into the panel using four M3 screws and connect the transformer cable and earth cable, see
Figure 10
.
j) Attach the top and bottom
metal plates using four M3 screws,
see Figure 11
.
NOTE: Each terminal in a panel will accept a maximum conductor size of 2.5mm
2
.
NOTE: The installation of all outstanding parts is usually carried out during Commissioning of the System.
Panel fixing Fire Panels
6 4188-424 issue 4_Part 1_10-09
Description
For fuse location see Figure 12
Quantity supplied with control panel
Repeat panel
1 zone 2 zone 4 zone 8 zone
10K end-of-line resistor 2 2 4 8
Capacitor unit or bipolar capacitor
12 4 8
End of line label 3 4 8 16
Fuse 3.15A 20mm x 5mm AS (mains terminal block )
11 1 1 1
Fuse 3.15A 20mm x 5mm QB (battery FS2)
11 1 1 1
Fuse 0.5A 20mm x 5mm QB (24V) UL Rated FS11
11 1 1
Battery link 1 1 1 1 1
Zone designation label 1 1 1 1 1
M3 screws 8 8 8 8 8
Table 1 Spare parts supplied with each panel
Dedicated mains
cable entry points
Panel size
395mm wide x 274mm high x 87mm deep
89mm 89mm
19mm
197mm
111mm
4-off earth points
How to knock-in a cable entry point
Knock here to open the entry point
Panel Backbox
Transformer
cables
to electronic
assembly
Earth connection
to the electronic
assembly
Figure 9 Panel fixings
Store all spare parts and loose components including the batteries inside the panel carton and keep in a safe place until required.
Fire Panels Panel fixing
4188-424 issue 4_Part 1_10-09 7
Dedi
catedmains
cable entry points
4-off earth points
Red
Battery connections
Bl
ac
k
Fixing points for the electronic assembly
Electronic assembly
P1
To To
Transformer Earth
T1A T1B E
Panel Backbox
Transformer
cables
to electronic
assembly
Earth connection
to the electronic
assembly
+ve
-ve
Bottom Plate (instructions printed onto plate)
Ribs
NOTE: The metal plates are to be located under the ribs on the front panel and fixed in place using M3 screws.
Figure 10 Refitting electronic assembly
378mm wide
245mm high
60mm deep
cross section of the wall to which the panel is to be flush mounted
Control or Repeat panel
A
perture
Flush shroud
4.5 mm
diameter holes
12 h
oles
Figure 11 Installing a flush shroud
Terminals
Terminals Fire Panels
8 4188-424 issue 4_Part 1_10-09
Zones
FIRE
Faults
System
Power
Earth
Sounder
Disabled
Sound Alarms
Silence Alarms
1
23
4
56
7
8
9
0
v
Test
Access/ Function
1 2 3 4 5 6 7 8
Cancel Buzzer
Reset System
CN5 CN6 CN7 CN8 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN16 CN17 CN18 CN19 CN20 CN21 CN22 CN23 CN24 CN25CN26 CN27 CN28CN29 CN30
F1 F2 F3 F4 F5 F6 F7 F8
F9 F10 F11
SECTOR1 SECTOR2 SECTOR3 SECTOR4 SECTOR5 SECTOR6 SECTOR7 SECTOR8BATTERIES
T1AT1B T2BT2AENCNCNONOZ1+Z1-S1-S1+ Z2+ Z2- S2-S2+ Z3+ Z3- S3-S3+ Z4-Z4+ S4+ S4- Z5+Z5- S5-S5+ Z6+ Z6- S6-S6+ Z7+ Z7- S7-S7+ Z8-Z8+ S8+ S8- CC1CC2 24+ 0CFTCFR R+ R-
POWER1 POWER2
FS2 QB
3.15A
3.15A
3.15A
3.15A
3.15A
FS3 750mA
750mA
750mA
750mA
FS11 QB - UL Rated 500mA
500mA
500mA
500mA
FS5
750mA
750mA
FS7
750mA
FS9
750mA
FS4 750mA
750mA
750mA
750mA
FS6
750mA
750mA
FS8
750mA
FS10
750mA
Fuse 1-Zone panel
2-Zone panel
4-Zone panel
8- Zone panel
Repeat panel
SECTOR 1
SECTOR 2
SECTOR 3
SECTOR 4
SECTOR 5
SECTOR 6
SECTOR 7
SECTOR 8BATTERIES
24V
18
All other fuses, ie FS1, FS2 and FS11
are 20mm x 5mm diameter
QB - Quick Blow AS - Anti-Surge
Fuses
T1A
T1B
E
CFR
24+
CFT
0
CC1
CC2
R+
R-
NC
NC
NO
NO
Zn+
Zn-
To Zone and Sounder
Circuits, where `n' signifies
circuit number 1 to 8
Sn-
Sn+
Auxiliary contacts
1A at 24Vdc resistive
To transformer
Mains input supply
Software
version
label
P1
P3 to P6
P7
Class change, connect to XEN-FFR
Common fault,
Common Fire
Repeat panel
Panel
P8
EEPROM Protection fitted across pins 1 and 2
Power
Shift
Display
NE L
The terminal blocks are not fitted on the
shaded
Repeat panel.
FS1 (MAINS) AS
3.15A
3.15A
3.15A
3.15A
3.15A
All sector outputs have resettable 0.75A fuses which do not need replacing. The individual outputs will recover after removing the fault. The recovery time is 30 seconds minimum and it is recommended that the sectors be switched off (Silence Alarms).
Delay
Figure 12 Panel terminals and fuses
Loading...
+ 16 hidden pages