Hitachi BRD-EZ3-110K SPECIFICATIONS SHEET

Standard specifications for BRD-EZ3-110K
Model BRD-EZ3-110K Enclosure Open type Voltage class applicable 400V-class
Operating voltage
(ON/OFF) Service status indication LED ON Discharging resistance I 3 ohms or more Allowable operation cycle 20%ED (2 minutes ON, 8 minutes OFF) Continuous ON time 2 minutes maximum Discharging resistance II 6 ohms or more Allowable operation cycle Continuous
Protective function Protection of power modules against overheating
Thermal relay for protection Operates at a cooling fin temperature of 100 °C.
Normally closed (b contact) Contact rating: 240 VAC, 3A (R load), 0.2A (L load)
Minimum load: 15 VDC, 50 mA (R load) Ambient temperature 10 to 50°C Storage temperature 10 to 60°C Relative humidity 20 to 90% (Non-condensing) Vibration Less than 4.9m/s2 (0.5G)
*1
36 VDC, 2A (R load)
Location Altitude 1000 meters or less, indoors (no corrosive gasses or dust)
General specifications
Coating color Munsell color system 5Y7/1 (The aluminum-cooling fin is not coated.)
Others Equipped with a parallel connection interlocking function (for main or subsidiary unit)
*1 Operating voltage set/change: -5% and -10% (set by the DIP switch) *2 Parallel connection operation: set with the DIP switch
*2
1/2
Dimensional Drawings
Model
Dynamic Braking Unit
BRD-EZ3-110K (Weight: 10kg (22lbs))
Mounting hole
Grounding
M5 screw
7. Price
Please contact SX department.
TM1: Terminal width 6.4mm, M3 screw
TM2: Terminal width 33mm, M10 screw
TM3: Terminal width 7.5mm, M3 screw
2/2D