Grundfos MAGNA3 Installation Manual

0 (0)

GRUNDFOS INSTRUCTIONS

MAGNA3

Installation and operating instructions

contents of Table

MAGNA3

English (US)

Installation and operating instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Español (MX)

Instrucciones de instalación y funcionamiento . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Français (CA)

Notice d'installation et de fonctionnement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

2

English (US) Installation and operating instructions

Original installation and operating instructions.

CONTENTS

 

 

Page

1.

Limited warranty

4

2.

Symbols used in this document

4

3.

General information

5

3.1

Applications

5

3.2

Pumped liquids

5

3.3

Operating conditions

6

3.4

Frost protection

6

3.5

Insulating shells

6

3.6

Non-return valve

6

3.7

Nameplate

7

3.8

Radio communication

8

3.9

Tools

8

4.

Mechanical installation

8

4.1

Installing the pump

8

4.2

Positioning

9

4.3

Control box positions

9

4.4

Pump head position

9

4.5

Changing the control box position

10

5.

Electrical installation

11

5.1

Supply voltage

12

5.2Connection to the power supply (models 40-XX,

 

50-XX, 65-XX, 80-XX, 100-XX)

12

5.3

Connection to the power supply (models 32-XX)

13

5.4

Connection diagram

14

5.5

Input/output communication

16

5.6

Analog input for external sensor

18

5.7

Electrical connection for external sensor

19

5.8

Priority of settings

19

6.

First start-up

20

7.

Settings

21

7.1

Overview of settings

21

8.

Menu overview

22

9.

Control panel

23

10.

Menu structure

23

11.

"Home" menu

23

12.

"Status" menu

24

13.

"Settings" menu

24

13.1

Setpoint

24

13.2

Operating mode

25

13.3

Control mode

25

13.4

FLOWLIMIT

29

13.5

Automatic Night Setback

29

13.6

Relay outputs

30

13.7

Setpoint influence

30

13.8

Bus communication

31

13.9

General settings

31

14.

"Assist" menu

35

14.1

Assisted pump setup

35

14.2

Setting of date and time

35

14.3

Multi-pump setup

35

14.4

Setup, analog input

35

14.5

Description of control mode

35

14.6

Assisted fault advice

35

14.7

Wireless GENIair

35

14.8

Multi-pump function

35

15.

Selection of control mode

36

16.

Fault finding

38

16.1

Grundfos Eye operating indications

38

16.2

Signalling communication with remote control

38

16.3

Fault finding

39

17.

Sensor

40

17.1

Sensor specifications

40

18.

Accessories

41

18.1

Grundfos GO Remote

41

18.2

Communication

41

18.3

Fitting the CIM module

44

19.

Technical data

45

20.

Disposal

45

 

 

 

Warning

Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.

Warning

The use of this product requires experience with and knowledge of the product.

Persons with reduced physical, sensory or mental capabilities must not use this product, unless they are under supervision or have been instructed in the use of the product by a person responsible for their safety.

Children must not use or play with this product.

English (US)

3

(US) English

1. Limited warranty

Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of 24 months from date of installation, but not more than 30 months from date of manufacture. Grundfos' liability under this warranty shall be limited to repairing or replacing at Grundfos' option, without charge, F.O.B. Grundfos' factory or authorized service station, any product of Grundfos' manufacture. Grundfos will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim. Products which are sold but not manufactured by Grundfos are subject to the warranty provided by the manufacturer of said products and not by Grundfos' warranty. Grundfos will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating instructions.

To obtain service under this warranty, the defective product must be returned to the distributor or dealer of Grundfos' products from which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions.

Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation supporting the warranty claim and/or a Return Material Authorization must be included if so instructed.

GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE.

Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction.

2. Symbols used in this document

Warning

If these safety instructions are not observed, it may result in personal injury.

Warning

If these instructions are not observed, it may lead to electric shock with consequent risk of serious personal injury or death.

Warning

The surface of the product may be so hot that it may cause burns or personal injury.

Warning

Risk of dropping objects which may cause personal injury.

Warning

Escaping vapor involves the risk of personal injury.

If these safety instructions are not observed,

Caution it may result in malfunction or damage to the

 

equipment.

Note

Notes or instructions that make the job easier

and ensure safe operation.

 

4

3. General information

The Grundfos MAGNA3 is a complete range of circulator pumps with integrated controller enabling adjustment of pump performance to the actual system requirements. In many systems, this will reduce the power consumption considerably, reduce noise from thermostatic radiator valves and similar fittings and improve the control of the system.

The desired head can be set on the pump control panel.

3.1 Applications

The Grundfos MAGNA3 is designed for circulating liquids in the following systems:

heating systems

domestic hot-water systems

air-conditioning and cooling systems.

The pump can also be used in the following systems:

ground source heat pump systems

solar-heating systems.

3.2 Pumped liquids

The pump is suitable for thin, clean, non-aggressive and non-explosive liquids, not containing solid particles or fibers that may attack the pump mechanically or chemically.

In heating systems, the water should meet the requirements of accepted standards on water quality in heating systems.

In domestic hot-water systems, we recommend to use MAGNA3 pumps only for water with a degree of hardness lower than approx. 14 °dH.

In domestic hot-water systems, we recommend to keep the liquid temperature below 150 °F (+65 °C) to eliminate the risk of lime precipitation.

Warning

Do not use the pump for flammable liquids, such as diesel oil and gasoline.

Warning

Do not use the pump for aggressive liquids, such as acids and sea water.

Max. 95 % RH

Enclosure Type 2

TM05 2857 0612

Fig. 1 Pumped liquids

3.2.1 Glycol

The pump can be used for pumping water/glycol mixtures up to 50 %.

Example of a water/ethylene glycol mixture:

Maximum viscosity: 50 cSt ~ 50 % water / 50 % ethylene glycol mixture at +14 °F (-10 °C).

The pump has a power-limiting function that protects against overload.

The pumping of glycol mixtures will affect the max. curve and reduce the performance, depending on the water/ethylene glycol mixture and the liquid temperature.

To prevent the ethylene glycol mixture from degrading, avoid temperatures exceeding the rated liquid temperature and minimize the operating time at high temperatures.

It is important to clean and flush the system before the ethylene glycol mixture is added.

To prevent corrosion or lime precipitation, check and maintain the ethylene glycol mixture regularly. If further dilution of the supplied ethylene glycol is required, follow the glycol supplier's instructions.

Additives with a density and/or kinematic Note viscosity higher than those/that of water will

reduce the hydraulic performance.

English (US)

5

(US) English

3.3Operating conditions

1Min./Max. +14 °F - 230 °F (-10 °C - +110 °C)

2

175 psi (12 bar)

 

3

+32 to +104 °F

 

(0 to +40 °C)

 

 

 

4

< 43 dB(A)

1413

TM05 7662

 

 

Fig. 2 Operating conditions

3.3.1Liquid temperature

See fig. 2, pos. 1.

Continuously: +14 °F to +230 °F (-10 °C to +110 °C). Domestic hot-water systems:

• Up to +150 °F (+65 °C).

3.3.2System pressure

See fig. 2, pos. 2.

The maximum permissible system pressure is stated on the pump nameplate.

3.3.3 Ambient temperature

See fig. 2, pos. 3.

+32 °F to +104 °F (0 °C to +40 °C).

The control box is air-cooled. Therefore, it is important that the maximum permissible ambient temperature is not exceeded during operation.

During transport: -40 °F to +158 °F (-40 °C to +70 °C).

3.3.4Sound pressure level

See fig. 2, pos. 4.

The sound pressure level of the pump is lower than 43 dB(A).

3.3.5Approvals

Conforms to ANSI/UL Standard 778.

Certified to CAN/CSA Standard C22.2 No. 108.

• The protective earth (ground) symbol identifies any terminal which is intended for connection to an external conductor for protection against electric shock in case of a fault, or the terminal of a protective earth (ground) electrode.

3.4 Frost protection

If the pump is not used during periods of frost, Caution necessary steps must be taken to prevent frost

bursts.

Additives with a density and/or kinematic Note viscosity higher than those/that of water will

reduce the hydraulic performance.

3.5 Insulating shells

Insulating shells are available for single-head pumps only.

 

Limit the heat loss from the pump housing and

Note

pipework.

 

The heat loss from the pump and pipework can be reduced by insulating the pump housing and the pipework. See fig. 3 and fig. 13.

Insulating shells for pumps in heating systems are supplied with the pump; see fig. 3.

For pumps in air-conditioning and cooling systems (down to +14 ° (-10 °C)) it is required to apply a silicon sealant to the internal contours of the shell in order to eliminate any air gaps and prevent condensation between the insulation shell and pump housing. Alternatively, the pump can also be insulated manually in accordance with standard insulating requirements for heating and cooling systems (fig. 13).

The fitting of insulating shells will increase the pump dimensions.

TM05 2859 0612

Fig. 3 Fitting insulating shells to the pump

 

Do not insulate the control box or cover the

Caution

 

control panel.

 

3.6 Non-return valve

If a non-return valve is fitted in the pipe system (fig. 4), it must be ensured that the set minimum discharge pressure of the pump is always higher than the closing pressure of the valve. This is especially important in proportional-pressure control mode (reduced head at low flow). The closing pressure of a single non-return valve is accounted for in the pump settings as the minimum head delivered is 5 ft (1.5 m).

TM05 3055 0912

Fig. 4 Non-return valve

6

3.7 Nameplate

The pump nameplate provides the following information:

TYPE 2

PSI

BOITIER DE TYPE 2

THERMALLY PROTECTED

 

Nonsubmersible Pump

 

 

For use with maximum 230° F water

RISK OF ELECTRIC SHOCK. DE-ENERGIZE EQUIPMENT BEFORE REMOVAL OF COVER & SERVICING. FOR SUPPLY

CONNECTION USE COPPER WIRE SUITABLE FOR 90 °C OR EQUIVALENT. THIS PUMP HAS NOT BEEN INVESTIGATED FOR USE

IN SWIMMING POOL OR MARINE AREAS. TO REDUCE THE RISK OF ELECTRIC SHOCK, SEE INSTRUCTION MANUAL FOR

PROPER INSTALLATION; ACCEPTABLE FOR INDOOR USE ONLY.

RISQUE DE CHOC ELECTRIQUE. HORS DES EQUIPEMENT AVANT ENLEVEMENT DE LA COUVERTURE ET D’ENTRENTIEN. POUR

LE RECCORDEMENT D’ALIMENTATION, EMPLOYEZ DES FILS QUI RESISTENT AU MOINS A 90 °C UTILISEZ UNIQUEMENT DES

CONDUCTEURS DE CUIVRE. POUR RE’DUIRE LES RISQUES DE CHOC E’LECTRIQUE, CONSULTES LE MANUEL D’INSTRUCTIONS

Contains FCC ID: OG3-RADIOM01-2G4 POUR UNE INSTALLATION CORRECTE. EMPLOYER UNIQUEMENT A L’INTERIEUR.

Fig. 5 Example of nameplate

Pos. Description

1Product name

2Model

3Production code (year and week)

4Serial number

5Product number

6Enclosure type

7Energy Efficiency Index (EEI)

8Part (according to EEI)

9TF-class

10Minimum current [A]

11Maximum current [A]

12Minimum power [W]

13Maximum power [W]

14Maximum pressure

15Voltage [V] and frequency [Hz]

16QR (Quick Response) code

17Approvals (nameplate)

18Assembled in USA

English (US)

TM05 6381 4612

7

(US) English

3.8 Radio communication

The wireless radio in this product is class B.

Intended use

This product incorporates a radio for remote control.

The product can communicate with Grundfos Go Remote and with other MAGNA3 pumps of the same type via the built-in radio.

Only Grundfos-approved external antennae may be connected to this product, and only by a Grundfos-approved installer.

3.9 Tools

1.2 x 8.0

0.6 x 3.5

TX20

5.0

1

2

3

4

 

5

6

7

TM05 6472 4712

Fig. 6

Recommended tools

 

 

Pos.

Tool

 

Size

 

1

Screwdriver, straight slot

1.2 x 8.0 mm

 

2

Screwdriver, straight slot

0.6 x 3.5 mm

 

3

Screwdriver, torx bit

 

TX20

 

4

Hexagon key

 

5.0 mm

 

5

Open-end wrench

 

Depending on flange bolt

 

 

size

 

 

 

 

 

6

Wire cutter

 

 

 

7

Pipe wrench

 

 

 

4. Mechanical installation

4.1 Installing the pump

MAGNA3 is designed for indoor installation.

The pump must be installed in such a way that it is not stressed by the pipework.

The pump may be suspended direct in the pipes, provided that the pipework can support the pump.

Twin-head pumps are prepared for installation on a mounting bracket or base plate.

To ensure adequate cooling of motor and electronics, the following must be observed:

Position the pump in such a way that sufficient cooling is ensured.

The temperature of the ambient air must not exceed +104 °F (+40 °C).

Warning

Observe local regulations setting limits for manual lifting or handling.

Step

Action

Illustration

 

 

 

 

Arrows on the pump housing

 

 

indicate the liquid flow direction

 

1

through the pump. The liquid

0612

flow direction can be horizontal

 

2862

 

or vertical, depending on the

 

 

 

control box position.

TM05

 

 

 

 

 

 

Close the isolating valves and

 

2

make sure that the system is not

0612

pressurized during the

 

 

 

 

installation of the pump.

TM05 2863

 

 

 

 

 

3

Mount the pump with gaskets in

0612

the pipework.

 

TM05 2864

 

 

 

 

 

 

Fit bolts and nuts. Use the right

0612

4

size of bolts according to system

 

pressure.

TM05 2865

 

 

 

 

 

8

Grundfos MAGNA3 Installation Manual

4.2 Positioning

Always install the pump with horizontal motor shaft.

Pump installed correctly in a vertical pipe. See fig. 7, pos. A.

Pump installed correctly in a horizontal pipe. See fig. 7, pos. B.

Do not install the pump with vertical motor shaft. See fig. 7, pos. C and D.

A B

C D

TM05 2866 0712

Fig. 7 Pump installed with horizontal motor shaft

4.3 Control box positions

To ensure adequate cooling, the control box must be in horizontal position with the Grundfos logo in vertical position. See fig. 8.

TM05 2915 0612

Fig. 8 Pump with control box in horizontal position

If the pump head is removed before the pump is installed in the pipework, pay special attention when fitting the pump head to the pump housing:

1.Gently lower the pump head with rotor shaft and impeller into the pump housing.

2.Make sure that the contact face of the pump housing and that of the pump head are in contact before the clamp is tightened. See fig. 9.

TM05 5837 4112

Fig. 9 Fitting the pump head to the pump housing

4.4 Pump head position

If the pump head is removed before the pump is installed in the pipework, pay special attention when fitting the pump head to the pump housing:

3.Visually check that the floating ring in the sealing system is centered. See figs. 10 and 11.

4.Gently lower the pump head with rotor shaft and impeller into the pump housing.

5.Make sure that the contact face of the pump housing and that of the pump head are in contact before the clamp is tightened. See fig. 12.

TM05 6650 5012

Fig. 10 Correctly centered sealing system

English (US)

9

(US) English

TM05 6651 5012

Fig. 11 Incorrectly centered sealing system

Observe the position of the clamp before the clamp is tightened. Incorrect position of the Caution clamp will cause leakage from the pump and

damage the hydraulic parts in the pump head. See fig. 12.

TM05 5837 4112

Fig. 12 Fitting the pump head to the pump housing

4.5 Changing the control box position

Warning

The warning symbol on the clamp holding the pump head and pump housing together indicates that there is a risk of personal injury. See specific warnings below.

Warning

When loosening the clamp, do not drop the pump head.

Warning

Risk of escaping vapor.

Step

Action

Illustration

 

 

 

 

 

 

 

 

 

 

Loosen the screw in the clamp

 

 

 

 

 

 

 

 

holding the pump head and pump

 

 

 

 

 

 

 

 

housing together.

0612

1

Warning: If the screw is loosened

 

too much, the pump head will be

2867

 

completely disconnected from the

 

 

 

 

 

 

 

TM05

 

pump housing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Carefully rotate the pump head to

0612

 

the desired position.

 

2868

2

If the pump head is stuck, loosen it

 

 

 

 

 

 

 

 

with a light blow of a rubber

 

 

 

 

 

 

TM05

 

mallet.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Position the control box in

0612

 

horizontal position so that the

3

Grundfos logo is in vertical

2869

 

position. The motor shaft must be

 

horizontal.

 

 

 

 

 

 

TM05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Due to the drain hole in the stator

 

 

 

 

 

 

 

4

housing, position the gap of the

 

 

 

 

 

 

 

clamp as shown in step 4a, 4b, 4c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM05 2870 0612

 

or 4d.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-head pump.

 

 

 

 

 

2871 0612

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM05

4a

Position the clamp so that the gap

 

 

 

 

 

 

-

points towards the arrow.

 

 

 

 

 

 

 

0612

 

 

 

 

 

 

 

 

It can be in position 3 or 9 o'clock.

 

 

 

 

 

 

 

 

 

 

 

 

 

TM05 2918

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Step

Action

Illustration

 

 

 

 

 

 

 

 

Single-head pump.

 

 

 

 

 

 

Note: The gap of the clamp can

 

 

 

 

 

 

also be in position 6 o'clock for the

 

 

 

 

 

 

1912

4b

following pump sizes:

 

MAGNA3 65-XX

2899

 

 

 

 

 

 

 

MAGNA3 80-XX

 

 

 

 

TM05

 

MAGNA3 100-XX.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Twin-head pump.

2873 0612

 

 

 

 

 

TM05-

 

Position the clamps so that the

 

 

 

 

 

 

 

 

 

 

4c

gaps point towards the arrows.

0612

 

They can be in position 3 or

 

 

 

 

 

 

 

9 o'clock.

 

 

 

 

TM05 2917

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Twin-head pump.

 

 

 

 

 

 

Note: The gap of the clamp can

 

 

 

 

 

 

also be in position 6 o'clock for the

1912

4d

following pump sizes:

 

MAGNA3 65-XX

2897

 

 

 

 

 

 

 

MAGNA3 80-XX

 

 

 

 

TM05

 

MAGNA3 100-XX.

 

 

 

 

 

Fit and tighten the screw holding

0612

6

the clamp to minimum

 

6 ± 0.7 ft-lbs (8 ± 1 Nm).

 

 

 

 

TM05 2872

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fit the insulating shells.

 

 

 

 

 

 

Note: For air conditioning and

 

 

 

 

 

 

cooling systems a silicone sealant

 

 

 

 

 

 

must be applied inside the

 

 

 

 

 

 

insulation shell to eliminate all air

 

 

 

 

 

7

gaps and prevent condensation

 

 

 

 

 

between the pump housing and

 

 

 

 

 

 

0412

 

insulation shell. Alternatively, the

 

 

 

 

 

 

 

pump may be insulated manually

2874

 

in accordance with standard

 

insulation practices for cooling

 

 

 

 

TM05

 

applications.

 

 

 

 

 

 

 

 

 

 

 

 

 

If insulating the pump manually, do not insulate

Caution

 

 

 

 

the control box or cover the control panel.

 

 

 

TM05 5549 3812

Fig. 13 Insulation of pump housing and pipework

5. Electrical installation

Carry out the electrical connection and protection according to local regulations.

Check that the supply voltage and frequency correspond to the values stated on the nameplate.

Warning

Never make any connections in the pump control box unless the power supply has been switched off for at least 5 minutes.

Warning

The pump must be connected to an external mains switch with a contact separation of at least 1/8 inch (3 mm) in each pole.

The ground terminal of the pump must be connected to ground. Grounding or neutralization can be used for protection against indirect contact.

If the pump is connected to an electric installation where a Ground Fault Circuit Interrupter (GFCI) is used as additional protection, this circuit interrupter must trip out when ground fault currents with DC content (pulsating DC) occur.

If rigid conduit is to be used, the hub must be connected to the conduit system before it is connected to the terminal box of the pump.

The pump must be connected to an external mains switch.

The pump requires no external motor protection.

The motor incorporates thermal protection against slow overloading and blocking.

When switched on via the power supply, the pump will start pumping after approx. 5 seconds.

Note

The number of starts and stops via the power

supply must not exceed four times per hour.

 

English (US)

11

(US) English

5.1 Supply voltage

1 x 115 V ± 10 %, 50/60 Hz, PE.

1 x 208-230 V ± 10 %, 50/60 Hz, PE.

See pump nameplate for rated supply voltage

The voltage tolerances are intended for mains voltage variations. They should not be used for running pumps at other voltages than those stated on the nameplate.

5.2Connection to the power supply (models 40-XX, 50-XX, 65-XX, 80-XX, 100-XX)

Step

Action

Illustration

 

 

 

 

Remove the front

0612

1

cover from the

2875TM05

 

control box.

 

 

 

 

 

 

Locate the power

 

 

supply plug and

 

2

conduit adapter in

0612

 

the box supplied

 

2876TM05

 

with the pump.

 

 

 

 

 

 

Connect the

 

3

conduit adapter to

 

 

the control box.

TM05 2877 0612

 

 

 

 

 

 

Pull the power

 

4

supply cable

 

through the

 

 

06122878TM05

 

conduit adapter.

 

 

 

 

 

 

Strip the cable

 

5

conductors as

 

 

illustrated.

TM05 5534 3812

 

 

 

 

 

Step Action

Illustration

Connect the cable conductors to the

6power supply plug. L - L or L1 Ground - Ground N - N or L2

Insert the power supply plug into

7the male plug in the pump control box.

Tighten the

8conduit adapter. Refit the front cover.

TM05 2880 0612

TM05 2881 0612

TM05 2882 0612

12

5.3 Connection to the power supply (models 32-XX)

Step

Action

Illustration

 

 

 

 

 

 

 

 

 

 

Remove two

 

 

 

 

 

 

 

 

screws.

 

 

 

 

 

 

 

 

Remove the front

1614

1

cover from the

 

 

 

 

 

 

 

 

control box and

1102

 

access the power

 

connection.

 

 

 

 

 

 

TM06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Locate the power

L (L1) N (L2)

 

 

16141103TM06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

plug inside.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connect the conduit to the control box.

3Pull the power supply cable through the conduit.

Strip the cable as illustrated.

Connect the cable

5conductors to the power supply plug. L - L or L1 Ground - Ground N - N or L2

Insert the power plug into its mating

6connector.

Tighten the conduit.

TM06 1104 1614

TM06 1105 1614

TM06 1106 1614

Step Action

Illustration

7Refit the front cover.

TM06 1107 1614

English (US)

13

(US)English

5.4 Connection diagram

External switch

 

 

GFCI

 

Fuse

 

(min. 10 A, time lag)

Fig. 14

Example of typical connection, 1 x 230 V ± 10 %, 50/60 Hz

 

 

Note

All cables used must be connected in accordance with local regulations.

5.4.1 Connection to external controllers

 

 

 

 

 

 

Analog input

 

 

 

 

 

24V

IN

 

 

 

 

 

Vcc

signal

 

 

 

 

 

sensor

 

 

 

 

 

M

M

NC NO C

NC NO C

 

 

 

A

I S/S

 

 

 

 

 

 

L

N

Mains

 

 

 

 

 

 

 

 

Alarm

 

 

connection

 

 

 

 

 

 

 

 

 

Operation

 

 

 

Start/

On/off timer

 

 

 

stop

 

 

 

 

Fig. 15 Example of connections in the control box

Warning

Wires connected to supply terminals, outputs NC, NO, C and start/stop input must be separated

from each other and from the supply by reinforced insulation.

Concerning demands on signal wires and signal transmitters, see section 19. Technical data.

Use screened cables for external on/off switch, digital input, sensor and setpoint signals.

Note

All cables used must be heat-resistant up to

+185 °F (+85 °C).

 

TM03 2397 0312

TM05 2673 3812

14

English (US)

TM05 8539 2413

Fig. 16 Wiring diagram, 32-XX versions

The connection terminals of 32-XX versions differ from those of terminal-connected versions, but they have the same function and connection options.

Use screened cables for external on/off switch, digital input, sensor and setpoint signals.

Connect screened cables to the ground connection as follows:

Terminal-connected versions:

Connect the cable screen to ground via the digital-input terminal (earth).

Plug-connected versions:

Connect the cable screen to ground via cable clamp.

 

Warning

 

Wires connected to supply terminals, outputs

 

NC, NO, C and start/stop input must be separated

 

from each other and from the supply by

 

reinforced insulation.

 

All cables used must be heat-resistant up to

 

+85 °C.

Note

All cables used must be installed in accordance

 

 

with EN 60204-1 and EN 50174-2:2000.

15

(US) English

5.5 Input/output communication

Relay outputs

Alarm, ready and operating indication via signal relay.

Digital input

Start/Stop (S/S)

Min. curve (MI)

Max. curve (MA).

Analog input

0-10 V or 4-20 mA control signal.

To be used for external control of the pump or as sensor input for the control of the external setpoint.

The 24 V supply from pump to sensor is optional and is normally used when an external supply is not available.

5.5.1 Relay outputs

See fig. 15, pos. 1.

The pump incorporates two signal relays with a potential-free changeover contact for external fault indication.

The function of the signal relay can be set to "Alarm", "Ready" or "Operation" on the pump control panel or with Grundfos GO Remote.

The relays can be used for outputs up to 250 V and 2 A.

Relay 1

 

Relay 2

 

 

 

 

 

 

 

 

 

 

 

 

NC NO C

 

NC NO C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The functions of the signal relays appear from the table below:

Signal relay

Alarm signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

The power supply has been switched off.

 

 

NC NO

C

C

 

The pump has not registered a fault.

 

NC NO

 

 

 

1

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The pump has registered a fault.

1

2

 

3

 

 

NC NO

 

C

 

 

Signal relay

Ready signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

• The pump has registered a fault and is

 

NC NO

C

C

 

 

unable to run.

 

 

NC NO

3

 

 

 

 

1

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Activated:

 

 

 

 

 

 

 

 

 

• The pump has been set to stop, but is ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to run.

1

2

 

3

 

 

NC NO

 

C

The pump is running.

 

 

 

 

 

 

 

 

 

 

 

Signal relay

Operating signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

3

 

The pump is not running.

 

1

2

3

 

 

 

 

 

 

 

NC NO

C

 

 

 

 

 

 

NC NO

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The pump is running.

1

2

 

3

 

 

NC NO

 

C

 

 

Alarm

Operation

Fig. 17 Relay output

TM05 3338 1212

Contact symbol

Function

 

 

NC

Normally closed

NO

Normally open

C

Common

16

5.5.2 Digital inputs

See fig. 15, pos. 2.

The digital input can be used for external control of start/stop or forced max. or min. curve.

If no external on/off switch is connected, the jumper between terminals Start/Stop (S/S) and frame () should be maintained. This connection is the factory setting.

MM

A I S/S

On/off timer

Start/stop

TM05 3339 1212

Fig. 18 Digital input

Contact symbol

Function

 

 

 

M

Max. curve

A

100 % speed

M

Min. curve

I

25 % speed

S/S

Start/Stop

 

 

Frame connection

 

 

 

 

 

External start/stop

The pump can be started or stopped via the digital input.

Start/stop

 

 

 

S/S

H

 

 

Normal duty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Factory setting with

 

 

 

 

 

 

 

 

Q jumper between S/S and

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S/S

H

 

 

Stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External forced max. or min. curve

The pump can be forced to operate on the max. or min. curve via the digital input.

Max. curve

M H

A

Normal duty

Q

M H

A

Max. curve

Q

Min. curve

MH

I

Normal duty

Q

M H

I

Min. curve

Q

Select the function of the digital input on the pump control panel or with Grundfos GO Remote.

English (US)

17

(US) English

5.6 Analog input for external sensor

The analog input can be used for the connection of an external sensor for measuring temperature or pressure.

The analog input can also be used for an external signal for the control from a BMS system or similar control system.

The electrical signal for the input can be 0-10 VDC or 4-20 mA.

The selection of electrical signal (0-10 V or 4-20 mA) can be changed on the control panel or with Grundfos GO Remote.

24V

 

 

 

IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1112

Vcc

 

 

 

signal

3221

 

 

 

 

 

 

 

 

 

 

TM05

 

 

sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 19 Analog input for external sensor or control

In order to optimize the pump performance, external sensors can advantageously be used in the following cases:

Function/control mode

Sensor type

 

 

 

 

 

Heat energy meter

Temperature sensor

Constant temperature

Temperature sensor

Differential pressure

Pressure sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- +

Sensor

 

 

 

 

 

 

 

 

 

TM06 0882 1114

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor

Fig. 20

Wiring, analog input

 

 

 

 

 

 

 

 

 

 

 

 

PIN

Description

 

Load

 

 

 

 

 

 

 

 

 

 

IN

Analog input

150 Ω (4-20 mA signal)

78 kΩ (0-10 V signal)

 

 

 

 

 

 

 

 

24 V 24 V supply to external sensor

 

Max. 22 mA

Ground for external sensor

1

24V IN

Vcc

Signal

2

TM05 2947 1212

Fig. 21 Examples of external sensors

Pos. Sensor type

Differential pressure transmitter,

1Grundfos type DPI V.2

1/2" connection and 4-20 mA signal. Relative pressure transmitter,

2combined pressure and temperature sensor, Grundfos type RPI/T G 1/2" connection and 4-20 mA signal.

For further details, visit WebCAPS and reference Magna3 Data booklet 98439208.

BMS

PLC

24V

TM05 2888 0612

Fig. 22 Example of external signal for the control via BMS or PLC

18

5.7 Electrical connection for external sensor

 

 

 

 

2

 

 

 

 

1

 

 

 

 

4

 

 

 

 

7156TM041610

 

 

 

 

3

Fig. 23 Example electrical connections for external sensor

PIN

1

2

3

4

Wire color

Brown

Grey

Blue

Black

Output

+

not used

-

not used

4 to 20 mA

 

 

 

 

Output

+

Pressure

-*

Temperature

2 x 0 to 10 V

signal

signal

 

 

*Common ground for both pressure and temperature signal.

*Power supply (screened cable): SELV or PELV.

5.8 Priority of settings

The external forced-control signals will influence the settings available on the pump control panel or with Grundfos GO Remote. However, the pump can always be set to max. curve duty or to stop on the pump control panel or with Grundfos GO Remote.

If two or more functions are enabled at the same time, the pump will operate according to the setting with the highest priority.

The priority of the settings is as shown in the table below.

Example: If the pump has been forced to stop via an external signal, the pump control panel or Grundfos GO Remote can only set the pump to max. curve.

 

 

Possible settings

 

 

 

 

 

Priority

Pump control

External

 

panel or

Bus signal

 

 

Grundfos GO

signals

 

 

 

Remote

 

 

 

 

 

 

1

Stop

 

 

2

Max. curve

 

 

3

 

Stop

 

4

 

 

Stop

5

 

 

Max. curve

6

 

 

Min. curve

7

 

 

Start

8

 

Max. curve

 

9

Min. curve

 

 

10

 

Min. curve

 

11

Start

 

 

As illustrated in the table, the pump does not react to external signals (max. curve and min. curve) when it is controlled via bus.

For further details, please contact Grundfos.

English (US)

19

English

6. First start-up

 

Do not start the pump until the system has been filled with liquid

 

 

 

 

and vented. Furthermore, the required minimum inlet pressure

 

(US)

must be available at the pump inlet. See section 19. Technical

 

data.

 

 

 

 

 

 

The system cannot be vented through the pump. The pump is

 

 

self-venting.

 

 

 

Step

Action

Illustration

Switch on the power supply to the pump.

1Note: When switched on, the pump will start in AUTOADAPT after approx. 5 seconds.

Pump display at first start-up.

2After a few seconds, the pump display will change to the start-up guide.

The start-up guide will guide you through the general settings of the pump, such as language, date and time.

3If the buttons on the pump control panel are not touched for 15 minutes, the display will go into sleep mode.

When a button is touched, the "Home" display will appear.

When the general settings have been made, select the

4desired control mode or let the pump run in AUTOADAPT. For additional settings, see section 7. Settings.

TM05 2884 0612

TM05 2885 0612

TM05 2886 0612

TM05 2887 0612

20

7. Settings

7.1 Overview of settings

All settings can be made on the pump control panel or with Grundfos GO Remote.

Menu

Submenu

Further information

 

 

 

 

Setpoint

 

 

See section 13.1 Setpoint.

 

 

 

 

Operating mode

 

 

See section 13.2 Operating mode.

 

Normal

 

 

Stop

 

 

Min.

 

 

Max.

 

Control mode

 

 

See section 13.3 Control mode.

 

AUTOADAPT

See section 13.3.1 AUTOADAPT.

 

FLOWADAPT

See section 13.3.2 FLOWADAPT.

 

Prop. press.

See section 13.3.3 Proportional pressure.

 

Const. press.

See section 13.3.4 Constant pressure.

 

Const. temp.

See section 13.3.5 Constant temperature.

 

Differential temperature

See section 13.3.6 Differential temperature.

 

Constant curve

See section 13.3.7 Constant curve.

FLOWLIMIT

 

 

See section 13.4 FLOWLIMIT.

 

Set FLOWLIMIT

 

Automatic Night Setback

 

 

See section 13.5 Automatic Night Setback.

 

Not active

 

 

Active

 

Relay outputs

 

 

See section 13.6 Relay outputs.

 

Relay output 1

 

 

Relay output 2

 

Setpoint influence

 

 

See section 13.7 Setpoint influence.

 

External setpoint function

See section 13.7.1 External setpoint function.

 

Temperature influence

See section 13.7.2 Temperature influence.

Bus communication

 

 

See section 13.8 Bus communication.

 

Pump number

See section 13.8.1 Pump number.

General settings

 

 

See section 13.9 General settings.

 

Language

See section 13.9.1 Language.

 

Set date and time

See section 13.9.2 Set date and time.

 

Units

See section 13.9.3 Units.

 

Enable/disable settings

See section 13.9.4 Enable/disable settings.

 

Delete history

See section 13.9.5 Delete history.

 

Define Home display

See section 13.9.6 Define Home display.

 

Display brightness

See section 13.9.7 Display brightness.

 

Return to factory settings

See section 13.9.8 Return to factory settings.

 

Run start-up guide

See section 13.9.9 Run start-up guide.

English (US)

21

(US) English

8. Menu overview

Status

Settings

Assist

Operating status

Setpoint

Assisted pump setup

Operating mode, from

Operating mode

Setting of pump

Control mode

Control mode

Setting of date and time

Pump performance

FLOWLIMIT

Date format, date and time

Max. curve and duty point

Enable FLOWLIMIT function

Date only

Resulting setpoint

Set FLOWLIMIT

Time only

Liquid temperature

Automatic Night Setback

Multi-pump setup

Speed

Relay outputs

Setup, analog input

Operating hours

Relay output 1

Description of control mode

Power and energy consumption

Relay output 2

AUTOADAPT

Power consumption

Not active

FLOWADAPT

Energy consumption

Ready

Prop. press.

Warning and alarm

Alarm

Const. press.

Actual warning or alarm

Operation

Const. temp.

Warning log

Setpoint influence

Differential temperature

Warning log 1 to 5

External setpoint function

Constant curve

Alarm log

Temperature influence

Assisted fault advice

Alarm log 1 to 5

Bus communication

Blocked pump

Heat energy meter

Pump number

Pump communication fault

Heat power

General settings

Internal fault

Heat energy

Language

Internal sensor fault

Flow rate

Set date and time

Dry running

Volume

Select date format

Forced pumping

Hours counter

Set date

Undervoltage

Temperature 1

Select time format

Overvoltage

Temperature 2

Set time

External sensor fault

Differential temp.

Units

 

Work log

SI or US units

 

Operating hours

Customized units

 

Trend data

Pressure

 

Duty point over time

Differential pressure

 

3D showing (Q, H, t)

Head

 

3D showing (Q, T, t)

Level

 

3D showing (Q, P, t)

Flow rate

 

3D showing (T, P, t)

Volume

 

Fitted modules

Temperature

 

Date and time

Differential temp.

 

Date

Power

 

Time

Energy

 

Pump identification

Enable/disable settings

 

Multi-pump system

Delete history

 

Operating status

Delete work log

 

Operating mode, from

Delete heat energy data

 

Control mode

Delete energy consumption

 

System performance

Define Home display

 

Duty point

Select Home display type

 

Resulting setpoint

List of data

 

System identification

Graphical illustration

 

Power and energy consumption

Define Home display contents

 

Power consumption

List of data

 

Energy consumption

Graphical illustration

 

Other pump 1, multi-pump sys.

Display brightness

 

 

Brightness

 

 

Return to factory settings

 

 

Run start-up guide

 

22

9. Control panel

Warning

At high liquid temperatures, the pump housing may be very hot. In that case, only touch the control panel.

TM05 7642 1313

Fig. 24 Control panel

Button Function

Goes to the "Home" menu.

Returns to the previous action.

Navigates between main menus, displays and digits.

When the menu is changed, the display will always show the top display of the new menu.

Navigates between submenus.

Saves changed values, resets alarms and expands the value field.

10. Menu structure

The pump incorporates a start-up guide which is started at the first start-up. After the start-up guide, the four main menus will appear in the display. See section 6. First start-up.

1. Home

This menu shows up to four user-defined parameters with shortcuts or a graphical illustration of a Q/H performance curve. See section 11. "Home" menu.

2. Status

This menu shows the status of the pump and system as well as warnings and alarms. See section 12. "Status" menu.

Note

No settings can be made in this menu.

3. Settings

This menu gives access to all setting parameters. A detailed setting of the pump can be made in this menu.

See section 13. "Settings" menu.

4. Assist

This menu enables assisted pump setup, provides a short description of the control modes and offers fault advice.

See section 14. "Assist" menu.

11. "Home" menu

TM05 7929 1613

Navigation

Home

Press to go to the "Home" menu.

"Home" menu (factory setting)

Shortcut to control mode settings

Shortcut to setpoint settings

Flow rate

Head.

Navigate in the display with or and change between the two shortcuts with or .

The "Home" display can be defined by the user. See section 13.9.6 Define Home display.

English (US)

23

(US) English

12. "Status" menu

13. "Settings" menu

 

2.1.0.0.0.0 Status

 

3.1.0.0.0.0 Settings

Navigation

Navigation

Home > Status

Home > Settings

Press and go to the "Status" menu with .

Press and go to the "Settings" menu with .

"Status" menu

"Settings" menu

This menu offers the following status information:

This menu offers the following setting options:

Operating status

Setpoint

Pump performance

Operating mode

• Power and energy consumption

Control mode

Warning and alarm

FLOWLIMIT

Heat energy meter

Automatic Night Setback

Work log

Relay outputs

Fitted modules

Setpoint influence

Date and time

Bus communication

Pump identification

General settings.

Multi-pump system.

Navigate between submenus with or .

Navigate between submenus with or .

13.1 Setpoint

 

 

TM05 7925 1613

Navigation

Home > Settings > Setpoint

Setpoint

Set the setpoint so that it matches the system.

Setting:

1.Press [OK] to start the setting.

2.Select digit with and and adjust with or .

3.Press [OK] to save.

A too high setting may result in noise in the system whereas a too low setting may result in insufficient heating or cooling in the system.

Control mode

Measuring unit

 

 

Proportional pressure

m, ft

Constant pressure

m, ft

Constant temperature

°C, °F, K

Constant curve

%

24

13.2 Operating mode

13.3 Control mode

3.1.2.0.0.0 Operating mode

Navigation

Home > Settings > Operating mode

Operating mode

Normal (control mode)

Stop

Min. (min. curve)

Max. (max. curve). Setting:

1. Select operating mode with or .

2. Press [OK] to save.

The pump can be set to operate according to the max. or min. curve, like an uncontrolled pump. See fig. 25.

H

Max.

Min.

5111

TM05 2446

 

Q

 

Fig. 25 Max. and min. curves

Normal: The pump runs according to the selected control mode.

Stop: The pump stops.

Min.: The min. curve mode can be used in periods in which a minimum flow is required.

This operating mode is for instance suitable for manual night setback if Automatic Night Setback is not desired.

Max.: The max. curve mode can be used in periods in which a maximum flow is required.

This operating mode is for instance suitable for hot-water priority.

3.1.3.0.0.0 Control mode

Navigation

Home > Settings > Control mode

Control mode

AUTOADAPT

FLOWADAPT

Prop. press. (proportional pressure)

Const. press. (constant pressure)

Const. temp.(constant temperature)

Constant curve.

 

The operating mode must be set to "Normal"

Note

before a control mode can be enabled.

 

Setting:

1. Select control mode with or .

2. Press [OK] to enable.

The setpoint for all control modes, except AUTOADAPT and FLOWADAPT, can be changed in the "Setpoint" submenu under "Settings" when the desired control mode has been selected.

All control modes, except "Constant curve", can be combined with Automatic Night Setback. See section 13.5 Automatic Night Setback.

The FLOWLIMIT function can also be combined with the last five control modes mentioned above. See section 13.4 FLOWLIMIT.

English (US)

25

(US) English

13.3.1 AUTOADAPT

The AUTOADAPT control mode continuously adapts the pump performance according to the actual system characteristic.

Note

Manual setting of the setpoint is not possible.

 

H

 

 

 

 

Hfac

Hset1

 

 

 

A1

 

 

 

Hauto_min

A2

Hset2

1312

 

A3

TM05 2452

 

 

 

Q

Fig. 26

AUTOADAPT

 

 

 

When the AUTOADAPT control mode has been enabled, the pump will start with the factory setting, Hfac = Hset1, corresponding to

approx. 55 % of its maximum head, and then adjust its performance to A1. See fig. 26.

When the pump registers a lower head on the max. curve, A2, the AUTOADAPT function will automatically select a correspondingly lower control curve, Hset2. If the valves in the system close, the pump will adjust its performance to A3.

A1: Original duty point.

A2: Lower registered head on the max. curve.

A3: New duty point after AUTOADAPT control. Hset1: Original setpoint setting.

Hset2: New setpoint after AUTOADAPT control. Hfac.: MAGNA3 xx-60: 11.4 ft (3.5 m)

MAGNA3 xx-80: 14.7 ft (4.5 m) MAGNA3 xx-100: 18 ft (5.5 m) MAGNA3 xx-120: 21.3 ft (6.5 m) MAGNA3 xx-150: 26.2 ft (8.0 m) MAGNA3 xx-180: 31.1 ft (9.5 m).

Hauto_min: A fixed value of 4.9 ft (1.5 m).

The AUTOADAPT control mode is a form of proportional-pressure control where the control curves have a fixed origin, Hauto_min.

The AUTOADAPT control mode has been developed specifically for heating systems and is not recommended for air-conditioning

and cooling systems.

To reset AUTOADAPT, see section 13.9.8 Return to factory settings.

13.3.2 FLOWADAPT

When FLOWADAPT is selected, the pump will run AUTOADAPT and ensure that the flow never exceeds the entered FLOWLIMIT value.

The setting range for the FLOWLIMIT is 25 to 90 % of the Qmax of the pump.

The factory setting of the FLOWLIMIT is the flow where the AUTOADAPT factory setting meets the max. curve. See fig. 27.

 

H

90 % Qmax

 

 

Setting range

 

 

 

Hfac

 

 

Hauto_min

 

12123334

 

 

 

Qfac

Q

TM05

 

 

Fig. 27

FLOWADAPT

 

 

13.3.3 Proportional pressure

The pump head is reduced at decreasing water demand and increased at rising water demand. See fig. 28.

 

H

 

 

 

 

 

 

 

 

Hset

 

 

 

 

Hset

 

 

 

1212

 

 

 

2448

 

2

 

 

 

 

 

 

 

 

 

Q

TM05

 

 

 

 

 

Fig. 28 Proportional pressure

26

13.3.4 Constant pressure

The pump maintains a constant pressure, irrespective of water demand. See fig. 29.

H

Q

TM05 2449 0312

Fig. 29 Constant pressure

13.3.5 Constant temperature

This control mode ensures a constant temperature.

Constant temperature is a comfort control mode that can be used in domestic hot-water systems to control the flow to maintain a fixed temperature in the system. See fig. 30. When this control mode is used, no balancing valves must be installed in the system.

If the pump is installed in the return pipe of the system, the internal temperature sensor can be used. In this case, the pump must be installed as close as possible to the consumer (radiator, heat exchanger, etc.).

If the pump is installed in the flow pipe, an external temperature sensor must be installed in the return pipe of the system.

The sensor must be installed as close as possible to the consumer (radiator, heat exchanger, etc.).

The constant-temperature control mode also reduces the risk of bacterial growth (for example Legionella) in the system.

It is possible to set the sensor range:

min. +14 °F (-10 °C)

max. +266 °F (+130 °C).

To ensure that the pump is able to control, we Note recommend to set the sensor range between

+3 °F and +257 °F (-5 and +125 °C).

H

Q

TM05 2451 5111

Fig. 30 Constant temperature

13.3.6 Differential temperature

This control mode ensures a constant differential temperature drop across a heating system.

The pump should be installed in the flow pipe so the built-in sensor measures the liquid temperature going out to the load. An external temperature sensor must be installed in the system to measure the liquid temperature returning from the heating load. In this mode, the pump will maintain a constant temperature. See figs 31 and 32, differential between the pump and the external sensor.

H

t

Q

TM05 2451 5111

Fig. 31 Differential temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2113

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

TM05 8236

Fig. 32

Differential temperature

 

 

Changing Kp and Ti values are only possible with

Note

 

 

 

Grundfos GO.

 

 

Changing the Kp and Ti values will affect all control modes. If the control mode is to be

Note changed back to another mode you must set the Kp and Ti values back to default values. For all

other modes the default values are Kp = 0.5, Ti = 0.5.

English (US)

27

(US) English

See table, fig. 33.

The table shows the suggested controller settings:

 

 

Kp

 

System/application

Heating

Cooling

Ti

 

system1)

system2)

 

t

0.5

- 0.5

10 + 5L2

 

 

 

L2 [m]

 

 

 

t

 

-0.5

10 + 5L2

L2 [m]

 

 

 

L2 [m]

 

 

 

t

0.5

- 0.5

30 + 5L2

Fig. 33 Suggested controller settings

1)Heating systems are systems in which an increase in pump performance will result in a rise in temperature at the sensor.

2)Cooling systems are systems in which an increase in pump performance will result in a drop in temperature at the sensor.

L2 = Distance in [m] between heat exchanger and sensor.

Proceed as follows:

1.Increase the gain (Kp) until the motor becomes unstable. Instability can be seen by observing if the measured value starts to fluctuate. Furthermore, instability is audible as the motor starts hunting up and down.

Some systems, such as temperature controls, are slow-reacting, meaning that it may be several minutes before the motor becomes unstable.

2.Set the gain (Kp) to half the value of the value which made the motor unstable. This is the correct setting of the gain.

3.Reduce the integral time (Ti) until the motor becomes unstable.

4.Set the integral time (Ti) to twice the value which made the motor unstable. This is the correct setting of the integral time.

General rules of thumb:

If the controller is too slow-reacting, increase Kp.

If the controller is hunting or unstable, dampen the system by reducing Kp or increasing Ti.

13.3.7 Constant curve

The pump can be set to operate according to a constant curve, like an uncontrolled pump. See fig. 34.

The desired speed can be set in % of maximum speed in the range from 25 to 100 %.

H

Q

TM05 2446 0312

Fig. 34 Constant curve

Depending on the system characteristic and the duty point, the 100 % setting may be slightly smaller than the pump's actual max. curve even

Note though the display shows 100 %. This is due to power and pressure limitations built into the pump. The deviation varies according to pump type and pressure loss in the pipes.

H [%]

100 %

Limited max. curve

Max. curve

 

Actual duty point

TM05 3041 1212

Q [m3/h]

Fig. 35 Power and pressure limitations influencing the max. curve

28

13.4 FLOWLIMIT

3.1.5.0.0.0 FLOWLIMIT

Navigation

Home > Settings > FLOWLIMIT

FLOWLIMIT

Enable FLOWLIMIT function

Set FLOWLIMIT.

Setting:

1. To enable the function, select "Active" with or and press [OK].

2. To set the FLOWLIMIT, press [OK] to start the setting. 3. Select digit with and and adjust with or .

4. Press [OK] to save.

H

90 % Qmax

 

Setting range

 

 

 

Q

2445 1212

Qlimit

TM05

 

Fig. 36 FLOWLIMIT

The FLOWLIMIT function can be combined with the following control modes:

Prop. press.

Const. press.

Const. temp.

Constant curve.

A flow-limiting function ensures that the flow never exceeds the entered FLOWLIMIT value.

The setting range for FLOWLIMIT is 25 to 90 % of the Qmax of the pump.

The factory setting of the FLOWLIMIT is the flow where the AUTOADAPT factory setting meets the max. curve. See fig. 27.

13.5 Automatic Night Setback

English (US)

Night Setback

3.1.6.0.0.0 Automatic

 

Navigation

Home > Settings > Automatic Night Setback

Automatic Night Setback

To enable the function, select "Active" with or and press [OK].

Once Automatic Night Setback has been enabled, the pump automatically changes between normal duty and night setback (duty at low performance).

Changeover between normal duty and night setback depends on the flow-pipe temperature.

The pump automatically changes over to night setback when the built-in sensor registers a flow-pipe temperature drop of more than +18 to +27 °F (-8 to -3 °C) within approx. two hours.

The temperature drop must be at least 0.18 °F/min (0.1 °C/min).

Changeover to normal duty takes place without a time lag when the temperature has increased by approx. +18 °F (-8 °C).

 

Automatic Night Setback cannot be enabled

Note

when the pump is in constant-curve mode.

 

29

(US) English

13.6 Relay outputs

13.7 Setpoint influence

3.1.12.0.0.0 Relay outputs

Navigation

Home > Settings > Relay outputs

Relay outputs

Relay output 1

Relay output 2.

The relay outputs can be set to the following:

Not active

Ready

Alarm

Operation.

The pump incorporates two signal relays, terminals 1, 2 and 3, for a potential-free alarm signal, ready signal and operating signal. For further information, see section 5.5.1 Relay outputs.

Set the function of the signal relays, alarm signal (factory setting), ready signal and operating signal, on the pump control panel.

The output, terminals 1, 2 and 3, is electrically separated from the rest of the controller.

The signal relay is operated as follows:

Not active

The signal relay is deactivated.

Ready

The signal relay is active when the pump is running or has been set to stop, but is ready to run.

Alarm

The signal relay is activated together with the red indicator light on the pump.

Operation

The signal relay is activated together with the green indicator light on the pump.

3.1.15.0.0.0 Setpoint influence

Navigation

Home > Settings > Setpoint influence

Setpoint influence

External setpoint function

Temperature influence.

13.7.1 External setpoint function

Range

4-20 mA

[0-100 %]

 

0-10 V

[0-100 %]

 

Control

 

 

 

 

 

0-20 %

(e.g. 0-2 V)

Setpoint = Min.

20-100 %

(e.g. 2-10 V)

Setpoint = Min. ↔ setpoint

The external setpoint function is an external 0-10 V or 4-20 mA signal that will control the pump speed in a range from 0 to 100 % in a linear function. See fig. 37.

 

Before the "External setpoint function" can be

Note

enabled, the analog input must be set to "External

setpoint influence" via the "Assist" menu.

 

See section 5.6 Analog input for external sensor.

 

rpm

 

 

 

 

 

Max.

 

 

 

 

 

Min.

 

 

 

1212

 

0

2

10

 

3219

 

V

TM05

 

 

 

 

 

Fig. 37

External setpoint function, 0-10 V

 

 

 

30

Loading...
+ 106 hidden pages