Grundfos MAGNA3 User Manual

4.4 (10)
Grundfos MAGNA3 User Manual

GRUNDFOS INSTRUCTIONS

MAGNA3

Installation and operating instructions

(US) English

English (US) Installation and operating instructions

Original installation and operating instructions.

CONTENTS

1.Limited warranty

2.Symbols used in this document

3.General information

3.1Applications

3.2Pumped liquids

3.3Operating conditions

3.4Frost protection

3.5Insulating shells

3.6Non-return valve

3.7Nameplate

3.8Radio communication

3.9Tools

4.Mechanical installation

4.1Installing the pump

4.2Positioning

4.3Control box positions

4.4Changing the control box position

5.Electrical installation

5.1Supply voltage

5.2Connection to the power supply

5.3Connection diagram

5.4Connection to external controllers

5.5Input/output communication

5.6Priority of settings

6.First start-up

7.Settings

7.1Overview of settings

8.Menu overview

9.Control panel

10.Menu structure

11."Home" menu

12."Status" menu

13."Settings" menu

13.1Setpoint

13.2Operating mode

13.3Control mode

13.4FLOWLIMIT

13.5Automatic Night Setback

13.6Relay outputs

13.7Setpoint influence

13.8Bus communication

13.9General settings

14."Assist" menu

14.1Assisted pump setup

14.2Setting of date and time

14.3Multi-pump setup

14.4Setup, analog input

14.5Description of control mode

14.6Assisted fault advice

14.7Wireless GENIair

14.8Multi-pump function

15.Selection of control mode

16.Fault finding

16.1Grundfos Eye operating indications

16.2Signalling communication with remote control

16.3Fault finding

17.Sensor

17.1Sensor specifications

 

18.

Accessories

34

 

18.1

Grundfos GO Remote

34

 

18.2

Communication

34

Page

18.3

Fitting the CIM module

35

2

19.

Technical data

36

3

20.

Disposal

36

3

 

 

 

3

 

Warning

 

3

 

Prior to installation, read these installation and

 

4

 

 

 

operating instructions. Installation and operation

4

 

 

must comply with local regulations and accepted

4

 

 

codes of good practice.

 

4

 

 

 

5

 

Warning

 

6

 

The use of this product requires experience with

6

 

and knowledge of the product.

 

6

 

Persons with reduced physical, sensory or

 

6

 

mental capabilities must not use this product,

 

7

 

unless they are under supervision or have been

7

 

instructed in the use of the product by a person

8

 

responsible for their safety.

 

9

 

Children must not use or play with this product.

 

 

 

9

1. Limited warranty

 

9

 

11

Products manufactured by GRUNDFOS PUMPS CORPORATION

11

(Grundfos) are warranted to the original user only to be free of

 

11

defects in material and workmanship for a period of 24 months

 

14

from date of installation, but not more than 30 months from date

15

of manufacture. Grundfos' liability under this warranty shall be

 

16

limited to repairing or replacing at Grundfos' option, without

 

charge, F.O.B. Grundfos' factory or authorized service station,

 

16

 

any product of Grundfos' manufacture. Grundfos will not be liable

17

for any costs of removal, installation, transportation, or any other

18

charges which may arise in connection with a warranty claim.

 

18

Products which are sold but not manufactured by Grundfos are

 

18

subject to the warranty provided by the manufacturer of said

 

18

products and not by Grundfos' warranty. Grundfos will not be

 

liable for damage or wear to products caused by abnormal

 

19

 

operating conditions, accident, abuse, misuse, unauthorized

 

19

 

alteration or repair, or if the product was not installed in

 

19

 

accordance with Grundfos' printed installation and operating

 

20

 

instructions.

 

23

 

To obtain service under this warranty, the defective product must

23

be returned to the distributor or dealer of Grundfos' products from

23

which it was purchased together with proof of purchase and

 

24

 

installation date, failure date, and supporting installation data.

 

25

 

Unless otherwise provided, the distributor or dealer will contact

 

25

 

Grundfos or an authorized service station for instructions. Any

 

27

defective product to be returned to Grundfos or a service station

27

must be sent freight prepaid; documentation supporting the war-

27

ranty claim and/or a Return Material Authorization must be

 

27

included if so instructed.

 

27

GRUNDFOS WILL NOT BE LIABLE FOR ANY

 

27

 

INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR

27

EXPENSES ARISING FROM INSTALLATION, USE, OR ANY

 

27

OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED

 

28

WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS

29

FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND

 

31

THOSE WARRANTIES DESCRIBED OR REFERRED TO

 

31

ABOVE.

 

 

31

Some jurisdictions do not allow the exclusion or

 

32

limitation of incidental or consequential damages and some juris-

33

dictions do not allow limit actions on how long implied warranties

may last. Therefore, the above limitations or exclusions may not

33

2

apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction.

2. Symbols used in this document

Warning

If these safety instructions are not observed, it may result in personal injury.

Warning

If these instructions are not observed, it may lead to electric shock with consequent risk of serious personal injury or death.

Warning

The surface of the product may be so hot that it may cause burns or personal injury.

Warning

Risk of dropping objects which may cause personal injury.

Warning

Escaping vapor involves the risk of personal injury.

If these safety instructions are not observed,

Caution it may result in malfunction or damage to the

 

equipment.

Note

Notes or instructions that make the job easier

and ensure safe operation.

 

3. General information

The Grundfos MAGNA3 is a complete range of circulator pumps with integrated controller enabling adjustment of pump performance to the actual system requirements. In many systems, this will reduce the power consumption considerably, reduce noise from thermostatic radiator valves and similar fittings and improve the control of the system.

The desired head can be set on the pump control panel.

3.1 Applications

The Grundfos MAGNA3 is designed for circulating liquids in the following systems:

heating systems

domestic hot-water systems

air-conditioning and cooling systems.

The pump can also be used in the following systems:

ground source heat pump systems

solar-heating systems.

3.2 Pumped liquids

The pump is suitable for thin, clean, non-aggressive and non-explosive liquids, not containing solid particles or fibers that may attack the pump mechanically or chemically.

In heating systems, the water should meet the requirements of accepted standards on water quality in heating systems.

In domestic hot-water systems, we recommend to use MAGNA3 pumps only for water with a degree of hardness lower than approx. 14 °dH.

In domestic hot-water systems, we recommend to keep the liquid temperature below 150 °F (+65 °C) to eliminate the risk of lime precipitation.

Warning

Do not use the pump for flammable liquids, such as diesel oil and gasoline.

Warning

Do not use the pump for aggressive liquids, such as acids and sea water.

Max. 95 % RH

Enclosure Type 2

TM05 2857 0612

Fig. 1 Pumped liquids

3.2.1 Glycol

The pump can be used for pumping water/ethylene glycol mixtures up to 50 %.

Maximum viscosity: 50 cSt ~ 50 % water / 50 % ethylene glycol mixture at +14 °F (-10 °C).

The pump has a power-limiting function that protects against overload.

The pumping of glycol mixtures will affect the max. curve and reduce the performance, depending on the water/ethylene glycol mixture and the liquid temperature.

To prevent the ethylene glycol mixture from degrading, avoid temperatures exceeding the rated liquid temperature and minimize the operating time at high temperatures.

It is important to clean and flush the system before the ethylene glycol mixture is added.

To prevent corrosion or lime precipitation, check and maintain the ethylene glycol mixture regularly. If further dilution of the supplied ethylene glycol is required, follow the glycol supplier's instructions.

Additives with a density and/or kinematic Note viscosity higher than those/that of water will

reduce the hydraulic performance.

English (US)

3

(US) English

3.3 Operating conditions

 

Min./Max.

 

1 +14 °F – 230 °F

 

 

(-10 °C – +110 °C)

 

2

175 psi (12 bar)

 

3

+32 to +104 °F

 

(0 to +40 °C)

 

4

<43 dB(A)

1413

 

 

TM05 7662

Fig. 2 Operating conditions

3.3.1Liquid temperature

See fig. 2, pos. 1.

Continuously: +14 °F to +230 °F (-10 °C to +110 °C). Domestic hot-water systems:

• Up to +150 °F (+65 °C).

3.3.2System pressure

See fig. 2, pos. 2.

The maximum permissible system pressure is stated on the pump nameplate.

3.3.3 Ambient temperature

See fig. 2, pos. 3.

+32 °F to +104 °F (0 °C to +40 °C).

The control box is air-cooled. Therefore, it is important that the maximum permissible ambient temperature is not exceeded during operation.

During transport: -40 °F to +158 °F (-40 °C to +70 °C).

3.3.4Sound pressure level

See fig. 2, pos. 4.

The sound pressure level of the pump is lower than 43 dB(A).

3.3.5Approvals

Conforms to ANSI/UL Standard 778.

Certified to CAN/CSA Standard C22.2 No. 108.

• The protective earth (ground) symbol identifies any terminal which is intended for connection to an external conductor for protection against electrical shock in case of a fault, or the terminal of a protective earth (ground) electrode.

3.4 Frost protection

If the pump is not used during periods of frost, Caution necessary steps must be taken to prevent frost

bursts.

Additives with a density and/or kinematic Note viscosity higher than those/that of water will

reduce the hydraulic performance.

3.5 Insulating shells

Insulating shells are available for single-head pumps only.

Note

Limit the heat loss from the pump housing and

pipework.

 

The heat loss from the pump and pipework can be reduced by insulating the pump housing and the pipework. See fig. 3 and fig. 10.

Insulating shells for pumps in heating systems are supplied with the pump; see fig. 3.

For pumps in air-conditioning and cooling systems

(down to +14 ° (-10 °C)) it is required to apply a silicon sealant to the internal contours of the shell in order to eliminate any air gaps and prevent condensation between the insulation shell and pump housing. Alternatively, the pump can also be insulated manually in accordance with standard insulating requirements for heating and cooling systems (fig. 10).

The fitting of insulating shells will increase the pump dimensions.

TM05 2859 0612

Fig. 3 Fitting insulating shells to the pump

 

Do not insulate the control box or cover the

Caution

 

control panel.

 

3.6 Non-return valve

If a non-return valve is fitted in the pipe system (fig. 4), it must be ensured that the set minimum discharge pressure of the pump is always higher than the closing pressure of the valve. This is especially important in proportional-pressure control mode (reduced head at low flow). The closing pressure of a single non-return valve is accounted for in the pump settings as the minimum head delivered is 5 ft (1.5 m).

TM05 3055 0912

Fig. 4 Non-return valve

4

3.7 Nameplate

The pump nameplate provides the following information:

TYPE 2

PSI

BOITIER DE TYPE 2

THERMALLY PROTECTED

 

Nonsubmersible Pump

 

 

For use with maximum 230° F water

 

 

 

 

 

 

 

 

RISK OF ELECTRIC SHOCK. DE-ENERGIZE EQUIPMENT BEFORE REMOVAL OF COVER & SERVICING. FOR SUPPLY

4612

 

 

 

 

 

 

 

 

CONNECTION USE COPPER WIRE SUITABLE FOR 90 °C OR EQUIVALENT. THIS PUMP HAS NOT BEEN INVESTIGATED FOR USE

 

 

 

 

 

 

 

 

IN SWIMMING POOL OR MARINE AREAS. TO REDUCE THE RISK OF ELECTRIC SHOCK, SEE INSTRUCTION MANUAL FOR

6381

 

 

 

 

 

 

 

 

PROPER INSTALLATION; ACCEPTABLE FOR INDOOR USE ONLY.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RISQUE DE CHOC ELECTRIQUE. HORS DES EQUIPEMENT AVANT ENLEVEMENT DE LA COUVERTURE ET D’ENTRENTIEN. POUR

TM05

 

 

 

 

 

 

 

 

LE RECCORDEMENT D’ALIMENTATION, EMPLOYEZ DES FILS QUI RESISTENT AU MOINS A 90 °C UTILISEZ UNIQUEMENT DES

 

 

 

 

 

 

 

 

CONDUCTEURS DE CUIVRE. POUR RE’DUIRE LES RISQUES DE CHOC E’LECTRIQUE, CONSULTES LE MANUEL D’INSTRUCTIONS

 

Contains FCC ID: OG3-RADIOM01-2G4

 

POUR UNE INSTALLATION CORRECTE. EMPLOYER UNIQUEMENT A L’INTERIEUR.

 

Fig. 5 Example of nameplate

Pos. Description

1Product name

2Model

3Production code (year and week)

4Serial number

5Product number

6Enclosure type

7Energy Efficiency Index (EEI)

8Part (according to EEI)

9TF-class

10Minimum current [A]

11Maximum current [A]

12Minimum power [W]

13Maximum power [W]

14Maximum pressure

15Voltage [V] and frequency [Hz]

16QR (Quick Response) code

17Approvals (nameplate)

18Assembled in USA

English (US)

5

(US) English

3.8 Radio communication

The wireless radio in this product is class B.

Intended use

This product incorporates a radio for remote control.

The product can communicate with the Grundfos Go Remote and with other MAGNA3 pumps of the same type via the built-in radio.

Only Grundfos-approved external antennae may be connected to this product, and only by a Grundfos-approved installer.

3.9 Tools

1.2 x 8.0

0.6 x 3.5

TX20

5.0

1

2

3

4

 

5

6

7

TM05 6472 4712

Fig. 6

Recommended tools

 

 

Pos.

Tool

 

Size

 

1

Screwdriver, straight slot

1.2 x 8.0 mm

 

2

Screwdriver, straight slot

0.6 x 3.5 mm

 

3

Screwdriver, torx bit

TX20

 

4

Hexagon key

 

5.0 mm

 

5

Open end wrench

 

Depending on PN size

 

6

Wire cutter

 

 

 

7

Pipe wrench

 

 

 

4. Mechanical installation

4.1 Installing the pump

The MAGNA3 is designed for indoor installation.

The pump must be installed in such a way that it is not stressed by the pipework.

The pump may be suspended direct in the pipes, provided that the pipework can support the pump.

Twin-head pumps are prepared for installation on a mounting bracket or base plate.

To ensure adequate cooling of motor and electronics, the following must be observed:

Position the pump in such a way that sufficient cooling is ensured.

The temperature of the ambient air must not exceed +104 °F (+40 °C).

Warning

Observe local regulations setting limits for manual lifting or handling.

Step

Action

Illustration

 

 

 

 

Arrows on the pump housing

 

 

indicate the liquid flow direction

 

1

through the pump. The liquid

0612

flow direction can be horizontal

 

2862

 

or vertical, depending on the

 

 

 

control box position.

TM05

 

 

 

 

 

 

Close the isolating valves and

 

2

make sure that the system is not

0612

pressurized during the

 

 

 

 

installation of the pump.

TM05 2863

 

 

 

 

 

3

Mount the pump with gaskets in

0612

the pipework.

 

TM05 2864

 

 

 

 

 

 

Fit bolts and nuts. Use the right

0612

4

size of bolts according to system

 

pressure.

TM05 2865

 

 

 

 

 

6

4.2 Positioning

Always install the pump with horizontal motor shaft.

Pump installed correctly in a vertical pipe. See fig. 7, pos. A.

Pump installed correctly in a horizontal pipe. See fig. 7, pos. B.

Do not install the pump with vertical motor shaft. See fig. 7, pos. C and D.

A B

C D

TM05 2866 0712

Fig. 7 Pump installed with horizontal motor shaft

4.3 Control box positions

To ensure adequate cooling, the control box must be in horizontal position with the Grundfos logo in vertical position. See fig. 8.

TM05 2915 0612

Fig. 8 Pump with control box in horizontal position

If the pump head is removed before the pump is installed in the pipework, pay special attention when fitting the pump head to the pump housing:

1.Gently lower the pump head with rotor shaft and impeller into the pump housing.

2.Make sure that the contact face of the pump housing and that of the pump head are in contact before the clamp is tightened. See fig. 9.

TM05 5837 4112

Fig. 9 Fitting the pump head to the pump housing

English (US)

7

(US) English

4.4 Changing the control box position

Warning

The warning symbol on the clamp holding the pump head and pump housing together indicates that there is a risk of personal injury. See specific warnings below.

Warning

When loosening the clamp, do not drop the pump head.

Warning

Risk of escaping vapor.

Step

Action

Illustration

 

 

 

 

 

 

 

 

 

Loosen the screw in the clamp

 

 

 

 

 

 

 

holding the pump head and

 

 

 

 

 

 

 

pump housing together.

0612

1

Warning: If the screw is

 

loosened too much, the pump

2867

 

head will be completely

 

disconnected from the pump

 

 

 

 

 

TM05

 

housing.

 

 

 

 

 

 

Carefully rotate the pump head

0612

 

to the desired position.

 

2868

2

If the pump head is stuck,

 

 

 

 

 

 

 

loosen it with a light blow of a

 

 

 

 

 

TM05

 

rubber mallet.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Position the control box in

0612

 

horizontal position so that the

3

Grundfos logo is in vertical

2869

 

position. The motor shaft must

 

be horizontal.

 

 

 

 

 

TM05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Due to the drain hole in the

 

 

 

 

 

 

4

stator housing, position the gap

 

 

 

 

 

 

of the clamp as shown in step

 

 

 

 

 

 

 

 

 

 

 

 

TM05 2870 0612

 

4a, 4b, 4c or 4d.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-head pump.

 

 

 

 

2871 0612

 

 

 

 

 

 

 

 

 

 

4a

 

 

 

 

 

TM05-

gap points towards the arrow.

 

 

 

 

 

 

Position the clamp so that the

0612

 

It can be in position 3 or

 

 

 

 

 

 

 

 

9 o’clock.

 

 

 

 

 

TM05 2918

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-head pump.

 

 

Note: The gap of the clamp can

 

 

 

 

 

 

 

 

 

 

 

 

also be in position 6 o’clock for

 

 

 

 

 

4b

the following pump sizes:

1912

 

MAGNA3 65-XX

 

MAGNA3 80-XX

2899

 

MAGNA3 100-XX.

 

TM05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Twin-head pump.

2873 0612

 

- TM05

 

Position the clamps so that the

4c

gaps point towards the arrows.

 

They can be in position

0612

 

3 or 9 o’clock.

 

TM05 2917

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Twin-head pump.

 

 

Note: The gap of the clamp can

 

 

also be in position 6 o’clock for

 

4d

the following pump sizes:

1912

 

MAGNA3 65-XX

 

MAGNA3 80-XX

2897

 

 

 

MAGNA3 100-XX.

TM05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fit and tighten the screw

 

6

holding the clamp to minimum

0612

6 ± 0.7 ft-lbs

 

2872TM05

 

(8 ± 1 Nm).

 

 

 

 

 

 

 

 

 

 

Fit the insulating shells.

 

 

Note: For air conditioning and

 

 

cooling systems a silicone

 

 

sealant must be applied inside

 

 

the insulation shell to eliminate

 

 

all air gaps and prevent

 

7

condensation between the

 

 

pump housing and insulation

0412

 

shell. Alternatively, the pump

 

 

 

may be insulated manually in

2874

 

accordance with standard

 

insulation practices for cooling

TM05

 

applications.

 

 

 

 

 

If insulating the pump manually, do not insulate

 

Caution

 

 

 

 

 

the control box or cover the control panel.

 

 

 

 

 

8

5. Electrical installation

Carry out the electrical connection and protection according to local regulations.

Check that the supply voltage and frequency correspond to the values stated on the nameplate.

Warning

Never make any connections in the pump control box unless the electricity supply has been switched off for at least 5 minutes.

Warning

The pump must be connected to an external mains switch with a contact separation of at least 1/8 inch (3 mm) in each pole.

The ground terminal of the pump must be earth ground. Grounding or neutralization can be used for protection against indirect contact.

If the pump is connected to an electric installation where a Ground Fault Circuit Interrupt (GFCI) is used as additional protection, this circuit breaker must trip out when ground fault currents with DC content (pulsating DC) occur.

If rigid conduit is to be used, the hub must be connected to the conduit system before it is connected to the terminal box of the pump.

The pump must be connected to an external mains switch.

The pump requires no external motor protection.

The motor incorporates thermal protection against slow overloading and blocking.

When switched on via the power supply, the pump will start pumping after approx. 5 seconds.

Note

The number of starts and stops via the power

supply must not exceed four times per hour.

 

5.1 Supply voltage

1 x 115 V ± 10 %, 50/60 Hz, PE.

1 x 208-230 V ± 10 %, 50/60 Hz, PE.

See Pump Nameplate for rated supply voltage

The voltage tolerances are intended for mains voltage variations. They should not be used for running pumps at other voltages than those stated on the nameplate.

5.2 Connection to the power supply

Step Action

Illustration

Remove the front

1cover from the control box.

Locate the power supply plug and

2conduit adapter in the box supplied with the pump.

Connect the

3conduit adapter to the control box.

Pull the power supply cable

4through the conduit adapter and thread on conduit.

Strip the cable

5conductors as illustrated.

Connect the cable conductors to the

6power supply plug. L - L or L1 Ground - Ground N - N or L2

TM05 2875 0612

TM05 2876 0612

TM05 2877 0612

TM05 2878 0612

TM05 5534 3812

TM05 2880 0612

English (US)

9

English

 

Insert the power

(US)

 

 

supply plug into

 

 

 

7

the male plug in

 

 

the pump control

 

 

box.

 

Tighten the

8

conduit adapter.

Refit the front

 

 

cover.

TM05 5549 3812

Fig. 10 Insulation of pump housing and pipework

TM05 2881 0612

TM05 2882 0612

10

5.3 Connection diagram

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELCB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(min. 10 A, time lag)

 

 

 

 

 

 

 

 

 

 

TM03 2397 0312

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 11 Example of typical connection, 1 x 230

 

 

 

 

 

 

 

 

 

 

 

 

 

V ± 10 %, 50/60 Hz

 

 

 

 

 

 

 

 

 

All cables used must be connected in

Note

 

 

accordance with local regulations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.4 Connection to external controllers

Fig. 12 Connection diagram

Max.

 

 

 

3

 

 

 

 

 

 

 

Max.

 

 

 

 

 

 

 

 

 

 

 

24 V DC

 

24V

 

IN

 

 

 

250 V AC

22 mA

 

 

 

 

 

2 A AC1

 

Vcc

 

Signal

 

 

 

 

 

 

 

 

 

 

 

 

 

0-10 V DC

 

 

 

 

 

 

 

 

 

 

 

Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 V DC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vcc

 

Signal

20 mA

 

 

 

 

 

 

4-20 mA

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

M

S/S

 

 

 

 

NC NO C

 

 

A

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

TM05 2901 1912 - TM05 3343 1212

Warning

Wires connected to supply terminals, outputs NC, NO, C and start/stop input must be separated

from each other and from the supply by reinforced insulation.

Concerning demands on signal wires and signal transmitters, see section 19. Technical data.

Use screened cables for external on/off switch, digital input, sensor and setpoint signals.

Note

All cables used must be heat-resistant up to

+185 °F (+85 °C).

 

5.5 Input/output communication

Relay outputs

Alarm, ready and operating indication via signal relay.

Digital input

Start/Stop (S/S)

Min. curve (MI)

Max. curve (MA).

Analog input

0-10 V or 4-20 mA control signal.

To be used for external control of the pump or as sensor input for the control of the external setpoint.

The 24 V supply from pump to sensor is optional and is normally used when an external supply is not available.

English (US)

11

(US) English

5.5.1 Relay outputs

See fig. 12, pos. 1.

The pump incorporates two signal relays with a potential-free changeover contact for external fault indication.

The function of the signal relay can be set to "Alarm", "Ready" or "Operation" on the pump control panel or with the Grundfos GO Remote.

The relays can be used for outputs up to 250 V and 2 A.

Relay 1

 

Relay 2

 

 

 

 

 

 

 

 

 

 

 

 

NC NO C

 

NC NO C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.5.2 Digital inputs

See fig. 12, pos. 2.

The digital input can be used for external control of start/stop or forced max. or min. curve.

If no external on/off switch is connected, the jumper between terminals Start/Stop (S/S) and frame () should be maintain ed. This connection is the factory setting.

M M

A I S/S

 

 

 

 

 

 

 

 

 

 

Alarm

 

 

 

 

 

 

3338 1212

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

TM05

Fig. 13 Relay output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact symbol

 

 

 

 

Function

 

 

 

 

 

 

 

 

 

 

 

 

 

NC

 

 

 

Normally closed

 

 

 

NO

 

 

 

 

Normally open

 

 

 

C

 

 

 

 

Common

 

The functions of the signal relays appear from the table below:

Signal relay

Alarm signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

The power supply has been switched off.

 

 

NC NO

C

C

 

• The pump has not registered a fault.

 

NC NO

 

 

 

1

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The pump has registered a fault.

1

2

 

3

 

 

NC NO

 

C

 

 

Signal relay

Ready signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

• The pump has registered a fault and is

 

NC NO

C

C

 

 

unable to run.

 

 

NC NO

3

 

 

 

 

1

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Activated:

 

 

 

 

 

 

 

 

 

The pump has been set to stop, but is ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to run.

1

2

 

3

 

 

NC NO

 

C

The pump is running.

 

 

 

 

 

 

 

 

 

 

 

Signal relay

Operating signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

3

 

The pump is not running.

 

1

2

3

 

 

 

 

 

 

 

NC NO

C

 

 

 

 

 

 

NC NO

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Activated:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The pump is running.

1

2

 

3

 

 

NC NO

 

C

 

 

On/off timer

Start/stop

TM05 3339 1212

Fig. 14 Digital input

Contact symbol

Function

 

 

 

M

Max. curve

A

100 % speed

M

Min. curve

I

25 % speed

S/S

Start/Stop

 

 

Frame connection

 

 

 

 

 

External start/stop

The pump can be started or stopped via the digital input.

Start/stop

 

 

 

S/S

H

 

 

Normal duty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Factory setting with

 

 

 

 

 

 

 

 

Q jumper between S/S and

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S/S

H

 

 

Stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Loading...
+ 28 hidden pages