Groen HY-12GF Service Manual

IMPORTANT INFORMATION, KEEP FOR OPERATOR
This manual provides information for:
HY-12GF(CE) & HY-24GF(CE) HYPERSTEAM
ATMOSPHERIC CONVECTION STEAMER INTERNATIONAL
· Self-Contained
· Gas Heated
THIS MANUAL MUST BE RETAINED FOR FUTURE REFERENCE. READ, UNDERSTAND AND FOLLOW THE INSTRUCTIONS AND WARNINGS CONTAINED IN THIS MANUAL.
NOTIFY CARRIER OF DAMAGE AT ONCE
It is the responsibility of the consignee to inspect the container upon receipt of same and to determine the possibility of any damage, including concealed dam age. Unified Brands suggests that if you are suspicious of damage to make a notation on the delivery receipt. It will be the responsibility of the consignee to file a claim with the carrier. We recommend that you do so at once.
Manufacture Service/Questions 888-994-7636.
PART NUMBER 132465, REV. C (1/09)
PART NUMBER 132465, REV. B (4/06)
-
1055 Mendell Davis Drive
Jackson, MS 39272
888-994-7636, fax 888-864-7636
unifiedbrands.net
2 OM/SM-HY-12GF(CE) & HY-24GF(CE)
OM/SM-HY-12GF(CE) & HY-24GF(CE)
IMPORTANT — READ FIRST — IMPORTANT
IT IS MOST IMPORTANT THAT THESE INSTRUCTIONS AND THE OPERATOR AND SERVICE MANUALS BE CONSULTED BEFORE INSTALLING AND COMMISSIONING THE APPLIANCE. FAILURE TO COMPLY WITH
SPECIFIED PROCEDURES MAY RESULT IN DAMAGE OR THE NEED FOR A SERVICE CALL.
THESE APPLIANCES HAVE BEEN CE MARKED ON THE BASIS OF COMPLIANCE WITH THE GAS APPLIANCE DIRECTIVE, EMC AND LOW VOLTAGE DIRECTIVE FOR THE COUNTRIES, GAS TYPES AND PRESSURES AS STATED ON THE DATA PLATE.
THESE APPLIANCES MUST BE INSTALLED BY A COMPETENT PERSON IN CONFORMITY WITH THE INSTALLATION AND SERVICING INSTRUCTIONS AND NATIONAL REGULATIONS IN FORCE AT THE TIME. PARTICULAR ATTENTION MUST BE PAID TO THE FOLLOWING:
I. E. E. REGULATIONS FOR ELECTRICAL INSTALLATIONS ELECTRICITY AT WORK REGULATIONS GAS SAFETY (INSTALLATION AND USE) REGULATIONS HEALTH AND SAFETY AT WORK ACT LOCAL AND NATIONAL BUILDING REGULATIONS FIRE PRECAUTIONS ACT
DETAILED RECOMMENDATIONS ARE CONTAINED IN INSTITUTE OF GAS ENGINEERS PUBLISHED DOCUMENTS: IGE/UP/1, IGE/UP/2, BS6173 AND BE5440.
FURTHERMORE, IS A NEED ARISES TO CONVERT THE APPLIANCE FOR USE WITH ANOTHER GAS, A COMPETENT PERSON MUST BE CONSULTED. THOSE PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER MUST NOT BE ADJUSTED BY THE USER.
USERS SHOULD BE CONVERSANT WITH THE APPROPRIATE PROVISIONS OF THE FIRE PRECAUTIONS ACT AND THE REQUIREMENTS OF THE GAS SAFETY REGULATIONS. IN PARTICULAR THEY SHOULD BE AWARE OF THE NEED FOR REGULAR SERVICING BY A COMPETENT PERSON TO ENSURE THE CONTINUED SAFE AND EFFICIENT PERFORMANCE OF THE APPLIANCE.
WARNING: TO PREVENT SHOCKS, ALL APPLIANCES GAS OR ELECTRIC, MUST BE EARTHED.
UPON COMPLETION OF THE INSTALLATION, THE OWNERS MANUAL SHOULD BE HANDED TO THE USERS AND THE INSTALLER SHOULD INSTRUCT THE RESPONSIBLE PERSON(S) IN THE CORRECT OPERATION AND MAINTENANCE OF THE APPLIANCE.
THIS EQUIPMENT IS ONLY FOR PROFESSIONAL USE, AND SHALL BE OPERATED BY QUALIFIED PERSONS. IT IS THE RESPONSIBILITY OF THE SUPERVISOR OR EQUIVALENT TO ENSURE THAT USERS WEAR SUITABLE PROTECTIVE CLOTHING AND TO DRAW ATTENTION TO THE FACT THAT, SOME PARTS WILL, BY NECESSITY, BECOME VERY HOT AND WILL CAUSE BURNS IF TOUCHED ACCIDENTALLY.
WARNING: BEFORE REMOVING ANY PARTITION OR PANEL, ALWAYS TURN OFF THE ELECTRIC
POWER AND ALLOW THE FAN TO STOP ROTATING. BEFORE WORKING ON ANY ELECTRICAL COMPONENT, DISCONNECT THE POWER SOURCE FROM THE UNIT.
NOTE: IT IS IMPORTANT THAT THE END-USER ROUTINELY EXAMINE THE FLUE OUTLET ON A
REGULAR BASIS. DEBRIS COVERING THE FLUE OUTLET CAN CAUSE A POTENTIALLY HAZARDOUS CONDITION. REMOVE ANY FOREIGN MATERIAL BEFORE USING THIS PIECE OF EQUIPMENT.
WARNINGS AND CAUTIONS PROVIDED IN THE BASIC OPERATOR AND SERVICE MANUALS (OM-HY-6G AND GROEN HYPERSTEAM SERVICE MANUAL) MUST BE COMPLIED WITH.
OM/SM-HY-12GF(CE) & HY-24GF(CE) 3
OM/SM-HY-12GF(CE) & HY-24GF(CE)
TABLE OF CONTENTS
WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1. INSTALLATION, ASSEMBLY AND COMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
2. SERVICING AND CONVERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
PARTS IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
STEAMER BLOCK DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
INTERCONNECT BLOCK DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
CONTROL BOARD BLOCK DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
CONTROL BOARD LED LOCATIONS DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3. TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
TRUTH TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
ELECTRICAL SCHEMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
TROUBLESHOOTING CHARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4. OPERATOR MANUAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
EQUIPMENT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
WATER CONDITIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
SERVICE LOG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
4 OM/SM-HY-12GF(CE) & HY-24GF(CE)
1. Installation, Assembly and Commissioning
CAUTION IT IS MOST IMPORTANT THAT THESE INSTRUCTIONS AND THE OPERATOR AND SERVICE MANUALS BE CONSULTED BEFORE INSTALLING AND COMMISSIONING THE APPLIANCE. FAILURE TO COMPLY WITH SPECIFIED PROCEDURES MAY RESULT IN DAMAGE OR THE NEED FOR A SERVICE CALL.
These appliances have been CE marked on the basis of compliance with the gas appliance directive, EMC and low voltage directive for the countries, gas types and pressures as stated on the data plate.
These appliances must be installed by a competent person in conformity with the installation and servicing instructions and national regulations in force at the time. Particular attention must be paid to the following:
I. E. E. Regulations For Electrical Installations Electricity at Work Regulations Gas Safety (Installation And Use) Regulations Health And Safety at Work Act Local And National Building Regulations Fire Precautions Act
Detailed recommendations are contained in Institute of Gas Engineers published documents: IGE/UP/1, IGE/UP/2, BS6173 and BE5440. Furthermore, is a need arises to convert the appliance for use with another gas, a competent person must be consulted. Those parts which have been protected by the manufacturer must not be adjusted by the user.
Users should be conversant with provisions of the Fire Precautions Act and requirements of Gas Safety Regulations. In particular they should be aware of the need for regular servicing by a competent person to ensure safe and efficient performance of the appliance.
WARNING TO PREVENT SHOCKS, ALL APPLIANCES GAS OR ELECTRIC, MUST BE EARTHED
.
Upon completion of the installation, the owners manual should be handed to the users and the installer should instruct the responsible person(s) in the correct operation and maintenance of the appliance.
This equipment is only for professional use, and shall be operated by qualified persons. It is the responsibility of the supervisor or equivalent to ensure that users wear suitable protective clothing and to draw attention to the fact that, some parts will, by necessity, become very hot and will cause burns if touched accidentally.
1.1 General
Unpack the appliance and place it on a firm, level floor. Adjust and fix the feet.
1.1.1 Model Number and Dimensions
MODEL
WIDTH
mm (in.)
DEPTH
mm (in,)
HEIGHT
mm (in.)
WEIGHT
Kg (lbs)
HY-12GF
815
(32.06)
1025
(40.4)
1590
(62.6)
256 (565)
HY-24GF
815
(32.06)
1025
(40.4)
1853
(73.37)
512
(1130)
1.1.2 Siting and Clearances
CAUTION DO NOT INSTALL THIS UNIT SO RIGHT SIDE VENTS ARE BLOCKED OR WITHIN 300 mm OF
A HEAT SOURCE SUCH AS BRAISING PAN, DEEP FRYER, CHAR BROILER OR KETTLE.
LEVEL THE UNIT FRONT TO BACK
OR PITCH IT SLIGHTLY TO THE REAR TO AVOID DRAINAGE PROBLEMS.
The HY-12GF(CE) steamer is suitable for installation in combustible and noncombustible locations. Minimum installation clearances are:
Right Side 300 mm (12 inches) Left Side 0 mm (0 inches) Rear of Flue 150 mm (6 inches)
The steamer requires 600 mm (24 inches) clearance on the right side for service.
Allow minimum vertical clearance of 750 mm (30 inches) between the top edge of the flue outlet and any overlying surface.
1.1.3 Ventilation
CAUTION THE APPLIANCE FLUE DISCHARGES VERTICALLY FROM THE TOP OF THE UNIT. IT MUST NOT BE DIRECTLY CONNECTED TO ANY FLUE, MECHANICAL EXTRACTION SYSTEM, OR DUCTS LEADING TO OUTSIDE THE BUILDING. THE UNIT IS BEST DISCHARGED UNDER AN OPEN CANOPY WHICH CONNECTS WITH A VENTILATING SYSTEM
.
OM/SM-HY-12GF(CE) & HY-24GF(CE) 5
OM/SM-HY-12GF(CE) & HY-24GF(CE)
For multiple installations the requirements for individual appliances should be added together. (See table, page 5). Installation must comply withlocal and/or national regulations and a competent installer must be employed. Recommendations for ventilation for catering appliances are given in BS 5440:2, and are shown in the table at right.
1.2 Electrical Supply Connection
The unit is designed for connection to fixed wiring. A suitably rated isolating switch with contact separation of at least 3 mm on both poles must be fitted to the installation.
Wiring must be executed in accordance
with the regulations listed in this manual.
Equipment
Required Ventilation Rate
m³/min ft³/m
Units Type Range 17 600
Pastry Oven 17 600
Fryer 26 900
Grill 17 600
Steak Grill 26 900
Boiling Pan 17 600
Steamer 17 600
Sterilizing Sink 14 500
Bains Marie 11 400
Tea/Coffee Machine 8.5 - 14 300 - 500
6 OM/SM-HY-12GF(CE) & HY-24GF(CE)
OM/SM-HY-12GF(CE) & HY-24GF(CE)
Cable entry is at the top rear right side of the appliance for model HY-12GF(CE). There are two cable entries on model HY-24GF(CE), at the rear right side of each cavity. Access is gained as described in the Operator and Service Manuals for this appliance.
Provide 230 Volt, 50 Hz, Single Phase, 15 Ampere service. Maximum load is 2½ Amps. The electrical schematic is located in the service compartment and in this manual.
WARNING
THIS APPLIANCE MUST BE EARTHED.
1.3 Gas Supply Connection
Incoming service must be of sufficient size to supply full rate without excessive pressure drop. A gas meter is connected to the service pipe by the Gas Supplier. Any existing meter should be checked out by the Gas Supplier to ensure that it has adequate capacity to provide the required rate of gas to the steamer, in addition to any other installed equipment.
GAS INPUT RATE BTU/HR AND KW
Natural Gas Propane Gas
HY-12GF
150130 BTU/hr
44 KW
150130 BTU/hr
44 KW
HY-24GF
2 x 150130
BTU/hr
2 x 44 KW
2 x 150130
BTU/hr
2 x 44 KW
Installation pipe work must be fitted in accordance with IGE/UP/2.
The appliance governor is suitable for both natural and propane gas without conversion. The governor is incorporated in the gas control valve, which is inside the control cabinet.
Connection to the gas supply can be completed with ¾” BSPT pipe. Although the immediate connection to the appliance is ¾” BSPT, gas supply piping must be large enough to provide 160,000 BTU/hour. Minimum supply pressure is 20 mBar for natural gas, or 37 mBar for propane gas.
An isolating cock must be located close to the appliance to allow shut down in an emergency, or for servicing. The installation must be tested for gas soundness and purged as specified in IGE/UP/1. For the part of the integral gas supply downstream
from the gas valve, leak detection spray or some solution may be used with the burners lit.
1.3.1 Gas Pressure Adjustment
Gas pressure has been set at the factory but should be checked by connecting a manometer to the pressure tap on the burner manifold. The adjusted gas pressures are shown in the table below.
Model
Natural Gas Propane Gas
mBar WCI mBar WCI
HY-12GF(CE) 7.75 3.1 25 10
HY-24GF(CE) 7.75 3.1 25 10
If necessary, the gas pressure may be readjusted as described in Section 3..
1.3.2 Injector Diameters
Natural Gas Propane Gas
Injector
Dia. (mm)
No. of
Injectors
Injector
Dia. (mm)
No. of
Injectors
HY-12GF(CE) Main Burner (high fire)
1.18 30 0.70 30
HY-24GF(CE) Main Burner (high fire)
1.18 30 x 2 0.70 30 x 2
HY-12GF(CE) Igniter Burner (low fire)
0.64
1 0.41 1
HY-24GF(CE) Igniter Burner (low fire)
0.64 1 x 2 0.41 1 x 2
HY-12GF(CE) Pilot Burner
0.60
1 0.36 1
HY-24GF(CE) Pilot Burner
0.6 1 x 2 0.36 1 x 2
1.3.3 Burner Air Adjustment
The unit is equipped with fixed aeration type burners which have no provision for air inlet adjustment.
1.4 Water Supply Connection
Water entry is at the rear right side of the appliance. There are two water entries on the HY-24GF(CE).
The steamer is fitted for a ¾ inch BSPT cold water connection. The water supply must be provided at a
OM/SM-HY-12GF(CE) & HY-24GF(CE) 7
OM/SM-HY-12GF(CE) & HY-24GF(CE)
Drain Connection with Drain Box
rate of not less than
7.6 liters (tw
o gallons) per minute. Pressure must
be
2.0 to 4.0 Bar (30 to 60 PS
I) maximum.
Water qualit
y minimums requir
e
totally dissolve
d
solids (T.D.S.) of
30 parts per million maximum, and a water pH of 7.0 or greater. If the available wate
r supply fails to meet these requirements, water treatmen
t equipment must be provided to ensure
steamer reliability and operating life
.
Install a WRAS approved double-check valve or an equally effective backflow preventive device in the incoming cold water line at the point of connnection(s) to the steamer and in compliance with all local plumbing codes. This installation must be per WRAS­IRN R160 Schedule 2-15(1). For units with the dual water connection option, a double-check valve shall be installed on each water line.
1.
5 Drain Connection
The unit must be leveled front to back or pitched slightly to the rear (one to two degrees)
by adjustment of the bullet feet on the cabinet base. All units are shipped from the factory with a drain box and vent pipe.
The drain box and vent pipe provide the necessary air gap when properly installed. The illustrations
at
right shows proper installation of drain lines.
Leave
a air gap to any building drain. Do NOT
create any water traps in the drain line.
A trap could
cause pressure to build up in the cavity durin
g
steaming and cause the door gasket to leak
.
WARNING VARIATION FROM THESE INSTRUCTIONS CAN CREA
TE A HAZARD.
DO NOT USE PLASTIC PIPING — DRAIN MUST WITHSTAND VERY HOT WATER.
1.
6 Initial Start-Up
After the HY-12GF(CE) Steamer has been installed, test it to be sure that it is operating correctly.
1. Remove all literature and packing materials from the interior and exterior of the unit.
2. Make sure the water supply line is open.
3. Make sure the gas supply line is open and that the gas shut-off valve in the unit is in the OPEN
position. This valve is located behind an access panel on the right side of the uni
t
4. Turn on electrical service to the unit. The unit will not operate without electrical power. Do not try to operate the un
it during a power failure.
5. The steamer will not operate until the pilot burner has been ignited. To light the pilot burner
,
ac
tivate the pilot switch next to the main gas
valve. (See photo below)
. When the ignition sequence is successful a green light on the electrical panel will glow.
8 OM/SM-HY-12GF(CE) & HY-24GF(CE)
OM/SM-HY-12GF(CE) & HY-24GF(CE)
6. The “trial for ignition” period is roughly 90 seconds. If the pilot burner does not light within 90 seconds, the system automatically stops gas flow to the pilot burner and lights the Lockout neon on the front control panel. If this happens, turn off the pilot switch, push the Gas Reset switch, and repeat the trial for ignition. During the first start-up, the pilot may require several trials for ignition to bleed air from the piping. Subsequent start-ups should only need about five seconds to achieve pilot ignition. NOTE:See Automatic Pilot
Operation at the end of this section.
7. Once the pilot flame has been established (the green light on the electrical panel is on), press the “ON” switch for the desired steamer cavity. The steam generator will fill with water.
NOTE:The door MUST be closed for the main (high) heater to work.
8. When the steam generator has filled with water, the main and low burners will automatically light. The READY light should come on within 10 minutes, to show that the water has reached its standby temperature. When the READY light is on, the operator may take any of the following steps:
a. Set the timer to the desired time for timed
steaming.
WARNING WHEN YOU OPEN THE DOOR, STAY AWAY FROM STEAM COMING OUT OF THE UNIT. THE STEAM CAN CAUSE BURNS.
b. Turn the timer knob to the manual ON
position for continuous steam.
c. Let the unit wait at standby temperature. The
steam generator is equipped with a high-limit thermostat which will trip if the liquid level probe fails.
9. If this happens, the High Temperature neon on the front control panel will glow and trip a reset switch. The Reset Switch must be pressed to re-start steam generation. This switch is located next to the pilot switch (towards the rear of the unit) and can be reached through the access
door on the right side of the unit.
10. To shut down the unit, turn the ON switch to the OFF position. The steam generator will automatically drain. You may also switch OFF the pilot switch to conserve energy
11. If your steamer works as described, it is functioning correctly and is ready for use.
Automatic Pilot Operation
Once the pilot burner has been lit, it essentially functions as a standing pilot. When the pilot switch is on, if the pilot is accidentally extinguished (by a very strong gust of wind or the like), it will re-ignite automatically. The unit will shut off completely for a few seconds while the pilot is re-ignited. The unit will then come back on and resume operation in the mode and at the (running) timer value existing just prior to shutdown. The pilot switch may be turned off during “off hours” to conserve energy.
If the pilot burner ever fails to re-ignite automatically within 90 seconds, after the unit has been running, the Gas Lockout neon on the front control panel will light. Wait five minutes and push the Gas Reset switch to reignite the pilot. Should ignition problems persist, contact your authorized Groen Service Agency.
1.7 Setting the Gas Pressure
1. During commissioning, a gas pressure check is essential. Connect a suitable pressure gauge to the gas manifold to perform this test. The pressure gauge should be connected to the test nipple (See photograph at right).
OM/SM-HY-12GF(CE) & HY-24GF(CE) 9
OM/SM-HY-12GF(CE) & HY-24GF(CE)
Adjust Gas Pressure by Turning the Screw inside the Gas Pressure Adjustment Turret.
To test pressure, attach a pressure gauge to the test nipple on the gas manifold.
2. Turn the main gas and electricity supply on.
3. Light the burners as described in Paragraph 1.6 above.
4. Manifold gas pressure should be as noted in Section 1.3.1 of the manual. If adjustment is necessary, follow steps below.
5. Remove the governor cap screw on the gas control valve to gain access to the screw inside the turret. (See photograph).
6. The governor is suitable for both natural and propane gas.
7. Turn the screw inside the turret clockwise to increase the pressure, anti-clockwise to reduce it. Check the burner pressure again after 15 minutes operation, and adjust if necessary.
8. Disconnect the pressure gauge from the test point. Reseal the test point and test for gas soundness.
9. Replace governor cap screw, and replace control box panel and lid.
NOTE
: For operation at high altitudes (1000 meters and
above) consult the Groen Food Service Engineering Department.
1.8 Instructions to User
IMPORTANT: After installing and commissioning the appliance, the User’s Instructions should be handed to the user or purchaser. Ensure that the instructions for lighting, turning off, correct use and cleaning are properly understood. Emphasize the location of the main gas isolating valve and demonstrate the emergency shut down procedure.
10 OM/SM-HY-12GF(CE) & HY-24GF(CE)
OM/SM-HY-12GF(CE) & HY-24GF(CE)
2. Servicing and Conversion
CAUTION BEFORE ATTEMPTING ANY SERVICING, ENSURE THAT THE ISOLATING COCK IS TURNED OFF AND CANNOT BE INADVERTENTLY TURNED ON. CHECK THAT THE ELECTRICITY SUPPLY IS DISCONNECTED.
AFTER ANY MAINTENANCE TASK CHECK THE APPLIANCE TO ENSURE THAT IT PERFORMS CORRECTLY AND CARRY OUT ANY NEEDED ADJUSTMENTS AS DETAILED IN SECTION 1.
AFTER CARRYING OUT ANY SERVICING OR EXCHANGE OF GAS CARRYING COMPONENTS ALWAYS CHECK FOR GAS SOUNDNESS.
Conversion
To change from natural gas to propane gas or vice versa, change the following:
Burner injectors (high fire orifices)
Rimner Tube Injector (low fire orifice)
Pilot orifice
Pressure setting
Data Plate
The governor spring does not need to be changed — only the pressure setting.
After Servicing
1. Test for gas soundness as specified in IGE/UP1 as appropriate after any gas connection has been disturbed.
2. Check for correct operation (see Commissioning of Appliance)
2.1 Assembly/Disassembly Procedures
GENERAL INFORMATION
The procedures which follow are based on having full access to the steamer on all four sides. If the steamer is installed between other appliances and there is not enough room on the sides for access, it must be puled out from its position. Exercise care when moving the steamer to avoid stress or pull on electrical, water and gas connections.
2.1.1 Right Side Panel (Louvered) — Removal
P/N 123196
1.
With a flat blade screwdriver, remove the two 10-32 screws on the lower edge of the panel. The panel is retained to the steamer by an interlocking guide track on the top edge and three spring-like clips at the rear edge.
2. Once the screws are removed, SLIDE the panel toward the front of the appliance with a lifting
motion. Do not attempt to pry the panel. Once the panel is clear of the rear clips, it may be lifted off of the top rack.
ASSEMBLY TIP: When replacing the panel, press the rear edge inward so that all three clips are retained by the back flange. Make sure that the holes in the panel align with the two tapped holes in the steamer so that replacing the screws will be easy and will not damage the threads.
2.1.2 Left Side Cover — Removal
Left P/N 123197
Under normal conditions, the left side cover should never have to be removed, since there are no operational or replacement parts to be accessed. The single exception occurs when the door has been reversed so that the handle is on the left and the Door Interlock Switch requires replacement. The door switches for both door positions are installed at the factory, so there is no need to have access to them if the door is to be reversed.
1. If the left side cover is to be removed because of a faulty door switch, remove the right side panel first. Using a 7mm nut driver and the flat blade screwdriver, remove the retaining clip and the two screws on the lower edge of the left side cover. The assembly may then be slid forward. Once clear of the retaining clip, it may be lifted off.
ASSEMBLY TIP: When replacing the left cover assembly, be sure that the retaining clip is replaced and screwed down tightly.
2.1.3 Water Inlet Valve — Three Way
P/N 090827
1. Turn off power and water supply to the steamer.
2. Remove the water supply hose connection on the rear of the steamer.
3. Remove the right side panel, as described in Paragraph 2.1.1, above.
OM/SM-HY-12GF(CE) & HY-24GF(CE) 11
4. Remove the screws holding the water inlet valve bracket, and pull the bracket with the valve a few cm away from the body of the appliance.
5. The water inlet valve branches to three individual solenoid-activated valves within its housing. These are connected with the following three sets of wires:
Steam Generator Fill . . . . . . . . Yellow & Orange
Steam Generator Clean . . . . . . . . Violet & Gray
Condensate Spray . . . . . . . . . . . . Green & Blue
6. Using a 7 mm nut driver, loosen the hose clamps on the inlet valve.
7. Slide the hose clamps down the hose until needed for reassembly. Loosen and remove the hoses from the valve with a gentle rocking motion.
8. Remove the bracket from the valve and lower the valve
WITH THE WIRES STILL ATTACHED.
9. Carefully unplug the connectors one at a time and attach to the new valve.
10. To install a new valve, reverse the procedures. First install the six wires (three sets) as listed in item 5, above. Make certain that the valve is NOT installed upside down.
11. Attach the valve to its bracket with the two screws and return it to its position.
12. Re-attach the hoses to the valve. Slide the hoses all the way so that the end of the hose is flush against the face of the valve.
IMPORTANT: Be sure the correct hose is connected to the corresponding outlet.
13. Slide the clamps back into position around the end of the hoses and tighten the clamps.
CAUTION DO NOT OVER-TIGHTEN THE CLAMPS. OVER­TIGHTENING CAN DAMAGE THE VALVE.
2.1.4 Adjustable Legs
P/N 042505
1. Each leg is provided with a screw-type support post. These may be extended or retracted by turning them with a wrench or Channel Lock. Be sure that all four legs are in tight contact with the floor for proper steamer support.
2. If damaged, the posts may be replaced by tapping out the threaded fitting (on the opposite side of the leg) which is friction-held in each leg. The stainless steel leg and threaded fitting are a single assembly.
2.1.5 Main Gas Valve and Gas Pressure
Adjustment P/N 122158
1. Disconnect power to the steamer.
2. Remove the right side panel, as described in Paragraph 2.1.1, above.
3. Turn the manual gas valve to the closed position. Disconnect the wire to the solenoids.
4. Note the color and position of the two connectors for assembly.
5. Remove all aluminum tubing from the piping assembly using an open-ended wrench. Be careful not to move the aluminum tubing excessively, or to bend it.
6.
With a pipe wrench or Channel Lock, open the pipe union on the left side of the main gas valve and the right side near the solenoid valves. Remove the assembly.
7. From both sides of the main gas valve, using a Channel Lock, turn to remove the nipples. Support the valve with a vise or Channel
Lock/pipe wrench.
To Assemble:
8. Screw in and tighten the nipples into both sides of the main gas valve using approved gas pipe sealant.
12 OM/SM-HY-12GF(CE) & HY-24GF(CE)
9. Using a pipe wrench or Channel Lock attach the union and tighten.
10. Attach all aluminum tubing and tighten with an open-ended wrench.
11. Plug in the two connectors to the main gas valve:
2.1.6 Gas Solenoid Valve
P/N 122120
The gas solenoid valves must be removed as an assembly along with the regulators, using the following procedures:
1. Turn off the gas supply and power to the steamer.
2. Disconnect wires from the main gas (Step 4, Paragraph 2.1.5) and from the gas solenoid valves.
3. From the front of the steamer, using a Channel Lock wrench, loosen and disconnect the pipe union which connects the assembly to the main gas valve.
4. From the left side (or back) of the steamer, use an open-ended wrench to loosen and disconnect the compression fittings which connect the 9.5 mm aluminum tubing, from the inner and outer manifolds.
5. From the left side (or back) of the steamer, use an open ended wrench to loosen and disconnect the compression fittings which connect the 9.5 mm aluminum tubing, from the inner and outer manifolds.
6. The entire assembly of both regulators and the
gas solenoid valves for the upper and lower steam generators may be removed as an integrated unit.
7. Remove the failed gas solenoid valve.
To Reinstall:
8. Clean pipe threads and apply compound to all joints being connected.
9. Install the new gas solenoid valve.
10. Slide the assembly into the steamer and align the tee fitting with the pipe union. Align the gas valves with their respective aluminum tubing.
11. Connect the pipe union using a Channel Lock wrench.
12. Using an open-ended wrench, connect the 9.5 mm aluminum tubing to the inner and lower steam generator manifold.
13. Using an open-ended wrench, connect the 12.7 mm aluminum tubing from the inner and outer steam generator manifolds.
14. Reconnect the wires to the correct valve.
2.1.7 Igniter Module
P/N 154059
1. Shut off power and gas to the steamer.
2. Remove the cover to the electrical compartment.
OM/SM-HY-12GF(CE) & HY-24GF(CE) 13
OM/SM-HY-12GF(CE) & HY-24GF(CE)
3. The igniter module is located next to the motor.
4. Note or tag the wires for reinstallation before unplugging. Carefully disconnect the seven push terminals from the igniter module. be careful not to pull the terminal by the wire. Use needle nose plers to grip onto the terminal itself.
5. Use a nut driver (preferably with a magnetic tip) to remove the two 6-32 screws.
6.
To Install:
7.
8. When all screws are in place, tighten them one at a time.
9. Plug in each of the six terminals. Double check to ensure that they are correct.
2.1.8 Pilot Switch (SW3) Removal
P/N 087951
1. Shut off the power supply. Disconnect the four color coded wires from the switch assembly. Remove the two retaining screws which attach the switch bracket to the lower frame rail of the steamer.
2. The switch snaps into the bracket where it is retained by plastic tabs on the top and bottom. To remove the switch from the bracket, press in on both tabs at the same time and slide the switch out of the bracket hole.
To replace the switch
3. Insert the new switch into the bracket hole until its tabs clear the hole and snap into position.
4. Reattach the wires to the switch.
5. Replace the switch bracket with two screws.
2.1.9 Pilot Burner Replacement/Current Check/ Adjustment - Pilot Flame Sensor Replacement
P/N 102258 (Natural) P/N 106610 (Propane) P/N 003328 Flame Sensor
1. Turn off the main gas and power supply.
2. Remove the front cover.
3. Remove the right side panel as described in Paragraph 2.1.1.
4. Turn the manual gas valve to the OFF position. Place pilot switch SW3 in the OFF position.
5. Disconnect the pilot line from the pilot burner.
6. Disconnect the “spark” lead from the pilot burner.
7. Remove the flame sensor from the flame sensor bracket.
8. Remove the pilot burner.
Installation:
9. Connect the pilot line to the pilot burner.
10. Connect the “spark” lead to the pilot burner. Be sure to route the lead around the outside of the gas lines.
11. Replace the flame sensor on the flame sensor bracket.
12. Apply anti-seize lubricant to mounting head screw threads. Install the pilot burner and flame sensor assembly, and tighten the screws.
NOTE
: Route the “spark” lead and flame sensor wire
away from the manifold to prevent improper operation.
13. Turn manual gas valve to the ON position.
14. Connect unit to the branch circuit and turn on the main gas supply.
15. Place pilot switch SW3 in the ON position. Check for gas soundness.
Remove the igniter module.
Position the new igniter against the back wall or mounting bracket of the electrical compartment Place a hex head screw in the nut driver and start each of the two screws.
14 OM/SM-HY-12GF(CE) & HY-24GF(CE)
Pilot Flame Current Check
WARNING WHEN STEAMER POWER IS TURNED ON, THERE IS HIGH VOLTAGE PRESENT IN THE ELECTRICAL COMPONENTS COMPARTMENT. BE SURE THAT STEAMER IS DISCONNECTED FROM BRANCH CIRCUIT BEFORE PERFORMING ANY REPAIRS.
1. Turn off steamer power.
2. Disconnect the ground (green) wire from the igniter module.
3. Connect a DC micrometer between the igniter ground terminal and the disconnected green wire.
WARNING DO NOT ATTEMPT TO LIGHT THE PILOT BURNER WITH A FLAME.
4. Ignite the pilot. The micrometer should read 3 microamps minimum.
If current reading is correct, replace the
igniter module (see 2. 1. 7).
* If current reading is below 3 microamps,
continually check the Flame Rectification Circuit (large orange wire, spark electrode, pilot burner hood, and ground connections). If necessary, tighten ground connections and/or replace defective component(s).
5. Check for moisture around the pilot burner, and for corrosion on the electrode and the pilot burner hood. If necessary, remove moisture with a dry, clean cloth. If hood and/or electrode are excessively corroded, replace pilot burner assembly.
2.1.10 Steam Generator Probes (High and Low
Water) P/N 070178
NOTE
: There are two probes for each steam generator.
1. Shut off power to the steamer.
2.
With an 8 mm nut driver LOOSEN, but do not remove the nuts holding the wire(s) on the probe terminal(s).
3. The wires are connected to wire fork terminals. These will "snap" on and off the terminal post. Unsnap them by gently pulling on the terminal.
4. Using a 21mm open ended wrench, turn the probe counter-clockwise to remove. Clean or replace water level probes.
To Install:
5. Apply high temperature pipe compound to the probe and screw it in by hand. Using a 21mm open ended wrench, tighten the probe into the fitting.
6. Replace the wire(s) to the probes by snapping the fork terminals around the terminal post. Using an 8 mm nut driver, tighten the terminal nut.
NOTE
: If two probes are to be replaced, either replace
them one at a time or note the color of the wires attached to the probes. Do not mix them up.
2.1.11 Water Level Control Board
P/N 106258
1. Shut off electrical power to the steamer.
2. Remove the side panel screws and slide panel away from steamer.
3. Remove two kep nuts and star washers securing main control board mounting bracket. Lay main control board to the side.
4. Unplug the three terminals on the side of the water level control board: "C", "Low" and "High". Note wire colors and terminal positions.
5. Remove four nuts holding the board to the steamer frame and remove board.
6. Unplug the multi-conductor plug on the opposite side of the board.
To Install:
7. Plug in the multi-conductor plug on the bottom of the board. Make sure the plug is firmly and properly seated.
8. Place the water level control board over the mounting studs and fasten with four nuts.
9. Plug in the three terminals on the side of the board, making sure to plug the low wire into the
OM/SM-HY-12GF(CE) & HY-24GF(CE) 15
OM/SM-HY-12GF(CE) & HY-24GF(CE)
low terminal, the high wire into the high
terminal and the "
C" into the "C" terminal.
10. Install two star washers and kep nuts to secure main control board mounting bracket.
11. Install the side cover and fasten with screws.
2.1.12 Steam Generator Gas Jet Manifold
P/N 106224
1. Shut-off power and gas to the steamer.
2. Remove the right side panel.
3. Turn manual gas valve to the closed position.
4. Remove the three aluminum tubes connected to the manifold. Disconnect the tubes using an open ended wrench.
5. Remove the two screws from the pilot mounting bracket. Remove pilot from the gas manifold.
6. Using a nutrunner or socket wrench remove the two top and two bottom bolts which hold the manifold to the steam generator manifold mounting bracket.
7. Remove the burner manifold from the appliance.
8. Remove the flame retention springs and injectors as required.
To Reassemble
:
9. Replace the injectors and retention springs. Ensure a suitable gas sealant is used on the threads of the injectors to ensure a gas tight seal.
10. Fit the burner manifold to the steam generator manifold mounting bracket.
11. Reinstall and tighten the aluminum tubes to the burner manifold.
NOTE
: Ensure all gas connections are sound before
continuing.
2.1.13 Steam Generator Drain Valve
P/N 071234
1. Turn off power and allow steamer to drain completely. Remove back cover panel and loosen clamps or spring.
2. Using a 7mm nut driver or spring clamp pliers, disconnect both ends of the drain hose from the spray box and the steam generator.
3. Unplug and disconnect the valve electrical wires. Remove the 10-32 kep nuts holding the valve to the plate. Remove the valve from the threaded studs. Then remove silicone hose from the valve.
4. Inspect the silicone hose for any damage or lime buildup. Clean or replace hose if required.
5. Attach new drain valve to valve bracket if bracket applicable. Pull silicone hose through drain valve and loosely install hose clamps over both ends of the hose. Be sure that the silicone hose is properly aligned and does not have any kinks, bends or twists in it.
6. Position the valve over the valve mounting threaded studs, and connect both ends of the hose to drain box or drain tube and steam generator.
7. Position the clamps so that the worm screw may be easily tightened. Using a 7mm nut driver, tighten both hose clamps. Be careful not to over­tighten clamps since they could cut the hose. If using spring clamps, use pliers to position them.
8. Install and tighten the valve mounting 10-32 cap nuts.
9. Plug electrical leads into wiring harness.
Test: Operate the steamer and allow steam generator
to fill. Check for leaks and observe if the drain valve fully closes. Turn off the steamer and make sure that the drain valve opens and the steam generator drains. Install back cover.
2.1.14 Drain Box Spray Nozzle
P/N 106445
Disassemble
1. Turn off power to the steamer. Turn off the water supply to the steamer. Remove the water supply hose connection on the rear of the steamer
2. Remove the two screws on the right side of the water inlet panel. Pull the water inlet valve mounting plate away from the steamer and slide it free.
3. Loosen the hose clamp nearest the end of the black hose. Pull the hose off from valve nipple.
Loading...
+ 33 hidden pages