SPLIT TYPE ROOM AIR CONDITIONER
INSTALLATION INSTRUCTION
SHEET
(PART NO. 9369233012)
For authorized service personnel only.
WARNING
CAUTION
(1) For the room air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
(2) Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available standards parts. This
installation instruction sheet describes the correct connections using the installation set available from our standard parts.
(3) Installation work must be performed in accordance with national wiring standards by authorized personnel only.
(4) If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a flame, it
produces a toxic gas.
(5) Do not use an extension cord.
(6) Do not turn on the power until all installation work is complete.
••
• Be careful not to scratch the room air conditioner when handling it.
••
••
• After installation, explain correct operation to the customer, using the operating manual.
••
••
• Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
••
SELECTING THE MOUNTING POSITION
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not
topple or fall.
(1) Do not install where there is the danger of combustible gas leakage.
(2) Do not install near heat sources.
(3) If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of
the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to
the user, or damage to property.
WARNING
WARNING
CAUTION
STANDARD ACCESSORIES
The following installation accessories are supplied. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Wall hook bracket
Remote
control unit
Battery (penlight)
Remote control
unit holder
Tapping screw (big)
(ø4 × 20)
Tapping screw (small)
(ø3 × 12)
OUTDOOR UNIT ACCESSORIES
Hexagon
wrench
Drain pipe
Flexible tube
Drain cap
Q’ty
For indoor unit installation
1
Use for air conditioner
operation
1
For remote control unit
2
Use as remote control unit
holder
1
For wall hook bracket
installation
12
For remote control unit
holder installation
2
For vacuuming and addi-
1
tional charge
1
For outdoor unit drain
piping work
1
[Heat & Cool model
(Reverse cycle) only]
2
Use
INSTALLATION PROCEDURE
1
INDOOR UNIT INSTALLATION
The piping can be connected in the six directions indicated by 1, 2, 3,
4, 5 and 6 in Fig. 4. When the piping is connected in direction 2 or 5,
cut along the piping groove in the side of the front panel with metal shears.
When connecting the piping in direction 3, cut along the piping groove at
the bottom of the front panel.
Fig. 4
5 Left piping
2 Right
piping
1 Rear piping
3 Bottom piping
6 Center piping
1. INSTALLING THE WALL HOOK BRACKET
[Removing THE WALL HOOK BRACKET]
Remove the wall hook bracket in the following order.
(1) Remove the hook inside the panel. (Fig. 5)
(2) Pull off the wall hook bracket.
Fig. 5
Wall hook bracket
Unhook
2 places
[Installation directly to a wall]
Before fastening the wall hook bracket to the wall with the screws, level it
by tapping the hook at the center of bracket to the wall with the handle of
a screwdriver.
• Fasten the wall hook bracket to the wall with 6 or more screws and
anchor bolts through the holes near the outer edge of the bracket.
• Do not install the wall hook bracket at only one place or at an angle. For
a concrete wall, embed anchor bolts (10 mm dia.) into the wall at the
wall hook bracket holes (11 × 43 mm dia. and 11 × 94 mm dia. (Fig. 6)).
Allow the anchor bolts to stick out at least 18 mm from the wall. (Fig. 7)
Install the unit to the anchor bolts with nuts through the wall hook bracket.
Use 2 bolts for concrete wall and 4 bolts for blister concrete wall (Fig. 8).
• Finally tighten the bolts and tapping screws after confirming, using the
level indicator, that the clamp is horizontal.
4 Left rear piping
Panel
WARNING
(1) Install the wall hook bracket so that it is correctly posi-
tioned horizontally and vertically. If the wall hook
bracket is tilted, water will drip to the floor.
(2) As the weight of the indoor unit is 15 to 18 kg (33 to 40
lbs), it should be installed after properly examining the
place where it is intended to be installed. If the place is
not strong enough, a plank or girder should be used to
make the place sufficiently strong so that the wall can
support the weight.
UNIT [mm]
Fig. 6
11x43hole
523
50
Piping inlet
Wall hook bracket
296
305
252
40- 6hole
for tapping screw
498 429
110
8-12x18hole
11x94hole
557557
251
265
293
451
523
41
68
96
221
257
300
Piping inlet
Fig. 7
Bolt
WALL
23/32” (18 mm) max.
Fig. 8
Anchor bolt
Wall hook
bracket
Tapping screw
(big)
Tapped
(Handle of screwdriver)
Hook
Center notch
Hook
Wall hook
bracket
String
Counter weight
2. CUTTING THE HOLE IN THE WALL FOR THE
CONNECTING PIPING
WARNING
If the wall pipe is not used, the cord interconnecting the
indoor and outdoor units may touch metal and cause electric leakage.
(1) Cut a 80 mm diameter hole in the wall at the position shown in Fig. 9.
(2) When cutting the wall hole at the inside of the installation frame, cut
the hole to a point of intersection of center marks.
When cutting the wall hole at the outside of the installation frame, cut
the hole at least 10 mm below less.
(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the
inside end.
(4) Always align the center of the wall hole. If misaligned, water leakage
will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the wall cap,
fasten the cap with vinyl tape, and stick the pipe through the hole.
(The connection pipe is supplied in the installation set.) (Fig. 9).
(6) For 5 left piping and 2 right piping, cut the hole a little lower so that
drain water will flow freely (Fig. 9).
4. CUT-OUT FOR PIPING ON FRONT PANEL
[For 2 Right piping, 3 Bottom piping and 5 Left piping]
• Use a metal shears or other cutting tool to cut along the groove in the
plastic for the piping that will coming out of the front panel.
Fig. 11
Fig. 9
Center mark
Lower
315
10 mm
or over
80 mm dia. hole
Lower
10 mm
or over
For 2 Right piping
5. FORMING THE DRAIN HOSE AND PIPE
For 3 Bottom piping
CAUTION
For 5 Left piping
(1) Do not remove the flare nut from the indoor unit pipe
until immediately before connecting the connection
Fasten with
vinyl tape
5 to 10 mm low
pipe.
(2) To prevent breaking of the pipe, avoid sharp bends.
• Perform “5 ELECTRICAL WIRING” before performing this piping.
• Wrap the pipes of the indoor unit that are visible from the outside with
decorative tape.
• After passing the indoor piping and drain hose through the wall hole,
hang the indoor unit on the hooks at the top of the wall hook bracket.
Fig. 14
Top hook
Indoor unit
Wall hook bracket
[For 4 Left rear piping, 5 Left piping and 6 Center piping]
• For 4 Left rear piping, 5 Left piping and 6 Center piping, preset the
end of the pipe to the dimensions shown in Fig. 15 and form the connection pipe.
• Bend the connection piping at a bend radius of at least 100 mm and
position it no more than 50 mm from the wall.
Fig. 15
Connection pipe
(9.52 mm dia.)
Connection pipe
(15.88 mm dia.)
Bend the pipe with a radius of curvature of 100 mm or
(Wall pipe)
Wall cap
(Inside)
Wall
(Outside)
3. ATTACH THE DRAIN HOSE.
CAUTION
Insert the drain hose and drain cap into the drain port,
making sure that it comes in contact with the back of the
drain port, and then mount it. If the drain hose is not connected properly, leaking will occur.
[For 1 Rear piping, 2 Right piping and 3 Bottom piping]
• The drain hose and drain cap are used as they are.
[For 4 Left rear piping, 5 Left piping and 6 Center piping]
• Remove the drain cap and drain hose. Mount the drain cap and drain
hose to the drain port on its opposite side.
Fig. 10
Left side
Drain hose
Right side
Drain cap
Drain hose
Drain cap
Insert the drain cap until it
butts against the drain port.
Insert the drain hose until it
butts against the drain port.
over.
(3) If the pipe is bent repeatedly at the same place, it will
break.
[For 1 Rear piping, 2 Right piping and 3 Bottom piping]
• Install the indoor unit piping in the direction of the wall hole and bind the
drain hose and pipe together with vinyl tape (Fig. 12).
• Install the piping so that the drain hose is at the bottom.
Fig. 12
Decorative tape
pipe (top)
2 Right piping
Drain hose (bottom)
Bind with vinyl tape
3 Bottom piping
1 Rear piping
CAUTION
Do not wrap the tape too tightly on drain hose. If the tape
is too tight (as shown in the Figure below) the insulation
effect will be lost and the moisture from condensation may
accumulate.
Fig. 13 Bad Example
Vinyl Tape Too Tight
About 380 mm
Bend (R100) with
a pipe bender
•
The two methods for mounting the drain hose and piping 4, 5 and 6 are
as shown below. Please choose the most efficient method of installation.
Method A : Floating the panel method.
Method B : Removing the panel.
About 460 mm
Method A
(1) Create a box using material from the packing carton. This box is called
the support box. (Fig. 16)
(2) Mount the indoor unit to the wall hook bracket.
(3)
Insert the support box between the indoor unit and wall hook bracket. (Fig. 17)
(4) Mount the drain hose and pipe to the indoor unit. (Fig. 18)
(5) Remove the support box from the indoor unit. (Fig. 19)
(6) Hang the inside panel hook. (Fig. 20)
Fig. 16
Carton
Support box
Fig. 17
Wall hook
bracket
Indoor unit
Support box
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject to
vibration.
(2) The inlet and outlet ports should not be obstructed : the air should be
able to blow all over the room.
(3) Do not install the unit where it will be exposed to direct sunlight.
(4) Install the unit where connection to the outdoor unit is easy.
(5) Install the unit where the drain pipe can be easily installed.
(6) Take servicing, etc. into consideration and leave the spaces shown in
Fig. 1. Also install the unit where the filter can be removed.
Fig. 1
Left side
5 cm
or over
6 cm or over
150 cm
or over
150 to 200 cm
Right side
5 cm
or over
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to direct
sunlight. (If necessary, install a blind that does not interfere with the
air flow.)
(2) Do not install the unit where a strong wind blows or where it is very
dusty.
(3) Do not install the unit where people pass.
(4) Take your neighbors into consideration so that they are not disturbed
by air blowing into their windows or by noise.
(5) Provide the space shown in Fig. 2 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four directions
front, rear, and both sides.
Fig. 2
60 cm
or over
30 cm
or over
60 cm
or over
80.4 cm
30 cm
or over
40 cm
or over
33.3 cm
Fig. 3
INDOOR UNIT
To power
supply
9.52 mm
(3/8”) dia.
OUTDOOR UNIT
15.88 mm
(5/8”) dia.
CONNECTION PIPE REQUIREMENT
Table 1
Diameter
Small Large
9.52 mm (3/8 in.)
••
• Use 0.7 mm to 1.2 mm thick pipe.
••
••
• Use pipe with water-resistant heat insulation.
••
••
• Use pipe that can withstand a pressure of 3,040 kPa.
••
15.88 mm (5/8 in.)
Maximum
length
20 m (66 ft) 8 m (26 ft)
Maximum Height
(between indoor
and outdoor)
ELECTRICAL REQUIREMENT
••
• Electric wire size and fuse capacity:
••
Table 2
MODEL
Power supply cord (mm
Connection cord (mm
Fuse capacity (A)
••
• Install the disconnect device with a contact gap of at least 3 mm nearby
••
the units. (Both indoor unit and outdoor unit)
••
• Always make the air conditioner power supply a special branch circuit
••
and provide a special breaker.
••
• Always use H07RN-F or equivalent as the power supply cord and the
••
connection cord.
2
)
2
)
18,000 BTU class 24,000 BTU class
MAX.
MIN.
MAX.
MIN.
3.5 4.0
2.5 3.5
2.5 2.5
1.5 1.5
20 30
• Piping work can be made easier by laying out, shaping, and temporarily
fastening the connection pipe and connection cord as shown in Fig. 18
beforehand.
Fig. 18 (4 Left rear piping)
Drain hose
Connect the piping
Connection pipe
Connection cord
Fig. 19
Fig. 20
Wall hook bracket
Hook
2 places
Panel
Method B
(1) Open the screw cover and intake grille. (Fig. 21)
(2) Remove the seven tapping screws. (Fig. 22)
(3) Remove the panel. (Fig. 23)
(4) Mount the indoor unit to the wall hook bracket.
(5) Mount the drain hose and pipe to the indoor unit. (Fig. 24)
(6) Hang the inside panel hook and then mount the panel and secure it
with seven tapping screws. (Fig. 25)
Fig. 21
Intake grille
Fig. 22
Fig. 23
Screw cover
Tapping screw
Panel
• Piping work can be made easier by laying out, shaping, and temporarily
fastening the connection pipe and connection cord as shown in Fig. 24
beforehand.
Fig. 24 (4 Left rear piping)
Drain hose
Connection pipe
Connection cord
Connect the piping
Fig. 25
Panel
3 places
Panel
Tapping screw
Wall hook
bracket
Hook
Hook
2 places
2
OUTDOOR UNIT INSTALLATION
WARNING
(1) Install the unit where it will not be tilted by more than
5˚.
(2) When installing the outdoor unit where it may exposed
to strong wind, fasten it securely.
• Set the unit on a strong stand, such as one made of concrete blocks to
minimize shock and vibration.
• Do not set the unit directly on the ground because it will cause trouble.
• Since the drain water flows out of the outdoor unit during heating op-
eration, install the drain pipe sold separately and connect it to an commercial 16 mm hose. (Heat & Cool model (Reverse cycle) only)
• When installing the drain pipe, plug all the holes (• holes at two places)
other than the drain pipe mounting hole in the bottom of the outdoor
unit with putty so there is no water leakage. (Fig. 26) (Heat & Cool
model (Reverse cycle) only)
NOTE:
Installation in cold regions. Do not use the accessory drain pipe.
(If the drain pipe is used, the drain water in the pipe may freeze in
extremely cold weather.)
Fig. 26
804 mm (31-21/32”)
Drain pipe
mounting hole
333 mm (13-7/64”)
3
Plug the holes.
Bottom
Drain pipe mounting hole
Drain pipe (sold separately)
CONNECTING THE PIPING
CAUTION
The maximum lengths of this product are shown in Table
1. If the units are further apart than this, correct operation
can not be guaranteed.
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and
remove the burrs.
(3) Insert the flare nut onto the pipe and flare the pipe with a flaring tool.
Fig. 27
L
Check if [L] is flared uniformly and
is not cracked or scratched.
Table 3
Pipe
9.52 mm dia.
15.88 mm dia.
L dimension
1.8 to 2.0 mm
2.2 to 2.4 mm
2. BENDING PIPES
(1) When bending the pipe, be careful not to crush it.
(2) To prevent crushing of the pipe, do not bend the pipe at a radius cur-
vature of 100 mm or over.
(3) If the copper pipe is bend the pipe or pulled to often, it will become
stiff. Do not bend the pipes more than three times at one place.
3. CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional installation
set or procured at the site) to the wall hole pipe.
(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the flare surface and tightening the nut
hand tight, tighten the nut to the specified tightening torque with a
torque wrench.
Fig. 28
Tighten with two wrenches.
Wrench (fixed)
Flare nut
Torque wrench
Indoor unit
pipe
Connection pipe
Table 4 Flare nut tightening torque
Flare nut
9.52 mm (3/8 in.) dia.
15.88 mm (5/8 in.) dia.
Do not remove the cap from the connection pipe before connecting
the pipe.
4
VACUUM PROCESS
30.4 to 34.3 N · m (310 to 350 kgf · cm)
73.6 to 78.5 N · m (750 to 800 kgf · cm)
Tightening torque
CAUTION
(1) When moving and installing the room air conditioner,
do not mix gas other than the specified refrigerant (R22)
inside the refrigerant cycle.
(2) Charging of additional refrigerant (R22) according to
the piping length is unnecessary.
To prevent gas
leakage, coat the
flare surface with
refrigerator oil.
1. VACUUM
(1) Remove the cap, and connect the gauge manifold and the vacuum
pump to the charging valve by the service hoses.
(2) Vacuum the indoor unit and the connecting pipes until the pressure in
them lowers to below 1.5 mmHg.
(3) Disconnect the service hoses and fit the cap to the charging valve
(Tightening torque : 70 to 90 kgf · cm).
(4) Remove the blank caps, and fully open the spindles of the 2-way and
3-way valves with a hexagon wrench (Torque : 2-way valve: 70 to 90
kgf · cm, 3-way valve: 100 to 120 kgf · cm).
(5) Tighten the blank caps of the 2-way valve and 3-way valve to the
specified torque (200 to 250 kgf · cm).
Fig. 29
Connecting pipe
Blank cap
Outdoor unit
Service hose
with valve core
3-way valve
Charging port
Cap
Service hose
Hexagon wrench
Gauge
manifold
Vacuum
pump
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor
unit at the factory.
When the piping is longer than 7.5 m, additional charging is necessary.
For the additional amount, see the table below.
Table 5
7.5 m
10 m
15 m
300 g
150 g
20 m
(66 ft)
500 g
(17.7 oz)
250 g
(8.9 oz)
40 g/1 m
(1.41 oz/3.3 ft)
20 g/1 m
(0.71 oz/3.3 ft)
Pipe length
Heat&cool
model
Additional
refrigerant
Between 7.5 m and 20 m, when using a connection pipe other than that in
the table, charge additional refrigerant with 40 g (1.41 oz) / 1 m (3.3 ft)
(Heat & Cool model (Reverse cycle)), 20 g (0.71 oz) / 1 m (3.3 ft) (Cooling
model) as the criteria.
(Reverse cycle)
Cooling
model
(25 ft)
None
None
(33 ft)
100 g
(3.5 oz)
50 g
(1.8 oz)
(49 ft)
(10.6 oz)
(5.3 oz)
3. GAS LEAKAGE INSPECTION
CAUTION
After connecting the piping, check the joints for gas leakage with gas leak detector.
- Continuted on back -
5
ELECTRICAL WIRING
WARNING
(1) Before starting work, check that power is not being sup-
plied to indoor unit and the outdoor unit.
(2) Match the terminal block numbers and connection cord
colors of the indoor unit and the outdoor unit. Erroneous wiring may cause burning of the electric parts.
(3) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
(4) Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)
(5) Always connect the ground wire.
HOW TO CONNECT WIRING
TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 25 mm (15/16”) to expose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using pliers, bend the solid wire to form a loop suitable for the
terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 10 mm (3/8”) to expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using a round terminal fastener or pliers, securely clamp a round
terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the ter-
minal screw using a screwdriver.
Fig. 30
A. Solid wire
”)
Insulation
Strip 25 mm (15/16
Wire
Loop
Screw with
special washer
Round
terminal
Terminal
board
Wire
Terminal block
B. Strand wire
”)
Strip 10 mm (3/8
Round
terminal
Screw with
special washer
Round
terminal
1. CONNECTION DIAGRAM
Fig. 31
[Heat & Cool model (Reverse cycle)]
Connection cord
6
5
4
3
2(N)
1(L)
Indoor unit side
terminal block
To power supply
and ground
Power supply cord
6
5
4
3
2(N)
1(L)
N
L
Outdoor unit side
terminal block
[Cooling model]
Connection cord
3
2
(N)
1
(L)
Indoor unit side
terminal block
To power supply
and ground
Power supply cord
3
2
(N)
1
(L)
N
L
Outdoor unit side
terminal block
2. INDOOR UNIT SIDE
(1) Open the intake grille. Remove the tapping screw for the control box
cover and remove the control box cover. (Fig. 32)
(2) Remove the tapping screw and while minding the cord holder hook,
remove the cord holder. (Fig. 33)
(3) Connect the end of the connection cord fully into the terminal block.
(Fig. 34 and 35)
Fig. 32
Control box cover
Fig. 33
Cord holder
[Heat & Cool model (Reverse cycle)]
Fig. 34
1(L) 3 4 5 62(N)
Earth screw
Connection cord
[Cooling model]
Fig. 35
31(L) 2(N)
Earth screw
Hook
Terminal block
Terminal block
3. OUTDOOR UNIT SIDE
CAUTION
Use VW-1, 12 mm diamater, 0.5 to 1.0 mm thick, connection PVC tube as the insulation tube.
(1) Remove the outdoor unit terminal cover and cord clamp. (Fig. 36)
(2)
Process the end of the connection cords to the dimensions shown in Fig. 38.
(3) Connect the end of the connection cord fully into the terminal block
and fasten with the screws.
(4) Fasten the sheath with a cord clamp. (Fig. 37)
(5) Install the terminal cover.
Fig. 36
Cord clamp
Terminal cover
Outdoor unit
Fig. 37
After passing the connection
cord through the insulation
tube, fasten it with the cord
clamp.
Fig. 38
[Heat & Cool model (Reverse cycle)]
NL1
(L)2(N)
Terminal block
Power supply cord
3456
Control
box
Cord clamp
Insulation tube
Connection cord
[Cooling model]
NL1
(L)2(N)
Terminal block
3
Control
box
6
FINISHING
1. CONNECTION PIPE, CORD AND DRAIN HOSE
(1) Insulate between pipes.
• For 1 Rear, 2 Right, and 3 Bottom piping, overlap the connec-
tion pipe heat insulation and indoor unit pipe heat insulation and
bind them with vinyl tape so that there is no gap. (Fig. 39)
• For 4 Left rear and 5 Left piping, butt the connection pipe heat
insulation and indoor unit pipe heat insulation together and bind
them with vinyl tape so that there is no gap. (Fig. 40)
Fig. 39 (1 Rear, 2 Right, and 3 Bottom piping)
Overlap the insulation.
Indoor unit pipe
Connection pipe
(heat insulation)
Bind the pipes together so
that there is no gap.
• For 4 Left rear piping, 5 Left piping and 6 Center piping, wrap the
area which accommodates the rear piping housing section with cloth
tape.
Fig. 40
Connection pipe
• For 4 Left rear piping, 5 Left piping and 6 Center piping bind the
(4 Left rear piping, 5 Left piping and 6 Center piping)
Cloth tape
connection cord to the top of the pipe with vinyl tape.
Fig. 41
Connection cord
Vinyl tape
Check that:
• When connected from the left rear, the drain hose is at the bottom
left of the wall pipe.
Fig. 42
(For connection from the left rear)
Connection cord
Drain hose
(heat insulation)
Vinyl tape
Indoor unit pipe
Wrap with cloth tape.
Pipe
(View from indoors)
Wall pipe
Connection pipe
(2) Temporarily fasten the connection cord along the connection pipe with
vinyl tape. (Wrap to about 1/3 the width of the tape from the bottom of
the pipe so that water does not enter.)
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer
so that rain water and wind cannot blow in.
Fig. 43
Outside wall cap
Saddle
Sealer putty
Pipe
Wall
(5) Fasten the drain hose to the outside wall, etc.
(Outdoors)
Fig. 44
Check the following:
GOOD BAD BAD BAD
Drain hose
Lifted up
Saddle
Wave
End in water
2. INSTALLING FINAL PARTS
(1) Secure the cord holder with tapping screw. (Fig. 45)
(2) Secure the control box cover and tapping screw. (Fig. 45)
(3) Close the intake grille. (Fig. 46)
Fig. 45 (1 Rear piping)
Control box
cover
Cord holder
Fig. 46
Intake grille
Check that:
• The top and bottom hooks are hooked firmly and the indoor unit
does not move to the front and rear or left and right.
• The indoor unit is accurately positioned horizontally and vertically.
Fig. 47
7
POWER
WARNING
(1) The rated voltage of this product is 220-240 V A.C.
50 Hz.
(2) Before turning on the verify that the voltage is within
the 198 V to 264 V range.
(3) Always use a special branch circuit and install a spe-
cial breaker to supply power to the room air conditioner.
(4) Use a circuit breaker matched to the capacity of the
room air conditioner. (Install in accordance with standard)
(5) The circuit breaker is installed in the permanent wir-
ing. Always use a circuit that can trip all the poles of
the wiring and has an isolation distance of at least 3
mm between the contacts of each pole.
(6) Perform wiring work in accordance with standards so
that the room air conditioner can be operated safely
and positively.
(7) Install a leakage circuit breaker in accordance with the
related laws and regulations and electric company
standards.
CAUTION
(1) The power source capacity must be the sum of the room
air conditioner current and the current of other electrical appliances. When the current contracted capacity
is insufficient, change the contracted capacity.
(2) When the voltage is low and the air conditioner is diffi-
cult to start, contact the power company the voltage
raised.
8
• Perform test operation and check items 1 and 2 below.
• For the operation method, refer to the operating manual.
• The outdoor unit may not run, depending on the room temperature.
In this case, press the test run button at the back of the remote control
unit while the room air conditioner is running.
(With the transmit section of the remote control unit facing the body,
press the TEST RUN button with the tip of a ball point pen.)
Fig. 48
Operation can be checked by lighting and flashing of the display section
OPERATION and TIMER lamps.
Perform judgement in accordance with the following.
• Test running
When the air conditioner is run by pressing the remote control unit
test run button, the OPERATION and TIMER lamps flash slowly at
the same time.
• Error
The OPERATION, TIMER and SWING lamps operate as follows (Table 6) according to the error contents.
TEST RUNNING
Remote control
unit (rear)
TEST RUN button
TIME ADJUST button
Table 6
(RED)
2 times
2 times
3 times
3 times
6 times
Error display
TIMER SWING
(GREEN)
(ORANGE)
—
—
—
—
Error contents
Indoor unit circuit board error
Indoor unit room temperature sensor wire
opened
Indoor unit room temperature sensor wire
short circuited
Indoor unit piping sensor wire opened
Indoor unit piping sensor short circuited
Indoor unit fan error
: Fast flashing : Slow flashing — :Off
OPERATION
CHECK ITEMS
(1) INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do not air flow direction louvers operate normally?
(4) Is the drain normal?
(5) Is there any abnormal noise and vibration during operation?
(2) OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
9
REMOTE CONTROL UNIT
INSTALLATION
CAUTION
(1) Check that the indoor unit correctly receives the sig-
nal from the remote control unit, then install the remote
control unit holder.
(2) Select the remote control unit holder selection site by
paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from
a stove, etc.
1. REMOTE CONTROL UNIT HOLDER INSTALLATION
• Install the remote control unit with a distance of 7 m between the re-
mote control unit and the photocell as the criteria. However, when installing the remote control unit, check that it operates positively.
• Install the remote control unit holder to a wall, pillar, etc. with the tap-
ping screw (Fig. 49).
Connection cord
Power supply
cord
Cord clamp
Insulation tube
Connection cord
• Do not operate the air conditioner in the test running state for a long
time.
• For the operation method, refer to the operating manual and perform
operation check.
Panel
Fig. 49
Remote control unit
holder fixing
Remote control
unit holder
Tapping
screw
(small)
10
CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating
manual:
(1) Starting and stopping method, operation switching, temperature ad-
justment, timer, air flow switching, and other remote control unit op-
erations.
(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating manual and installation instruction sheet to the
customer.
1 Set
2 Push
Remote
control unit
Remote control
unit mounting
PART NO. 9369233012