Energy saving (AO A24LACL, AO A24LALL connection model)
High energy saving was realized by making the indoor unit and outdoor
unit fan motor and compressor all DC and optimal design of the refrigerant cycle. Rank A was achieved in European energy rank.
Installation styles
Embedded in Ceiling
Hanging from Ceiling
DUCT TYPE
AR A24L
Slim & compact design
In the case of bottom suction type, as seen from lower rear part.
Control Box united with main unit
One-touch operating and easy-to-install
long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further
com-pactification is attained by reducing 65 mm from the width with the
flanking control box embedded inside the chassis.
- (01 - 01) -
EASY MAINTENANCE
DUCT TYPE
AR A24L
In the case of rear suction type, as seen from lower rear part.
1
1. Control box
4
2. Fan casing
3. Fan
4. Motor
2
3
Bottom panel: 2 units
The motor and fan maintenance and dismounting can be made easily by removing
the rear panel and lower part of the casing with the main chassis installed.
Quiet mode
Operation at *25dB(A) possible by Quiet Mode.
* See our measurement conditions page (01-14).
DUCT TYPE
AR A24L
FUNCTION SETTING
Static pressure mode setting
Air flow, noise, etc. can be used under the optimum conditions by selecting
the static pressure mode matched to the installation conditions.
Room temperature adjustment correction
Suitable room temperature control is performed by changing the room temperature correction value by simple remote control operation to match the
conditions under which the air conditioner is installed.
Auto restart
The units restart automatically when the current was returned even when
there was a power interruption during operation.
- (01 - 02) -
2. REMOTE CONTROLLER
WIRED REMOTE CONTROLLER
DUCT TYPE
AR A24L
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Economy operation are possible.
Easy installation with a slim shape with no bulge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
DUCT TYPE
AR A24L
High performance and compact size
Three functions are combined in
one unit.
Wired
remote
controller
Built-in timers
Possible to set ON/OFF time to operate twice each day
of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
At "Weekly timer" + "Set back timer" setup
Easy-to-understand time bar display
SUMOTUWETH FR SA
7
3126 9
15 18 21
24°C
24°C 28°C 24°C
Screen
after setup
Weekly
timer
Setback
timer
Setback timerWeekly timer
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
0 3 6 9 12 15 18 21 Time
24°C
0 3 6 9 12 15 18 21 Time
28°C
28°C
Easy-to-understand operationSimple installation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
Timer
area
[
Variable timer control
]
Operation
area
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
- (01 - 03) -
needed.
European
switch box
JIS box
DUCT TYPE
AR A24L
FUNCTIONS
2
6
7
8
9
10
11
Display panel
16
19
20
18
17
15
13
12
14
DUCT TYPE
1
START/STOP button
Pressed to start and stop operation.
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
1
3
4
5
Fan control button
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
5
Economy button
Turns the economy efficient mode on and off.
6
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER).
Set the current time.
7
Day (DAY OFF) button
Temporarily cancels of one day timer.
8
Set back button
Pressed to select the set back timer.
9
Set time button
Pressed to set time.
10
Delete button
The schedule of a weekly timer is deleted.
11
Set button
Sets the date, hour, minute and on-off time.
12
Vertical airflow direction and swing button*
Push for two seconds to change the swing mode.
13
Horizontal airflow direction and swing button*
Push for two seconds to change the swing mode.
AR A24L
DIMENSION
120
Front View
SPECIFICATION
21
[ Unit : mm ]
120
14
Filter button*
15
Operation lamp
Lights during operation and when the timer is on.
16
Timer and clock display
17
17
Operation mode display
18
Fan speed display
19
Operation lock display
20
Temperature display
21
Function display
Defrost display
Thermo sensor display
Economy display
Vertical swing display*
Horizontal swing display*
Filter display*
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT ( g )160
CABLE LENGTH ( m )
POWER ( V )
10
12
*These functions are not available.
- (01 - 04) -
3. SPECIFICATIONS
DUCT TYPE
AR A24L
Type
Model name
Power source
Available voltage range
European energy label
Cooling
Capacity
Heating
Input power
Current
EER3.21
COP3.61
Moisture removal
Fan
Recommended static pressurePa30 to 150
Sound pressure level
Heat exchanger type
Enclosure
Dimensions
( H×W ×D )
Weight
Connection pipe
Operation range
Remote controller type
Drain pipe
Cooling
Heating
Cooling
Heating
Airflow
rate
Type × Q'tySirocco × 2
Motor outputW115
Net270 × 1135 × 700
Gross300 × 1300 × 790
Net38 ( 84 )
Gross45 ( 99 )
Sizemm
MethodFlare
Material
Size
Rated
Min.-Max.
Rated
Min.-Max.
Rated
*Max.
Rated
*Max.
Rated
*Max.
Rated
*Max.
Cooling
Heating
Cooling
Heating
Cooling
Heating
Dimensions (H × W × D)294 × 1000 × 39.9
Fin pitch1.40
Rows x Stages3 × 14
Pipe typeCopper
Fin type Aluminium
MaterialSteel
Colour
Liquid 6.35 ( 1 / 4 in.)
Gas 15.88 ( 5 / 8 in.)
Cooling
Heating°C30 or less
CoolingA
HeatingA
kW7.10
BTU/h24200
kW0.90 - 8.00
BTU/h3100 - 27300
kW8.00
BTU/h27300
kW0.90 - 9.10
BTU/h3100 - 31000
kW
A
kW/kW
l/h (pints/h)2.5 (4.4)
High1100
Med950
Low800
Quiet600
Quiet600
Quiet25
Quiet25
m3/h
High1100
Med950
Low800
High31
Med29
Low27
dB(A)
High31
Med29
Low27
mm
mm
kg(lb.)
°C18 to 32
%RH 80 or less
mmOuter diameter : 38.0 / Inner diameter : 36.0
DUCTED MODEL
INVERTER HEATPUMP
AR A24LATU
AO A24LACL, AO A24LALL
230V50Hz
198-264V 50Hz
2.21
2.85
2.21
3.19
9.7
12.0
9.7
13.5
Wired
Steel
DUCT TYPE
AR A24L
Note :
Specifications are ased on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24°CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 30 Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
*
The maximum current and the maximum input value are the maximum values when operated within the operation range (temperature).
- (01 - 05) -
DUCTED MODEL
INVERTER HEATPUMP
AR A24LATU
AO B24LACL, AO B24LALL
230V50Hz
198-264V 50Hz
CoolingB
HeatingB
kW7.10
BTU/h24200
kW0.90 - 7.80
BTU/h3100 - 26600
kW8.00
BTU/h27300
kW0.90 - 8.80
BTU/h3100 - 30000
2.32
2.85
2.33
3.19
10.1
12.0
10.2
13.5
EER3.06
COP3.43
l/h (pints/h)2.5 (4.4)
High1100
Med950
Low800
Quiet600
High1100
Med950
Low800
Quiet600
Type × Q'tySirocco × 2
Motor outputW115
Recommended static pressurePa30 to 150
High31
Med29
Low27
Quiet25
High31
Med29
Low27
Quiet25
Dimensions (H × W × D)294 × 1000 × 39.9
Fin ptich1.40
Rows x Stages3 × 14
Pipe typeCopper
Fin type Aluminium
MaterialSteel
Colour
Net270 × 1135 × 700
Gross300 × 1300 × 790
Net38 ( 84 )
Gross45 ( 99 )
Liquidφ 6.35 (φ 1 / 4 in.)
Gasφ15.88 (φ 5 / 8 in.)
MethodFlare
°C18 to 32
%RH 80 or less
Heating°C30 or less
Wired
Steel
mmOuter diameter 38.0 / Inner diameter 36.0
Operation range
Cooling
Remote controller type
Drain pipe
Material
Size
Weightkg(lb.)
Connection pipe
Sizemm
Heat exchanger type
mm
Enclosure
Dimensions
( H×W ×D )
mm
Sound pressure level
Cooling
dB(A)
Heating
Fan
Airflow
rate
Cooling
m3/h
Heating
Cooling
kW/kW
Heating
Moisture removal
Current
Cooling
Rated
A
*Max.
Heating
Rated
*Max.
Input power
Cooling
Rated
kW
*Max.
Heating
Rated
*Max.
Capacity
Cooling
Rated
Min.-Max.
Heating
Rated
Min.-Max.
Type
Power source
Available voltage range
European energy label
Model name
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24°CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 30 Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
The maximum current and the maximum input value are the maximum values when operated within the operation range (temperature).
- (01 - 06) -
DUCT TYPE
AR A24L
DUCT TYPE
AR A24L
4. DIMENSIONS
MODEL : AR A24L
DUCT TYPE
AR A24L
Front view
(Unit : mm)
DUCT TYPE
AR A24L
Side view (L)
Top view
Rear view
Side view (R)
Refrigerant piping flare connection (Gas)
Refrigerant piping flare connection (Liquid)
Drain piping connection
Drain piping connection with cap.
Knock out hole for fresh air.
- (01 - 07) -
DUCT TYPE
AR A24L
MOUNTING POSITION
MAINTENANCE HOLE
(Unit : mm)
DUCT TYPE
AR A24L
It shall be possible to install and remove
the control box.
WHEN USING A SQUARE DUCT
It shall be possible to install and remove
the control box, fan units and filter.