High energy saving was realized by making the indoor unit and outdoor
unit fan motor and compressor all DC and optimal design of the refrigerant cycle. Rank A was achieved in European energy rank.
Installation styles
Embedded in Ceiling
Hanging from Ceiling
Slim & compact design
In the case of bottom suction type, as seen from lower rear part.
Control Box united with main unit
One-touch operating and easy-to-install
long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further compactification is attained by reducing 65 mm from the width with the flanking
control box embedded inside the chassis.
- (01 - 01) -
Page 3
EASY MAINTENANCE
DUCT TYPE
AR A24L
In the case of rear suction type, as seen from lower rear part.
4
1
1.Control box
DUCT TYPE
AR A24L
2.Fan casing
3.Fan
2
4.Motor
3
Bottom panel: 2 units
The motor and fan maintenance and dismounting can be made easily by removing
the rear panel and lower part of the casing with the main chassis installed.
Quiet mode
Operation at *25dB(A) possible by Quiet Mode.
* See our measurement conditions page (01-14).
Static pressure mode setting
Air flow, noise, etc. can be used under the optimum conditions by selecting
the static pressure mode matched to the installation conditions.
Room temperature adjustment correction
Suitable room temperature control is performed by changing the room temperature correction value by simple remote control operation to match the
conditions under which the air conditioner is installed.
Auto restart
The units restart automatically when the current was returned even when
there was a power interruption during operation.
- (01 - 02) -
Page 4
2. COMBINATION
2-1. OUTDOOR UNIT
DUCT TYPE
AR A24L
MODEL : AO A24LACL
2-2. REMOTE CONTROLLER
2-2-1. WIRED REMOTE CONTROLLER
MODEL : UTB- UD
DUCT TYPE
AR A24L
CAUTION
Remote controller is not supplied with the indoor unit.
Separate purchase is necessary.
- (01 - 03) -
Page 5
3. SPECIFICATIONS
AR A24LATN
230V 50Hz
198-264V 50Hz
Pipe typeCopper
6.35 ( 1 / 4 in.)
15.88 ( 5 / 8 in.)
Type
Model name
mm
Rated
Min-Max
Rated
Min-Max
Rated
Min-Max
Power source
Available voltage range
Capacity
Cooling
Heating
European energy label
kW/kW
Input power
Cooling
kW
Heating
Rated
Min-Max
Current
Cooling
A
Rated
Max
Rated
Max
Heating
Cooling
Heating
Heating
Cooling
Moisture removal
Cooling
Heating
mm
Weight
m3/h
Fan
Dimensions
( H × W × D )
mm
Airflow
rate
Enclosure
Heat exchanger type
Sound pressure level
dB(A)
Remote controller type
Drain pipe
Material
Size
Operation range
Cooling
kg(lb.)
Connection pipe
Size
DUCT TYPE
AR A24L
EER3.21
COP3.61
Type × Q'tySirocco × 2
Motor outputW115
Recommended static pressurePa30 to 150
Dimensions (H × W × D)294 × 1000 × 39.9
Fin pich1.40
Rows x Stages3 × 14
DUCTED MODEL
INVERTER HEATPUMP
CoolingA
HeatingA
kW7.1
BTU/h24200
kW0.9 - 8.0
BTU/h3100 - 27300
kW8.0
BTU/h27300
kW0.9 - 9.1
BTU/h3100 - 31000
2.21
0.09 - 2.62
2.21
0.09 - 2.77
9.7
11.5
9.7
12.2
l/h (pints/h)2.5 (4.4)
High1100
Med950
Low800
Quiet600
High1100
Med950
Low800
Quiet600
High31
Med29
Low27
Quiet25
High31
Med29
Low27
Quiet25
DUCT TYPE
AR A24L
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 30 Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
Fin type Aluminium
MaterialSteel
Colour
Net270 × 1135 × 700
Gross300 × 1300 × 790
Net38 ( 84 )
Gross45 ( 99 )
Liquid
Gas
MethodFlare
°C18 to 32
%RH 80 or less
Heating°C30 or less
mmOuter diameter: 38.0 / Inner diameter: 36.0
- (01 - 04) -
-
Wired
Steel
Page 6
4. DIMENSIONS
MODEL : AR A24L
DUCT TYPE
AR A24L
Front view
(Unit : mm)
DUCT TYPE
AR A24L
Side view (L)
Top view
Rear view
Side view (R)
Refrigerant piping flare connection (Gas)
Refrigerant piping flare connection (Liquid)
Drain piping connection
Drain piping connection with cap.
Knock out hole for fresh air.
- (01 - 05) -
Page 7
MOUNTING POSITION
DUCT TYPE
AR A24L
(Unit : mm)
DUCT TYPE
AR A24L
MAINTENANCE HOLE
It shall be possible to install and remove
the control box.
WHEN USING A SQUARE DUCT
It shall be possible to install and remove
the control box, fan units and filter.
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB.
Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB.
Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
- (02 - 01) -
Page 21
2. DIMENSIONS
MODELS : AO A18L, AO A24L
OUTDOOR UNIT
AO A18-24L
Top view
(Unit : mm)
OUTDOOR UNIT
AO A18-24L
Front view
Bottom view
MOUNTING POSITION
When there are obstacles at the
back or front sides.
Air flow
When there are obstacles at the
back, side(s), and top.
AO A18LAO A24L
Side view
When there are obstacles at the
back, side with the installation of
more than one unit.
600 - 1000
100 or more
600 or more
100 - 300
300 or more
25
(
Ser
0
or
v
mor
i
c
e
s
e
pac
e)
250 or more
250 or more
If the space is larger that is stated, the condition will be the same as that are no obstacles.
- (02 - 02) -
300 or more
Page 22
3. REFRIGERANT CIRCUIT
OUTDOOR UNIT
AO A18-24L
OUTDOOR UNIT
AO A18-24L
- (02 - 03) -
Page 23
4. WIRING DIAGRAMS
MODELS : AO A18L, AO A24L
OUTDOOR UNIT
AO A18-24L
OUTDOOR UNIT
AO A18-24L
- (02 - 04) -
Page 24
5. COEFFICIENT OF COMPENSATION FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
MODEL : AO A18L
COOLING
57.510152025
15---
OUTDOOR UNIT
AO A18-24L
Indoor unit is upper
than outdoor unit.
Height
difference H
(m)
Indoor unit is under
than outdoor unit
HEATING
Indoor unit is upper
than outdoor unit.
Height
difference H
(m)
Indoor unit is under
than outdoor unit
1
2
1
2
10--
7.5-
5
01.0001.0000.9990.9840.9820.978
-5
-7.5-
-10--
-15---
15---
10--
7.5-
5
00.9931.0000.9820.9200.8940.867
-5
-7.5-
-10--
-15---
0.9920.9920.9910.9760.9740.970
1.0001.0000.9990.9840.9820.978
57.510152025
0.9931.0000.9820.9200.8940.867
0.9880.9950.9770.9160.8890.862
0.9880.9870.9720.9700.966
1.0000.9990.9840.9820.978
1.0000.9820.9200.8940.867
0.9930.9750.9130.8870.860
Pipe length (m)
0.9530.9500.947
0.9830.9680.9660.962
0.9990.9840.9820.978
0.9840.9820.978
Pipe length (m)
0.9200.8940.867
0.9820.9200.8940.867
0.9720.9110.8850.858
0.9020.8760.849
OUTDOOR UNIT
AO A18-24L
Indoor unit
H
Outdoor unit
Connection pipe
1
Indoor unit is upper than outdoor unit.
Height difference H
Outdoor unit
Connection pipe
2
Indoor unit is under than outdoor unit.
- (02 - 05) -
H
Indoor unit
Page 25
MODEL : AO A24L
COOLING
Pipe length (m)
57.51015202530
20
OUTDOOR UNIT
AO A18-24L
1
10
----0.9630.9610.959
--0.9840.9810.9790.9770.975
OUTDOOR UNIT
AO A18-24L
Indoor unit is upper
-0.9880.9880.9850.9830.9810.979
0.9920.9920.9920.9890.9870.9850.983
1.0001.0001.0000.9970.9950.9930.991
1.0001.0001.0000.9970.9950.9930.991
-1.0001.0000.9970.9950.9930.991
--1.0000.9970.9950.9930.991
----0.9950.9930.991
Height
difference H
(m)
than outdoor unit.
2
Indoor unit is under
than outdoor unit
7.5
5
0
-5
-7.5
-10
-20
Pipe length (m)
HEATING
57.51015202530
20----
1
10--
0.9920.9520.9270.8930.863
0.9270.8930.863
Indoor unit is upper
Height
difference H
(m)
than outdoor unit.
2
7.5-
5
1.0011.0000.9920.9520.9270.8930.863
01.0011.0000.9920.9520.9270.8930.863
-5
0.9960.9950.9870.9470.9220.8880.859
-7.5-
1.0000.9920.9520.9270.8930.863
0.9930.9840.9450.9200.8860.857
Indoor unit is under
than outdoor unit
-10--
-20----
0.9820.9430.9170.8840.855
0.9080.8750.846
Indoor unit
H
Outdoor unit
Connection pipe
1
Indoor unit is upper than outdoor unit.
Height difference H
Outdoor unit
Connection pipe
2
Indoor unit is under than outdoor unit.
- (02 - 06) -
H
Indoor unit
Page 26
6. ADDITIONAL CHARGE CALCULATION
20g/m
1700
R410A
1250
20g/m
R410A
MODEL : AO A18L
Refrigerant type
Refrigerant amountg
OUTDOOR UNIT
AO A18-24L
REFRIGERANT CHARGE
Pipe lengthm 152025
Additional chargeg0 (Chargeless)+100+200
OUTDOOR UNIT
AO A18-24L
MODEL : AO A24L
Refrigerant type
Refrigerant amountg
REFRIGERANT CHARGE
Pipe lengthm 15202530
Additional chargeg0 (Chargeless)+100+200+300
- (02 - 07) -
Page 27
7. AIR FLOW
m3/h
2000
m3/h
1910
m3/h
2470
m3/h
2470
1050
NUMBER OF
ROTATIONS
(r.p.m)
NUMBER OF
ROTATIONS
(r.p.m)
NUMBER OF
ROTATIONS
(r.p.m)
NUMBER OF
ROTATIONS
(r.p.m)
860
820
1050
Airflow
Airflow
Airflow
Airflow
MODEL : AO A18L
COOLING
OUTDOOR UNIT
AO A18-24L
HEATING
l/s556
CFM1177
OUTDOOR UNIT
AO A18-24L
l/s531
CFM1124
MODEL : AO A24L
COOLING
l/s686
CFM1454
HEATING
l/s686
CFM1454
- (02 - 08) -
Page 28
8. OPERATION NOISE
8-1. NOISE LEVEL CURVE
COOLING
MODEL : AO A18L
80
70
OUTDOOR UNIT
AO A18-24L
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
631252505 001,0002,0004,0008,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AO A24L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
631252505 001,0002,0004,0008,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
OUTDOOR UNIT
AO A18-24L
HEATING
MODEL : AO A18L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AO A24L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
631252505 001,0002,0004,0008,000
Octave band center frequency,Hz
- (02 - 09) -
0
631252505 001,0002,0004,0008,000
Octave band center frequency,Hz
Page 29
8-2. SOUND LEVEL CHECK POINT
OUTDOOR UNIT
AO A18-24L
OUTDOOR UNIT
AO A18-24L
- (02 - 10) -
Page 30
9. ELECTRIC CHARACTERISTICS
Model NameAOA18LAOA24L
VoltageV
230
Power Supply
FrequencyHz
50
Max Operating Current A15.016.2
OUTDOOR UNIT
AO A18-24L
Starting CurrentA7.710.0
*1) Wiring Spec.
Main Fuse (Circuit breaker)
Current
Power Cable
A2020
mm
2
3.5 - 4.5
OUTDOOR UNIT
AO A18-24L
*2)Limited wiring lengthm2422
*1) Wiring Spec.
Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length :
This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
- (02 - 11) -
Page 31
10. SAFETY DEVICES
AO A18LAO A24L
OFF:100
+15
-10
°C
ON:95
+15
-10
°C
OFF:110
+15
-10
°C
ON:105
+15
-10
°C
15A 250V
3.15A 250V
Compressor protection
Circuit protection
OFF:110°C
ON: After 40 minutes
OFF:110°C
ON: After 7 minutes
Current fuse (NEAR THE TERMINAL)
Current fuse
(MAIN PRINTED CIRCUIT BOARD)
Protection form
20A 250V
5A 250V
Model
OUTDOOR UNIT
AO A18-24L
Fan motor protectionThermal protection program
Thermal protection program
(COMPRESSOR TEMP.)
Thermal protection program
(DISCHARGE TEMP.)
OUTDOOR UNIT
AO A18-24L
- (02 - 12) -
Page 32
REMOTE CONTROLLER
3. WIRED REMOTE CONTROLLER
UTB - UD
:
D2D_RC001E/02
2007.09.03
Page 33
REMOTE CONTROLLER UTB- UD
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Economy operation are possible.
Easy installation with a slim shape with no bulge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
High performance and compact size
REMOTE CONTROLLER UTB- UD
Three functions are combined in
one unit.
Wired
remote
controller
Built-in timers
Possible to set ON/OFF time to operate twice each day
of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
At "Weekly timer" + "Set back timer" setup
Easy-to-understand time bar display
SUMOTUWETH FR SA
7
3126 9
15 18 21
24°C
24°C 28°C 24°C
Weekly
timer
Setback
timer
Setback timerWeekly timer
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
Screen
after setup
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
0 3 6 9 12 15 18 21 Time
24°C
0 3 6 9 12 15 18 21 Time
28°C
3126 9
15 18 21
28°C
Easy-to-understand operationSimple installation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
needed.
Timer
area
[
Variable timer control
]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
Operation
area
European
switch box
- (03 - 01) -
JIS box
Page 34
REMOTE CONTROLLER UTB- UD
FUNCTIONS
2
6
7
8
9
10
11
Display panel
16
19
20
18
17
15
13
12
14
1
START/STOP button
Pressed to start and stop operation.
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
1
3
4
5
Fan control button
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
5
Economy button
Turns the economy efficient mode on and off.
6
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
7
Day (DAY OFF) button
Temporarily cancels of one day timer.
8
Set back button
Pressed to select the set back timer.
9
Set time button
Pressed to set time.
10
Delete button
The schedule of a weekly timer is deleted.
11
Set button
Sets the date, hour, minute and on-off time.
12
Vertical airflow direction and swing button
Push for two seconds to change the swing mode.
13
Horizontal airflow direction and swing button
Push for two seconds to change the swing mode.
REMOTE CONTROLLER UTB- UD
DIMENSION
120
Front View
SPECIFICATION
21
[ Unit : mm ]
120
14
Filter button
15
Operation lamp
Lights during operation and when the timer is on.
16
Timer and clock display
17
17
Operation mode display
18
Fan speed display
19
Operation lock display
20
Temperature display
21
Function display
Defrost display
Thermo sensor display
Economy display
Vertical swing display
Horizontal swing display
Filter display
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT( g )160
CABLE LENGTH( m )
POWER( V )
10
12
- (03 - 02) -