AR A18LALUAO A18LACLAO B18LACL
AR F18LALUAO A18LALLAO B18LALL
FEATURES
Energy saving (AO A18LACL, AO A18LALL connection model)
High energy saving was realized by making the indoor unit and outdoor
unit fan motor and compressor all DC and optimal design of the refrigerant cycle. Rank A was achieved in European energy rank.
Universal design indoor unit
Since vertical and horizontal installation is possible, and the intake direction can also be selected
from two directions, flexible installation is possible.
Ceiling concealedFloor concealed
DUCT TYPE
AR A18L
Thin and compact indoor unit
Quiet mode
Operation at *27dB(A) possible by Quiet Mode.
* See our measurement conditions page (01-16).
FUNCTION SETTING
Static pressure mode setting
Air flow, noise, etc. can be used under the optimum conditions by selecting
the static pressure mode matched to the installation conditions.
Room temperature adjustment correction
Suitable room temperature control is performed by changing the room temperature correction value
by simple remote control operation to match the conditions under which the air conditioner is installed.
Auto restart
The units restart automatically when the current was returned even when
there was a power interruption during operation.
- (01 - 01) -
Page 3
2. REMOTE CONTROLLER
WIRED REMOTE CONTROLLER
DUCT TYPE
AR A18L
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Economy operation are possible.
Easy installation with a slim shape with no bulge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
DUCT TYPE
AR A18L
High performance and compact size
Three functions are combined in
one unit.
Wired
remote
controller
Weekly
timer
Setback
timer
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day
of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 18 21
Screen
after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
0 3 6 9 12 15 18 21 Time
24°C
28°C
Easy-to-understand operationSimple installation
15 18 21
28°C
Timer
area
[
Variable timer control
]
Operation
area
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
- (01 - 02) -
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
needed.
European
switch box
JIS box
Page 4
DUCT TYPE
AR A18L
FUNCTIONS
2
6
7
8
9
10
11
Display panel
16
19
20
18
17
15
13
12
14
DUCT TYPE
1
START/STOP button
Pressed to start and stop operation.
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
1
3
4
5
Fan control button
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
5
Economy button
Turns the economy efficient mode on and off.
6
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER).
Set the current time.
7
Day (DAY OFF) button
Temporarily cancels of one day timer.
8
Set back button
Pressed to select the set back timer.
9
Set time button
Pressed to set time.
10
Delete button
The schedule of a weekly timer is deleted.
11
Set button
Sets the date, hour, minute and on-off time.
12
Vertical airflow direction and swing button*
Push for two seconds to change the swing mode.
13
Horizontal airflow direction and swing button*
Push for two seconds to change the swing mode.
AR A18L
DIMENSION
120
Front View
SPECIFICATION
21
[ Unit : mm ]
120
14
Filter button*
15
Operation lamp
Lights during operation and when the timer is on.
16
Timer and clock display
17
17
Operation mode display
18
Fan speed display
19
Operation lock display
20
Temperature display
21
Function display
Defrost display
Thermo sensor display
Economy display
Vertical swing display*
Horizontal swing display*
Filter display*
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT ( g )160
CABLE LENGTH ( m )
POWER ( V )
10
12
*These functions are not available.
- (01 - 03) -
Page 5
DUCTED MODEL
INVERTER HEATPUMP
AR A18LALU, AR F18LALU
AO A18LACL, AO A18LALL
230V50Hz
198-264V 50Hz
CoolingA
HeatingA
kW5.20
BTU/h17700
kW0.90 - 5.90
BTU/h3100 - 20100
kW6.00
BTU/h20500
kW0.90 - 7.50
BTU/h3100 - 25600
1.62
2.16
1.66
2.96
7.1
9.0
7.3
12.5
EER3.21
COP3.61
l/h (pints/h)2.0 ( 3.5 )
High820
Med720
Low610
Quiet550
High820
Med720
Low610
Quiet550
Type × Q'tySirocco × 2
Motor outputW60
Recommended static pressurePa0 to 90
High33
Med31
Low29
Quiet27
High33
Med31
Low29
Quiet27
Dimensions (H × W × D)294 × 700 × 39.9
Fin pitch1.30
Rows x Stages3 × 14
Pipe typeCopper
Fin type Aluminium
MaterialSteel
Colour
Net217 × 953 × 595
Gross324 × 1075 × 686
Net23 ( 51 )
Gross27 ( 60 )
Liquid6.35 ( 1 / 4 in.)
Gas 12.70 ( 1 / 2 in.)
MethodFlare
°C18 to 32
%RH 80 or less
Heating°C30 or less
Wired
PS
mm
Outer diameter 26.0 / Inner diameter 21.5
Type
mm
Rated
Min.-Max.
Rated
Min.-Max.
Rated
*Max.
Power source
Available voltage range
Capacity
Cooling
Heating
European energy label
kW/kW
Input power
Cooling
kW
Heating
Rated
*Max.
Current
Cooling
A
Rated
*Max.
Rated
*Max.
Cooling
Heating
Heating
Cooling
Moisture removal
Cooling
Heating
m3/h
Fan
Dimensions
( H×W ×D )
mm
Airflow
rate
Enclosure
Heat exchanger type
Sound pressure level
Heating
kg(lb.)
Connection pipe
Size
mm
Weight
Model name
dB(A)
Remote controller type
Drain pipe
Material
Size
Operation range
Cooling
3. SPECIFICATIONS
DUCT TYPE
AR A18L
DUCT TYPE
AR A18L
- (01 - 04) -
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24°CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 0 Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
The maximum current and the maximum input value are the maximum values when operated within the operation range (temperature).
Page 6
DUCT TYPE
AR A18L
DUCT TYPE
AR A18L
- (01 - 05) -
DUCTED MODEL
INVERTER HEATPUMP
AR A18LALU, AR F18LALU
AO B18LACL, AO B18LALL
230V50Hz
198-264V 50Hz
CoolingB
HeatingB
kW5.20
BTU/h17700
kW0.90 - 5.70
BTU/h3100 - 19500
kW6.00
BTU/h20500
kW0.90 - 7.20
BTU/h3100 - 24600
1.70
2.16
1.75
2.96
7.4
9.0
7.7
12.5
EER3.06
COP3.43
l/h (pints/h)2.0 ( 3.5 )
High820
Med720
Low610
Quiet550
High820
Med720
Low610
Quiet550
Type × Q'tySirocco × 2
Motor outputW60
Recommended static pressurePa0 to 90
High33
Med31
Low29
Quiet27
High33
Med31
Low29
Quiet27
Dimensions (H × W × D)294 × 700 × 39.9
Fin pitch1.30
Rows x Stages3 × 14
Pipe typeCopper
Fin type Aluminium
MaterialSteel
Colour
Net217 × 953 × 595
Gross324 × 1075 × 686
Net23 ( 51 )
Gross27 ( 60 )
Liquid 6.35 ( 1 / 4 in.)
Gas 12.70 ( 1 / 2 in.)
MethodFlare
°C18 to 32
%RH 80 or less
Heating°C30 or less
Wired
PS
mm
Outer diameter 26.0 / Inner diameter 21.5
Operation range
Cooling
Remote controller type
Drain pipe
Material
Size
Weight
kg(lb.)
Connection pipe
Size
mm
Heat exchanger type
mm
Enclosure
Dimensions
( H×W ×D )
mm
Sound pressure level
Cooling
dB(A)
Heating
Fan
Airflow
rate
Cooling
m3/h
Heating
Cooling
kW/kW
Heating
Moisture removal
Current
Cooling
Rated
A
*Max.
Heating
Rated
*Max.
Input power
Cooling
Rated
kW
*Max.
Heating
Rated
*Max.
Capacity
Cooling
Rated
Min.-Max.
Heating
Rated
Min.-Max.
Type
Power source
Available voltage range
European energy label
Model name
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24°CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 0 Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
The maximum current and the maximum input value are the maximum values when operated within the operation range (temperature).
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB.
Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB.
Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
- (02 - 01) -
Page 23
2. DIMENSIONS
MODELS : AO A18L, AO A24L
OUTDOOR UNIT
AO A18-24L
Top view
(Unit : mm)
OUTDOOR UNIT
AO A18-24L
Front view
Bottom view
MOUNTING POSITION
When there are obstacles at the
back or front sides.
Air flow
When there are obstacles at the
back, side(s), and top.
AO A18LAO A24L
Side view
When there are obstacles at the
back, side with the installation of
more than one unit.
600 - 1000
100 or more
600 or more
100 - 300
250 or more
(Service space)
300 or more
250 or more
250 or more
If the space is larger that is stated, the condition will be the same as that are no obstacles.
- (02 - 02) -
300 or more
Page 24
3. REFRIGERANT CIRCUIT
OUTDOOR UNIT
AO A18-24L
OUTDOOR UNIT
AO A18-24L
- (02 - 03) -
Page 25
4. WIRING DIAGRAMS
MODELS : AO A18L, AO A24L
OUTDOOR UNIT
AO A18-24L
OUTDOOR UNIT
AO A18-24L
- (02 - 04) -
Page 26
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
MODEL : AO A18L
OUTDOOR UNIT
AO A18-24L
Height
difference H
(m)
Height
difference H
(m)
COOLING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
HEATING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Pipe length (m)
57.510152025
15---
10--
7.5-
5
01.0001.0000.9990.9840.9820.978
-5
-7.5-
-10--
-15---
15---
10--
7.5-
5
00.9931.0000.9820.9200.8940.867
-5
-7.5-
-10--
-15---
0.9920.9920.9910.9760.9740.970
1.0001.0000.9990.9840.9820.978
57.510152025
0.9931.0000.9820.9200.8940.867
0.9880.9950.9770.9160.8890.862
0.9880.9870.9720.9700.966
1.0000.9990.9840.9820.978
1.0000.9820.9200.8940.867
0.9930.9750.9130.8870.860
0.9830.9680.9660.962
0.9990.9840.9820.978
Pipe length (m)
0.9820.9200.8940.867
0.9720.9110.8850.858
0.9530.9500.947
0.9840.9820.978
0.9200.8940.867
0.9020.8760.849
OUTDOOR UNIT
AO A18-24L
Indoor unit
H
Outdoor unit
Connection pipe
1
Indoor unit is upper than outdoor unit.
Height difference H
Outdoor unit
Connection pipe
2
Indoor unit is under than outdoor unit.
- (02 - 05) -
H
Indoor unit
Page 27
MODEL : AO A24L
OUTDOOR UNIT
AO A18-24L
Height
difference H
(m)
Height
difference H
(m)
COOLING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
HEATING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Pipe length (m)
57.51015202530
20
10
7.5
5
0
-5
-7.5
-10
-20
----0.9630.9610.959
--0.9840.9810.9790.9770.975
-0.9880.9880.9850.9830.9810.979
0.9920.9920.9920.9890.9870.9850.983
1.0001.0001.0000.9970.9950.9930.991
1.0001.0001.0000.9970.9950.9930.991
-1.0001.0000.9970.9950.9930.991
--1.0000.9970.9950.9930.991
----0.9950.9930.991
Pipe length (m)
57.51015202530
20----
10--
7.5-
5
1.0011.0000.9920.9520.9270.8930.863
1.0000.9920.9520.9270.8930.863
0.9920.9520.9270.8930.863
0.9270.8930.863
01.0011.0000.9920.9520.9270.8930.863
-5
-7.5-
-10--
-20----
0.9960.9950.9870.9470.9220.8880.859
0.9930.9840.9450.9200.8860.857
0.9820.9430.9170.8840.855
0.9080.8750.846
OUTDOOR UNIT
AO A18-24L
Indoor unit
H
Outdoor unit
Connection pipe
1
Indoor unit is upper than outdoor unit.
Height difference H
Outdoor unit
Connection pipe
2
Indoor unit is under than outdoor unit.
- (02 - 06) -
H
Indoor unit
Page 28
6. ADDITIONAL CHARGE CALCULATION
20g/m
1700
R410A
1250
20g/m
R410A
MODEL : AO A18L
Refrigerant type
Refrigerant amountg
OUTDOOR UNIT
AO A18-24L
REFRIGERANT CHARGE
Pipe lengthm 152025
Additional chargeg0 (Chargeless)+100+200
MODEL : AO A24L
Refrigerant type
Refrigerant amountg
REFRIGERANT CHARGE
Pipe lengthm 15202530
Additional chargeg0 (Chargeless)+100+200+300
OUTDOOR UNIT
AO A18-24L
- (02 - 07) -
Page 29
7. AIR FLOW
m3/h
2000
m3/h
1910
m3/h
2470
m3/h
2470
1050
NUMBER OF
ROTATIONS
(r.p.m)
NUMBER OF
ROTATIONS
(r.p.m)
NUMBER OF
ROTATIONS
(r.p.m)
NUMBER OF
ROTATIONS
(r.p.m)
860
820
1050
Airflow
Airflow
Airflow
Airflow
MODEL : AO A18L
COOLING
OUTDOOR UNIT
AO A18-24L
HEATING
l/s556
CFM1177
OUTDOOR UNIT
AO A18-24L
l/s531
CFM1124
MODEL : AO A24L
COOLING
l/s686
CFM1454
HEATING
l/s686
CFM1454
- (02 - 08) -
Page 30
8. OPERATION NOISE
8-1. NOISE LEVEL CURVE
COOLING
OUTDOOR UNIT
AO A18-24L
MODEL : AO A18L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
631252505001,0002,0004,0008,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AO A24L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
631252505001,0002,0004,0008,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
OUTDOOR UNIT
AO A18-24L
HEATING
MODEL : AO A18L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AO A24L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
631252505001,0002,0004,0008,000
Octave band center frequency,Hz
- (02 - 09) -
0
631252505001,0002,0004,0008,000
Octave band center frequency,Hz
Page 31
8-2. SOUND LEVEL CHECK POINT
OUTDOOR UNIT
AO A18-24L
OUTDOOR UNIT
AO A18-24L
- (02 - 10) -
Page 32
9. ELECTRIC CHARACTERISTICS
Model NameAOA18LAOA24L
OUTDOOR UNIT
AO A18-24L
VoltageV
230
Power Supply
FrequencyHz
50
Max Operating Current A15.016.2
Starting CurrentA7.710.0
*1) Wiring Spec.
Main Fuse (Circuit breaker)
Current
Power Cable
A2020
mm
2
3.5 - 4.5
*2)Limited wiring lengthm2422
*1) Wiring Spec.
Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length :
This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
OUTDOOR UNIT
AO A18-24L
- (02 - 11) -
Page 33
10. SAFETY DEVICES
AO A18LAO A24L
OFF:100
+15
-10
°C
ON:95
+15
-10
°C
OFF:110
+15
-10
°C
ON:105
+15
-10
°C
15A 250V
3.15A 250V
Compressor protection
Circuit protection
OFF:110°C
ON: After 40 minutes
OFF:110°C
ON: After 7 minutes
Current fuse (NEAR THE TERMINAL)
Current fuse
(MAIN PRINTED CIRCUIT BOARD)
Protection form
20A 250V
5A 250V
Model
OUTDOOR UNIT
AO A18-24L
Fan motor protectionThermal protection program
Thermal protection program
(COMPRESSOR TEMP.)
Thermal protection program
(DISCHARGE TEMP.)
OUTDOOR UNIT
AO A18-24L
- (02 - 12) -
Page 34
R410A
D2D_AO021E/02
2008.04.08
2.
SINGLE TYPE :
AO B18LACL
AO B18LALL
OUTDOOR UNIT
AO B24LACL
AO B24LALL
Page 35
- (02 - 01) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
1. SPECIFICATIONS
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB.
Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB.
Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
When there are obstacles at the
back or front sides.
When there are obstacles at the
back, side(s), and top.
When there are obstacles at the
back, side with the installation of
more than one unit.
600 or more
250 or more
250 or more
300 or more
600 - 1000
100 or more
300 or more
100 - 300
250 or more
(Service space)
MOUNTING POSITION
Front view
AO B18LAO B24L
Side view
Bottom view
If the space is larger that is stated, the condition will be the same as that are no obstacles.
Page 37
- (02 - 03) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
3. REFRIGERANT CIRCUIT
Page 38
- (02 - 04) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
MODEL : AO B18L, AO B24L
4. WIRING DIAGRAMS
Page 39
- (02 - 05) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
MODEL : AO B18L
Indoor unit
Height difference H
Connection pipe
H
Outdoor unit
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is upper than outdoor unit.
1
Indoor unit is under than outdoor unit.
2
57.510152025
15---
0.9840.9820.978
10--
0.9990.9840.9820.978
7.5-
1.0000.9990.9840.9820.978
5
1.0001.0000.9990.9840.9820.978
01.0001.0000.9990.9840.9820.978
-5
0.9920.9920.9910.9760.9740.970
-7.5-
0.9880.9870.9720.9700.966
-10--
0.9830.9680.9660.962
-15---
0.9530.9500.947
57.510152025
15---
0.9020.8760.849
10--
0.9720.9110.8850.858
7.5-
0.9930.9750.9130.8870.860
5
0.9880.9950.9770.9160.8890.862
00.9931.0000.9820.9200.8940.867
-5
0.9931.0000.9820.9200.8940.867
-7.5-
1.0000.9820.9200.8940.867
-10--
0.9820.9200.8940.867
-15---
0.9200.8940.867
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Pipe length (m)
Pipe length (m)
HEATING
COOLING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Height
difference H
(m)
Page 40
- (02 - 06) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
MODEL : AO B24L
Indoor unit
Height difference H
Connection pipe
H
Outdoor unit
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is upper than outdoor unit.
1
Indoor unit is under than outdoor unit.
2
57.51015202530
20
10
7.5
5
0
-5
-7.5
-10
-20
57.51015202530
20----
0.9080.8750.846
10--
0.9820.9430.9170.8840.855
7.5-
0.9930.9840.9450.9200.8860.857
5
0.9960.9950.9870.9470.9220.8880.859
01.0011.0000.9920.9520.9270.8930.863
-5
1.0011.0000.9920.9520.9270.8930.863
-7.5-
1.0000.9920.9520.9270.8930.863
-10--
0.9920.9520.9270.8930.863
-20----
0.9270.8930.863
HEATING
COOLING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Height
difference H
(m)
Pipe length (m)
Pipe length (m)
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
----0.9630.9610.959
--0.9840.9810.9790.9770.975
-0.9880.9880.9850.9830.9810.979
0.9920.9920.9920.9890.9870.9850.983
1.0001.0001.0000.9970.9950.9930.991
1.0001.0001.0000.9970.9950.9930.991
-1.0001.0000.9970.9950.9930.991
--1.0000.9970.9950.9930.991
----0.9950.9930.991
Page 41
- (02 - 07) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
6. ADDITIONAL CHARGE CALCULATION
MODEL : AO B18L
REFRIGERANT CHARGE
MODEL : AO B24L
REFRIGERANT CHARGE
Refrigerant type
Refrigerant amountg
Pipe lengthm 152025
Additional chargeg0 (Chargeless)+100+200
Refrigerant type
Refrigerant amountg
Pipe lengthm 15202530
Additional chargeg0 (Chargeless)+100+200+300
20g/m
1700
R410A
1250
20g/m
R410A
Page 42
- (02 - 08) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
MODEL : AO B18L
7. AIR FLOW
COOLING
HEATING
MODEL : AO B24L
COOLING
HEATING
m3/h
2000
l/s556
CFM1177
m3/h
1910
l/s531
CFM1124
m3/h
2470
l/s686
CFM1454
m3/h
2470
l/s686
CFM1454
1050
NUMBER OF
ROTATIONS
(r.p.m)
NUMBER OF
ROTATIONS
(r.p.m)
NUMBER OF
ROTATIONS
(r.p.m)
NUMBER OF
ROTATIONS
(r.p.m)
860
820
1050
Airflow
Airflow
Airflow
Airflow
Page 43
- (02 - 09) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
8-1. NOISE LEVEL CURVE
COOLING
HEATING
8. OPERATION NOISE
MODEL : AO B18L
COOLINGHEATING
MODEL : AO B24L
Octave band sound pressure level, dB:(0dB=0.0002µbar)
Octave band center frequency,Hz
0
10
20
30
40
50
60
70
80
631252505001,0002,0004,0008,000
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
Octave band sound pressure level, dB:(0dB=0.0002µbar)
Octave band center frequency,Hz
0
10
20
30
40
50
60
70
80
631252505001,0002,0004,0008,000
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
Octave band sound pressure level, dB:(0dB=0.0002µbar)
Octave band center frequency,Hz
0
10
20
30
40
50
60
70
80
631252505001,0002,0004,0008,000
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
Octave band sound pressure level, dB:(0dB=0.0002µbar)
Octave band center frequency,Hz
0
10
20
30
40
50
60
70
80
631252505001,0002,0004,0008,000
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
Page 44
- (02 - 10) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
8-2. SOUND LEVEL CHECK POINT
Page 45
- (02 - 11) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
9. ELECTRIC CHARACTERISTICS
*1) Wiring spec.
Selected sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited wiring length :
This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
Model nameAO B18LAO B24L
VoltageV
FrequencyHz
Max. operating current A15.016.2
Starting currentA7.710.0
Main fuse (Circuit breaker)
current
A2020
Power cable
mm
2
*2)Limited wiring lengthm2422
Power supply
*1) Wiring spec.
230
~
50
4.0
Page 46
- (02 - 12) -
OUTDOOR UNIT
AOB18-24L
OUTDOOR UNIT
AOB18-24L
10. SAFETY DEVICES
AO B18LAO B24L
Fan motor protectionThermal protection program
OFF:100
+15
-10
°C
ON:95
+15
-10
°C
OFF:110
+15
-10
°C
ON:105
+15
-10
°C
Thermal protection program
(COMPRESSOR TEMP.)
Thermal protection program
(DISCHARGE TEMP.)
15A 250V
3.15A 250V
Compressor protection
Circuit protection
OFF:110°C
ON: After 40 minutes
OFF:110°C
ON: After 7 minutes
Current fuse (NEAR THE TERMINAL)
Current fuse
(MAIN PRINTED CIRCUIT BOARD)
Protection form
20A 250V
5A 250V
Model
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.