General ARHA18L, ARHA18LATN, AOHA18LACL, ARHA24L, ARHA24LATN Service Manual

...
Page 1
SPLIT TYPE ROOM AIR CONDITIONER
SERVICE
INSTRUCTION
Models Indoor unit Outdoor unit
AR*A12LATN AR*A14LATN AR*A18LATN AR*A24LATN AR*A36LATN AR*A45LATN
DUCT
type
AO*A12LACL AO*A14LACL AO*A18LACL AO*A24LACL AO*A36LATL AO*A45LATL
R410A
Page 2
CONTENTS
1. SPECIFICATIONS
SPECIFICATIONS.......................................................................................................... 01-01
2. DIMENSIONS
DIMENSIONS.................................................................................................................. 02-01
3. REFRIGERANT SYSTEM DIAGRAM
REFRIGERANT CIRCUIT............................................................................................... 03-01
4. CIRCUIT DIAGRAM
CIRCUIT DIAGRAM........................................................................................................ 04-01
5. DESCRIPTION OF EACH CONTROL OPERATION
5-1 COOLING OPERATION............................................................................................
5-1-1 COOLING CAPACITY CONTROL......................................................................
5-2 HEATING OPERATION.............................................................................................
5-2-1 HEATING CAPACITY CONTROL......................................................................
5-3 DRY OPERATION......................................................................................................
5-3-1 INDOOR UNIT CONTROL.................................................................................
5-4 AUTO CHANGEOVER OPERATION........................................................................
5-5 INDOOR FAN CONTROL.........................................................................................
5-6 OUTDOOR FAN CONTROL......................................................................................
5-7 COMPRESSOR CONTROL......................................................................................
5-8 TIMER OPERATION CONTROL...............................................................................
5-9 ELECTRONIC EXPANSION VALVE CONTROL....................................................
5-10 TEST OPERATION CONTROL...............................................................................
5-11 PREVENT TO START FOR 3 MINUTES (3 MINUTES ST)....................................
5-12 4-WAY VALVE EXTENSION SELECT....................................................................
5-13 AUTO RESTART.....................................................................................................
05-01
05-01
05-02
05-02
05-03
05-03
05-04
05-05
05-08
05-10
05-11
05-13
05-13
05-13
05-14
05-14
5-14 PUMP DOWN (For AR*30/ 36/ 45LUAN/ 45/ 54LUAK)..........................................
5-15 COMPRESSOR PREHEATING...............................................................................
5-16 FRESH AIR CONTROL...........................................................................................
5-17 EXTERNAL ELECTRICAL HEATER CONTROL....................................................
5-18 DEFROST OPERATION CONTROL.......................................................................
5-19 OFF DEFROST OPERATION CONTROL...............................................................
5-20 ECONOMY OPERATION.........................................................................................
5-21 VARIOUS PROTECTIONS......................................................................................
5-22 FORCED COOLING OPERATION..........................................................................
5-23 COMPRESSOR STOP CONTROL..........................................................................
05-14
05-14
05-15
05-15
05-16
05-18
05-19
05-20
05-22
05-22
Page 3
6. REFRIGERANT CAUTION -R410A-
6-1 R410A TOOLS............................................................................................................ 06-01
6-2 PRECAUTION FOR INSTALLATION.........................................................................
6-3 PRECAUTION FOR SERVICING...............................................................................
6-4 NEW REFRIGERANT R410A.....................................................................................
6-5 DEFFERENCE FROM CONVENTIONAL MODEL (R22) AND PRECAUTIONS.......
06-02
06-04
06-05
06-08
7. TROUBLE SHOOTING
7-1 ERROR DISPLAY......................................................................................................
7-1-1 WIRED REMOTE CONTROLLER DISPLAY......................................................
7-1-2 OUTDOOR UNIT DISPLAY................................................................................
7-2 TROUBLE SHOOTING WITH ERROR CODE..........................................................
7-3 TROUBLE SHOOTING WITH NO ERROR CODE....................................................
7-4 SERVICE PARTS INFORMATION............................................................................
07-01
07-01 07-03
07-04 07-30
07-35
8. APPENDING DATA
8-1 CAPACITY TABLE..................................................................................................... 08-01
8-2 OPERATION RANGE.................................................................................................
8-3 ELECTRIC CHARACTERISTICS...............................................................................
8-4 SAFETY DEVICE........................................................................................................
8-5 FUNCTION SETTING.................................................................................................
8-5-1 INDOOR UNIT....................................................................................................
8-5-2 Procedures to change the Function Setting........................................................
8-5-3 WIRED REMOTE CONTROLLER......................................................................
9. INSTALLATION MANUAL
08-07
08-08
08-10
08-10
08-12
08-14
08-15
Page 4
DUCT type
R410A
INVERTER
1 . SPECIFICATIONS
Page 5
1. SPECIFICATIONS FOR INDOOR UNIT
AR A12LATN AR A14LATN
Pipe type
9.52 ( 3 / 8 in.) 12.70 ( 1 / 2 in.)
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
dB(A)
Remote controller type
Drain pipe Material
Size
Operation range Cooling
kg(lb.)
Connection pipe SizemmWeight
m3/h
Fan
Dimensions ( H×W ×D )
mm
Airflow rate
Enclosure
Heat exchanger type
Sound pressure level
Heating
Cooling
Heating
Heating
Cooling
Moisture removal
Cooling
Heating
Rated
*Max.
Rated
*Max.
kW/kW
Input power
Cooling
kW
Heating Rated
*Max.
Current
Cooling
A
Power source
Available voltage range
Capacity
Cooling
Heating
European energy label
Type Model name
mm
Rated
Min.-Max.
Rated
Min.-Max. Rated
*Max.
DUCTED MODEL
INVERTER HEATPUMP
230V 50Hz
198-264V 50Hz
Sirocco × 2
60
0 to 90
Copper
Aluminium
Steel
217 × 953 × 595
324 × 1075 × 686
Wired
PS
Outer diameter : 26.0 / Inner diameter : 21.5
6.35 ( 1 / 4 in.)
Flare
18 to 32
80 or less
30 or less
Cooling A A
Heating A A
kW 3.5 4.3
BTU/h 11950 14650
kW 0.9 - 4.4 0.9 - 5.4
BTU/h 3100 - 15000 3100 - 18400
kW 4.1 5.0
BTU/h 14000 17050
kW 0.9 - 5.7 0.9 - 6.5
BTU/h 3100 - 19400 3100 - 22100
1.05 1.33
1.73 2.07
1.11 1.34
2.30 2.88
4.6 5.8
7.5 9.0
4.9 5.9
10.0 12.5
EER 3.33 3.21
COP 3.69 3.71
l/h (pints/h) 1.3 ( 2.3 ) 1.5 ( 2.6 )
High 720 820
Med 630 720
Low 560 610
Quiet 480 550
High 720 820
Med 630 720
Low 560 610
Quiet 480 550
Type × Q'ty
Motor output W
Recommended static pressure Pa
High 32 33
Med 30 31
Low 28 29
Quiet 26 27
High 32 33
Med 30 31
Low 28 29
Quiet 26 27
Dimensions (H × W × D) 294 × 700 × 26.6 294 × 700 × 39.9
Fin pitch 1.30 1.30
Rows x Stages 2 × 14 3 × 14
Fin type
Material
Colour - -
Net
Gross
Net 23 ( 51 ) 23 ( 51 )
Gross 27 ( 60 ) 27 ( 60 )
Liquid
Gas
Method
Heating °C
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB. Standard static pressure : 0 Pa
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction port and measure. *The maximum current and the maximum input value are the maximum values when operated within the operation (temperature) range.
°C
%RH
mm
01-01
Page 6
DUCTED MODEL
AR A18LATN
230V 50Hz
198-264V 50Hz
Pipe type Copper
6.35 ( 1 / 4 in.)
12.70 ( 1 / 2 in.)
Type Model name
mm
Rated
Min-Max
Rated
Min-Max Rated
Min-Max
Power source
Available voltage range
Capacity
Cooling
Heating
European energy label
kW/kW
Input power
Cooling
kW
Heating Rated
Min-Max
Current
Cooling
A
Rated
Max
Rated
Max
Heating
Cooling
Heating
Heating
Cooling
Moisture removal
Cooling
Heating
mm
Weight
m3/h
Fan
Dimensions ( H × W × D )
mm
Airflow rate
Enclosure
Heat exchanger type
Sound pressure level
dB(A)
Remote controller type
Drain pipe Material
Size
Operation range Cooling
kg(lb.)
Connection pipe Size
INVERTER HEATPUMP
Cooling A
Heating A
kW 5.2
BTU/h 17700
kW 0.9 - 5.9
BTU/h 3100 - 20100
kW 6.0
BTU/h 20500
kW 0.9 - 7.5
BTU/h 3100 - 25600
1.62
0.09 - 1.80
1.66
0.09 - 2.46
7.1
9.0
7.3
10.8
EER 3.21
COP 3.61
l/h (pints/h) 2.0 ( 3.5 )
High 820
Med 720
Low 610
Quiet 550
High 820
Med 720
Low 610
Quiet 550
Type × Q'ty Sirocco × 2
Motor output W 60
Recommended static pressure Pa 0 to 90
High 33
Med 31
Low 29
Quiet 27
High 33
Med 31
Low 29
Quiet 27
Dimensions (H × W × D) 294 × 700 × 39.9
Fin pich 1.30
Rows x Stages 3 × 14
Fin type Aluminium
Material Steel
Colour
Net 217 × 953 × 595
Gross 324 × 1075 × 686
Net 23 ( 51 )
Gross 27 ( 60 )
Liquid
Gas
Method Flare
°C 18 to 32
%RH 80 or less
Heating °C 30 or less
mm Outer diameter: 26.0 / Inner diameter: 21.5
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB. Standard static pressure : 0 Pa Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit) Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
-
Wired
PS
01-02
Page 7
DUCTED MODEL
AR A24LATN
230V 50Hz
198-264V 50Hz
Pipe type Copper
6.35 ( 1 / 4 in.)
15.88 ( 5 / 8 in.)
Type Model name
mm
Rated
Min-Max
Rated
Min-Max Rated
Min-Max
Power source
Available voltage range
Capacity
Cooling
Heating
European energy label
kW/kW
Input power
Cooling
kW
Heating Rated
Min-Max
Current
Cooling
A
Rated
Max
Rated
Max
Heating
Cooling
Heating
Heating
Cooling
Moisture removal
Cooling
Heating
mm
Weight
m3/h
Fan
Dimensions ( H × W × D )
mm
Airflow rate
Enclosure
Heat exchanger type
Sound pressure level
dB(A)
Remote controller type
Drain pipe Material
Size
Operation range Cooling
kg(lb.)
Connection pipe Size
INVERTER HEATPUMP
Cooling A
Heating A
kW 7.1
BTU/h 24200
kW 0.9 - 8.0
BTU/h 3100 - 27300
kW 8.0
BTU/h 27300
kW 0.9 - 9.1
BTU/h 3100 - 31000
2.21
0.09 - 2.62
2.21
0.09 - 2.77
9.7
11.5
9.7
12.2
EER 3.21
COP 3.61
l/h (pints/h) 2.5 (4.4)
High 1100
Med 950
Low 800
Quiet 600
High 1100
Med 950
Low 800
Quiet 600
Type × Q'ty Sirocco × 2
Motor output W 115
Recommended static pressure Pa 30 to 150
High 31
Med 29
Low 27
Quiet 25
High 31
Med 29
Low 27
Quiet 25
Dimensions (H × W × D) 294 × 1000 × 39.9
Fin pich 1.40
Rows x Stages 3 × 14
Fin type Aluminium
Material Steel
Colour
Net 270 × 1135 × 700
Gross 300 × 1300 × 790
Net 38 ( 84 )
Gross 45 ( 99 )
Liquid
Gas
Method Flare
°C 18 to 32
%RH 80 or less
Heating °C 30 or less
mm Outer diameter: 38.0 / Inner diameter: 36.0
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB. Standard static pressure : 30 Pa Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit) Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
01-03
-
Wired
Steel
Page 8
AR A36LATN AR A45LATN
Cooling A A
Pipe type Copper Copper
9.52 ( 3 / 8 in.) 9.52 ( 3 / 8 in.)
15.88 ( 5 / 8 in.) 15.88 ( 5 / 8 in.)
DUCTED MODEL
INVERTER HEATPUMP
230V 50Hz
198-264V 50Hz
dB(A)
Remote controller type
Drain pipe Material
Size
Operation range Cooling
kg(lb.)
Connection pipe SizemmWeight
m3/h
Fan
Dimensions ( H × W × D )
mm
Airflow rate
Enclosure
Heat exchanger type
Sound pressure level
Heating
Cooling
Heating
Heating
Cooling
Moisture removal
Cooling
Heating
Rated
*Max.
Rated
*Max.
kW/kW
Input power
Cooling
kW
Heating Rated
*Max.
Current
Cooling
A
Power source
Available voltage range
Capacity
Cooling
Heating
European energy label
Type Model name
mm
Rated
Min.-Max.
Rated
Min.-Max. Rated
*Max.
Heating A A
kW 10.0 12.5
BTU/h 34100 42700
kW 3.8 - 11.2 4.0 - 14.0
BTU/h 13000 - 38200 13700 - 47800
kW 11.2 14.0
BTU/h 38200 47800
kW 4.0 - 14.0 4.2 - 16.2
BTU/h 13700 - 47800 14300 - 55300
3.11 3.89
4.33 4.56
3.02 3.77
4.33 4.56
13.6 17.0
19.0 20.0
13.2 16.5
19.0 20.0
EER 3.21 3.21
COP 3.71 3.71
l/h (pints/h) 3.0 (5.3) 3.5 (6.2)
High 2020 2250
Med 1710 1710
Low 1340 1340
Quiet 1020 1020
High 2020 2250
Med 1710 1710
Low 1340 1340
Quiet 1020 1020
Type × Q'ty Sirocco × 2 Sirocco × 2
Motor output W 197 197
Recommended static pressure Pa 30 to 150 30 to 150
High 42 44
Med 37 38
Low 32 33
Quiet 29 29
High 42 44
Med 37 38
Low 32 33
Quiet 29 29
Dimensions (H × W × D) 294 × 1000 × 53.2 294 × 1000 × 53.2
Fin pitch 1.40 1.40
Rows x Stages 4 × 14 4 × 14
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB. Standard static pressure : 30Pa Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit) Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure. *The maximum current and the maximum input value are the maximum values when operated within the operation (temperature) range.
Fin type Aluminium Aluminium
Material Steel Steel
Colour - -
Net 270 × 1135 × 700 270 × 1135 × 700
Gross 300 × 1300 × 790 300 × 1300 × 790
Net 41 ( 90 ) 41 ( 90 )
Gross 48 ( 106 ) 48 ( 106 )
Liquid
Gas
Method Flare Flare
°C 18 to 32 18 to 32
%RH 80 or less 80 or less
Heating °C 30 or less 30 or less
Wired Wired
Steel Steel
mm Outer diameter : 38.0 / Inner diameter : 36.0 Outer diameter : 38.0 / Inner diameter : 36.0
01-04
Page 9
2. SPECIFICATIONS FOR OUTDOOR UNIT
AO A12LACL AO A14LACL
9.52 ( 3/8 in.) 12.70 ( 1/2 in.)
Cooling
Heating
Type
Gross
Liquid
Gas
Method
Colour
Net
Gross
Net
Motor output
Type
Charge
Material
Rows x Stages
Pipe type
Fin type
Type × Q'ty
Motor output
Cooling
Heating
Dimensions (H × W × D) Type
Model name
Power source
Available voltage range
578 × 790 × 300
25 (chargeless : 15)
15
546 × 876 × 18.2 546 × 842 × 18.2
1.30
2 × 26
Copper
Aluminium
Steel sheet
Beige (10YR7.5/1.0NN)
54
°C
Operation range
Fan Airflow
rate
m3/h
dB(A)
mm mm
Weight
kg(lb.)
Dimensions (H × W × D)
Refrigerant oil
Enclosure
Heat exchanger type
Fin pitch
Compressor
Refrigerant
Sound pressure level Starting current
Cooling
Heating
Type × Q'ty
m
Connection pipe
Size
mm
Max. length
Max. height difference
INVERTER HEATPUMP
230V 50Hz
198-264V 50Hz
Propeller × 1
Twin Rotary × 1
1100
R410A
POE
Flare
-10 to 46
-15 to 24
648 × 910 × 380
6.35 ( 1/4 in.)
A 4.9 5.9
1780 1910
1630 1740
W
47 49
48 49
W
g 1150 1250
40 (88) 40 (88)
44 (97) 44 (97)
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB. Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB. Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
01-05
Page 10
AO A18LACL AO A24LACL
A 7.7 10.0
546 × 876 × 18.2 546 × 842 × 18.2
546 × 866 × 18.2 546 × 832 × 18.2 504 × 589 × 18.2
2 × 26 1 × 24
12.70 ( 1/2 in.) 15.88( 5/8 in.)
Cooling
Heating
Dimensions (H × W × D) Charge
Type
Material
Colour
Motor output
Cooling
Heating
Fin pich
Type
Model name
Power source
Available voltage range
°C
Operation range
Fan Airflow
rate
m3/h
dB(A)
mm mm
Weight
kg(lb.)
Dimensions ( H × W × D)
Net
Gross
Net
Gross
Refrigerant oil
Enclosure
Heat exchanger type
Rows x Stages Pipe type
Fin type
Type × Q'ty
Motor output
Type
Compressor
Refrigerant
Sound pressure level Type × Q'ty
Starting currente
Cooling
Heating
m
Connection pipe
Size
mm
Liquid
Gas
Method
Max. length
Max. height difference
INVERTER HEATPUMP
230V 50Hz
198-264V 50Hz
Propeller × 1
Copper
Aluminium
Steel sheet
Beige (10YR7.5/1.0NN)
Twin Rotary × 1
1100
R410A
POE
Flare
-10 to 46
-15 to 24
648 × 910 × 380
6.35 ( 1/4 in.)
2000 2470
1910 2470
W 54 65
50 52
50 53
1.30 1.40
2 × 26
W
g 1250 1700
578 × 790 × 300 578 × 790 × 315
40 (88) 44 (97)
44 (97) 48 (106)
25(chargeless : 15) 30(chargeless : 15)
15 20
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB. Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB. Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
01-06
Page 11
AO A36LATL AO A45LATL
A 15.0 15.0
1260 × 900 × 36.4
1260 × 900 × 36.4
Colour
Net
Gross
Motor output
Type
Charge
Type
Material
Motor output
Cooling
Heating
Dimensions (H × W × D)
Type
Model name
Power source
Available voltage range
1290 × 900 × 330
98 (216)
107 (236)
15.88 ( 5/8 in.)
Flare
-15 to 46
-15 to 24
1430 × 1050 × 445
9.52 ( 3/8 in.)
Copper
Aluminium
Steel sheet
Beige (10YR7.5/1.0NN)
Twin Rotary × 1
3750
R410A
POE
3350
INVERTER HEATPUMP
230V 50Hz
198-264V 50Hz
Propeller × 2
m
Connection pipe
Size
mm
Liquid
Gas
Method
Max. length
Max. height difference
Compressor
Refrigerant
Sound pressure level Starting current
Cooling
Heating
Type × Q'ty
Refrigerant oil
Enclosure
Heat exchanger type
Fin pitch
Rows x Stages
Pipe type
Fin type
Type × Q'ty
mm
Weight
kg(lb.)
Dimensions (H × W × D)
Net
Gross
°C
Operation range
Fan Airflow
rate
m3/h
dB(A)
mm
Cooling
Heating
6600 6600
6600 6600
W 103 × 2 103 × 2
54 55
55 56
1.30 1.30
2 × 60 2 × 60
W
g
50 (chargeless : 20) 50 (chargeless : 20)
30 30
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB. Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB. Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
01-07
Page 12
DUCT type
R410A
INVERTER
2 . DIMENSIONS
Page 13
2. DIMENSIONS
MODEL : AR*A12LATN / AO*A12LACL AR*A14LATN / AO*A14LACL
886 850
390
(Unit : mm)
1 2
Top view
953
920
600
150
Front view
1
Refrigerant piping flare connection (Gas)
2
Refrigerant piping flare connection (Liquid)
3
Drain piping connection
150
85 75
12
595 57520
364
Side view
194
217
3
Front view
Air flow
(Unit : mm)
Side view
Bottom view
02-01
Page 14
MODEL : AR*A18LATN / AO*A18LACL
886 850
390
1 2
Top view
(Unit : mm)
953
920
600
150
Front view
1
Refrigerant piping flare connection (Gas)
2
Refrigerant piping flare connection (Liquid)
3
Drain piping connection
150
85 75
Side view
364
12
595 57520
194
217
3
(Unit : mm)
Front view
Air flow
Bottom view
Side view
02-02
Page 15
MODEL : AR*A24LATN / AO*A24LACL
Front view
(Unit : mm)
Side view (L)
Front view
Top view
Rear view
Side view (R)
Refrigerant piping flare connection (Gas) Refrigerant piping flare connection (Liquid) Drain piping connection Drain piping connection with cap. Knock out hole for fresh air.
(Unit : mm)
Side view
Air flow
Bottom view
02-03
Page 16
MODEL : AR*A36LATN / AO*A36LATL AR*A45LATN / AO*A45LATL
Front view
(Unit : mm)
Side view (L)
Top view
Rear view
900
1290
77 31
12330
Side view (R)
Refrigerant piping flare connection (Gas) Refrigerant piping flare connection (Liquid) Drain piping connection Drain piping connection with cap. Knock out hole for fresh air.
(Unit : mm)
21
370
Drain cap mounting places
9
Front view
650
Air flow
Bottom view
4-Ø12mm hole
02-04
400
Side view
151 170
196
99
Page 17
DUCT type
R410A
INVERTER
3 . REFRIGERANT SYSTEM DIAGRAM
Page 18
3. REFRIGERANT CIRCUIT
MODEL : AR*A12LATN / AO*A12LACL
Outdoor Unit Indoor Unit
MUFFLER
THHM
MUFFLER
Refrigerant Pipe
Ø9.52mm(3/8")
3-way VALVE
4-Way valve
THD
CONDENSER EVAPOLATOR
THC
ACCUMULATOR
COMPRESSOR
THO
THHO
THC
THD
THHM
THHO
THO
EXPANSION VALVE
THERMISTOR(COMPRESSOR TEMP.)
THERMISTOR(DISCHARGE TEMP.)
THERMISTOR(HEAT EXCHANGER MED TEMP.)
THERMISTOR(HEAT EXCHANGER OUT TEMP.)
THERMISTOR(OUTDOOR TEMP.)
STRAINERSTRAINER
2-way VALVE
Refrigerant Pipe
Ø6.35mm(1/4")
THR
THPI
THR
THERMISTOR(ROOM TEMP.)
THPI
THERMISTOR(PIPE TEMP.)
COOL HEAT
03-01
Page 19
MODEL : AR*A14LATN / AO*A14LACL AR*A18LATN / AO*A18LACL
Outdoor Unit Indoor Unit
MUFFLER
THHM
MUFFLER
Refrigerant Pipe
Ø12.7mm(1/2")
3-way VALVE
4-Way valve
THD
CONDENSER EVAPOLATOR
THC
ACCUMULATOR
COMPRESSOR
THO
THHO
THC
THD
THHM
THHO
THO
EXPANSION VALVE
THERMISTOR(COMPRESSOR TEMP.)
THERMISTOR(DISCHARGE TEMP.)
THERMISTOR(HEAT EXCHANGER MED TEMP.)
THERMISTOR(HEAT EXCHANGER OUT TEMP.)
THERMISTOR(OUTDOOR TEMP.)
STRAINERSTRAINER
2-way VALVE
Refrigerant Pipe
Ø6.35mm(1/4")
THR
THPI
THR
THERMISTOR(ROOM TEMP.)
THPI
THERMISTOR(PIPE TEMP.)
COOL HEAT
03-02
Page 20
MODEL : AR*A24LATN / AO*A24LACL
Outdoor Unit Indoor Unit
MUFFLER
THHM
MUFFLER
Refrigerant Pipe
Ø15.88mm(5/8")
3-way VALVE
4-Way valve
THD
CONDENSER EVAPOLATOR
THC
ACCUMULATOR
COMPRESSOR
THO
THHO
THC
THD
THHM
THHO
THO
EXPANSION VALVE
THERMISTOR(COMPRESSOR TEMP.)
THERMISTOR(DISCHARGE TEMP.)
THERMISTOR(HEAT EXCHANGER MED TEMP.)
THERMISTOR(HEAT EXCHANGER OUT TEMP.)
THERMISTOR(OUTDOOR TEMP.)
STRAINERSTRAINER
2-way VALVE
Refrigerant Pipe
Ø6.35mm(1/4")
THR
THPI
THR
THERMISTOR(ROOM TEMP.)
THPI
THERMISTOR(PIPE TEMP.)
COOL HEAT
03-03
Page 21
MODEL : AR*30/ 36LUAN / AO*30/ 36LMAWL
Outdoor Unit Indoor Unit
THHM
HIGH PRESSURE SWITCH
PRESSURE CHECK VALVE
STRAINER
Refrigerant Pipe
Ø15.88mm(5/8")
Charging Valve
4-Way
CONDENSER
THD
valve
MUFFLER
THC
ACCUMULATOR
EVAPOLATOR
COMPRESSOR
THO
THR
THHO
EXPANSION
THPI
VALVE
STRAINER
STRAINER
Refrigerant Pipe
Ø9.52mm(3/8")
Charging Valve
THC
THD
THHM
THHO
THO
THERMISTOR(COMPRESSOR TEMP.)
THERMISTOR(DISCHARGE TEMP.)
THERMISTOR(HEAT EXCHANGER MED TEMP.)
THERMISTOR(HEAT EXCHANGER OUT TEMP.)
THERMISTOR(OUTDOOR TEMP.)
THR
THERMISTOR(ROOM TEMP.)
THPI
THERMISTOR(PIPE TEMP.)
COOL HEAT
03-04
Page 22
DUCT type
R410A
INVERTER
4 . CIRCUIT DIAGRAM
Page 23
4. CIRCUIT DIAGRAM
MODEL : AR*A12/ 14/ 18LATN
04-01
Page 24
MODEL : AR*A24/ 36/ 45LATN
COIL
04-02
Page 25
MODEL : AO*A12/ 14/ 18/ 24LACL
04-03
Page 26
MODEL : AO*A36/ 45LATL
04-04
Page 27
DUCT type
R410A
INVERTER
5 . DESCRIPTION OF EACH CONTROL OPERATION
Page 28
5-1. COOLING OPERATION
5-1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 2 degC higher than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is 2.5 degC lower than a set temperature, the compressor will be stopped.
* When the room temperature is between +2 degC to -2.5 degC of the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode and the outdoor temperature.
( Table 1 : Compressor Frequency Range )
AR*A12LATN 18Hz AR*A14LATN AR*A18LATN AR*A24LATN 18Hz 113Hz AR*A36LATN AR*A45LATN
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outdoor air temperature
34°C
30°C
19°C
10°C
0°C
A zone
B zone
C zone
D zone
E zone
F zone
When the room temperature drops
minimum frequency
18Hz 18Hz
18Hz 70Hz 18Hz 77Hz
maximum frequency
113Hz 113Hz
When the room temperature rises
36°C
32°C
21°C
12°C
2°C
80Hz
Fan speed mode
AR*A12LATN
AR*A14LATN
AR*A18LATN
AR*A24LATN
AR*A36LATN
AR*A45LATN
Hi Me Lo Quiet
A zone 80Hz B zone C zone D-F zone A zone B zone C zone D-F zone A zone B zone C zone D-F zone A zone B zone C zone D-F zone A zone B zone C zone D-F zone A zone B zone C zone D-F zone
80Hz 80Hz
49Hz 113Hz 113Hz
80Hz
54Hz 113Hz 113Hz
80Hz
54Hz 113Hz 113Hz
80Hz
54Hz
70Hz
70Hz
48Hz
37Hz
77Hz
77Hz
55Hz
41Hz
49Hz 49Hz 49Hz 42Hz 38Hz 30Hz
66Hz 66Hz 54Hz 45Hz 45Hz 38Hz
66Hz 66Hz 54Hz 45Hz 45Hz 38Hz 66Hz 66Hz 54Hz 45Hz 45Hz 38Hz
43Hz 43Hz 37Hz 33Hz 33Hz 29Hz
48Hz 48Hz 41Hz 37Hz 37Hz 33Hz
42Hz 42Hz
54Hz 54Hz
54Hz 54Hz
54Hz 54Hz
37Hz 37Hz
41Hz 41Hz
34Hz 34Hz 34Hz 22Hz
34Hz 34Hz 34Hz 24Hz
34Hz 34Hz 34Hz 24Hz 34Hz 34Hz 34Hz 24Hz
29Hz 29Hz 29Hz 23Hz
31Hz 31Hz 31Hz 25Hz
05-01
Page 29
5-2. HEATING OPERATION
5-2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower 3 degC than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 2.5 degC than a set temperature, the compressor will be stopped.
* When the room temperature is between +2.5 degC to -3 degC of the setting temperature, the compressor frequency is controlled within the range shown in Table2. However, the maximum frequency is limited in the range shown in Figure 2 based on the outdoor temperature.
( Table 2 : Compressor Frequency Range )
minimum frequency
AR*A12LATN 18Hz AR*A14LATN AR*A18LATN AR*A24LATN 18Hz 120Hz AR*A36LATN AR*A45LATN
18Hz 18Hz
18Hz 90Hz 18Hz 90Hz
maximum frequency
120Hz 120Hz 120Hz
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
Outdoor air temperature
19°C
14°C
When the room temperature rises
C zone
B zone
A zone
17°C
12°C
When the room temperature drops
Fan speed mode
AR*A12LATN
AR*A14LATN
AR*A18LATN
AR*A24LATN
AR*A36LATN
AR*A45LATN
Hi Me+
A zone 120Hz B zone C zone A zone B zone C zone A zone B zone C zone A zone B zone C zone A zone B zone C zone A zone B zone C zone
120Hz 120Hz 120Hz 120Hz 120Hz 120Hz 120Hz 120Hz 120Hz 120Hz 120Hz
90Hz 90Hz 90Hz 90Hz 90Hz 90Hz
Me Lo Quiet
70Hz 70Hz
70Hz 60Hz 101Hz 101Hz 101Hz 75Hz 101Hz 101Hz 101Hz 75Hz 101Hz 101Hz 101Hz 75Hz
66Hz
66Hz
66Hz 53Hz
66Hz
66Hz
66Hz 53Hz
60Hz 60Hz
75Hz 75Hz
75Hz 75Hz
75Hz 75Hz
53Hz 53Hz
53Hz 53Hz
49Hz 49Hz 49Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
60Hz 60Hz 60Hz 45Hz 45Hz 45Hz 45Hz 45Hz 45Hz
05-02
Page 30
5-3. DRY OPERATION
5-3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to set temperature and room temperature variation which the room temperature sensor of the indoor unit has detected as shown in the Fig 3.
( Table 3 : Compressor frequency )
Operating frequency
AR*A12LATN 34Hz AR*A14LATN AR*A18LATN AR*A24LATN 34Hz AR*A36LATN AR*A45LATN
( Fig.3 : Compressor Control based on Room Temperature )
Room temperature
Compressor ON
34Hz 34Hz
31Hz 31Hz
Room temperature
Ts+1.5 degC
Ts+0.5 degC
Compressor OFF
( Fig.4 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan
Dry air flow
S-Lo
OFF
Ts : Setting temperature
10 30 60 180 60 180 60 10 30
05-03
(SEC)
Page 31
5-4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the optimum mode is automatically swiched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1 degC steps.
When operation starts, only the indoor and outdoor fans are operated for 1 minute.
1
After 1 minute, the room temperature and outdoor air temperature are sensed and the operation mode is selected in accordance with the table below.
( Fig.5 : Outdoor air temperature zone selection )
[ For AR*A12/ 14/ 18/ 24LATN ]
C zone
32°C
B zone
-10°C A zone
[ For AR*A36/ 45LATN ]
C zone
32°C
B zone
-15°C A zone
( Table 4 : Operation mode selection table )
Outdoor temperature :To
A zone B zone C zone
Room temperature :Tb
Tb > Ts +2 degC
Ts +2 degC > Tb > Ts-2 degC
Ts +2 degC > Tb
Ts : Setting temperature
2
When COOLING was selected at , the air conditioner operates as follow:
The same operation as COOLING OPERATION of item 5-1 above is performed. However, the setting temperature is raised 1degC and the room temperature correct coefficient value is 0°C
=
=
Monitoring
Monitoring Monitoring Monitoring
Heating Heating
1
Cooling (Automatic Dry)
Cooling (Automatic Dry)
Monitoring
When the compressor frequency have been below 20Hz for 8 minutes or the room temperature reaches "setting temperature -1.5°C" , operation is automatically switched to DRY OPERATION of item 5-3 above is performed. However, compressor control based on room temperature is as follows.
Room temperature
Ts -1.5°C
If the room temperature reaches "setting temperature +2°C" during DRY operation, operation returns to COOLING operation.
3
When HEATING was selected at , the same operation as HEATING OPERATION of item 5-2 above is performed. However, the room temperature correct coefficient value is 0°C.
4
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the COOLING or HEATING operation mode was selected at above, operation is switched to MONITORING and the operation mode is selected again.
Compressor :ON
Ts -0.5°C
Compressor :OFF
1
1
05-04
Page 32
5-5. INDOOR FAN CONTROL
1. Fan speed
( Table 5 : Indoor Fan Speed )
AR*A12LATN
Operation mode Air flow mode
Cooling Heating Fan
Dry Monitoring
Hi 880
Me
Lo Quiet Auto S- Lo
AR*A18LATN
Operation mode Air flow mode
Cooling Heating Fan
Dry Monitoring
Hi 1040
Me
Lo Quiet Auto S- Lo
AR*A36LATN
Operation mode Air flow mode
Cooling Heating Fan
Heating
Dry Monitoring
Hi 1200
Me
Lo Quiet
Hi
Me
Lo Quiet Auto S- Lo
Speed (rpm)
780 720 620 620 450
Speed (rpm)
950 840 740 740 450
Speed (rpm)
1020
840
670 1220 1020
840
670
670
370
AR*A14LATN
Operation mode Air flow mode
Cooling Heating Fan
Dry Monitoring
Hi 1040
Me
Lo Quiet Auto S- Lo
AR*A24LATN
Operation mode Air flow mode
Cooling Heating Fan
Dry Monitoring
Hi 830
Me
Lo Quiet Auto S- Lo
AR*A45LATN
Operation mode Air flow mode
Cooling Heating Fan
Heating
Dry Monitoring
Hi 1310
Me
Lo Quiet
Hi
Me
Lo Quiet Auto S- Lo
Speed (rpm)
950 840 740 740 450
Speed (rpm)
700 600 550 550 350
Speed (rpm)
1020
840
670 1300 1020
840
670
670
370
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor fan only runs. When Fan mode is set at (Auto), it operates on [MED] Fan Speed.
05-05
Page 33
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 6. On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL] operation modes QUIET, LOW, MED, HIGH, as shown in Table 5.
( Fig.6 : Airflow change - over ( Cooling : AUTO ) )
When the room temperature rises
TR-Ts > 2.5 degC
=
2.5 degC > TR-Ts > 1.5 degC
1.5 degC > TR-Ts
=
TR-Ts > 2 degC
=
2 degC > TR-Ts > 1 degC
1 degC > TR-Ts
=
HIGH mode
MED mode
LOW mode
When the room temperature drops
TR : Room temperature Ts : Setting temperature
4. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 7. On the other hand, if switched [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table 5.
( Fig.7 : Airflow change - over ( Heating : AUTO ) )
When the room temperature rises
TR-Ts > - 1 degC
=
- 1 degC > TR-Ts > - 2 degC
- 2 degC > TR-Ts
=
LOW mode
MED mode
HIGH mode
TR : Room temperature Ts : Setting temperature
TR-Ts > - 1.5 degC
=
- 1.5 degC > TR-Ts > - 2.5 degC
- 2.5 degC > TR-Ts
When the room temperature drops
=
05-06
Page 34
5. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
( Fig.8 : Cool Air Prevention Control )
(1) Fan mode : HIGH (2) Fan mode : MED, LOW, QUIET
Indoor heat exchanger temperature
Indoor heat exchanger temperature
Indoor heat exchanger temperature
HIGH mode
37°C
32°C
37°C
LOW mode
30°C
24°C
30°C
S-LOW mode
6. DRY OPERATION
Refer to the Figure 4. During the dry mode operation, the fan speed setting can not be changed.
Indoor heat exchanger temperature
SETTING FAN MODE
32°C
LOW mode
24°C
S-LOW mode
05-07
Page 35
5-6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor 1-1. For AR*A12/ 14/ 18/ 24LATN
Following table shows the fan speed of the outdoor unit.
Table 6 : Fan speed of the outdoor unit
AR*A12LATN
AR*A14LATN AR*A18LATN
AR*A24LATN
Outdoor temperature
Over than 12°C
Less than 12°C
Over than 12°C
Less than 12°C
Over than 12°C
Less than 12°C
Cooling
860/ 820/ 770/ 670/ 500 rpm
400/ 340/ 280/ 250/ 230 rpm
860/ 820/ 670/ 500 rpm
400/ 340/ 280/ 250/ 230 rpm
950/ 820/ 670/ 500 rpm
400/ 340/ 280/ 250/ 230 rpm
500 rpm
400/ 340/ 280/ 250/ 230 rpm
500 rpm
400/ 340/ 280/ 250/ 230 rpm
500 rpm
400/ 340/ 280/ 250/ 230 rpm
Dry
Heating
AR*A12LATN
AR*A14LATN AR*A18LATN
AR*A24LATN
950/ 820/ 750/ 700/ 550/ 450 rpm
950/ 820/ 750/ 670/ 550/ 450 rpm
1050/ 1000/ 730/ 670/ 550/ 450 rpm
The outdoor fan speed is changed in the range of the speed shown in the above table, based on the frequency of the compressor. (When the compressor frequency increases, the outdoor fan speed is also changed to higher speed. If the compressor frequency decreases, the outdoor fan speed is changed to the lower speed as well.) After starting up the outdoor fan, it operates with the following speed for initial 20 seconds.
Table 7 : Fan speed when starting up outdoor fan
Outdoor temperature
AR*A12LATN AR*A14LATN AR*A18LATN
AR*A24LATN
Over than 12°C
Less than 12°C
After operating the defrost control function on heating mode except economy operation, its speed becomes 950rpm (AR*A12/14/18L) and 1050rpm (AR*A24L) regardless of the compressor frequency. However, it returns to the normal speed control when the defrosting operation does not function for 240 minutes after releasing the defrost operation or when the outdoor temperature sensor detection value becomes higher than 5°C.
Fan speed
500 rpm
200 rpm
05-08
Page 36
1-2. For AR*A36/ 45LATN
Following table shows the fan speed of the outdoor unit.
Table 8 : Fan speed of the outdoor unit
AR*A36LATN AR*A45LATN
Upper fan
Lower fan
Cooling
850/ 780/ 520/ 400/ 350/ 300/ 280 rpm 850/ 780/ 350/ 200/ 170/ 150 rpm
780/ 750/ 520/ 350/ 280/ 0 rpm
780/ 750/ 350/ 200/ 170/ 150 rpm
Heating
AR*A36/ 45LATN have two fan motors.
The outdoor fan speed changs in the range mentioned avobe depending on the compressor frequency and outdoor temperature.
It runs at 500rpm for 20 seconds after starting up the outdoor fan. When the outdoor heat exchanger temperature is lower than 2°C, the fan speed switches to 850rpm(Upper fan) and 750rpm(Lower fan) on heating mode.
05-09
Page 37
5-7. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in Table 9.
(Table 9 : Compressor Operation Frequency Range)
Cooling Heating
Min Max Min Max
Dry
AR*A12LATN AR*A14LATN AR*A18LATN AR*A24LATN
AR*A36LATN
AR*A45LATN
18Hz 18Hz 18Hz 18Hz 18Hz 18Hz
80Hz 113Hz 113Hz 113Hz
70Hz
77Hz
18Hz 18Hz 18Hz 18Hz 18Hz 18Hz
120Hz 120Hz 120Hz 120Hz
90Hz 90Hz
34Hz 34Hz 34Hz 34Hz 31Hz 31Hz
2. OPERATION FREQUENCY CONTROL AT START UP
2-1. For AR*A12/ 14/ 18/ 24LATN
The compressor frequency soon after the start-up is controlled as shown in Figure 9.
(Fig.9 : Compressor Control at Start-up)
85Hz
59Hz
40Hz
90sec 180sec 270sec
2-2. For AR*A36/ 45LATN
The compressor frequency soon after the start-up is controlled as shown in Figure 10.
(Fig.10 : Compressor Control at Start-up)
70Hz
54Hz
43Hz
28Hz
90sec 180sec 270sec
360sec
05-10
Page 38
5-8. TIMER OPERATION CONTROL
5-8-1 Wired Remote Controller
AR-6TC1
ON / TIMER OFF / TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Use this timer function to set operating time for each day of the week. The weekly timer allows up to two ON and OFF time to set up per day.
Operation mode
Stop mode
Set time
The operating time can be set in 30 min increments only. The OFF time can be carried over to next day. The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
Operation mode
Stop mode
Set time Set time Set time
Operation mode
Stop mode
05-11
Page 39
2-2. DAY OFF setting
The DAY OFF setting is only available for days for which weekly settings already exist. If the operating time carries over to the next day (during a next day setting), the effective
DAY OFF range will be set as shown below.
Normal
DAY OFF
Operation mode
Operation mode
Stop mode
Stop mode
Preceding day Next day
Setting day
Stop mode
Next day setting
DAY OFF
Stop mode
Operation mode
Stop mode
Preceding day Next daySetting day
Operation mode
Stop mode
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
3. TEMPERATURE SET BACK TIMER
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used.
During the COOL/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature is set to 17°C or lower.
Case of SET BACK timer on the Cooling operation. ( Setting temperature :22°C, SET BACK temperature :26°C)
SET BACK setting
Operation temperature
*1
Operation temperature
*1: During the SET BACK function, the setting temperature is changed.
26°C
22°C
26°C
24°C
22°C
ON OFF OFFON
Chenge the setting temperature: 22°C 24°C
05-12
Page 40
5-9. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
(1) Pulse range of EEV
Pulse range
60 480 pulse
50 480 pulse
62 480 pulse
AR*A12LATN AR*A14LATN AR*A18LATN AR*A24LATN
AR*A36LATN AR*A45LATN
Operation
Cooling/ Dry
Heating
Cooling/ Dry
Heating
(2) The EEV is set up at 480 pulses when the compressor is stopped.
(3) Intialization (Input of 528 pulses toward closing direction) is operated under the following condition.
* When the power is turned on.
* 4 hours has passed since the last initialization, and 3 minutes has passed after the compressor stop. (If 12 hours has passed since the last initialization, the compressor is compulsorily stopped.)
5-10. TEST OPERATION CONTROL
Under the condition where the air conditioner stops, press the MASTER CONTROL button and the FAN CONTROL button simultaneously for 2 seconds or more, and the test operation control mode will appear. During test running, " " will display on the remote controller display. Set the test operation mode, and the compressor will continue to run regardless of whatever the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
5-11. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
05-13
Page 41
5-12. 4-WAY VALVE EXTENSION SELECT
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the 4-way valve is switched in 3 minutes later after the compressor stopped.
5-13. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically resumed with the memorized operation contents. When the power is interrupted and recovered during timer operation, timer operation is canceled, but only setting time is memorized.
[Operation contents memorized when the power is interrupted]
Operation mode Set temperature
Set air flow
Timer mode and timer time Thermistor detected position (When using the Wired Remote Controller)
5-14. PUMP DOWN ( For AR*A36/ 45LATN )
Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit.
When the product is stopped:
1. Press the PUMP DOWN switch (SW2) on the outdoor unit. (The LED on the outdoor unit circuit board starts flashing (1sec.ON / 1sec.OFF repeated).)
2. The pump down operation (cooling operation) begins right away. After operation starts, close the 3-way valve (liquid).
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.
When the product is operating:
1. Press the PUMP DOWN switch (SW2) on the outdoor unit. The LED on the outdoor unit circuit board starts flashing (1sec.ON / 1sec.OFF repeated), and operation stops. At this point, recovery has not been completed, so do not close the 3-way valves (liquid and gas).
2. The pump down operation (cooling operation) begins after 3minutes. Close the 3-way valve (liquid) after operation starts.
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.
5-15. COMPRESSOR PREHEATING
When the outdoor heat exchanger temperature is lower than 5°C and the heating operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to 7°C or greater, preheating is ended.
05-14
Page 42
5-16. FRESH AIR CONTROL
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as shown in Figure 11.
(Fig.11 : Fresh air control)
Fan motor (Indoor unit)
Fan motor (for Fresh Air)
Operation
Stop
Operation
Stop
5-17. EXTERNAL ELECTRICAL HEATER CONTROL
The external electrical heater is operated as shown in Figure 12.
(Fig.12 : External electrical heater control)
When the room temperature rises
Heater : OFF
Ts -1°C
Ts -3°C
Ts -12°C
Heater : ON
Heater : OFF
Ts -10°C
Ts : Setting temperature
When the compressor stop, External electrical heater is OFF.
When the room temperature drops
05-15
Page 43
5-18. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects the temperature lower than the values shown in Table 11.
(Table 11 : Condition of starting Defrost Operation)
1st time defrosting after starting operation
Compressor contiguous operation time
Compressor integrating operation time
Operation temperature
Below 10 min.
Less than 17 min.
Does not operate
17 to 62 min.
- 9°C
Above 10 min.
62 min. to 4 hours
Defrosting after 2nd time upon starting operation
Compressor contiguous operation time
Compressor integrating operation time
Operation temperature
Below 10 min.
Less than 35 min.
Does not operate
Above 10 min.
35 min. to 4 hours
- 6°C
After 4 hours
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 12.
- 5°C
- 3°C
After 4 hours
- 3°C
(Table 12 : Defrost Release Condition)
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +10°C or Compressor operation time has passed 15 minutes.
05-16
Page 44
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger emperature as follows.
Heating operation start : Compressor ON
(Not defrosted for 10 minutes)
Compressor integrating operation: Over 17 minutes to below 62 minutes
Outdoor heat exchanger temperature: Below - 9°C
Outdoor temp ­Outdoor heat exchanger temperature: Above 5 degC
(In case of 1st defrost)
Compressor integrating operation: Over 62 minutes to below 240 minutes
Outdoor heat exchanger temperature: Below - 5°C
Compressor integrating operation: Over 240 minutes
Outdoor heat exchanger temperature: Below - 3°C
(In case of 2nd and later defrost)
Compressor integrating operation: Over 35 minutes to below 240 minutes
Outdoor heat exchanger temperature: Below - 6°C
Compressor integrating operation: Over 240 minutes
Outdoor heat exchanger temperature: Below - 3°C
Defrost start
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
AR*A12/ 14/ 18/ 24LATN AR*A36/ 45LATN
Outdoor fan : OFF Compressor : OFF EEV : 480pulse 4-way valve : OFF Compressor : ON (Frequency : 70Hz)
Outdoor heat exchanger temperature: Over 10°C or Compressor ON time: Over 15 minutes
Defrost end
Outdoor fan : Lo Compressor frequency : 20 Hz EEV : 480pulse 4-way valve : OFF Outdoor fan : OFF Compressor frequency : 70Hz
05-17
Page 45
5-19. OFF DEFROST OPERATION CONTROL
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
1. OFF DEFROST OPERATION CONDITION
In heating operation, the outdoor heat exchanger temperature is less than - 4 C, and compressor operation integrating time lasts for more than 30 minutes. and compressor operation contiguous time lasts for more than 10 minutes.
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +10°C or Compressor operation time has passed 15 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature: Below - 4°C and Compressor integrating operation: Over 30 minutes and Compressor contiguous operation: Over 10 minutes
Defrost start
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature: Over 10°C or Compressor ON time: Over 15 minutes
Defrost end
05-18
Page 46
5-20. ECONOMY OPERATION
At the maximum output, ECONOMY OPERATION is approximately 70% of normal air conditioner operation for cooling and heating. When ECONOMY OPERATION is performed during the cooling mode,dehumidification is improved. This function is especially convenient when you want to remove the humidity in the room without significantly lowering the room temperature. During ECONOMY OPERATION, the thermostat setting automatically changes according to the temperature to avoid Unnecessary cooling and heating for the most economical operation.
If the room is not cooled (or heated) well during economy operation, select normal operation.
During the monitor period in the AUTO mode, the air conditioner operation will not change to ECONOMY OPERATION even if ECONOMY OPERATION is selected by pressing the ECONOMY button.
05-19
Page 47
5-21. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
1-1. For AR*A12/ 14/ 18/ 24LATN
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature. When the discharge temperature becomes higher than 104°C, the compressor frequency is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until the temperature becomes lower than 101°C. When the discharge temperature becomes lower than 101°C, the control of the compressor frequency is released. When the discharge temperature becomes higher than 110°C, the compressor stops
1-2. For AR*A36/ 45LATN
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature. When the discharge temperature becomes higher than 105°C, the compressor frequency is decreased 10 Hz, and it continues to decrease the frequency for 10 Hz every 120 seconds until the temperature becomes lower than 105°C. When the discharge temperature becomes lower than 100°C, the control of the compressor frequency is released. When the discharge temperature becomes higher than 115°C, the compressor stops
2. CURRENT RELEASE CONTROL
2-1. For AR*A12/ 14/ 18/ 24LATN
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit velue that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
(Table 13 : Current Release Operation Value / Release Value)
[ Heating ]
AR*A12LATN
OT (Control / Release)
6.5A/ 6.0A
17°C
8.0A/ 7.5A
12°C
8.5A/ 8.0A
5°C
9.5A/ 9.0A
OT : Outdoor Temperature
AR*A14/ 18LATN
OT (Control / Release)
7.0A/ 6.5A
17°C
9.0A/ 8.5A
12°C
10.5A/ 10.0A
5°C
12.0A/ 11.5A
OT : Outdoor Temperature
AR*A24LATN
OT (Control / Release)
7.0A/ 6.5A
17°C
9.0A/ 8.5A
12°C
11.5A/ 11.0A
5°C
13.0A/ 12.5A
OT : Outdoor Temperature
[ Cooling ]
AR*A12LATN
OT (Control / Release)
4.5A/ 4.0A
46°C
6.0A/ 5.5A
40°C
7.0A/ 6.5A
AR*A14/ 18LATN
OT (Control / Release)
4.5A/ 4.0A
46°C
6.0A/ 5.5A
40°C
8.5A/ 8.0A
AR*A24LATN
OT (Control / Release)
7.0A/ 6.5A
46°C
9.5A/ 9.0A
40°C
11.5A/ 11.0A
OT : Outdoor Temperature
OT : Outdoor Temperature
05-20
OT : Outdoor Temperature
Page 48
2-2. For AR*A36/ 45LATN
(Table 13-2 : Current Release Operation Value / Release Value)
[ Heating ]
Outdoor unit fan speed (UP / LO)
T0 > 20°C
=
20°C > T0 > 12°C
T0 < 12°C
T0: Outdoor temperature
=
[ Cooling ]
T0 > 46°C
=
46°C > T0 > 40°C
40°C > T0 > 31°C
31°C > T0 > 25°C
25°C > T0 > 13°C
13°C > T0 > 7°C
7°C > T0 > 0°C
T0 < 0°C
=
=
=
=
=
=
850/ 780 rpm 780/ 780 rpm 350/ 350 rpm
15.0A / 14.5A
18.0A / 17.5A
850/ 750 rpm 780/ 780 rpm
11.0A / 10.5A 11.0A / 10.5A 11.0A / 10.5A 11.0A / 10.5A 11.0A / 10.5A 11.0A / 10.5A
14.5A / 14.0A 14.5A / 14.0A
18.0A / 17.5A
17.5A / 17.0A
14.0A / 13.5A 14.0A / 13.5A
520/ 520 rpm 350/ 350 rpm 300/ 0 rpm350/ 0 rpm
15.0A / 14.5A
17.5A / 17.0A
200/ 200 rpm 170/ 170 rpm 150/ 150 rpm
13.0A / 12.5A13.0A / 12.5A
15.0A / 14.5A
Outdoor unit fan speed (UP / LO)
280/ 280 rpm 400/ 0 rpm
12.0A / 11.5A 12.0A / 11.5A
14.0A / 13.5A
12.0A / 11.5A
11.5A / 11.0A
T0: Outdoor temperature
3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature .
(Table 14 : Anti-freezing Protection Operation / Release Temperature)
Outdoor temperature
Over than 10°C *1
or 12°C *2
Less than 10°C *1
or 12°C *2
*1. When the temperature rises. *2. When the temperature drops.
Temperature Temperature
7°C
4°C
13°C
05-21
Page 49
4. COOLING PRESSURE OVER RISE PROTECTION
On cooling mode, the compressor frequency is controlled as following based on the detection value of the outdoor heat exchanger temperature sensor.
(Fig.13 : Cooling Pressure Over Rise Protection Control)
Outdoor heat exchange temperature
Compressor is OFF
67°C
62°C
59°C
(AR*A12 - 24LATN) The compressor frequency is decreased 2Hz every 60seconds.
(AR*A36/ 45LATN) The compressor frequency is decreased 5Hz every 60seconds.
Hold
Release of protection
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
(Fig.14 : Heating Overload Protection Control)
Indoor heat exchange temperature
Refer to below
53°C
50°C
Compressor Operation
Over than 18Hz Frequency down every 60 seconds Less than 18Hz OFF
5-22. FORCED COOLING OPERATION
The forced cooling operation starts up when MANUAL / AUTO button is pressed more than 10 seconds. During the forced cooling operation, it keeps operation regardless of detection value of room temperature sensor. Operation LED and Timer LED light up while the unit is on the forced cooling operation. The forced cooling operation is released after 60 minutes from starting time.
5-23. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than temperature in the table below, the compressor is stopped.
(Table 15 : Operation temperature of compressor stop control)
Temperature
Operation temperature
Cooling
- 20°C
Heating
05-22
Page 50
DUCT type
R410A
INVERTER
6 . REFRIGERANT CAUTION -R410A-
Page 51
6. REFRIGERANT CAUTION -R410A-
6-1. R410A TOOLS
This air conditioner used R410A. For installation and servicing, it is necessary to prepare the tools and machines that are different from the previous refrigerant.
Mark shows the exclusive use for R410A.
Gauge manifold . . . . . . . . . . . . . . . . . . . . . (Fig.4-1)
The specification of the gauge is different due to higher pressure. The size of connection pipe is also different to prevent mis-use.
Charge hose . . . . . . . . . . . . . . . . . . . . . . . (Fig.4-2)
Since the normal pressure is high, the connection pipe size is also different.
Refrigerant cylinder . . . . . . . . . . . . . . . . . (Fig.4-3)
Confirm the refrigerant type before charging. Always charge liquid-phase refrigerant.
Electronic balance for refrigerant
charging . . . . . . . . . . . . . . . . . . . . . . . . . . . (Fig.4-4)
Electronic balance is recommended as in the case of R410A.
Vacuum pump with adapter to prevent
reverse flow . . . . . . . . . . . . . . . . . . . . . . . .(Fig.4-5)
Conventional pump can be used.
Vacuum holder . . . . . . . . . . . . . . . . . . . . . (Fig.4-6)
Conventional pump can be used if adapter for preventing vacuum pump oil from flowing back is used.
Gas leakage tester . . . . . . . . . . . . . . . . . . (Fig.4-7)
Exclusive for HFC
Refrigerant cleaner . . . . . . . . . . . . . . . . . . (Fig.4-8)
Brown paint as designated by the ARI, USA
Flare tool . . . . . . . . . . . . . . . . . . . . . . . . . . (Fig.4-9)
The shape of flare is different for high pressure condition.
Torque wrench . . . . . . . . . . . . . . . . . . . . (Fig.4-10)
TOOLS AND EQUIPMENT (R410A)
Gas charging
Safety charger Fig.4-13
Electronic charging scale Fig.4-4
Refrigerant cylinder
Fig.4-3
Vacuum control
Thermistor vacuum gauge Fig.4-15
Vacuuming
Vacuum pump Fig.4-5
Piping work
Torque wrench Fig.4-10
Vacuum Valve Fig.4-16
Vacuum holder Fig.4-6
Flare tool Fig.4-9
Nitrogen Cylinder Fig.4-12
Pressure control and Circuit switching
Gauge manifold Fig.4-1
Charge hose Fig.4-2
Outdoor unit
Leakage tester Fig.4-7
Cleaner Fig.4-8
Collector Fig.4-11
Low pressure
side
side
High pressure
Control Valve Fig.4-14
Refrigerant recovering
equipment (Collector) . . . . . . . . . . . . . . (Fig.4-11)
The type which can be used for any refrigerant is available
Nitrogen cylinder . . . . . . . . . . . . . . . . . . . (Fig.4-12)
This prevents an oxide film from forming in the pipe silver­alloy brazing work by turning the air out of the pipe and preventing the inside combustion.
Safety charger . . . . . . . . . . . . . . . . . . . . . (Fig.4-13)
It is always compulsory to change the liquid, because R410A is a mixed refrigerant and there is some fear that a mixing ratio changes. In order to avoid the refrigerant from returning to the compressor in a liquid state, the refrigerant can be charged instead of giving a load to the compressor with a safety charger.
Control valve . . . . . . . . . . . . . . . . . . . . . . (Fig.4-14)
The control valve prevents the refrigerant from spouting when it is removed, as the charging hose side and the ser­vice port side are possible to open and close at the same time.
Thermistor vacuum gauge . . . . . . . . . . . (Fig.4-15)
To remove moisture from the refrigerating cycle complete­ly, it is necessary to perform appropriate vacuum drying. For that reason, vacuum conditions can be confirmed cer­tainly.
Vacuum valve . . . . . . . . . . . . . . . . . . . . . (Fig.4-16)
This valve builts in a check valve, and it is easily possible to vacuum a refrigerating cycle or check for degree of vac­uum with it.
06-01
1
*
High pressure gauge
Compond gauge
Port size
2
*
Normal pressure
Breaking pressure
Port size
Gauge Manifold
R410A
-0.1 5.3 Mpa
-0.1 3.8 Mpa
1/2UNF 5/16"
Charge hose
R410A
5.1 Mpa
27.4 Mpa
1/2UNF
R22, R407C
-0.1 3.5 Mpa
-0.1 1.7 Mpa
7/16UNF 1/4"
R22, R407C
3.4 Mpa
17.2 Mpa
7/16UNF
Page 52
6-2. PRECAUTION FOR INSTALLATION
Precaution for installation
Pipe diameter, recommended material and wall thickness
Nominal diameter
(in)
Outside diameter
(mm)
Material
Wall thickness
(mm)
1) Allowable tensile stress 33 (N/mm );
1/4" 3/8" 1/2" 5/8" 3/4" 7/8" 1 1/8" 1 1/4" 1 1/2"1 3/8"1"
6.35 9.52 12.70 15.88 19.05 22.22 28.58 31.75 38.1034.9225.40
COPPER
JIS H3300-C1220T-O or equivalent
3)
0.8 0.8 0.8 1.0 1.2 1.0 1.0 1.1 1.31.21.0
> =
2
2) Allowable tensile stress 61 (N/mm ); 3) Design pressure 4.2MPa.
The pipe must be properly pressure rated for R410A The pipe must be an air-conditioning refrigerant pipe.
Flare and flare nuts
Diameter 1/4 (6.35mm) 3/8(9.52mm) 1/2(12.7mm)
Refrigerant
A 9.1 9.0 13.2 13.0 16.6
R410A
R22 /R407C
R410A R410A
B 13 12 20 15 13 20
C 12 11 16 12.5 19 16
Nut width 17 22 26 24
R22 /R407C
1)
> =
R22 /R407C
16.2
COPPER
JIS H3300-C1220T-H or equivalent
2
3/8(15.88mm)
R410A
19.7
25
22
29
R22 /R407C
19.4
23
20
27
3/4(19.05mm)
R410A
24
29
24
36
R22 /R407C
23.7
29 24
2)
A
Do not use existing (for R22) pipes
Be sure to use new pipes when replacing
conventional (R22) model with HFC (R407C, R410A) model.
If you use existing pipes, it may cause
resolution of compressor oil by remaining mineral oil.
Always use the flare nut that is packed
B
C
with the product.
06-02
Page 53
Be careful not to mix moisture and
contamination into the pipe
Moisture and contamination
in the pipe is a cause of trouble.
Air purge
Always use a
vacuum pump
Refrigerant charge
Don't charge from the gas phase side.
Compressor oil is changed
We developed new synthetic oil, since HFC refrigerant doesn't dissolve in mineral (for R22)oil.
to purge air.
Do it always from the liquid phase side.
Be careful to handle synthetic oil, since it resolves easily by moisture and
Don't mix new synthetic oil and mineral oil.
It may cause trouble.
contamination.
06-03
Page 54
6-3. PRECAUTION FOR SERVICING
Feature 1 Refrigerant oil is different from before.
Refrigerant oil for New Refrigerant
Synthetic oil
Ether
Esther
Previously it was mineral oil.
Different point from previous one
Absorbent character is high.
Contamination occurs when mixed withe other kind of oil.
Precaution on Tools
Use the gauge manifold and charge hose for New Refrigerant(HFC), which shall be segregated from those of R22.
Attach the stop valve on the vacuum pump and avoid the oil from reverse frow.
It is necessary to use the vacuum pump which can obtain the high vacuum condition.
R410A R22
Feature 2 New Refrigerant has Approx 1.6 times higher pressure than previous refrigerant.
R410A
High Pressure
1.6 times of R22.
Different point from previous one
Diameter of Service port has been changed from 1/4 Flare to 5/16 Flare.
JIS standard of flare process It became lager
To keep thethickness of copper tube. (1/4,3/3=more than 0.8mm)
Precaution on Tools
It requires the gauge manifold and charge hose exclusively for R410A.
It requires the flare tool and torque wrench that satisfies New JIS standard.
Previous flare tool + flare adapter can be used as well.
06-04
Page 55
6-4. NEW REFRIGERANT R410A
What is HFC ?
*
Phase-out schedule of HCFC
(%)
100
80
60
40
20
0
100% =
started control
1996 20102000 2004 2015 2020 2030
(HCFC consumption of 1989) +
according to Montreal protocol
(CFC consumption of 1989) x 2.8%
65%
total abolition
35%
only service use
10%
0.5%
(Year)
06-05
Page 56
Ozone Layer depleting mechanism
sunbeam
CFC
Cl
Cl Ozone
ClO
CFCl
(O3)
2
O
2
What is CFC and HCFC?
CFC : Chloro-Fluoro-Carbon
High ODP( ozone depletion potential ) chemical compound, including chlorine. (ODP:0.6-1.0) For example : R12 (for refrigerator and car air-conditioner)
HCFC : Hydro-Chloro-Fluoro-Carbon
Low ODP chemical compound, including chlorine and hydrogen. (ODP:0.02-01) For example : R22 (for air-conditioner)
HFC3 : Hydro-Fluoro-Carbon
R134a (for Car air conditioner) R407C (for air conditioner)
Refrigerant characteristics
Composition
R32/R125
(wt%)
Boiling Point
Behavior ---
Pressure at 54.5
near azeotrope
C
(kPa)
R410A
(50/50)
- 51.4
3,406
R407C
R32/R125/R134a
(23/25/52)
R22
- 43.6
zeotrope
2,262
R22
(100)
- 40.8
2,151
Temperature Glide
ODP 0.055
(deg)
0.11
0
06-06
5.4
0
0
Page 57
Summary of R407C and R410A characteristics
Pressure (Mpa) Temp ( C)
Advantage
Disadvantage
Suitable for
Desighed pressure of R410A refrigerant
*
< Pressure Temp >
(difficult to design against
Relation between R410A condensing temperature and saturated pressure.
R410A
higher system
Near-Azeotropic
1.6 times higher
pressure resistance)
Small Air-Conditioners
performance
refrigerant
pressure than R22
(possible to design
R407C
similar pressure as R22
large equipment)
Zeotropic refrigerant
(handle with care)
Large Air-Conditioners
< Temp Pressure >
Temp ( C) Pressure (Mpa)
2.20 37.9
2.25 38.7
2.30 39.6
2.35 40.5
2.40 41.3
2.45 42.1
2.55 43.8
2.60 44.6
2.65 45.3
2.70 46.1
2.75 46.8
2.80 47.6
2.85 48.3
2.90 49.0
2.95 49.8
3.00 50.5
3.05 51.2
3.10 51.9
3.15 52.6
3.20 53.2
3.25 53.9
3.30 54.6
39 2.27 40 2.32 41 2.38 42 2.44 44 2.57 45 2.63 46 2.69 47 2.76 48 2.83 49 2.90 51 3.04 52 3.11 53 3.18 54 3.26 56 3.41 57 3.49 58 3.57 59 3.65 61 3.82 62 3.90 63 3.99 64 4.08
3.35 55.3
3.40 55.9
3.45 56.5
3.50 57.1
2.55 57.8
3.60 58.4
3.65 59.0
3.70 59.6
3.75 60.2
3.80 60.8
3.85 61.4
3.90 52.0
3.95 62.5
4.00 63.1
4.05 63.6
4.10 64.2
4.15 64.8
05-07
Page 58
6-5. DEFFERENCE FROM CONVENTIONAL MODEL (R22) AND PRECAUTIONS
OIL
• Use new synthetic oils such as ester because HFC series refrigerant has less solubility with mineral oils conventionally used for R22.
• As these new synthetic oils are easily influenced by moisture and dusts, they must be treated more care-
fully than the conventional lubricating oils.
CAUTION
For installation/servicing, take more precautions than the case of conventional refrigerants to avoid moisture and dusts entering the refrigerant circuit. Also, for storing parts, more precautions must be taken.
COMPRESSOR
• Use better grade of material for sliding parts for securing good lubrication of sliding part as HFC refrigerant does not contain chloride.
• Review insulating materials
• Increase pressure resistance strength
CAUTION
Check if the compressor is suitable for the refrigerant (model) when replacing. Complete welding within 15minutes after opening the cap when replacing.
HEAT EXCHANGER
• Review the water,contaminants controlling level
• Use thinner tube to increase pressure Increase capacity for resistance strength (only outdoor unit) improving performance
CAUTION
During storage, due care must be taken so that foreign matters such as dust and water do not enter.
4-WAY VALVE
• Review materials
CAUTION
Check if the valve is suitable for the refrigerant (model) when replacing.
2, 3-WAY VALVE
• Review material O-ring, valve core seal for securing suitability with oil.
CAUTION
Check if the valve is suitable for the refrigerant (model) when replacing.
Check Valve
• Review materials
Change shape of pipe ends to increase pressure resistance strength.
CAUTION
Check if the valve is suitable for the refrigerant (model) when replacing.
Other Piping
Review the water, contaminants controlling level.
Review thickness of pipes.
CAUTION
During storage, due care must be taken so that foreign matters such as dust and water do not enter.
06-08
Page 59
DUCT type
R410A
INVERTER
7 . TROUBLE SHOOTING
Page 60
7. TROUBLESHOOTING
7-1 ERROR DISPLAY
7-1-1 WIRED REMOTE CONTROLLER DISPLAY
1. SELF - DIAGNOSIS
When "EE" in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authoilzed servise personnel.
Unit number (usually 0)
Error code
SUMOTUWETH FR
ex. Self-diagnosis check
SA
Error code
Error contents
Communication error (indoor unit remote control)
Communication error (Serial reverse transfer error)
Room temperature sensor error
Indoor heat exchanger temperature sensor error
Outdoor heat exchanger temperature sensor(outlet) error
Water drain abnormal
Outdoor temperature sensor error
Outdoor discharge pipe temperature sensor error
Discharge temperature error
Indoor EEPROM abnormal (Model No.)
Indoor fan motor abnormal
Outdoor communication signal error (Forward transfer signal error)
Compressor temperature sensor error
Pressure switch error
IPM error
CT error
Active filter module (AFM) error
Compressor rotor location cannot detect (permanent stop)
Outdoor unit fan motor error
Outdoor unit computer communication error Indoor manual auto switch error
Exessive high pressure protection on cooling
PFC circuit error
Communication error (Main PCB Display PCB)
Communication error (Main PCB Display PCB)
Outdoor heat exchanger temperature sensor(middle) error
Compressor temperature error
4-way valve error
Trouble shooting
1 2 3 4 5
*(6)
7
8
9 10 11
12 13 14
15 16 17
18 19 20 21 22 23
*(24)
*(25)
26 27 28
If “CO” appears in the unit number display, there is a remote controller error. Refer to the installation instruction sheet included with the remote controller.
Trouble shooting No.6,24,and 25 have no application in this models.
07-01
Page 61
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more to start the self-diagnosis.
Error code
Error history number
SUMOTUWETH FR
3. Press the SET TEMPERATURE button to select the error history number.
SA
Lower
0 1 2 3 4 5 6 7
Raise
F E d c b A 9 8
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more or there is no key input for 60 seconds to stop the display.
07-02
Page 62
7-1-2 OUTDOOR UNIT DISPLAY
1. ERROR DISPLAY
1-1. For AR*A12L/ 14L/ 18L/ 24L (AO*A12L/ 14L/ 18L/ 24L)
Error contents
Discharge temperature error
IPM error
CT error
Compressor rotor location cannot detect
Outdoor unit sensor error (Discharge or Outdoor or Heat EX(In)(Out))
Outdoor unit fan motor error
Compressor temperature error
PFC circuit error
1-2. For AR*A36L/ 45L (AO*A36L/ 45L)
LED Flashing Pattern
Continuously lighting
0.5sec ON / 0.5sec OFF
2sec ON / 2sec OFF
0.1sec ON / 2sec OFF
0.1sec ON / 0.1sec OFF
5sec ON / 5sec OFF
2sec ON / 5sec OFF
5sec ON / 2sec OFF
Trouble shooting
9 15 16
18,30
5,7,8,26
19 27 23
Error contents
Outdoor communication signal error (Forward transfer signal error)
Outdoor discharge pipe temperature sensor error
Outdoor heat exchanger temperature(outlet) sensor error
Outdoor temperature sensor error
Outdoor heat exchanger temperature(middle) sensor error
Discharge temperature error
Compressor temperature sensor error
Heat sink temperature sensor error
Pressure switch abnormal
Compressor temperature error
IPM error
Compressor rotor location cannot detect
Compressor Start-up error
Outdoor unit fan motor error (upper fan)
Outdoor unit fan motor error (lower fan)
LED Flashing Pattern
1 time flash
2 times blink
3 times blink
4 times blink
5 times blink
6 times blink
7 times blink
8 times blink
9 times blink
10 times blink
12 times blink
13 times blink
14 times blink
15 times blink
16 times blink
Display priority
1
2
3
4
5
6 7 8
9 10
11
12 13
14
15
Trouble shooting
12
8
5
7
26
9 13 29 14 27
15
18 30
19
1-2-1. ERROR DISPLAY METHOD
Outdoor LED Blink (1 to 16 times) 0.5sec ON / 0.5sec OFF blinking
0.5sec 0.5sec 2sec
ON
OFF
1-2-2. NORMAL OPERATION DISPLAY
Operation LED Blinking Pattern Normal operation OFF Protected operation Pump down operation
5sec ON / 1sec OFF 1sec ON / 1sec OFF
07-03
Page 63
7-2 TROUBLE SHOOTING WITH ERROR CODE
Trouble shooting 1
INDOOR UNIT Error Method:
Communication Error (Indoor unit Remote control)
Detective Actuators:
Indoor unit controller PCB circuit Wired Remote Control
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 00
Detective details:
When the indoor unit cannot receive the signal from Wired Remote more than 10seconds after power ON, or the indoor unit cannot receive the signal more than 1minute during normal operation.
Forecast of Cause:
1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Check the connection of terminal between remote control and Indoor unit, and check if there is a disconnection of the cable.
OKOK
Check Point 2 : Check Remote Control and Controller PCB
Check Voltage at CN14 (terminal 1-3) of Controller PCB. (Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Upon correcting the removed connector or mis-wiring, reset the power.
07-04
Page 64
Trouble shooting 2
OUTDOOR UNIT Error Method:
Communication Error (Serial Reverse Transfer Error)
Indicate or Display:Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 01
Detective Actuators:
Outdoor Unit Main PCB Circuit Active Filter Module
Detective details:
When the indoor unit cannot receive the serial signal from Outdoor unit more than 10seconds, then permanent stop after 20seconds.
Forecast of Cause:
1. Connection failure 2. External cause 3. Main PCB failure 4. Active Filter Module failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
YESYES
Check Point 2 : Check Connection
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection between Outdoor Unit Main PCB and Filter PCB. (If there is loose connector or open cable)
NO
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
OK
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 1 - 3.
>> If it is abnormal, Check Active Filter Module. (PARTS INFORMATION 3)
>>If Active Filter Module is abnormal, replace it.
>>If Active Filter Module is normal, replace Main PCB.
WHITE
BLACK
RED
WHITE
BLACK
N
L
3
2
1
+
-
07-05
Page 65
Trouble shooting 3 INDOOR UNIT Error Method:
INDOOR UNIT
Room Temperature Sensor Error
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 02
Detective Actuators:
Indoor Unit Controller PCB Circuit Room Temperature Thermistor
Detective details:
When Room Temperature Thermistor open or short-circuit is detected at power ON.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
25°C20°C15°C10°C5°C0°C
10.012.515.820.225.933.6Resistance Value (k )
30°C
8.04
35°C
6.51
Temperature
50°C45°C40°C
3.594.355.30Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR (PIPE TEMP.)
THERMISTOR (ROOM TEMP.)
GRAY
GRAY
BLACK
BLACK
1 2 1 2 1 2 1 2
1 2
CN5 CN7 CN8
If the voltage does not appear, replace Controller PCB.
07-06
Page 66
Trouble shooting 4 INDOOR UNIT Error Method:
INDOOR UNIT
Indoor Heat Exchanger Temperature Sensor Error
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 04
Detective Actuators:
Indoor Unit Controller PCB Circuit Heat Exchanger Temperature Thermistor
Detective details:
When Heat Exchanger Temperature Thermistor open or short-circuit is detected at power ON.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
25°C20°C15°C10°C5°C0°C
49.762.980.3103134176Resistance Value (k )
30°C
39.6
35°C
31.7
Temperature
50°C45°C40°C
17.120.825.6Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR (PIPE TEMP.)
THERMISTOR (ROOM TEMP.)
GRAY
GRAY
BLACK
BLACK
1 2 1 2 1 2 1 21 2
CN5 CN7 CN8
If the voltage does not appear, replace Controller PCB.
07-07
Page 67
Trouble shooting 5 OUTDOOR UNIT Error Method: Outdoor Heat Exchanger Temperature
Sensor (Outlet) Error
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 0.1sec ON/ 0.1sec OFF (AR*A36L/ 45L) : LED 3 times blink
ERROR CODE : E : 06
Detective Actuators:
Outdoor Unit Main PCB Circuit Heat Exchanger Temperature
Detective details:
When Heat Exchanger Temperature Thermistor (Outlet) open or short-circuit is detected at power ON or while running the compressor.
Thermistor (Outlet)
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
15°C10°C5°C0°C-5°C-10°C
7.569.6312.416.121.027.8Resistance Value (k )
20°C
5.98
25°C
4.77
30°C
3.84
Temperature
If Thermistor is either open or shorted, replace it and reset the power.
70°C60°C50°C45°C40°C35°C
0.8401.191.712.082.533.11Resistance Value (k )
80°C
0.606
90°C
0.446
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
For AR*A12L- 24L For AR*A36L/ 45L
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
(OUTDOOR)
BLACK
(PIPE MID)
2 13 2 1 4 3 2 12 1 2 13 2 1 4 3 2 12 1
(COMPRESSOR)
BLACK
(DISCHARGE)
BROWN
CN70 CN72 CN73 CN71
BROWN
(PIPE OUT)
BLACK
THERMISTOR
(PIPE MID)
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE OUT)
THERMISTOR
(OUTDOOR)
BLACK
1 2 1 2
CN24 CN21 CN22 CN23 CN26 CN25
1 2 1 2
BBROWN
1 2 1 2
BLACK
1 2 1 2
100°C
0.333
THERMISTOR
BLUE
(COMPRESSOR)
1 2 1 2
DC
THERMISTOR
(HEAT SINK)
BROWN
BLACK
1 2 1 2
If the voltage does not appear, replace Main PCB.
07-08
Page 68
Trouble shooting 7 OUTDOOR UNIT Error Method:
INDOOR UNIT
Outdoor Temperature Sensor Error
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 0.1sec ON/ 0.1sec OFF (AR*A36L/ 45L) : LED 4 times blink
ERROR CODE : E : 0A
Detective Actuators:
Outdoor Unit Main PCB Circuit Outdoor Temperature Thermistor
Detective details:
When Outdoor Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
15°C10°C5°C0°C-20°C -10°C -5°C
16.1
20°C
12.620.726.935.246.662.3115Resistance Value (k )
Temperature
30°C
40°C
5.187.97
50°C 60°C 70°C
3.45 2.36 1.65Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
For AR*A12L- 24L For AR*A36L/ 45L
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
(OUTDOOR)
BLACK
(PIPE MID)
2 13 2 1 4 3 2 12 1 2 13 2 1 4 3 2 12 1
(COMPRESSOR)
BLACK
(DISCHARGE)
BROWN
CN70 CN72 CN73 CN71
BROWN
(PIPE OUT)
BLACK
THERMISTOR
(PIPE MID)
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE OUT)
THERMISTOR
BLACK
1 2 1 2
1 2 1 2
BBROWN
BLACK
1 2 1 2
CN24 CN21 CN22 CN23 CN26 CN25
(OUTDOOR)
1 2 1 2
THERMISTOR
(COMPRESSOR)
THERMISTOR
(HEAT SINK)
BLUE
1 2 1 2
BROWN
BLACK
1 2 1 2
If the voltage does not appear, replace Main PCB.
07-09
Page 69
Trouble shooting 8 OUTDOOR UNIT Error Method:
INDOOR UNIT
Outdoor Discharge Pipe Temperature Sensor Error
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 0.1sec ON/ 0.1sec OFF (AR*A36L/ 45L) : LED 2 times blink
ERROR CODE : E : 0C
Detective Actuators:
Outdoor Unit Main PCB Circuit Discharge Pipe Temperature Thermistor
Detective details:
When Discharge Pipe Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
15°C10°C5°C0°C
20°C
30°C
40.062.679.1101130169Resistance Value (k )
50°C40°C
17.826.3
60°C
12.3
Temperature
90°C80°C70°C
140°C120°C100°C
1.222.003.434.606.278.70Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
For AR*A12L- 24L For AR*A36L/ 45L
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
(OUTDOOR)
BLACK
(PIPE MID)
2 13 2 1 4 3 2 12 1 2 13 2 1 4 3 2 12 1
(COMPRESSOR)
BLACK
(DISCHARGE)
BROWN
CN70 CN72 CN73 CN71
BROWN
(PIPE OUT)
BLACK
THERMISTOR
(PIPE MID)
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE OUT)
THERMISTOR
BLACK
1 2 1 2
1 2 1 2
BBROWN
BLACK
1 2 1 2
CN24 CN21 CN22 CN23 CN26 CN25
(OUTDOOR)
1 2 1 2
THERMISTOR
(COMPRESSOR)
THERMISTOR
(HEAT SINK)
BLUE
1 2 1 2
BROWN
BLACK
1 2 1 2
If the voltage does not appear, replace Main PCB.
07-10
Page 70
Trouble shooting 9 OUTDOOR UNIT Error Method:
INDOOR UNIT
Discharge temperature error
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED continuously lighting (AR*A36L/ 45L) : LED 6 times blink
ERROR CODE : E : 0F
Detective Actuators:
Outdoor Unit Main PCB Circuit Discharge Pipe Temperature Thermistor
Detective details:
When the discharge temperature becomes higher than 110°C ( AR*A36L and 45L is 115°C ), the compressor stops. After the compressor restarts, if the same operation is repeated, the compressor stops permanently.
Forecast of Cause :
1. Valve is close 2. EEV failure 3. Gas Leak, less 4. Discharge Thermistor failure
5. Outdoor Fan Operation failure 6. Outdoor Heat Exchanger clogged
< Cooling mode >
Check Point 1 : Check if Gas Valve is open
If it is not open, open it and check the operation.
< Heating mode >
Check Point 1 : Check if LIquid Valve is open
If it is not open, open it and check the operation.
OK OK
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 4)
>>If EEV or Strainer is defective, replace it.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 4)
>>If EEV or Strainer is defective, replace it.
OK
MPa MPa
Check Point 3 : Check if gas leak or less gas
Measure Gas pressure, if there is a leak, correct it.
>>If recharging refrigerant, make sure to perform vacuuming and recharge the specified amount.
OK
Check Point 4 : Check Discharge Thermistor
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 8), If defective, replace the thermistor
OK
Check Point 5 : Check Outdoor FAN, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger? Is the Fan rotating? (Check by hand and if it is locked, replace the motor) Check Outdoor Fan Motor.
>>If the Fan Motor is defective, replace it.
OK
07-11
Page 71
Trouble shooting 10 INDOOR UNIT Error Method:
Indoor EEPROM abnormal (Model No.)
Indicate or Display:
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 11
Detective Actuators:
Indoor Unit Controller PCB circuit
Detective details:
When the model information being read from EEPROM has an apparent error.
Forecast of Cause:
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
YESYES
Check Point 2 : Check Indoor Unit electric components
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
Check Point 3 : Replace Controller PCB
Change Controller PCB.
NO
Check Point 1-2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
07-12
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
Page 72
Trouble shooting 11 INDOOR UNIT Error Method:
Indoor Fan Motor abnormal
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 12
Detective Actuators:
Indoor Unit Controller PCB Circuit Indoor Fan Motor
Detective details:
When the condition that actual frequency of Indoor Fan is below 1/3 of target frequency is continued more than 56 seconds.
Forecast of Cause:
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Control PCB failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Replace Controller PCB
If Check Point 1- 2 do not improve the symptom, replace Controller PCB.
07-13
Page 73
Trouble shooting 12
INDOOR UNIT Error Method:
Outdoor Communication Signal Error (Forward Transfer Signal Error)
Indicate or Display:Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : No indication (AR*A36L/ 45L) : LED 4 times blink
ERROR CODE : E : 13
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forecast of Cause:
1. Connection failure 2. External cause 3. Controller PCB failure
Check Point 1-1 : Reset the power
Does Error indication reappear?
YESYES
Check Point 2 : Check Connection
Check any loose or removed connection line of Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection between Indoor Unit Controller PCB and Filter PCB. (If there is loose connector or open cable)
Detective details:
When the outdoor unit cannot receive the serial signal from Indoor unit more than 10seconds.
NO
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
OK
Check Point 4 : Check Serial Signal (Forward Transfer Signal)
Check Serial Signal (Forward Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 2 - 3.
>> If it is abnormal, Controller PCB is failure. >> Replace Controller PCB
WHITE
BLACK
RED
WHITE
BLACK
N
L
3
2
1
+
-
07-14
Page 74
Trouble shooting 13 OUTDOOR UNIT Error Method:
Compressor Temperature Sensor Error
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 0.1sec ON/ 0.1sec OFF (AR*A36L/ 45L) : LED 7 times blink
ERROR CODE : E : 15
Detective Actuators:
Outdoor Unit Main PCB Circuit Compressor Temperature Thermistor
Detective details:
When Compressor Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature
15°C10°C5°C0°C
20°C
30°C
40.062.679.1101130169Resistance Value (k )
50°C40°C
17.826.3
60°C
12.3
Temperature
90°C80°C70°C
140°C120°C100°C
1.222.003.434.606.278.70Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
For AR*A12L- 24L For AR*A36L/ 45L
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
(OUTDOOR)
BLACK
(PIPE MID)
2 13 2 1 4 3 2 12 1 2 13 2 1 4 3 2 12 1
(COMPRESSOR)
BLACK
(DISCHARGE)
BROWN
CN70 CN72 CN73 CN71
BROWN
(PIPE OUT)
BLACK
THERMISTOR
(PIPE MID)
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE OUT)
THERMISTOR
(OUTDOOR)
BLACK
1 2 1 2
1 2 1 2
BBROWN
1 2 1 2
BLACK
1 2 1 2
CN24 CN21 CN22 CN23 CN26 CN25
THERMISTOR
(COMPRESSOR)
THERMISTOR
(HEAT SINK)
BLUE
1 2 1 2
BROWN
BLACK
1 2 1 2
If the voltage does not appear, replace Main PCB.
07-15
Page 75
( For AR*A36L/ 45L )
Trouble shooting 14 OUTDOOR UNIT Error Method:
INDOOR UNIT
Pressure Switch Error
Indicate or Display:
Outdoor Unit : LED 9 times blink
ERROR CODE : E : 16
Detective Actuators:
Outdoor Unit Main PCB Circuit Pressure Switch
Detective details:
When pressure switch open is detected in 10 seconds after the power is turned on.
Forecast of Cause :
1. Connector connection failure 2. Pressure Switch failure 3. Main PCB failure
Check Point 1 : Reset Power Supply and operate
Does abnormal LED indication show again?
NONO
YES
Check Point 3 : Check Point 2 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Pressure Switch. (DC5.0V)
HIGH PRESSURE SW
RED
121
1 2 3
2
1 2 3
RED
BLACK
BLACK
4WV
CN37
If the voltage does not appear, replace Main PCB.
OK
Check Point 3 : Check Pressure Switch
Check if connector is loose or cable is open.
>> If no abnormal connection is found, replace Pressure Switch.
After replacing Pressure Switch, check operating condition and pressure in operation.
OK
Check Point 4 : Check High Pressure Protection on cooling
Check Excessive high pressure protection on cooling. (Refer to Trouble shooting 22)
07-16
Page 76
Trouble shooting 15
OUTDOOR UNIT Error Method:
IPM error (Permanent Stop)
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 0.5sec ON/ 0.5sec OFF (AR*A36L/ 45L) : LED 12 times blink
ERROR CODE : E : 17
Detective Actuators:
Outdoor Unit Main PCB Circuit Compressor
Detective details:
When more than normal operating current to IPM in Main PCB flows, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged 4. Compressor failure 5. Main PCB failure
Check Point 1 : Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose. Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
OK
Check Point 3 : Check Outdoor Fan
Check Outdoor Fan Motor. (Refer to Trouble shooting 19)
>> If the Fan Motor is failure, replace it.
OKOK
Check Point 4 : Check Compressor
Check Compressor.
(PARTS INFORMATION 2)
OKOK
Check Point 5 : Replace Main PCB
If Check Point 1 4 do not improve the symptom, change Main PCB.
07-17
Page 77
Trouble shooting 16
OUTDOOR UNIT Error Method:
CT error
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 2sec ON/ 2sec OFF (AR*A36L/ 45L) : No indication ERROR CODE : E : 18
Detective Actuators:
Outdoor Unit Main PCB Circuit Outdoor Unit Filter PCB Circuit (Input current sensor unit)
Detective details:
When Input Current Sensor has detected 0A, while Inverter Compressor is operating at higher than 56Hz(for AR*A12L-24L) or 50Hz(for AR*A36L/ 45L), after 1minute upon starting the Compressor. (Except during the defrost operation)
Forecast of Cause :
1. Defective connection of electric components 2. External cause 3. Filter PCB failure 4. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
NO
YES
Check Point 2 : Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose. Check if connector is removed.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
AR*A12L- 24L
Check Point 1-2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check Point 3 : Check Filter PCB and Main PCB
Check DC voltage of CN1 (between 2 (Brown) and 3 (Red)) on Filter PCB.
>> After 40seconds upon starting the Compressor, If it is higher than 0.2V, Main PCB is failure. (Filter PCB is normal) >> Replace Main PCB >> If it is lower than 0.2V, Filter PCB is failure. >> Replace Filter PCB
If it does not improve the symptom, change Main PCB.
Check Point 4 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
07-18
Page 78
( For AR*A36L/ 45L )
Trouble shooting 17 OUTDOOR UNIT Error Method:
INDOOR UNIT
Active Filter Module (AFM) error
Detective Actuators:
Outdoor Unit Main PCB Circuit Active Filter Module
Indicate or Display:
Outdoor Unit : No indication ERROR CODE : E : 19
Detective details:
When inverter input DC voltage is higher than 467V or lower than 237V. When a momentary power cut off occurred on low voltage.
Forecast of Cause :
1. External cause 2. Connector connection failure 3. Active Filter Module failure 4. Main PCB failure
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit. Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 2 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3 : Check Active Filter Module
Check Active Filter Module. (PARTS INFORMATION 3)
>>If Active Filter Module is abnormal, replace it.
OKOK
Check Point 4 : Replace Main PCB
If Check Point 1 3 do not improve the symptom, change Main PCB.
07-19
Page 79
Trouble shooting 18
OUTDOOR UNIT Error Method:
Compressor rotor location cannot detect (Permanent Stop)
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 0.1sec ON/ 2sec OFF (AR*A36L/ 45L) : LED 13 times blink
ERROR CODE : E : 1A
Detective Actuators:
Outdoor Unit Main PCB Circuit Compressor
Detective details:
While running the compressor, if the detected rotor location is out of phase with actual rotor location more than 90 degrees, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 2 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed. Check erroneous connection. Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3: Replace Main PCB
If Check Point 1,2 do not improve the symptom, change Main PCB.
07-20
Page 80
Trouble shooting 19
OUTDOOR UNIT Error Method:
Outdoor Unit Fan Motor Error
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 5sec ON/ 5sec OFF (AR*A36L/ 45L) : LED 15 times blink (Upper fan) LED 16 times blink (Lower fan) ERROR CODE : E : 1b
Detective Actuators:
Outdoor Unit Main PCB Circuit Outdoor Fan Motor
Detective details:
When outdoor fan rotation speed is less than 100rpm in 20 seconds after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60sec is repeated 3 times in a row, compressor and fan motor stops. If and repeats 5 times in a row, compressor and fan motor stops permanently.
Forecast of Cause:
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
AR*A12L- 24L AR*A36L/ 45L
RED
1 2 3
BLACK
4
WHITE
5
YELLOW
6
BROWN
7
RED
1 2 3
BLACK
4
WHITE
5
YELLOW
6
BROWN
7
FAN MOTOR 1
FM
FAN MOTOR 2
FM
CN801
1 2 3 4 5 6
RED
BLACK WHITE YELLOW BROWN
FAN MOTOR
FM
Read wire DC voltage
Red - Black
White - Black
150 390V
15 1.5V
CN800
CN801
Read wire DC voltage
Red - Black
300 400V
If the voltage is not correct, replace Main PCB.
White - Black
07-21
15 1.5V
Page 81
Trouble shooting 20 OUTDOOR UNIT Error Method:
INDOOR UNIT
Outdoor unit computer communication error
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 1c
Detective Actuators:
Outdoor Unit Main PCB Circuit
Forecast of Cause :
1. Main PCB failure
Check Point 1 : Replace Main PCB
Change Main PCB.
Trouble shooting 21 INDOOR UNIT Error Method:
INDOOR UNIT
Indoor manual auto switch error
Detective Actuators:
Indoor Unit Controller PCB Circuit Forced auto switch
Detective details:
When it cannot receive an effective signal for 10sec between the Main CPU and Sub CPU in outdoor unit.
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 20
Detective details:
When the Forced auto switch becomes ON for 30 consecutive seconds.
Forecast of Cause :
1. Forced auto switch failure 2.Controller PCB failure
Check Point 1 : Check the Forced auto switch
Check if Forced auto switch is kept pressed. Check ON/OFF switching operation by using a meter.
>>If Forced auto switch is detective, replace it.
OKOK
Check Point 2 : Replace Controller PCB
If Check Point 1 do not improve the symptom, change Controller PCB.
07-22
Page 82
Trouble shooting 22
OUTDOOR UNIT Error Method:
Excessive high pressure protection on cooling
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 24
Detective Actuators:
Outdoor Unit Main PCB Circuit Outdoor Fan Motor
Detective details:
Excessive high pressure protection on cooling mode has been activated.
Heat Exchanger Temp. Thermistor (Middle) Outdoor unit Electronic Expansion Valve
Forecast of Cause :
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged 4. Thermistor failure 5. EEV failure 6. Main PCB failure
Check Point 1 : Check connections of Outdoor Unit Electrical Components
Check if the terminal connection is loose. Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
OK
Check Point 3 : Check Outdoor Fan
Check Outdoor Fan Motor. (Refer to Trouble shooting 19)
>> If the Fan Motor is failure, replace it.
OKOK
Check Point 4 : Check Thermistor (middle)
Check Thermistor (middle). (Refer to Trouble shooting 26)
>> If the Thermistor (middle) is failure, replace it.
OKOK
Check Point 5 : Check Electronic Expansion Valve
Check EEV.
(PARTS INFORMATION 4)
OKOK
Check Point 6 : Replace Main PCB
If Check Point 1 5 do not improve the symptom, change Main PCB.
07-23
Page 83
( For AR*A12L - 24L )
Trouble shooting 23 OUTDOOR UNIT Error Method:
INDOOR UNIT
PFC circuit error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Indicate or Display:
Outdoor Unit : No indication ERROR CODE : E : 25
Detective details:
When inverter output DC voltage is higher than 415V for over 3 seconds, the compressor stops. If the same operation is repeated 5 times, the compressor stops permanently.
Forecast of Cause :
1. External cause 2. Connector connection failure 3. Main PCB failure
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit. Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 2 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
07-24
Page 84
Trouble shooting 26 OUTDOOR UNIT Error Method: Outdoor Heat Exchanger Temperature
Sensor (Middle) Error
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 0.1sec ON/ 0.1sec OFF (AR*A36L/ 45L) : LED 5 times blink
ERROR CODE : E : 29
Detective Actuators:
Outdoor Unit Main PCB Circuit Heat Exchanger Temperature
Detective details:
When Heat Exchanger Temperature Thermistor (Middle) open or short-circuit is detected at power ON or while running the compressor.
Thermistor (Middle)
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
15°C10°C5°C0°C-5°C-10°C
7.569.6312.416.121.027.8Resistance Value (k )
20°C
5.98
25°C
4.77
30°C
3.84
Temperature
If Thermistor is either open or shorted, replace it and reset the power.
70°C60°C50°C45°C40°C35°C
0.8401.191.712.082.533.11Resistance Value (k )
80°C
0.606
90°C
0.446
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
For AR*A12L- 24L For AR*A36L/ 45L
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
(OUTDOOR)
BLACK
(PIPE MID)
2 13 2 1 4 3 2 12 1 2 13 2 1 4 3 2 12 1
(COMPRESSOR)
BLACK
(DISCHARGE)
BROWN
CN70 CN72 CN73 CN71
BROWN
(PIPE OUT)
BLACK
THERMISTOR
(PIPE MID)
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE OUT)
THERMISTOR
(OUTDOOR)
BLACK
1 2 1 2
CN24 CN21 CN22 CN23 CN26 CN25
1 2 1 2
BBROWN
1 2 1 2
BLACK
1 2 1 2
100°C
0.333
THERMISTOR
BLUE
(COMPRESSOR)
1 2 1 2
DC
THERMISTOR
(HEAT SINK)
BROWN
BLACK
1 2 1 2
If the voltage does not appear, replace Main PCB.
07-25
Page 85
Trouble shooting 27 OUTDOOR UNIT Error Method:
INDOOR UNIT
Compressor temperature error
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 2sec ON/ 5sec OFF (AR*A36L/ 45L) : LED 10 times blink
ERROR CODE : E : 2b
Detective Actuators:
Outdoor Unit Main PCB Circuit Compressor Temperature Thermistor
Detective details:
When the compressor temperature becomes higher than 110°C, the compressor stops. After the compressor restarts, if the same operation is repeated, the compressor stops permanently.
Forecast of Cause :
1. Valve is close 2. EEV failure 3. Gas Leak, less 4. Compressor Thermistor failure
5. Outdoor Fan Operation failure 6. Outdoor Heat Exchanger clogged
< Cooling mode >
Check Point 1 : Check if Gas Valve is open
If it is not open, open it and check the operation.
< Heating mode >
Check Point 1 : Check if LIquid Valve is open
If it is not open, open it and check the operation.
OK OK
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 4)
>>If EEV or Strainer is defective, replace it.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 4)
>>If EEV or Strainer is defective, replace it.
OK
MPa MPa
Check Point 3 : Check if gas leak or less gas
Measure Gas pressure, if there is a leak, correct it.
>>If recharging refrigerant, make sure to perform vacuuming and recharge the specified amount.
OK
Check Point 4 : Check Compressor Thermistor
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 13), If defective, replace the thermistor
OK
Check Point 5 : Check Outdoor FAN, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger? Is the Fan rotating? (Check by hand and if it is locked, replace the motor) Check Outdoor Fan Motor.
>>If the Fan Motor is defective, replace it.
OK
07-26
Page 86
Trouble shooting 28 INDOOR UNIT Error Method:
4-way valve error
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 2c
Detective Actuators:
Indoor Unit Controller PCB Circuit Heat Exchanger Temperature Thermistor Room Temperature Thermistor 4-way valve
Detective details:
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops.
Cooling or Dry operation [Indoor heat exchanger temp.] - [Room temp.] > 10degC
Heating operation [indoor heat exchanger temp.] - [room temp.] < -10degC
If the same operation is repeated 5 times, the compressor stops permanently.
Forecast of Cause :
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 : Check Heat exchanger temp. thermistor and Room temp. thermistor
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 3, 4), If defective, replace the thermistor
OKOK
Check Point 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN30 from PCB and check the resistance value of coil. Resistance value is about 1.4k
>>If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ]
Check each piping temperature, and the location of the valve by the temperature difference.
>>If the value location is not proper, replace 4-way valve.
OKOK
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
07-27
Page 87
( For AR*A36L/ 45L )
Trouble shooting 29 OUTDOOR UNIT Error Method:
Heat Sink Temperature Sensor Error
Indicate or Display:
Outdoor Unit : LED 8 times blink
ERROR CODE : No indication
Detective Actuators:
Outdoor Unit Main PCB Circuit Heat Sink Temperature Thermistor
Detective details:
When Heat Sink Temperature Thermistor open or short-circuit is detected at power ON or while running the compressor.
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
15°C10°C5°C0°C-5°C-10°C
7.569.6312.416.121.027.8Resistance Value (k )
20°C
5.98
25°C
4.77
30°C
3.84
Temperature
If Thermistor is either open or shorted, replace it and reset the power.
70°C60°C50°C45°C40°C35°C
0.8401.191.712.082.533.11Resistance Value (k )
80°C
0.606
90°C
0.446
OKOK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
For AR*A36L/ 45L
THERMISTOR
(PIPE MID)
THERMISTOR
(DISCHARGE)
THERMISTOR
(PIPE OUT)
THERMISTOR
(OUTDOOR)
THERMISTOR
(COMPRESSOR)
THERMISTOR
(HEAT SINK)
BLACK
1 2 1 2
CN24 CN21 CN22 CN23 CN26 CN25
1 2 1 2
BBROWN
1 2 1 2
BLACK
1 2 1 2
BLUE
1 2 1 2
BROWN
BLACK
1 2 1 2
100°C
0.333
DC
If the voltage does not appear, replace Main PCB.
07-28
Page 88
Trouble shooting 30
OUTDOOR UNIT Error Method:
Compressor Start-up error (Permanent Stop)
Indicate or Display:
Outdoor Unit (AR*A12L- 24L) : LED 0.1sec ON/ 2sec OFF (AR*A36L/ 45L) : LED 14 times blink
ERROR CODE : E : 1A
Detective Actuators:
Outdoor Unit Main PCB Circuit Compressor
Detective details:
On start-up the compressor, when detected rotor position is out of phase with actual rotor position more than 90 degrees,the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 2 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection. Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OKOK
Check Point 3 : Replace Main PCB
If Check Point 1,2 do not improve the symptom, replace Main PCB.
07-29
Page 89
7-3 TROUBLE SHOOTING WITH NO ERROR CODE
Trouble shooting 31
Forecast of Cause:
1. Power Supply failure 2. External cause
Indoor Unit - No Power
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down? Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components
Check Voltage of power supply.
>> Check AC198 - 264V appears at Indoor Unit Terminal 1 - 2 (Power Supply).
YESYES
Check Fuse in Filter PCB.
>> If Fuse is open, check if the wiring between Terminal and Filter PCB is loose, and replace Fuse.
Check Varistor in Filter PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor.
OKOK
If the symptom does not change by above Check3, replace Filter PCB.
NO
07-30
Page 90
Trouble shooting 32
Outdoor Unit - No Power
Forecast of Cause:
1. Power Supply failure 2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
OKOK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
YESYES
Check Fuse in Main PCB.
>> If Fuse is open, check loose terminal or removed connector (CN1) , and replace Fuse.
Check Varistor in Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor. Upon checking the normal power supply, replace Varistor.
YESYES
Check Active Filter Module. (PARTS INFORMATION 3) >>If Active Filter Module is abnormal, replace it.
OK
If the symptom does not change by above Check 3, replace Main PCB.
NO
07-31
Page 91
Trouble shooting 33
Forecast of Cause:
1. Setting/ Connection failure 2. External cause
No Operation (Power is ON)
3. Electrical Component defective
Check Point 1 : Check indoor and outdoor installation condition
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control, or terminals between Indoor Units. Or, check if there is an open cable connection. Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and Data & Technical Manual.
OK
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
OK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Electrical Components at Indoor and Outdoor
Check Voltage at CN14 of Controller PCB. (Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
07-32
Page 92
Trouble shooting 34
No Cooling / No Heating
Forecast of Cause:
1. Indoor Unit error 2. Outdoor Unit error
3. Effect by Surrounding environment
4. Connection Pipe / Connection Wire failure 5. Refrigeration cycle failure
Check Point 1 : Check Indoor Unit
Does Indoor Unit FAN run on HIGH FAN?
Is Air Filter dirty? Is Heat Exchanger clogged? Check if Energy save function is operated.
OKOK
Check Point 2 : Check Outdoor Unit Operation
Check if Outdoor Unit is operating
(If not, refer to Trouble shooting 32) Check any objects that obstruct the air flow route.
Check clogged Heat Exchanger.
Is the Valve open?
OKOK
Check Point 3 : Check Site Condition
Is capacity of Indoor Unit fitted to Room size?
Any windows open? Or direct sunlight ?
OKOK
Check Point 4 : Check Indoor/ Outdoor Installation Condition
Check connection pipe (specified pipe length & Pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
OKOK
MPa MPa
Check Point 5 : Check Refrigeration Cycle
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 4)
Check Compressor (PARTS INFORMATION 1,2)
Attention
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
07-33
Page 93
Trouble shooting 35
Abnormal Noise
Forecast of Cause :
1. Abnormal installation (Indoor/ Outdoor) 2. Fan failure(Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Indoor Unit. (Check and correct followings)
Abnormal noise is coming from Outdoor Unit. (Check and correct followings)
Is Main Unit installed in stable condition? Is the installation of Air suction grille and front panel normal?
OK
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Trouble shooting 36
Forecast of Cause:
Water Leaking
Is Main Unit installed in stable condition? Is Fan Guard installed normally?
OK
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
OK
Check if vibration noise by loose bolt or contact noise of piping is happening.
OK
Is Compressor locked?
>> Check Compressor (PARTS INFORMATION 1,2)
1. Erroneous installation 2. Drain hose failure
Diagnosis method when water leak occurs
Is Main Unit installed in stable condition?
Is Main Unit broken or deformed at the time of
transportation or maintenance?
OKOK
Is Drain Hose connection loose?
Is there a trap in Drain Hose?
Is Drain Hose clogged?
OKOK
Is Fan rotating?
Diagnosis method when water is spitting out.
Is the filter clogged?
OKOK
Check Gas Pressure and correct it if there was a gas leak.
MPa MPa
07-34
Page 94
7-4 SERVICE PARTS INFORMATION
SERVICE PARTS INFORMATION 1
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection cable?
Check Filter PCB, Main PCB,
connection of Compressor,and winding
resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor is considered (Locked compressor due to clogged dirt or less oil)
Replace Compressor
Stops soon after starting up
Is there open or loose connection cable?
Is Gas Pipe Valve open? (Low Pressure is too low)
MPa MPa
Check if Refrigerant is leaking. (Recharge Refrigerant)
Abnormal noise
Check if vibration noise by loose bolt or contact noise of piping is happening.
Defective Compressor can be considered. (due to inside dirt clogging or broken component)
Replace Compressor
Check if Strainer is clogged. (PARTS INFORMATION 4)
Check Filter PCB, Main PCB, connection of Compressor,and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor can be considered. (Compression part broken or valve defective.)
07-35
Replace Compressor
Page 95
SERVICE PARTS INFORMATION 2
Inverter Compressor
Check Point 1 : Check Connection
Check terminal connection of Compressor (loose or incorrect wiring)
Terminal cover opened
UU(RED)(RED)
V V (WHITE)(WHITE)WW
(BLACK)(BLACK)
Check Point 2 : Check Winding Resistance
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
Check connection of Main PCB (Loose or incorrect wiring)
MAIN PCB
AR*A36L/ 45L
AR*A12L-24L
RED
WHITE
W304 W8
W305 W7
Compressor
W303 W9
BLACK
U
Resistance Value :
0.73 (For AR*A12L/ 14L/ 18L)
0.97 (For AR*A24L)
0.26 (For AR*A36L/ 45L) at 20°C
W
V
Check Point 3 : Replace Main PCB
If the symptom does not change with above Check 1, 2, replace Main PCB.
07-36
Page 96
( For AR*A36L/ 45L )
SERVICE PARTS INFORMATION 3
Active Filter Module
Check Point 1 : Check Open or Short-circuit and Diode (D1)
Remove connector, check the open or short-circuit and the diode in the module
L2L1
(+)
D1
( )
Power factor control
If it is abnormal,replace ACTIVE FILTER MODULE
N1
N2
Io
Check the open or short-circuit
P
Terminal
Resistance value
Tester(+) Tester(-)
(+) ( )
P
L1
P
L1,L2
L2
( )
N1
(+)
L2
N1
Control Box
N2
360k
0
720k
5.4M (approx.)
360k
5.8M (approx.)
Check the diode
Terminal
Resistance value
Tester(+) Tester(-)
L2
P
P
L2
5.3M (approx.)
5.4M (approx.)
Check Point 2 : Check the Output DC voltage (between P and N1)
Check the Output DC voltage (between P and N1) of compressor stopping and operating.
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping, Active Filter Module is detective. >> Replace Active Filter Module
07-37
Page 97
SERVICE PARTS INFORMATION 4
Outdoor unit Electronic Expansion Valve ( EEV )
Check Point 1 : Check Connections
Check connection of connector (CN27 or CN40) ( Loose connector or open cable )
EXPANSION VALVE COIL
EV
CN40 (For AR*A12L-24L) CN27 (For AR*A36L/ 45L)
CN27 CN40
1 2 3 4 5 6
RED BROWN BLUE ORANGE YELLOW WHITE
Check Point 2 : Check Coil of EEV
Remove connector, check each winding resistance of Coil.
Read wire
Resistance value
White - Red
Yellow - Brown
Orange - Red
46 4
at 20°C
Blue - Brown
If Resistance value is abnormal, replace EEV.
Check Point 3 : Check Voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Check Point 4 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
DC
Check Point 5 : Check Opening and Closing Operation of Valve
When Valve is closed, it has a temp. difference between Inlet and Outlet.
CLOSE Example : Hot Gas
Pipe (In)
Hi TEMP.
Pipe (Out)
Normal TEMP.
If it is open, it has no temp. difference between Inlet and Outlet.
OPEN Example : Hot Gas
Pipe (In)
Hi TEMP.
Pipe (Out)
Hi TEMP.
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in ,
but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
07-38
Page 98
DUCT type
R410A
INVERTER
8 . APPENDING DATA
Page 99
8. APPENDING DATA
Outdoor temperature
Indoor temperature
182123
25
121516
183223
AFR
12.2
271929
21
°CDB
-10
0
5
10
15
20
25
30
35
40
46
Outdoor temperature
Indoor temperature
1618202224
AFR
12.2
8-1. CAPACITY TABLE
MODEL : AR*A12LATN / AO*A12LACL
COOLING
°CDB
°CWB
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3.52 3.13 0.31 3.92 3.15 0.31 4.05 3.42 0.32 4.32 3.43 0.32 4.46 3.70 0.32 4.72 3.69 0.32 4.99 3.93 0.33
3.33 3.00 0.51 3.71 3.02 0.52 3.84 3.28 0.52 4.09 3.29 0.53 4.22 3.55 0.53 4.47 3.54 0.54 4.73 3.77 0.54
3.33 3.00 0.49 3.71 3.02 0.50 3.84 3.28 0.50 4.09 3.29 0.51 4.22 3.55 0.51 4.47 3.54 0.52 4.73 3.77 0.52
3.33 2.99 0.45 3.71 3.01 0.46 3.84 3.27 0.46 4.09 3.29 0.46 4.21 3.55 0.47 4.47 3.53 0.47 4.72 3.76 0.48
3.22 2.92 0.55 3.59 2.94 0.56 3.71 3.19 0.56 3.95 3.20 0.57 4.08 3.46 0.57 4.32 3.44 0.58 4.57 3.67 0.58
4.20 3.60 1.29 4.68 3.63 1.31 4.84 3.94 1.32 5.16 3.95 1.33 5.32 4.27 1.34 5.64 4.25 1.35 5.95 4.53 1.36
4.03 3.49 1.44 4.49 3.51 1.46 4.64 3.81 1.47 4.95 3.83 1.48 5.10 4.13 1.49 5.41 4.11 1.51 5.71 4.38 1.52
3.80 3.32 1.53 4.23 3.34 1.56 4.37 3.63 1.56 4.66 3.64 1.58 4.81 3.93 1.59 5.09 3.92 1.60 5.38 4.17 1.62
3.48 3.10 1.54 3.88 3.12 1.57 4.01 3.39 1.57 4.27 3.40 1.59 4.40 3.67 1.60 4.67 3.65 1.61 4.93 3.89 1.63
2.93 2.72 1.31 3.26 2.74 1.33 3.37 2.98 1.33 3.59 2.99 1.35 3.70 3.22 1.35 3.93 3.21 1.37 4.15 3.42 1.38
2.16 2.20 1.01 2.40 2.21 1.03 2.48 2.40 1.03 2.65 2.41 1.04 2.73 2.60 1.05 2.89 2.59 1.06 3.06 2.76 1.07
AFR : Air flow rate (m3/min)
TC : Total capacity (kW)
SHC : Sensible Heat capacity (kW)
PI : Power Input (kW)
HEATING
°CDB
°CDB °CWB TC PI TC PI TC PI TC PI TC PI
-15 -16 3.41 1.87 3.32 1.91 3.24 1.95 3.16 1.99 3.08 2.03
-10 -11 4.16 1.87 4.06 1.91 3.96 1.95 3.86 1.99 3.76 2.03
-5 -7 4.76 2.15 4.65 2.19 4.53 2.24 4.42 2.28 4.26 2.30
0 -2 5.43 2.22 5.30 2.27 5.17 2.30 4.92 2.30 4.70 2.30
5 3 5.91 2.21 5.77 2.26 5.63 2.30 5.37 2.30 5.14 2.30
7 6 5.99 2.06 5.84 2.10 5.70 2.15 5.56 2.19 5.42 2.23
10 8 6.20 2.04 6.06 2.08 5.91 2.12 5.76 2.16 5.61 2.21
15 10 6.39 2.01 6.24 2.05 6.09 2.09 5.93 2.14 5.78 2.18
20 15 6.42 1.78 6.27 1.81 6.12 1.85 5.96 1.89 5.81 1.92
24 18 6.46 1.76 6.31 1.79 6.15 1.83 6.00 1.87 5.84 1.90
AFR : Air flow rate (m3/min)
TC : Total capacity (kW)
PI : Power Input (kW)
08-01
Page 100
MODEL : AR*A14LATN / AO*A14LACL
Outdoor temperature
Indoor temperature
18212325272932
122123
AFR
13.7
151618
19
°CDB
-10
051015202530
35
40
46
13.7
Outdoor temperature
Indoor temperature
1618202224
AFR
COOLING
°CDB
°CWB
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
4.06 3.64 0.36 4.52 3.67 0.36 4.68 3.98 0.36 4.99 4.00 0.37 5.14 4.32 0.37 5.45 4.30 0.37 5.76 4.58 0.38
3.97 3.58 0.42 4.42 3.60 0.43 4.57 3.91 0.43 4.87 3.92 0.43 5.03 4.24 0.44 5.33 4.22 0.44 5.63 4.50 0.44
3.84 3.49 0.53 4.28 3.51 0.54 4.43 3.81 0.54 4.72 3.82 0.54 4.87 4.13 0.55 5.16 4.11 0.55 5.45 4.38 0.56
3.70 3.38 0.63 4.12 3.40 0.64 4.26 3.70 0.64 4.54 3.71 0.65 4.68 4.01 0.65 4.96 3.99 0.66 5.24 4.25 0.67
3.75 3.42 0.55 4.18 3.44 0.56 4.32 3.74 0.56 4.60 3.75 0.57 4.75 4.05 0.57 5.03 4.03 0.58 5.32 4.30 0.58
4.78 4.17 1.20 5.32 4.19 1.22 5.51 4.56 1.22 5.87 4.57 1.24 6.05 4.94 1.24 6.41 4.92 1.26 6.78 5.24 1.27
4.56 4.01 1.35 5.08 4.03 1.37 5.25 4.38 1.38 5.60 4.40 1.39 5.77 4.75 1.40 6.12 4.73 1.41 6.47 5.04 1.43
4.33 3.84 1.50 4.82 3.86 1.52 4.98 4.20 1.53 5.31 4.21 1.55 5.48 4.55 1.55 5.81 4.53 1.57 6.13 4.82 1.59
4.27 3.79 1.78 4.75 3.81 1.81 4.91 4.15 1.82 5.24 4.16 1.84 5.40 4.49 1.85 5.72 4.47 1.87 6.05 4.77 1.88
3.12 2.97 1.27 3.47 2.99 1.29 3.59 3.25 1.29 3.83 3.26 1.31 3.95 3.52 1.31 4.18 3.50 1.33 4.42 3.73 1.34
2.22 2.34 0.96 2.47 2.35 0.98 2.56 2.56 0.98 2.73 2.56 0.99 2.81 2.77 1.00 2.98 2.76 1.01 3.15 2.94 1.02
AFR : Air flow rate (m3/min)
TC : Total capacity (kW)
SHC : Sensible Heat capacity (kW)
PI : Power Input (kW)
HEATING
°CDB
°CDB °CWB TC PI TC PI TC PI TC PI TC PI
-15 -16 4.35 2.16 4.25 2.21 4.14 2.25 4.04 2.30 3.94 2.34
-10 -11 4.92 2.16 4.80 2.21 4.68 2.25 4.56 2.30 4.45 2.34
-5 -7 5.48 2.39 5.35 2.44 5.22 2.49 5.09 2.54 4.96 2.59
0 -2 6.29 2.56 6.14 2.61 5.99 2.67 5.84 2.72 5.69 2.77
5 3 7.04 2.74 6.88 2.80 6.71 2.85 6.46 2.87 6.17 2.87
7 6 6.83 2.35 6.66 2.40 6.50 2.45 6.34 2.49 6.18 2.54
10 8 7.08 2.40 6.91 2.45 6.74 2.50 6.57 2.55 6.40 2.60
15 10 6.71 2.06 6.55 2.10 6.39 2.14 6.23 2.19 6.07 2.23
20 15 6.28 1.64 6.13 1.67 5.98 1.71 5.83 1.74 5.68 1.78
24 18 6.47 1.64 6.32 1.68 6.16 1.71 6.01 1.75 5.85 1.78
AFR : Air flow rate (m3/min)
TC : Total capacity (kW)
PI : Power Input (kW)
08-02
Loading...