6 . DUCT TYPE :
AR 45LUAK, ART45LUAK
AR 54LUAK, ART54LUAK, ARTC54LATU
D2D_AR005E/04
2007.10.10
Page 2
6-1. FEATURE
MODELS :
AR 45LUAK / AO 45LJAYL, AO 45LJBYL
ART45LUAK / AOT45LJAYL, AOT45LJBYL
AR 54LUAK / AO 54LJAYL, AO 54LJBYL
ART54LUAK / AOT54LJAYL, AOT54LJBYL
ARTC54LATU / AOT54LJBYL
FEATURES
Improvement of market suitability
Considerable improvement of installation work by compact size and light weight considering with
the conditions of installation in the ceiling.
The size which the indoor unit can be installed in the spacing between the beams
is required for the installation in the ceiling.
Restriction for dimension of width and height.
Indoor unit installation example
DUCT TYPE
AR45 - 54H
Carrying-in example in the ceiling
Restriction for space when being carried
into the ceiling for replacement
(Ceiling intake grille)
Correspondence to Network
Various networks can be constructed according to the user needs.
1.Fresh air output port
Fresh air is connected with the fan of an indoor unit.
Fresh air
IndoorOutdoor
2.Electrical heater output port
Electrical heater operates at the time of heating.
750mm
400mm
550mm
500mm
DUCT TYPE
AR45 - 54H
Heater
Indoor
3.External input port
Start / Stop of the air conditioner can be changed from the external equipment.
- (06 - 01) -
Page 3
Operation sound (Low noise)
Succeeding in the increasing air flow volume and decreasing noise to 49dB(A) because the internal
air pressure was made uniform by chamfering
Current modelNew model
Realizing large airflow volume of 3,500 cubic meter by adopting large fan. (At 100Pa)
Realizing low noise by adopting plastic case, plastic fan and three positions airflow volume switch.
Decreasing noise by adoption of plastics fan.
Plastic processing of sirocco fan for airflow and fan casing of indoor unit.
DUCT TYPE
AR45 - 54H
800mm
Metal fan
HEAT EXCHANGER
240mm
CASING (Metal Sheet
Current model : Metal fan [53.1dB(A)] New model : Plastic fan [49.0dB(A)]
* Model : Material (At 100Pa : Actual noise measurement value)
400mm
)
Plastic fan
500mm
225mm
EXCHANGER
400mm
CASING (Plastic
HEAT
)
Installation change to Scroll compressor.
IN
Recipro-type :
[ 59.0dB(A)]
OUT
DC SCROLL
TYPE :
[ 52.0dB(A)]
The measured noise is the value when a compressor was mounted to the outdoor unit and the
cooling operation was performed.
DUCT TYPE
AR45 - 54H
Easy installation (Compact size & Light weight)
Realizing light weight corresponding to compact size of basic chassis and considerable
reduction of materials.
1,250mm
400mm
Current model : 75kgNew model : 50kg
800mm
400mm
1,050mm
- (06 - 02) -
500mm
Page 4
6-2. REMOTE CONTROLLER
6-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no bulge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in
Wired
remote
controller
Built-in timers
Weekly
timer
Setback timerWeekly timer
Setback
timer
DUCT TYPE
AR45 - 54H
Possible to set ON/OFF time to operate twice each day
of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 18 21
Screen
after setup
At "Weekly timer" + "Set back timer" setup
24℃ 28℃ 24℃
0 3 6 9 12 15 18 21 Time
Timer
area
Operation
area
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
0 3 6 9 12 15 18 21 Time
24°C
28°C
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
needed.
DUCT TYPE
AR45 - 54H
[
Variable timer control
]
The operation/display sections are zoned according to time and operation, enabling variable
pro-gramming to match application.
- (06 - 03) -
European
switch box
JIS box
Page 5
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
Display
2
7
8
9
10
11
12
Display panel
14
SUMOTUWETH FR
SET BACK
3 6 9
CLOCK ADJUST
SUMOTUWETH FR
3 6 9
12 15 18 21
DAY OFF
DELETESET
12 15 18 21
2
SA
13
DAY
ENERGY
THERMO
SAVE
SENSOR
1
3
4
6
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
5
6
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
Set back button
Pressed to select the set back timer.
15
1617 18
10
Set time button
Pressed to set time.
SA
11
Delete button
The schedule of a weekly timer is deleted.
12
Set button
1920
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
DUCT TYPE
AR45 - 54H
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
3 6 9
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETESET
Front View
120
SA
ENERGY
SAVE
THERMO
SENSOR
SPECIFICATION
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT ( g )160
CABLE LENGTH ( m )
POWER ( V )
10
12
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
Central control display
18
Temperature display
19
Stand by display
Indicates during the oil recovery and defrosting operation.
20
Energy save display
DUCT TYPE
AR45 - 54H
- (06 - 04) -
Page 6
6-3. SPECIFICATIONS
DUCT TYPE
AR45 - 54H
TYPE
MODEL NAME
POWER SOURCE
AVAILABLE VOLTAGE RANGE 198-264V~ 50Hz
CAPACITY
INPUT POWER
STARTING CURRENT
EER COOLING2.912.61
COP HEATING3.683.40
MOISTURE REMOVAL
AIR
CIRCULATION
COOL/HEAT
FAN SPEED
COOL/HEAT
RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty
FAN MOTOR OUTPUTW
NOISE LEVEL
(SOUND
PRESSURE)
COOL/HEAT
COMPRESSOR
COOLING
HEATING
COOLINGRATED / MAX4.30 / 5.155.36 / 5.90
HEATINGRATED / MAX3.80 / 5.154.70 / 5.90
COOLINGRATED / MAX18.9 / 22.623.6 / 25.9
HEATINGRATED / MAX16.7 / 22.520.6 / 25.9
INDOOR
COOL
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
TYPE
OUTPUT
STARTING METHOD
INDOOR
OUTDOOR
RATED / MAX
RATED / MAX
High
Med
Low
QUIET
High
Low
High
Med
Low
QUIET
High
Low
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
kW12.5 / 14.014.0 / 15.3
BTU/h42700 / 4780047800 / 52200
kW14.0 / 18.016.0 / 19.0
BTU/h47800 / 6150054600 / 64900
kW
A CURRENT
A1515
kW/kW
l/h (pints/h)3.0 (1.4)4.0 (1.9)
m3/h
r.p.m
Pa100 to 250100 to 250
dB(A)
W25002500
AR*45LUAKAR*54LUAK
AO*45LJAYL,
AO*45LJBYL
52 / 5352 / 53
Coil
Surface treatment
HEAT
EXCHANGER
TYPE
INDOOR
OUTDOOR
Rows x Stages
Fin Pitch
Coil Dimensions
Coil
Surface treatment
Rows x Stages
Fin Pitch
mm
mm
Coil Dimensions
SAFETY DEVICES
CASING COLOUR
INDOOR
DIMENSIONS
H ×W ×D
WEIGHT
PIPE
REFRIGERANT
OPERATION(OUTDOOR)
REMOTE CONTROLLER
DRAIN PIPE
Note:Specifications are based on the following conditions.
Note:
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 100 Pa.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
dimensions( )* are indicated the including flange,control box,safety drain pan.
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
CONNECTION METHOD
SIZEmm
MAX LENGTH
MAX HEIGHT
MATERIAL
SIZE
INDOOR
OUTDOOR
INDOOR
OUTDOOR
NET
GROSS
NET /
GROSS
LIQUID
GAS
TYPE
CHARGEg34003400
TYPEREFRIGERANT OIL
COOLING
HEATING
mm
kg(lbs)
m
m
℃
mm
WIRED WIRED
Outer diameter 25.4 / Inner diameter 21.5
DUCTED MODEL
INVERTER HEAT PUMP
AO*54LJAYL,
230V~ 50Hz
3500/3500
3000/3000
2460/2460
-
6600/6600
-
1300/1300
1130/1130
950/950
-
UPPER FAN:850 LOWER FAN:750
-
Sirocco x 2
Propeller x 2
539
103
49 / 49
45 / 45
42 / 42
DC SCROLL
Inverter Method
Plate fin coil
Hydrophilic coating
4 x 16
1.3
336.0x890.0x53.2
Plate fin coil
Corrosion resistant coating
2 x 60
1.3
1260.0x900.0x36.38
Fan motor thermal protector,Fuse
Fan motor thermal protector,Fuse
Hot-dipped galvanized steel sheet
Beige(10YR7.5/1.0NN)
400 × 1050(1150)* × 500(585)*
1290 x 900 x 330
460 × 1230 × 640
1430 x 1050 x 445
50 (110) / 55 (121)
105 (231) / 112 (247)
FLARE
9.52 (3/8 inc.)
15.88 (5/8 inc.)
70 (chargeless:20m)
30
R410A
Synthetic (POE oil)
-15 to 43
-15 to 24
Steel
AO*54LJBYL
DUCT TYPE
AR45 - 54H
- (06 - 05) -
Page 7
DUCT TYPE
Note:Specifications are based on the following conditions.
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 100 Pa.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
dimensions( )* are indicated the including flange,control box,safety drain pan.
AR45 - 54H
TYPE
MODEL NAME
POWER SOURCE 240V~ 50Hz
AVAILABLE VOLTAGE RANGE 198-264V~ 50Hz
CAPACITY
INPUT POWERkW
CURRENTA
STARTING CURRENT
EER COOLING2.912.54
COP HEATING3.683.40
MOISTURE REMOVAL
AIR
CIRCULATION
COOL/HEAT
FAN SPEED
COOL/HEAT
RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty
FAN MOTOR OUTPUTW
NOISE LEVEL
(SOUND
PRESSURE)
COOL/HEAT
COMPRESSOR
COOLINGRATED / MAX
HEATINGRATED / MAX
COOLINGRATED / MAX4.30 / 5.355.70 / 6.15
HEATINGRATED / MAX3.80 / 5.354.70 / 6.15
COOLINGRATED / MAX18.1 / 22.523.8 / 25.9
HEATINGRATED / MAX16.0 / 22.519.8 / 25.9
INDOOR
COOL
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
TYPEDC SCROLL
OUTPUT
STARTING METHODInverter Method
INDOOR
OUTDOOR
High
Med
Low
QUIET
High
Low
High
Med
Low
QUIET
High
Low
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
kW12.5 / 14.014.5 / 15.3
BTU/h42700 / 4780049500 / 52200
kW14.0 / 18.016.0 / 20.0
BTU/h47800 / 6150054600 / 68300
A1515
kW/kW
l/h (pints/h)3.0 (1.4)4.0 (1.9)
m3/h
r.p.m
Pa100 to 250100 to 250
dB(A)
W25002500
ART45LUAKART54LUAK, ARTC54LATU
AOT45LJAYL, AOT45LJBYLAOT54LJAYL, AOT54LJBYL
52 / 5352 / 53
Coil
Surface treatment
HEAT
EXCHANGER
TYPE
INDOOR
OUTDOOR
Rows x Stages
Fin Pitch
Coil Dimensions
Coil
Surface treatment
Rows x Stages
Fin Pitch
mm
mm
Coil Dimensions
SAFETY DEVICES
CASING COLOUR
INDOOR
DIMENSIONS
H ×W ×D
WEIGHT
PIPE
REFRIGERANT
REFRIGERANT OIL TYPESynthetic (POE oil)
OPERATION(OUTDOOR)
REMOTE CONTROLLER
DRAIN PIPE
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
CONNECTION METHODFLARE
SIZEmm
MAX LENGTH70 (chargeless:20m)
MAX HEIGHT30
MATERIALSteel
SIZEOuter diameter 25.4 / Inner diameter 21.5
INDOOR
OUTDOOR
INDOOR
OUTDOOR
NET
GROSS
NET /
GROSS
LIQUID
GAS
TYPER410A
CHARGEg34003400
COOLING
HEATING
mm
kg(lbs)
m
m
℃
WIRED WIRED
mm
DUCTED MODEL
INVERTER HEAT PUMP
3500/3500
3000/3000
2460/2460
-
6600/6600
-
1300/1300
1130/1130
950/950
-
UPPER FAN:850 LOWER FAN:750
-
Sirocco x 2
Propeller x 2
539
103
49 / 49
45 / 45
42 / 42
Plate fin coil
Hydrophilic coating
4 x 16
1.3
336.0x890.0x53.2
Plate fin coil
Corrosion resistant coating
2 x 60
1.3
1260.0x900.0x36.38
Fan motor thermal protector,Fuse
Fan motor thermal protector,Fuse
Hot-dipped galvanized steel sheet
Beige(10YR7.5/1.0NN)
400 × 1050(1150)* × 500(585)*
1290 x 900 x 330
460 × 1230 × 640
1430 x 1050 x 445
50 (110) / 55 (121)
105 (231) / 112 (247)
9.52 (3/8 inc.)
15.88(5/8 inc.)
-15 to 43
-15 to 24
DUCT TYPE
AR45 - 54H
- (06 - 06) -
Page 8
6-4. DIMENSIONS
6-4-1. OUTDOOR UNIT
1290
Top view
900
7731
(Unit : mm)
12330
DUCT TYPE
AR45 - 54H
21
370
Drain cap
mounting places
MOUNTING POSITION
When there are
obstacles at the
back or front side.
When there are obstacles
at the back and front sides.
9
Front view
Air flow
Drain cap
mounting place
Bottom view
400
Side view
When there are obstacles at
the back, side(s), and top.
196
99
151
170
When there are obstacles
at the back side with the
installation of more than
one unit.
DUCT TYPE
AR45 - 54H
100 mm
or more
600 mm
or more
100 mm
or more
100 to 300 mm *
- (06 - 07) -
600 to 1000 mm
250 mm
or more
250 mm or more
(Service space)
* If the space is larger than that is stated, the
condition will be the same as that there are no
obstacles.
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger
diameter.
DUCT TYPE
AR45 - 54H
DUCT TYPE
AR45 - 54H
- (06 - 24) -
Page 26
6-14. SAFETY DEVICE
INDOOR UNIT
PROTECTION FORM
PCB FUSE-3.15A 250V3.15A 250V
FAN MOTOR PROTECTORTHERMAL PROTECTOR150°C ± 5°C OFF150°C ± 5°C OFF
FUSE FOR FAN MOTOR-10A 400V10A 400V
AR 45L
ART45L
OUTDOOR UNIT
AR
ART54L
ARTC54L
54L
DUCT TYPE
AR45 - 54H
PROTECTION FORM
FUSE (SIDE OF INDOOR UNIT)-10A 250V10A 250V
-3.15A 250V3.15A 250V
FUSE ON MAIN PCB
-5A 250V5A 250V
FAN MOTOR PROTECTORTHERMAL PROTECTOR150°C ± 5°C OFF150°C ± 5°C OFF
COMPRESSOR -165°C±5°C OFF165°C ± 5°C OFF
HIGH PRESSURE PROTECTION -DC5V 4.2MPaDC5V 4.2MPa
AO 45LAO
AOT45LAOT54L
54L
DUCT TYPE
AR45 - 54H
- (06 - 25) -
Page 27
6-15. EXTERNAL INPUT & OUTPUT
PREPARATION
When the external input / output is used,
connect the external signal wire as shown
in the figure below.
CONTROL INPUT
You can control air conditioner on/off by
external control. You can select either
Edge and Pulse.
DIP Switch (Indoor Unit)
CN106
(Black)
Indoor unit
PCB
[Example]
+
Indoor
unit
-
CN114
(White)
CN5
(Black)
PCB
Ch1
1
2
3
Field supply
DUCT TYPE
AR45 - 54H
SW state
ON
PulseEdge
SW2
DIP-Switch
NO.
OFF
2
1 Edge
1.The last command has priority.
2.The wire connection is separate from the power cable line.
Ch1
On
(Input)
Off
Remote
controller
Indoor
Operation
On
unit
Stop
2 Pulse
200ms200ms200ms
DUCT TYPE
AR45 - 54H
Ch1
(Input)
Remote
controller
Indoor
unit
Operation
Stop
On
- (06 - 26) -
Off
Page 28
OPERATION DISPLAY
[Example]
Operation
indicator
Field supply
Operation
Ic
Vc
or
Vc : DC20V or Iess
Ic : 10mA or Iess
Indoor
unit
(WHITE)
+
2
1
-
CN115
Indoor
unit
Stop
SHORT
CN115
(Output)
OPEN
FRESH AIR OUTPUT SETTING
You can control sub fan by synchronizaton with fan operation of indoor unit.
DUCT TYPE
AR45 - 54H
[Example]
+
Indoor
unit
-
CN14
(GREEN)
1
2
Indoor
unit fan
CN14
(Output)
Field supplied
Operation
Stop
14V
0V
Power
Fuse
Fan, other
DUCT TYPE
AR45 - 54H
- (06 - 27) -
Page 29
EXTERNAL ELECTRICAL HEATER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation.
When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON.
When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode.
1 minute delay control set by cutting JM3 on PCB.
[Example]
DUCT TYPE
AR45 - 54H
+
Indoor
unit
1
2
-
CN15
(ORANGE)
Indoor
Operation
unit
Heating
Indoor
Stop
Operation
unit fan
Stop
14V
CN15
(Output)
0V
<Operation condition>
All conditions shall be met.
Under heating operation.
Fan mode : Either Hi, Med, Low, Quiet.
Field supplied
Power
Fuse
External Heater, other.
1min
DUCT TYPE
AR45 - 54H
Cold air prevention function not working (Heat exchanger temperature over 27 C ).
Temperature subtracted set temperature from room temperature is between -10 C to -3 C.
-10 C < *T < -3 C *T=Room temperature
Compressor 3 minutes stop mode is released.
Defrosting mode is released.
<Release condition>
Do not meet above condition , or room temperature is 1 C below from set temperature.
CAUTION!
!
Please locate external a heater between the indoor unit and the ductwork.
Please be sure to use delay control of a fan.
External
Heater
Supply air
- (06 - 28) -
Indoor unit
Return air
Page 30
1
2
3
4
1Room temperature correct coefficient of heating
2External input select
3Auto restart validity/invalidity
Rotary SWSW 3Indoor unit number setting
JM1 Room temperature correct coefficient of cooling
JM2 Commercial mode setting
JM3 Fan delay setting
Jumper Wire
Forbidden
INDOOR UNIT
DIP SW
SW 1
SW 2
6-16. FUNCTION SETTING
6-16-1. INDOOR UNIT
SWITCH POSITION
DUCT TYPE
AR45 - 54H
Duct type Indoor unit control circuit board
MAIN PCBPOWER PCB
CN114
CN106
CN115
CN4
CN5
CN16
SW1SW2
1 2 31 2 34
ON
OFF
SW1 SW2
SW3
ON
OFF
JM1
JM2
JM3
DUCT TYPE
AR45 - 54H
CN14
CN15
CN16
- (06 - 29) -
Page 31
6-16-2. SWITCH FUNCTION (INDOOR UNIT)
SW1-1OFF
SW1-2OFF
SW1-3OFF
SW1-4OFF
SW2-1SW state
OFF+4deg (Ceiling setting)
ON0deg (Room setting)
SW2-2SW state
OFFEdge
ONPulse
SW2-3SW state
OFFValidity
ONInvalidity
SW3SW state
0single
1-15Indoor unit address
DIP SWITCH SETTING
1. SW1 setting
1-1 Dip SW 1-1,1-2,1-3,1-4 setting forbidden
(Factory setting)
2. SW2 setting
2-1 Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient value of heating.
DUCT TYPE
AR45 - 54H
Heat temperature correction
(Factory setting)
2-2 Control input setting
This switch is used to select the format of external input command as shown in the table below.
(Factory setting)
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
(Factory setting)
DUCT TYPE
AR45 - 54H
ROTARY SWITCH SETTING
This switch can be used when group control system. Set the indoor unit address in the 1,2,-,15 order.
(Factory setting)
- (06 - 30) -
Page 32
JUMPER WIRE SETTING
JM2JM state
ConnectResidencial
DisconnectCommercial
JM3JM state
ConnectInvalidity
DisconnectValidity
ConnectorINPUTOUTPUTREMARKS
CN114
CONTROL INPUT
(OPERATION/STOP)
-
CN115-OPERATION DISPLAY
CN14-FRESH AIR
CN15-ELECTRICAL HEATER
See external
input/output settings
for details.
Room temperature correct coefficient of cooling
Decide the cooling temperature correct coefficient value of cooling
Cool temperature correction
JM1JM state
Connect0 deg
Disconnect
Commercial mode setting
"Hot start" can be canceled,fan operates continously when indoor unit is ON on every mode.
When you select "FAN:AUTO"mode fan goes in "HIGH"
Fan delay setting
This setting can be used when the auxiliary heater is mounted.
When the fan operation is stopped when the indoor unit is operating
with an auxiliary heater,the fan operation continues one minutes.
Set the remote controller DIP switch No.1 and 2 according to the following table.
(Factory setting)
Number of
remote
controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple)
This is switched according to the number of connected indoor units.
DIP-SW
No.3
OFF
Master unitSlave unit
DIP-SW
No.1
DIP-SW
No.2
ON
OFF
(Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW
No.1
ONON
DIP-SW
No.2
DUCT TYPE
AR45 - 54H
ONMultiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
(Factory setting)
DIP-SW
No.4
OFF
ONCooling only model
Heat Pump model
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
(Factory setting)
DIP-SW
No.5
OFF
ONValidity
Auto changeover
Invalidity
DUCT TYPE
AR45 - 54H
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used,
all of the settings stored in memory will be deleted if there is a power failure.
Remote controller which gives priority to ease-of-use and allows operation
of the necessary functions only.
Simple remote
controllers
Remote sensor unit
UTD - RS100
Accurate and Comfortable
New amenity space can be offered by installing the thermo sensor in the remote controller.
Because the remote controller has the switching function, the user can select the position of the
sensor. (Room temperature sensor selection)
Remote Sensor
in the bed room (effective at night)
Example of room temperature
sensor selection
DUCT TYPE
AR45 - 54H
Sensor part
Wired Remote Controller
THERMO
Day
The detecting point can be freely changed.
SENSOR
Night
Remote Controller
in the living room (effective during the day)
Remote Sensor (Optional Parts)
DUCT TYPE
AR45 - 54H
Long life filter
UTD - LF60KA
Intake air filter can be mounted to the indoor unit.
- (06 - 36) -
Loading...