General ARH30L, ARH30LUAN, AOH30LMAWL, ARH36L, ARH36LUAN Technical Manual

...
R410A
3 . DUCT TYPE :  AR 30LUAN, AR 36LUAN
D2D_AR002E/03
2006.05.30
MODELS : AR 30LUAN / AO 30LMAWL AR 36LUAN / AO 36LMAWL
FEATURES
Installation styles
Embedded in Ceiling
DUCT TYPE
AR30 - 36
Hanging from Ceiling
DUCT TYPE
AR30 - 36
Low static pressure mode function
When installed, normal middle static pressure mode, and low static pressure mode can be selected by switching over using DIP switch on the board in the control box. Therefore, these models can be op­erated under the wide range of conditions.
Slim & compact design
In the case of bottom suction type, as seen from lower rear part.
Control Box that has been convex shape is now united with main unit (DIP Switch is located on the internal substrate.)
One-touch operating and easy-to-install long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further com­pactification is attained by reducing 65 mm from the width with the flanking control box embedded inside the chassis.
- (03 - 01) -
EASY MAINTENANCE
In the case of rear suction type, as seen from lower rear part.
Conventional model
1
3
4
New model
4
1
1.Control box
2.Fan casing
3.Fan
4.Motor
2
2
DUCT TYPE
AR30 - 36
3
Bottom panel: 2 units
DUCT TYPE
AR30 - 36
Large bottom panel: 1 unit
Structural improvement is attained by making the bottom panel two pieces, front and rear, and the internal fan casing is also made dismountable in two pieces namely, upper and lower ones. The motor and fan maintenance and dismounting can be made easily by removing the rear panel and lower part of the casing with the main chassis installed.
- (03 - 02) -
3-2. REMOTE CONTROLLER
3-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16) Error indication.(A maximum of 16 error histories are memorizable.) Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible. Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature
DUCT TYPE
AR30 - 36
accurately with built-in thermo sensor.
DUCT TYPE
AR30 - 36
High performance and compact size
Three functions are combined in
Wired
remote
controller
Weekly
timer
Setback
timer
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Timer area
Operation area
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
24°C
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
- (03 - 03) -
European switch box
JIS box
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
DUCT TYPE
AR30 - 36
Display
2 7 8
9
10
11
12
Display panel
14
SUMOTUWETH FR
CLOCK ADJUST
SET BACK
DELETE SET
369
SUMOTUWETH FR
369
12 15 18 21
DAY OFF
12 15 18 21
2
SA
13
DAY
ENERGY
THERMO
SAVE
SENSOR
1 3
4
6
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
5
6
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
DUCT TYPE
AR30 - 36
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
Set back button
pressed select the set back timer.
15
1617 18
10
Set time button
Pessed to select the set back timer.
SA
11
Delete button
The schedule of a weekly timer is deleted.
12
Set button
1920
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETE SET
Front View
120
SA
ENERGY
SAVE
THERMO
SENSOR
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m )
POWER ( V )
10
12
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
Central control display
18
Temperature display
19
Stand by display Indicates during the oil recovery and defrosting operation.
20
Energy save display
- (03 - 04) -
3-3. SPECIFICATIONS
AR*30LUAN AR*36LUAN
AO*30LMAWL AO*36LMAWL
C E
kW 8.50/10.00 10.00/11.20
BTU/h 29000/34100 34100/38200
kW 10.00/11.20 11.20/12.77
BTU/h 34100/38200 38200/43600
COOLING RATED/MAX 2.96/3.45 4.08/4.20
HEATING RATED/MAX
2.68/3.50 3.18/4.15
COOLING RATED/MAX 13.0/15.2 17.9/18.4
HEATING RATED/MAX 11.7/15.3 13.9/18.8
A 15 15
EER
COOLING 2.87 2.45
COP HEATING 3.73 3.52
l/h (pints/h) 2.5(5.3) 3.0(6.3)
High
Med
Low
Pa
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
53.0/55.0 54.0/55.0
OUTPUT W
Rows x Stages x Fin Pitch
mm
Coil Dimensions mm
Rows x Stages x Fin Pitch
mm
Coil Dimensions mm
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
LIQUID
GAS
m
m
CHARGE kg
COOLING
HEATING
mm
- -
DUCTED MODELS
REVERSE CYCLE TYPE
Permanent Starting Condenser
30 to 150
Sirocco x 2
Propeller x 1
176
103
DC TWIN SROTARY(INVERTER)
1300
Plate fin coil
Hydrophilic coating
3 x 14 x 1.40
294 x 1000 x 39.9
Plate fin coil
Corrosion resistant coating
798 x 900 x 36.38
2 x 38 x 1.30
FAN MOTOR THERMAL PROTECTER, PCB FUSE
FAN MOTOR THERMAL PROTECTOR
PCB FUSE COMPRESSOR
THERMISTOR
Galvanized steel sheet
Beige(10YR7.5/1.0NN)
270 x 1135 x 700
830 x 900 x 330
300 x 1300 x 790
970 x 1050 x 445
43 / 50 ( 95 / 110)
FLARE
9.52(3/8 inc.)
15.88(5/8 inc.)
64/70(141/154)
50(chargeless:15m)
30
R410A
2.2
Synthetic (POE oil)
-10 to 43
-10 to 24
WIRED(AR-3TA1)
Steel
Outer diameter 38.0mm / Inner diameter 36.0mm
Remote Senser(UTD-RS100)
Simple Wired Remocon
(Fujitsu:UTB-YPB,General:UTB-GPB)
Square flange(UTD-SF045T)
Round flange(UTD-RF204)
Long life filter(UTD-LF25NA)
E x ternal cable set(UTD-ECS5A)
2200
2050
1850
3600
43.0/43.0
41.0/41.0
39.0/39.0
CASING COLOR STARTING METHOD
Surface treatment
FAN MOTOR OUTPUT
W
OUTDOOR
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
Surface treatment
Coil
INDOOR
TYPE
MODEL NAME
OUTDOOR
POWER SOURCE
OUTDOOR
INDOOR
COOLING
HEATING STARTING CURRENT
INDOOR
MOISTURE REMOVAL
RATED/MAX
RATED/MAX
CURRENT
A
CAPACITY
m3/h
kW
INPUT POWER
kW/kW
SAFETY DEVICES
OUTDOOR
AIR CIRCULATION
TYPE
COMPRESSOR
HEAT E x CHANGER TYPE
RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty OUTDOOR
mm
OPTIONS
MA x LENGTH
REMOTE CONTROLLER
DRAIN PIPE MATERIAL
REFRIGERANT
SIZE
TYPE
OPERATION(OUTDOOR)
°C
INDOOR
INDOOR
Coil
dB(A)
NET
GROSS TYPE
REFRIGERANT OIL
PIPE
MA x HEIGHT
CONNECTION METHOD
SIZE
mm
kg(lbs)
DIMENSIONS H × W × D WEIGHT
NET / GROSS
AVAILABLE VOLTAGE RANGE
198-264V 50Hz
230V 50Hz
EUROPEAN ENERGY LABEL
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB. Standard static pressure : 30Pa Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
- (03 - 05) -
3-4. DIMENSIONS
3-4-1. OUTDOOR UNIT
MODELS :
DUCT TYPE
AR30 - 36
AO
30L, AO
36L
Top view
(Unit : mm)
DUCT TYPE
AR30 - 36
Front view
Bottom view
Side view
- (03 - 06) -
MOUNTING POSITION
When there are obstacles at the back or front sides.
When there are obstacles at the back, side(s), and top.
When there are obstacles at the back, side with the installation of more than one unit.
AIR
AIR
DUCT TYPE
AR30 - 36
600 mm or more
100 mm
or more
100 mm or more
AIR
250 mm or mor
(Service space)
e
300 mm or more
250 mm or more
250 mm
or more
300 mm or more
DUCT TYPE
AR30 - 36
- (03 - 07) -
3-4-1. INDOOR UNIT
MODELS :
AR 30L , AR 36L
(Unit : mm)
Front view
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
Side view (L)
Top view
Rear view
Side view (R)
Refrigerant piping flare connection (Gas) Refrigerant piping flare connection (Liquid) Drain piping connection (Drain pipe : I.D. 36 O.D. 38) Drain piping connection with cap. Knock out hole for fresh air.
- (03 - 08) -
MOUNTING POSITION
(Unit : mm)
300mm or more
DUCT TYPE
MAINTENANCE HOLE
AR30 - 36
It shall be possible to install and remove the control box.
It shall be possible to install and remove the control box, fan units and filter.
150mm or more
DUCT TYPE
AR30 - 36
When using a square duct
- (03 - 09) -
3-5. REFRIGERANT CIRCUIT
MODELS : AR 30L / AO 30L
AR 36L / AO 36L
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
- (03 - 10) -