MODELS :
AR 30LUAN / AO 30LMAWL
AR 36LUAN / AO 36LMAWL
FEATURES
Installation styles
Embedded in Ceiling
DUCT TYPE
AR30 - 36
Hanging from Ceiling
DUCT TYPE
AR30 - 36
Low static pressure mode function
When installed, normal middle static pressure mode, and low static
pressure mode can be selected by switching over using DIP switch
on the board in the control box. Therefore, these models can be operated under the wide range of conditions.
Slim & compact design
In the case of bottom suction type, as seen from lower rear part.
Control Box that has been convex shape
is now united with main unit (DIP Switch is
located on the internal substrate.)
One-touch operating and easy-to-install
long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further compactification is attained by reducing 65 mm from the width with the flanking
control box embedded inside the chassis.
- (03 - 01) -
Page 3
EASY MAINTENANCE
In the case of rear suction type, as seen from lower rear part.
Conventional model
1
3
4
New model
4
1
1.Control box
2.Fan casing
3.Fan
4.Motor
2
2
DUCT TYPE
AR30 - 36
3
Bottom panel: 2 units
DUCT TYPE
AR30 - 36
Large bottom panel: 1 unit
Structural improvement is attained by making the bottom panel two pieces, front and
rear, and the internal fan casing is also made dismountable in two pieces namely,
upper and lower ones.
The motor and fan maintenance and dismounting can be made easily by removing
the rear panel and lower part of the casing with the main chassis installed.
- (03 - 02) -
Page 4
3-2. REMOTE CONTROLLER
3-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature
DUCT TYPE
AR30 - 36
accurately with built-in thermo sensor.
DUCT TYPE
AR30 - 36
High performance and compact size
Three functions are combined in
Wired
remote
controller
Weekly
timer
Setback
timer
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day
of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen
after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Timer
area
Operation
area
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
24°C
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
needed.
[
Variable timer control
]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
- (03 - 03) -
European
switch box
JIS box
Page 5
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
DUCT TYPE
AR30 - 36
Display
2
7
8
9
10
11
12
Display panel
14
SUMOTUWETH FR
CLOCK ADJUST
SET BACK
DELETESET
369
SUMOTUWETH FR
369
12 15 18 21
DAY OFF
12 15 18 21
2
SA
13
DAY
ENERGY
THERMO
SAVE
SENSOR
1
3
4
6
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
5
6
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
DUCT TYPE
AR30 - 36
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
Set back button
pressed select the set back timer.
15
1617 18
10
Set time button
Pessed to select the set back timer.
SA
11
Delete button
The schedule of a weekly timer is deleted.
12
Set button
1920
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETESET
Front View
120
SA
ENERGY
SAVE
THERMO
SENSOR
SPECIFICATION
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT( g )160
CABLE LENGTH ( m )
POWER( V )
10
12
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
Central control display
18
Temperature display
19
Stand by display
Indicates during the oil recovery and defrosting operation.
20
Energy save display
- (03 - 04) -
Page 6
3-3. SPECIFICATIONS
AR*30LUANAR*36LUAN
AO*30LMAWLAO*36LMAWL
C E
kW8.50/10.0010.00/11.20
BTU/h29000/3410034100/38200
kW10.00/11.2011.20/12.77
BTU/h34100/3820038200/43600
COOLINGRATED/MAX2.96/3.454.08/4.20
HEATINGRATED/MAX
2.68/3.503.18/4.15
COOLINGRATED/MAX13.0/15.217.9/18.4
HEATINGRATED/MAX11.7/15.313.9/18.8
A1515
EER
COOLING2.872.45
COP HEATING3.733.52
l/h (pints/h)2.5(5.3)3.0(6.3)
High
Med
Low
Pa
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
53.0/55.054.0/55.0
OUTPUTW
Rows x Stages x
Fin Pitch
mm
Coil Dimensionsmm
Rows x Stages x
Fin Pitch
mm
Coil Dimensionsmm
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
LIQUID
GAS
m
m
CHARGEkg
COOLING
HEATING
mm
--
DUCTED MODELS
REVERSE CYCLE TYPE
Permanent Starting Condenser
30 to 150
Sirocco x 2
Propeller x 1
176
103
DC TWIN SROTARY(INVERTER)
1300
Plate fin coil
Hydrophilic coating
3 x 14 x 1.40
294 x 1000 x 39.9
Plate fin coil
Corrosion resistant coating
798 x 900 x 36.38
2 x 38 x 1.30
FAN MOTOR THERMAL PROTECTER, PCB FUSE
FAN MOTOR THERMAL PROTECTOR
PCB FUSE COMPRESSOR
THERMISTOR
Galvanized steel sheet
Beige(10YR7.5/1.0NN)
270 x 1135 x 700
830 x 900 x 330
300 x 1300 x 790
970 x 1050 x 445
43 / 50 ( 95 / 110)
FLARE
9.52(3/8 inc.)
15.88(5/8 inc.)
64/70(141/154)
50(chargeless:15m)
30
R410A
2.2
Synthetic (POE oil)
-10 to 43
-10 to 24
WIRED(AR-3TA1)
Steel
Outer diameter 38.0mm / Inner diameter 36.0mm
Remote Senser(UTD-RS100)
Simple Wired Remocon
(Fujitsu:UTB-YPB,General:UTB-GPB)
Square flange(UTD-SF045T)
Round flange(UTD-RF204)
Long life filter(UTD-LF25NA)
E x ternal cable set(UTD-ECS5A)
2200
2050
1850
3600
43.0/43.0
41.0/41.0
39.0/39.0
CASING COLOR
STARTING METHOD
Surface treatment
FAN MOTOR OUTPUT
W
OUTDOOR
NOISE LEVEL
(SOUND
PRESSURE)
COOL/HEAT
Surface treatment
Coil
INDOOR
TYPE
MODEL NAME
OUTDOOR
POWER SOURCE
OUTDOOR
INDOOR
COOLING
HEATING
STARTING CURRENT
INDOOR
MOISTURE REMOVAL
RATED/MAX
RATED/MAX
CURRENT
A
CAPACITY
m3/h
kW
INPUT POWER
kW/kW
SAFETY DEVICES
OUTDOOR
AIR
CIRCULATION
TYPE
COMPRESSOR
HEAT
E x CHANGER
TYPE
RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty
OUTDOOR
mm
OPTIONS
MA x LENGTH
REMOTE CONTROLLER
DRAIN PIPE
MATERIAL
REFRIGERANT
SIZE
TYPE
OPERATION(OUTDOOR)
°C
INDOOR
INDOOR
Coil
dB(A)
NET
GROSS
TYPE
REFRIGERANT OIL
PIPE
MA x HEIGHT
CONNECTION METHOD
SIZE
mm
kg(lbs)
DIMENSIONS
H × W × D
WEIGHT
NET /
GROSS
AVAILABLE VOLTAGE RANGE
198-264V50Hz
230V 50Hz
EUROPEAN ENERGY LABEL
Note:Specifications are based on the following conditions.
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 30Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
- (03 - 05) -
Page 7
3-4. DIMENSIONS
3-4-1. OUTDOOR UNIT
MODELS :
DUCT TYPE
AR30 - 36
AO
30L, AO
36L
Top view
(Unit : mm)
DUCT TYPE
AR30 - 36
Front view
Bottom view
Side view
- (03 - 06) -
Page 8
MOUNTING POSITION
When there are obstacles at the
back or front sides.
When there are obstacles at the
back, side(s), and top.
When there are obstacles at the
back, side with the installation of
more than one unit.
AIR
AIR
DUCT TYPE
AR30 - 36
600 mm
or more
100 mm
or more
100 mm
or more
AIR
250 mm or mor
(Service space)
e
300 mm
or more
250 mm
or more
250 mm
or more
300 mm
or more
DUCT TYPE
AR30 - 36
- (03 - 07) -
Page 9
3-4-1. INDOOR UNIT
MODELS :
AR 30L , AR 36L
(Unit : mm)
Front view
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
Side view (L)
Top view
Rear view
Side view (R)
Refrigerant piping flare connection (Gas)
Refrigerant piping flare connection (Liquid)
Drain piping connection (Drain pipe : I.D. 36 O.D. 38)
Drain piping connection with cap.
Knock out hole for fresh air.
- (03 - 08) -
Page 10
MOUNTING POSITION
(Unit : mm)
300mm
or more
DUCT TYPE
MAINTENANCE HOLE
AR30 - 36
It shall be possible to install and remove
the control box.
It shall be possible to install and remove
the control box, fan units and filter.
AFR: Air flow rate (m3/min)
TC : Total capacity (kW)
SHC: Sensible Heat capacity (kW)
PI : Power Input (kW)
- (03 - 14) -
Page 16
3-8. CAPACITY COMPENSATION FOR PIPE LENGTH
Pipe length (m)
Pipe length (m)
COOLING
PIPE LENGTH (m)
Outdoor unit is
bottom-side
Outdoor unit is
bottom-side
Outdoor unit is
up-side
PIPE LENGTH (m)
HEIGHT DIFFERENCE (m)
HEIGHT DIFFERENCE (m)
HEATING
Outdoor unit is
up-side
AND HEIGHT DIFFERENCE
MODELS:
AR 30L / AO 30L
AR 36L / AO 36L
COEFFICIENT OF COMPENSATION FOR PIPE LENGTH
COOLINGHEATING
1.200
1.150
1.100
1.050
1.000
DUCT TYPE
AR30 - 36
0.950
0.900
0.850
Coefficient of compensation
0.800
01020304050
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
1.200
1.150
1.100
1.050
1.000
0.950
0.900
Coefficient of compensation
0.850
0.800
01020304050
DUCT TYPE
AR30 - 36
57.51520304050
30----0.9600.9350.913
20---0.9830.9600.9350.913
10--0.9890.9830.9600.9350.913
7.5-1.0000.9890.9830.9600.9350.913
50.9941.0000.9890.9830.9600.9350.913
00.9941.0000.9890.9830.9600.9350.913
-50.9860.9920.9810.9750.9520.9270.906
-7.5-0.9880.9770.9710.9480.9240.903
-10--0.9730.9670.9450.9200.899
-20---0.9510.9290.9050.884
-30----0.9140.8900.870
57.51520304050
30----0.9060.8850.872
20---0.9380.9160.8940.881
10--0.9590.9470.9250.9030.890
7.5-0.9930.9620.9500.9270.9050.893
50.9950.9950.9640.9520.9300.9070.895
01.0001.0000.9690.9570.9340.9120.899
-51.0001.0000.9690.9570.9340.9120.899
-7.5-1.0000.9690.9570.9340.9120.899
-10--0.9690.9570.9340.9120.899
-20---0.9570.9340.9120.899
-30----0.9340.9120.899
- (03 - 15) -
Page 17
3-9. ADDITIONAL CHARGE CALCULATION
AR*30LAR*36L
AO*30LAO*36L
m
40
g
2200+200
2200+1400
2200+1000
2200+600
g/m
20m
50m(max)
30m
40m
PRECHARGE
REFREGERANT TYPE
R410A
PIPE LENGTH
AMOUNT
15
2200
TYPE
DUCTED MODEL
MODEL NAME
INDOOR
OUTDOOR
HEAT PUMP TYPE
MODELS:
AR 30L / AO 30L
AR 36L / AO 36L
REFRIGERANT CHARGE
DUCT TYPE
AR30 - 36
ADDITIONAL charge
DUCT TYPE
AR30 - 36
- (03 - 16) -
Page 18
3-10. OPERATION RANGE
Outdoor temperature(°CDB)
Indoor temperature(°CDB)
Outdoor temperature(°CDB)
Indoor temperature(°CDB)
Indoor unitOutdoor unitModeIndoor temperature Indoor humidity Outdoor temperature
Cooling
Dry
18 to 32 °CAbout 80% less-10 to 43 °C
Heating
30 °C or less--10 to 24 °C
Operation Range
Model
AO*30L
AO*36L
AR*30L
AR*36L
COOLING, DRY
40
DUCT TYPE
AR30 - 36
30
20
DUCT TYPE
AR30 - 36
10
0
-100102030405060
HEATING
40
30
20
10
0
-100102030405060
- (03 - 17) -
Page 19
3-11. FAN PERFORMANCE AND AIR FLOW
305080100120140150
m3/h2200208019001750158013201120
l/s611578528486439367311
CFM1295122411181030930777659
m3/h200019101740160014401180-
l/s556531483444400328-
CFM117711241024942848695-
m3/h17901720158014501300--
l/s497478439403361--
CFM10541012930853765--
230V
FAN SPEED
Hi
Med
Low
Static pressure (Pa)
3-11-1. NORMAL MODE
MODELS :
AR 30L / AO 30L , AR 36L / AO 36L
230V
DUCT TYPE
AR30 - 36
Q-h Characteris tic curve
COOLING
160
140
120
Hi
Med
Low
100
DUCT TYPE
AR30 - 36
80
60
40
20
0
1,0001,5002,0002,500
COOLING
102.0
100.0
98.0
96.0
94.0
92.0
90.0
Cooling capacity(%)STATIC PRESSURE(Pa)
88.0
86.0
1,0001,5002,0002,500
Air temp
Capacity
15.0
14.5
14.0
13.5
13.0
12.5
12.0
11.5
11.0
°C)
Air temperature(
HEATING
104.0
102.0
100.0
98.0
96.0
94.0
92.0
90.0
88.0
86.0
Heating capacity(%)
84.0
82.0
80.0
1,0001,5002,0002,500
Testcondition:NofilterandFanmode.
Air temp
Capacity
AIR FLOW (m3/h)
- (03 - 18) -
50
48
°C)
46
44
42
40
Air temperature(
38
36
Page 20
3-11-2. LOW STATIC MODE
305070100
m3/h
2020191017801580
l/s561531494439
CFM118911241048930
m3/h
180017201620-
l/s500478450-
CFM10591012953-
m3/h
158015201450-
l/s439422403-
CFM930895853-
230V
FAN SPEED
Hi
Med
Low
Static pressure (Pa)
MODELS :
AR 30L / AO 30L , AR 36L / AO 36L
230V
DUCT TYPE
AR30 - 36
Q-h Characteris tic curve
120
100
80
Hi
Med
Low
DUCT TYPE
AR30 - 36
60
40
20
0
1,0001,5002,0002,500
102.0
100.0
98.0
96.0
94.0
92.0
90.0
Cooling capacity(%)STATIC PRESSURE(Pa)
88.0
86.0
1,0001,5002,0002,500
105.0
100.0
95.0
90.0
85.0
Heating capacity(%)
80.0
1,0001,5002,0002,500
Testcondition:NofilterandFanmode.
Air temp
Capacity
AIR FLOW (m3/h)
- (03 - 19) -
COOLING
HEATING
Air temp
Capacity
15.0
14.5
14.0
13.5
13.0
12.5
12.0
11.5
11.0
55
53
51
49
47
45
43
41
39
37
35
°C)
Air temperature(
°C)
Air temperature(
Page 21
3-12. NOISE LEVEL CURVE
3-12-1. OUTDOOR UNIT
MODEL : AO 30L
COOLINGHEATING
Condition
Fan speed : High
Voltage : 230V /50Hz
80
70
µbar)
NC-65
60
50
DUCT TYPE
AR30 - 36
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
0
6312 52505001,0002,0004,0008,000
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Old octave-band limiting frequencies, Hz
80
70
µbar)
NC-65
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
0
6312 52505001,0002,0004,0008,000
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
DUCT TYPE
AR30 - 36
Old octave-band limiting frequencies, Hz
MODEL : AO 36L
COOLINGHEATING
80
70
µbar)
NC-65
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
80
70
µbar)
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63125250500 1,0002,0004,0008,000
Octave band center frequency, Hz
0
63125250500 1,0002,0004,0008,000
Octave band center frequency, Hz
- (03 - 20) -
Page 22
3-12-2. INDOOR UNIT
LO
MODEL : AR 30L
COOLINGHEATING
Condition
Voltage : 230V /50Hz
Static pressure : 30Pa
80
70
µbar)
NC-65
60
50
DUCT TYPE
AR30 - 36
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
0
6312 52505001,0002,0004,0008,000
LO
HI
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Old octave-band limiting frequencies, Hz
80
70
µbar)
NC-65
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
0
6312 52505001,0002,0004,0008,000
HI
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
DUCT TYPE
AR30 - 36
Old octave-band limiting frequencies, Hz
MODEL : AR 36L
COOLINGHEATING
80
70
µbar)
NC-65
60
50
40
30
20
10
LO
HI
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave-band sound-pressure level dB : (0dB=0.0002
80
70
µbar)
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
NC-65
NC-60
NC-55
NC-50
HI
LO
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
6312 52505001,0002,0004,0008,000
Old octave-band limiting frequencies, Hz
- (03 - 21) -
0
63125250500 1,0002,0004,0008,000
Old octave-band limiting frequencies, Hz
Page 23
SOUND LEVEL CHECK POINT
INDOOR UNIT
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
OUTDOOR UNIT
- (03 - 22) -
Page 24
3-13. ELECTRIC CHARACTERISTICS
Main Fuse (Circuit breaker) Current
A
mm
2
Model Name
AR 30L
AR 36L
AO 30L
AO 36L
Mode
Rated Value
Power Supply
50
50
230
2303030
Max Opetating Curent
Starting Current
4.0
4.0
*1) Wiring Spec
-
-
27
21
Outdoor Fan Motor
0.34
0.34
1.52
1.52
Indoor Fan Motor
0.13
0.13
MODELS:
AR 30L / AO 30L
AR 36L / AO 36L
Indoor Unit
Outdoor Unit
VoltageV
FrequencyHz
Cooling Heating Cooling Heating
CurrentA13.011.717.913.9
InputkW2.962.684.083.18
A15.215.318.418.8
DUCT TYPE
AR30 - 36
A15151515
Power Cable
*2)Limited wiring lengthm
InputkW
Full Load Amp.
A
DUCT TYPE
AR30 - 36
InputkW
Full Load Amp.
*1) Wiring Spec :
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
Selected Sample (Selected based on Japan Electrotechnical Standard and Codes
Committee E0005)
When the wiring length becomes long, please select the wiring of a more larger diameter.
A
- (03 - 23) -
Page 25
PROTECTION FORMAR*30LAR*36L
PROTECTION FORMAO*30LAO*36L
OFF:4.2 ± 0.1MPa
ON:3.2 ± 0.15MPa
OFF:4.2 ± 0.1MPa
ON:3.2 ± 0.15MPa
OFF:120 ± 5°C
ON:80 ± 15°C
OFF:120 ± 5°C
ON:80 ± 16°C
OFF:130 ± 5°C
ON:80 ± 16°C
OFF:130 ± 5°C
ON:80 ± 17°C
FUSE (SIDE OF POWER SUPPLY
TERMINAL)
FUSE ON MAIN PCB
3-14. SAFETY DEVICE
OUTDOOR UNIT
MODEL NAME
FUSE ON POWER PCB---
FAN MOTOR PROTECTORTHERMAL PROTECTOR150°C ± 5°C OFF150°C ± 5°C OFF
COMPRESSOR ---
DUCT TYPE
AR30 - 36
HIGH PRESSURE PROTECTION -
LOW PRESSURE PROTECTION---
TERMINAL FUSE---
-25A 250V25A 250V
-10A 250V10A 250V
-3.15A 250V3.15A 250V
-5A 250V5A 250V
DUCT TYPE
AR30 - 36
DISCHARGE THERMOSTAT
COMPRESSOR THERMOSTAT
-
-
INDOOR UNIT
MODEL NAME
PCB FUSE-3.15A 250V3.15A 250V
FAN MOTOR PROTECTORTHERMAL PROTECTOR150°C ± 5°C OFF150°C ± 5°C OFF
FUSE FOR FAN MOTOR---
TERMINAL FUSE---
- (03 - 24) -
Page 26
3-15. EXTERNAL INPUT & OUTPUT
PREP
ARA
TION
When the external input / output is used,
connect the external signal wire as shown
in the figure below.
CONTROL
INPUT
You can control air conditioner on/off by
external control. You can select either
DUCT TYPE
AR30 - 36
Edge and Pulse.
[Example]
+
Indoor
unit
-
CN114
(White)
Ch1
DUCT TYPE
AR30 - 36
1
2
3
Field supply
DIP Switch (Indoor Unit)
SW state
ON
PulseEdge
SW2
DIP-Switch
NO.
OFF
2
1 Edge
1.The last command has priority.
2.The wire connection is separate from the power cable line.
Ch1
(Input)
Remote
controller
Indoor
unit
On
Off
On
Operation
Stop
2 Pulse
Ch1
(Input)
Remote
controller
Indoor
unit
Operation
Stop
200ms200ms200ms
On
- (03 - 25) -
Off
Page 27
OPERA
[Example]
TION DISPLA
Y
Operation
indicator
Ic
Vc
or
Vc : DC20V or less
Ic : 10mA or less
Indoor
unit
CN115
(WHITE)
+
2
1
-
Field supply
Indoor
Operation
unit
DUCT TYPE
AR30 - 36
Stop
SHORT
DUCT TYPE
AR30 - 36
CN115
FRESH
(Output)
AIR OUTPUT SETTING
OPEN
You can control sub fan by synchronizaton with fan operation of indoor unit.
[Example]
+
Indoor
unit
-
CN14
(GREEN)
1
2
Indoor
unit fan
CN14
(Output)
Field supplied
Operation
Stop
14V
0V
Fuse
Power
Fan, other
- (03 - 26) -
Page 28
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation.
When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON.
When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode.
1 minute delay control set by cutting JM3 on PCB.
[Example]
+
-
CN15
1
2
Power
Field supplied
Operation
Indoor
unit
DUCT TYPE
AR30 - 36
(ORANGE)
Indoor
Fuse
External Heater, other.
DUCT TYPE
AR30 - 36
unit
Heating
Indoor
Stop
1min
Operation
unit fan
Stop
14V
CN15
(Output)
0V
<Operation condition>
All conditions shall be met.
Under heating operation.
Fan mode : Either Hi, Med, Low, Quiet.
Cold air prevention function not working (Heat exchanger temperature over 27 C ).
Temperature subtracted set temperature from room temperature is between -10 C to -3 C.
-10 C < *T < -3 C *T=Room temperature
Compressor 3 minutes stop mode is released.
Defrosting mode is released.
<Release condition>
Do not meet above condition , or room temperature is 1 C below from set temperature.
CAUTION!
!
Please locate external a heater between the indoor unit and the ductwork.
Please be sure to use delay control of a fan.
External
Heater
Supply air
Indoor unit
Return air
- (03 - 27) -
Page 29
Change current capacity
No use (OFF)
1
OUTDOOR UNIT
2
3
DIP SW 1
PUSH SW
3-16. FUNCTION SETTING
3-16-1. OUTDOOR UNIT
Pump down switch
SWITCH POSITION
Outdoor unit control circuit board
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
DIP SW 1
OFFON
1
2
3
PUSH SW
- (03 - 28) -
Page 30
3-16-2.
13.5A
12.0A
DIP-SW
CURRENT
(MAX.)
18.0A *1
15.0A *2
OFF
OFF
OFFONON
OFF
ON
OFF
1
OFF
ON23
OFF
OFF
D
*1=36000BTU model's factory setting
DUCT TYPE
AR30 - 36
*2=30000BTU model's factory setting
PU
SWITCH FUNCTION (OUTDOOR UNIT)
G
IN
T
T
SE
H
C
T
I
SW
P
I
Current capacity setting
G
IN
T
ET
S
H
S
H
SWIT
C
DUCT TYPE
AR30 - 36
SW2 setting
Press the this push-button switch, and "PUMP DOWN OPERATION" is starting.
- (03 - 29) -
Page 31
3-16-3. INDOOR UNIT
MODELS:
AR 30L / AO 30L
AR 36L / AO 36L
INDOOR UNIT
1
Low static pressure function setting
SW 1
DIP SW
SW 2
Rotary SWSW 3Indoor unit number setting
DUCT TYPE
AR30 - 36
Jumper Wire
SWITCH POSITION
Duct type Indoor unit control circuit board
2
Forbidden
3
4
1Room temperature correct coefficient of heating
2External input select
3Auto restart validity/invalidity
JM1 Room temperature correct coefficient of cooling
JM2 Commercial mode setting
JM3 Fan delay setting
DUCT TYPE
AR30 - 36
POWER PCB
CN114
CN106
CN115
MAIN PCB
ON
OFF
CN4
CN5
CN16
CN14
CN15
SW1SW2
1 2 31 2 34
SW1 SW2
SW3
ON
OFF
JM1
JM2
JM3
- (03 - 30) -
CN16
Page 32
3-16-4. SWITCH FUNCTION (INDOOR UNIT)
SW1-1SW state
OFFNormal
ONLow static pressure
SW1-2OFF
SW1-3OFF
SW1-4OFF
SW2-1SW state
OFF +4 deg (Ceiling setting)
ON0 deg (Room setting)
SW2-2SW state
OFFEdge
ONPulse
SW2-3SW state
OFFValidity
ONInvalidity
SW3SW state
0single
1-15Indoor unit address
DIP SWITCH SETTING
1. SW1 setting
1-1 Low static pressure function setting
In case of installing in low static , you can minimize air flow and noise.
(Factory setting)
1-2 Dip SW 1-2,1-3,1-4 setting forbidden
DUCT TYPE
AR30 - 36
(Factory setting)
DUCT TYPE
AR30 - 36
2-1 Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
Heat temperature correction
(Factory setting)
2-2 External input select edge/pulse
This switch is used to select the format of external input command as shown in the table below.
(Factory setting)
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTORESTART SETTING
(Factory setting)
ROTARY SWITCH SETTING
This switch can be used when group control system. Set the indoor unit address in the 1,2,-,15 order.
(Factory setting)
- (03 - 31) -
Page 33
JUMPER WIRE SETTING
JM2JM state
ConnectResidencial
DisconnectCommercial
JM3JM state
ConnectInvalidity
DisconnectValidity
ConnectorINPUTOUTPUTREMARKS
CN114
CONTROL INPUT
(OPERATION/STOP)
-
CN115-OPERATION DISPLAY
CN14-FRESH AIR
CN15-ELECTRICAL HEATER
See external
input/output settings
for details.
JM1JM state
Connect0 deg
Disconnect+ 2 deg
Room temperature correct coefficient of cooling.
Decide the cooling temperature correct coefficient value of cooling.
Cool temperature corrction
Commercial mode setting
"Hot start" can be canceled,fan operates continously when indoor unit is ON on every mode.
When you select "FAN:AUTO"mode fan goes in "HIGH".
DUCT TYPE
AR30 - 36
Fan delay setting
This setting can be used when the auxiliary heater is mounted.
When the fan operation is stopped when the indoor unit is operating
with an auxiliary heater,the fan operation continues one minutes.
Set the remote controller DIP switch No.1 and 2 according to the following table.
(Factory setting)
Number of
remote
controller
1 (Normal)
2 (Dual)
DUCT TYPE
AR30 - 36
1-2 Group control setting
Number of indoor unit connection (One/Multiple)
This is switched according to the number of connected indoor units.
DIP-SW
No.3
OFF
Master unitSlave unit
DIP-SW
No.1
DIP-SW
No.2
ON
OFF
(Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW
No.1
ONON
DIP-SW
No.2
DUCT TYPE
AR30 - 36
ONMultiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
(Factory setting)
DIP-SW
No.4
OFF
ONCooling only model
Heat Pump model
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
(Factory setting)
DIP-SW
No.5
OFF
ONValidity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used,
all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
(Factory setting)
DIP-SW
No.6
OFF
ONValidity
Memory backup
Invalidity
- (03 - 34) -
Loading...
+ hidden pages