General ARH30L, ARH30LUAN, AOH30LMAWL, ARH36L, ARH36LUAN Technical Manual

...
Page 1
R410A
3 . DUCT TYPE :  AR 30LUAN, AR 36LUAN
D2D_AR002E/03
2006.05.30
Page 2
MODELS : AR 30LUAN / AO 30LMAWL AR 36LUAN / AO 36LMAWL
FEATURES
Installation styles
Embedded in Ceiling
DUCT TYPE
AR30 - 36
Hanging from Ceiling
DUCT TYPE
AR30 - 36
Low static pressure mode function
When installed, normal middle static pressure mode, and low static pressure mode can be selected by switching over using DIP switch on the board in the control box. Therefore, these models can be op­erated under the wide range of conditions.
Slim & compact design
In the case of bottom suction type, as seen from lower rear part.
Control Box that has been convex shape is now united with main unit (DIP Switch is located on the internal substrate.)
One-touch operating and easy-to-install long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further com­pactification is attained by reducing 65 mm from the width with the flanking control box embedded inside the chassis.
- (03 - 01) -
Page 3
EASY MAINTENANCE
In the case of rear suction type, as seen from lower rear part.
Conventional model
1
3
4
New model
4
1
1.Control box
2.Fan casing
3.Fan
4.Motor
2
2
DUCT TYPE
AR30 - 36
3
Bottom panel: 2 units
DUCT TYPE
AR30 - 36
Large bottom panel: 1 unit
Structural improvement is attained by making the bottom panel two pieces, front and rear, and the internal fan casing is also made dismountable in two pieces namely, upper and lower ones. The motor and fan maintenance and dismounting can be made easily by removing the rear panel and lower part of the casing with the main chassis installed.
- (03 - 02) -
Page 4
3-2. REMOTE CONTROLLER
3-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16) Error indication.(A maximum of 16 error histories are memorizable.) Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible. Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature
DUCT TYPE
AR30 - 36
accurately with built-in thermo sensor.
DUCT TYPE
AR30 - 36
High performance and compact size
Three functions are combined in
Wired
remote
controller
Weekly
timer
Setback
timer
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Timer area
Operation area
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
24°C
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
- (03 - 03) -
European switch box
JIS box
Page 5
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
DUCT TYPE
AR30 - 36
Display
2 7 8
9
10
11
12
Display panel
14
SUMOTUWETH FR
CLOCK ADJUST
SET BACK
DELETE SET
369
SUMOTUWETH FR
369
12 15 18 21
DAY OFF
12 15 18 21
2
SA
13
DAY
ENERGY
THERMO
SAVE
SENSOR
1 3
4
6
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
5
6
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
DUCT TYPE
AR30 - 36
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
Set back button
pressed select the set back timer.
15
1617 18
10
Set time button
Pessed to select the set back timer.
SA
11
Delete button
The schedule of a weekly timer is deleted.
12
Set button
1920
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETE SET
Front View
120
SA
ENERGY
SAVE
THERMO
SENSOR
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m )
POWER ( V )
10
12
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
Central control display
18
Temperature display
19
Stand by display Indicates during the oil recovery and defrosting operation.
20
Energy save display
- (03 - 04) -
Page 6
3-3. SPECIFICATIONS
AR*30LUAN AR*36LUAN
AO*30LMAWL AO*36LMAWL
C E
kW 8.50/10.00 10.00/11.20
BTU/h 29000/34100 34100/38200
kW 10.00/11.20 11.20/12.77
BTU/h 34100/38200 38200/43600
COOLING RATED/MAX 2.96/3.45 4.08/4.20
HEATING RATED/MAX
2.68/3.50 3.18/4.15
COOLING RATED/MAX 13.0/15.2 17.9/18.4
HEATING RATED/MAX 11.7/15.3 13.9/18.8
A 15 15
EER
COOLING 2.87 2.45
COP HEATING 3.73 3.52
l/h (pints/h) 2.5(5.3) 3.0(6.3)
High
Med
Low
Pa
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
53.0/55.0 54.0/55.0
OUTPUT W
Rows x Stages x Fin Pitch
mm
Coil Dimensions mm
Rows x Stages x Fin Pitch
mm
Coil Dimensions mm
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
LIQUID
GAS
m
m
CHARGE kg
COOLING
HEATING
mm
- -
DUCTED MODELS
REVERSE CYCLE TYPE
Permanent Starting Condenser
30 to 150
Sirocco x 2
Propeller x 1
176
103
DC TWIN SROTARY(INVERTER)
1300
Plate fin coil
Hydrophilic coating
3 x 14 x 1.40
294 x 1000 x 39.9
Plate fin coil
Corrosion resistant coating
798 x 900 x 36.38
2 x 38 x 1.30
FAN MOTOR THERMAL PROTECTER, PCB FUSE
FAN MOTOR THERMAL PROTECTOR
PCB FUSE COMPRESSOR
THERMISTOR
Galvanized steel sheet
Beige(10YR7.5/1.0NN)
270 x 1135 x 700
830 x 900 x 330
300 x 1300 x 790
970 x 1050 x 445
43 / 50 ( 95 / 110)
FLARE
9.52(3/8 inc.)
15.88(5/8 inc.)
64/70(141/154)
50(chargeless:15m)
30
R410A
2.2
Synthetic (POE oil)
-10 to 43
-10 to 24
WIRED(AR-3TA1)
Steel
Outer diameter 38.0mm / Inner diameter 36.0mm
Remote Senser(UTD-RS100)
Simple Wired Remocon
(Fujitsu:UTB-YPB,General:UTB-GPB)
Square flange(UTD-SF045T)
Round flange(UTD-RF204)
Long life filter(UTD-LF25NA)
E x ternal cable set(UTD-ECS5A)
2200
2050
1850
3600
43.0/43.0
41.0/41.0
39.0/39.0
CASING COLOR STARTING METHOD
Surface treatment
FAN MOTOR OUTPUT
W
OUTDOOR
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
Surface treatment
Coil
INDOOR
TYPE
MODEL NAME
OUTDOOR
POWER SOURCE
OUTDOOR
INDOOR
COOLING
HEATING STARTING CURRENT
INDOOR
MOISTURE REMOVAL
RATED/MAX
RATED/MAX
CURRENT
A
CAPACITY
m3/h
kW
INPUT POWER
kW/kW
SAFETY DEVICES
OUTDOOR
AIR CIRCULATION
TYPE
COMPRESSOR
HEAT E x CHANGER TYPE
RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty OUTDOOR
mm
OPTIONS
MA x LENGTH
REMOTE CONTROLLER
DRAIN PIPE MATERIAL
REFRIGERANT
SIZE
TYPE
OPERATION(OUTDOOR)
°C
INDOOR
INDOOR
Coil
dB(A)
NET
GROSS TYPE
REFRIGERANT OIL
PIPE
MA x HEIGHT
CONNECTION METHOD
SIZE
mm
kg(lbs)
DIMENSIONS H × W × D WEIGHT
NET / GROSS
AVAILABLE VOLTAGE RANGE
198-264V 50Hz
230V 50Hz
EUROPEAN ENERGY LABEL
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB. Standard static pressure : 30Pa Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
- (03 - 05) -
Page 7
3-4. DIMENSIONS
3-4-1. OUTDOOR UNIT
MODELS :
DUCT TYPE
AR30 - 36
AO
30L, AO
36L
Top view
(Unit : mm)
DUCT TYPE
AR30 - 36
Front view
Bottom view
Side view
- (03 - 06) -
Page 8
MOUNTING POSITION
When there are obstacles at the back or front sides.
When there are obstacles at the back, side(s), and top.
When there are obstacles at the back, side with the installation of more than one unit.
AIR
AIR
DUCT TYPE
AR30 - 36
600 mm or more
100 mm
or more
100 mm or more
AIR
250 mm or mor
(Service space)
e
300 mm or more
250 mm or more
250 mm
or more
300 mm or more
DUCT TYPE
AR30 - 36
- (03 - 07) -
Page 9
3-4-1. INDOOR UNIT
MODELS :
AR 30L , AR 36L
(Unit : mm)
Front view
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
Side view (L)
Top view
Rear view
Side view (R)
Refrigerant piping flare connection (Gas) Refrigerant piping flare connection (Liquid) Drain piping connection (Drain pipe : I.D. 36 O.D. 38) Drain piping connection with cap. Knock out hole for fresh air.
- (03 - 08) -
Page 10
MOUNTING POSITION
(Unit : mm)
300mm or more
DUCT TYPE
MAINTENANCE HOLE
AR30 - 36
It shall be possible to install and remove the control box.
It shall be possible to install and remove the control box, fan units and filter.
150mm or more
DUCT TYPE
AR30 - 36
When using a square duct
- (03 - 09) -
Page 11
3-5. REFRIGERANT CIRCUIT
MODELS : AR 30L / AO 30L
AR 36L / AO 36L
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
- (03 - 10) -
Page 12
3-6. WIRING DIAGRAMS
3-6-1. OUTDOOR UNIT
MODELS : AO 30L, AO 36L
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
- (03 - 11) -
Page 13
3-6-2. INDOOR UNIT
MODELS : AR 30L, AR 36L
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
- (03 - 12) -
Page 14
3-7. CAPACITY TABLE
Outdoor temperature
Indoor temperature
26°CDB
27°CDB
29°CDB
18°CWB
19°CWB
21°CDB
23°CDB
15°CWB
16°CWB
30°CDB
21°CWB
22°CWB
23°CWB
32°CDB
Outdoor temperature
Indoor temperature
21°CDB
23°CDB
26°CDB
23°CWB
21°CWB
22°CWB
15°CWB
16°CWB
18°CWB
19°CWB
27°CDB
29°CDB
30°CDB
32°CDB
3-7-1. COOLING
COOLING CAPACITY
MODELS :
AFR 37
(°CDB) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-10 7.59 6.41 1.97 7.73 6.85 1.99 7.99 7.18 2.01 8.12 7.09 2.02 8.36 6.96 2.04 8.48 6.79 2.04 8.58 7.18 2.05
0 8.73 7.19 1.73 8.96 7.93 1.73 9.40 8.44 1.75 9.62 8.41 1.75 10.05 8.29 1.76 10.27 8.24 1.76 10.47 8.78 1.76
10 7.58 6.33 2.05 7.77 6.81 2.05 8.15 7.34 2.07 8.34 7.24 2.08 8.71 7.16 2.09 8.88 7.03 2.09 9.05 7.50 2.09
20 10.04 7.90 2.31 10.40 8.66 2.31 11.14 9.38 2.30 11.52 9.35 2.29 12.28 9.29 2.27 12.67 9.25 2.26 13.05 9.94 2.25
30 8.74 7.31 2.77 9.07 8.07 2.78 9.73 8.80 2.78 10.07 8.78 2.79 10.77 8.73 2.78 11.11 8.69 2.78 11.46 9.39 2.77
35 8.66 7.28 3.41 8.99 8.04 3.42 9.66 8.77 3.44 10.00 8.75 3.45 10.61 8.67 3.41 10.96 8.64 3.41 11.30 9.34 3.41
DUCT TYPE
AR30 - 36
40 7.09 6.00 3.30 7.37 6.72 3.30 7.95 7.44 3.30 8.25 7.52 3.30 8.86 7.62 3.30 9.08 7.54 3.30 9.38 8.21 3.30
43 6.53 5.80 3.30 6.79 6.42 3.30 7.25 7.03 3.30 7.53 7.09 3.30 8.08 7.13 3.30 8.36 7.12 3.30 8.64 7.76 3.30
MODELS :
AFR 37
(°CDB) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-10 10.91 8.62 1.93 11.18 9.34 1.95 11.72 9.96 1.99 12.01 9.90 2.01 12.58 9.75 2.04 12.87 9.67 2.06 13.14 10.34 2.07
0 9.83 7.88 2.31 10.07 8.61 2.32 10.54 9.25 2.36 10.78 9.17 2.37 11.23 9.01 2.39 11.46 8.93 2.40 11.66 9.59 2.41
10 9.73 7.84 2.12 10.01 8.58 2.12 10.57 9.26 2.13 10.85 9.20 2.13 11.40 9.07 2.13 11.67 9.01 2.13 11.93 9.68 2.13
20 10.77 8.31 2.58 11.15 9.09 2.58 11.93 9.82 2.58 12.33 9.80 2.57 13.14 9.73 2.56 13.55 9.69 2.55 13.95 10.39 2.54
30 10.04 8.22 3.38 10.40 9.05 3.39 11.15 9.85 3.40 11.54 9.82 3.41 12.31 9.76 3.41 12.71 9.72 3.41 13.09 10.48 3.41
35 9.73 7.84 4.18 10.11 8.62 4.21 10.80 9.36 4.18 11.20 9.34 4.20 11.93 9.27 4.16 12.33 9.24 4.18 12.73 9.96 4.19
40 7.31 6.18 3.40 7.60 6.92 3.40 8.20 7.67 3.40 8.51 7.75 3.40 9.13 7.85 3.40 9.36 7.78 3.40 9.67 8.47 3.40
43 6.73 5.98 3.40 7.00 6.62 3.40 7.48 7.25 3.40 7.76 7.31 3.40 8.33 7.35 3.40 8.62 7.34 3.40 8.91 8.00 3.40
AR 30L / AO 30L
AR 36L / AO 36L
DUCT TYPE
AR30 - 36
AFR: Air flow rate (m3/min) TC : Total capacity (kW) SHC: Sensible Heat capacity (kW) PI : Power Input (kW)
- (03 - 13) -
Page 15
3-7-2. HEATING
(°CWB)
(°CWB)
Outdoor temperature
Indoor temperature
16°CDB
18°CDB
20°CDB
23°CDB
25°CDB
27°CDB
30°CDB
23°CDB
25°CDB
27°CDB
30°CDB
Outdoor temperature
Indoor temperature
16°CDB
18°CDB
20°CDB
MODELS : AR 30L / AO 30L
AFR 37
HEATING CAPACITY
(°CDB)
-10 -11 7.73 2.79 7.56 2.85 7.49 3.00 7.22 3.08 6.99 3.09 6.76 3.10 6.38 3.10
-4 -6 8.87 3.02 8.69 3.08 8.44 3.09 8.02 3.09 7.77 3.11 7.52 3.12 7.11 3.11
1 -1 10.21 3.10 9.95 3.11 9.58 3.09 9.11 3.09 8.83 3.10 8.54 3.12 8.04 3.11
7 6 11.77 3.50 11.50 3.50 11.20 3.50 10.57 3.50 10.22 3.50 9.79 3.50 9.20 3.50
12 10 13.83 3.50 13.35 3.50 13.12 3.50 12.35 3.50 11.92 3.50 11.48 3.50 10.77 3.50
18 13 13.32 3.13 13.15 3.22 12.95 3.30 12.61 3.41 12.30 3.48 11.92 3.55 11.34 3.68
20 15 12.77 3.02 12.62 3.10 12.45 3.18 11.95 3.18 11.56 3.19 11.21 3.21 10.52 3.22
DUCT TYPE
AR30 - 36
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
DUCT TYPE
AR30 - 36
MODELS : AR 36L / AO 36L
AFR 37
(°CDB)
-10 -11 7.73 2.85 7.56 2.90 7.49 3.07 7.22 3.14 7.05 3.20 6.87 3.25 6.60 3.33
-4 -6 8.87 3.09 8.69 3.14 8.51 3.20 8.22 3.29 8.03 3.34 7.84 3.40 7.53 3.49
1 -1 10.29 3.20 10.10 3.27 9.88 3.33 9.55 3.43 9.32 3.49 9.09 3.56 8.72 3.66
7 6 13.27 3.98 13.05 4.06 12.77 4.15 12.30 4.28 11.99 4.36 11.65 4.45 10.97 4.46
12 10 13.95 3.79 13.74 3.88 13.51 3.96 13.03 4.09 12.67 4.18 12.29 4.26 11.68 4.40
18 13 13.32 3.20 13.15 3.28 12.95 3.37 12.61 3.48 12.30 3.55 11.92 3.63 11.34 3.76
20 15 12.77 3.08 12.62 3.17 12.45 3.25 11.95 3.25 11.56 3.25 11.21 3.27 10.52 3.28
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
AFR: Air flow rate (m3/min) TC : Total capacity (kW) SHC: Sensible Heat capacity (kW) PI : Power Input (kW)
- (03 - 14) -
Page 16
3-8. CAPACITY COMPENSATION FOR PIPE LENGTH
Pipe length (m)
Pipe length (m)
COOLING
PIPE LENGTH (m)
Outdoor unit is
bottom-side
Outdoor unit is
bottom-side
Outdoor unit is
up-side
PIPE LENGTH (m)
HEIGHT DIFFERENCE (m)
HEIGHT DIFFERENCE (m)
HEATING
Outdoor unit is
up-side
AND HEIGHT DIFFERENCE
MODELS:
AR 30L / AO 30L AR 36L / AO 36L
COEFFICIENT OF COMPENSATION FOR PIPE LENGTH
COOLING HEATING
1.200
1.150
1.100
1.050
1.000
DUCT TYPE
AR30 - 36
0.950
0.900
0.850
Coefficient of compensation
0.800 0 10 20 30 40 50
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
1.200
1.150
1.100
1.050
1.000
0.950
0.900
Coefficient of compensation
0.850
0.800 0 10 20 30 40 50
DUCT TYPE
AR30 - 36
5 7.5 15 20 30 40 50
30 - - - - 0.960 0.935 0.913
20 - - - 0.983 0.960 0.935 0.913
10 - - 0.989 0.983 0.960 0.935 0.913
7.5 - 1.000 0.989 0.983 0.960 0.935 0.913
5 0.994 1.000 0.989 0.983 0.960 0.935 0.913
0 0.994 1.000 0.989 0.983 0.960 0.935 0.913
-5 0.986 0.992 0.981 0.975 0.952 0.927 0.906
-7.5 - 0.988 0.977 0.971 0.948 0.924 0.903
-10 - - 0.973 0.967 0.945 0.920 0.899
-20 - - - 0.951 0.929 0.905 0.884
-30 - - - - 0.914 0.890 0.870
5 7.5 15 20 30 40 50
30 - - - - 0.906 0.885 0.872
20 - - - 0.938 0.916 0.894 0.881
10 - - 0.959 0.947 0.925 0.903 0.890
7.5 - 0.993 0.962 0.950 0.927 0.905 0.893
5 0.995 0.995 0.964 0.952 0.930 0.907 0.895
0 1.000 1.000 0.969 0.957 0.934 0.912 0.899
-5 1.000 1.000 0.969 0.957 0.934 0.912 0.899
-7.5 - 1.000 0.969 0.957 0.934 0.912 0.899
-10 - - 0.969 0.957 0.934 0.912 0.899
-20 - - - 0.957 0.934 0.912 0.899
-30 - - - - 0.934 0.912 0.899
- (03 - 15) -
Page 17
3-9. ADDITIONAL CHARGE CALCULATION
AR*30L AR*36L
AO*30L AO*36L
m
40
g
2200+200
2200+1400
2200+1000
2200+600
g/m
20m
50m(max)
30m
40m
PRECHARGE
REFREGERANT TYPE
R410A
PIPE LENGTH
AMOUNT
15
2200
TYPE
DUCTED MODEL
MODEL NAME INDOOR
OUTDOOR
HEAT PUMP TYPE
MODELS:
AR 30L / AO 30L AR 36L / AO 36L
REFRIGERANT CHARGE
DUCT TYPE
AR30 - 36
ADDITIONAL charge
DUCT TYPE
AR30 - 36
- (03 - 16) -
Page 18
3-10. OPERATION RANGE
Outdoor temperature(°CDB)
Indoor temperature(°CDB)
Outdoor temperature(°CDB)
Indoor temperature(°CDB)
Indoor unit Outdoor unit Mode Indoor temperature Indoor humidity Outdoor temperature
Cooling
Dry
18 to 32 °C About 80% less -10 to 43 °C
Heating
30 °C or less - -10 to 24 °C
Operation Range
Model
AO*30L AO*36L
AR*30L AR*36L
COOLING, DRY
40
DUCT TYPE
AR30 - 36
30
20
DUCT TYPE
AR30 - 36
10
0
-10 0 10 20 30 40 50 60
HEATING
40
30
20
10
0
-10 0 10 20 30 40 50 60
- (03 - 17) -
Page 19
3-11. FAN PERFORMANCE AND AIR FLOW
30 50 80 100 120 140 150
m3/h 2200 2080 1900 1750 1580 1320 1120
l/s 611 578 528 486 439 367 311
CFM 1295 1224 1118 1030 930 777 659
m3/h 2000 1910 1740 1600 1440 1180 -
l/s 556 531 483 444 400 328 -
CFM 1177 1124 1024 942 848 695 -
m3/h 1790 1720 1580 1450 1300 - -
l/s 497 478 439 403 361 - -
CFM 1054 1012 930 853 765 - -
230V
FAN SPEED
Hi
Med
Low
Static pressure (Pa)
3-11-1. NORMAL MODE
MODELS :
AR 30L / AO 30L , AR 36L / AO 36L
230V
DUCT TYPE
AR30 - 36
Q-h Characteris tic curve
COOLING
160
140
120
Hi
Med
Low
100
DUCT TYPE
AR30 - 36
80
60
40
20
0
1,000 1,500 2,000 2,500
COOLING
102.0
100.0
98.0
96.0
94.0
92.0
90.0
Cooling capacity(%) STATIC PRESSURE(Pa)
88.0
86.0
1,000 1,500 2,000 2,500
Air temp
Capacity
15.0
14.5
14.0
13.5
13.0
12.5
12.0
11.5
11.0
°C)
Air temperature(
HEATING
104.0
102.0
100.0
98.0
96.0
94.0
92.0
90.0
88.0
86.0
Heating capacity(%)
84.0
82.0
80.0 1,000 1,500 2,000 2,500
Testcondition:NofilterandFanmode.
Air temp
Capacity
AIR FLOW (m3/h)
- (03 - 18) -
50
48
°C)
46
44
42
40
Air temperature(
38
36
Page 20
3-11-2. LOW STATIC MODE
30 50 70 100
m3/h
2020 1910 1780 1580
l/s 561 531 494 439
CFM 1189 1124 1048 930
m3/h
1800 1720 1620 -
l/s 500 478 450 -
CFM 1059 1012 953 -
m3/h
1580 1520 1450 -
l/s 439 422 403 -
CFM 930 895 853 -
230V
FAN SPEED
Hi
Med
Low
Static pressure (Pa)
MODELS :
AR 30L / AO 30L , AR 36L / AO 36L
230V
DUCT TYPE
AR30 - 36
Q-h Characteris tic curve
120
100
80
Hi
Med
Low
DUCT TYPE
AR30 - 36
60
40
20
0 1,000 1,500 2,000 2,500
102.0
100.0
98.0
96.0
94.0
92.0
90.0
Cooling capacity(%) STATIC PRESSURE(Pa)
88.0
86.0 1,000 1,500 2,000 2,500
105.0
100.0
95.0
90.0
85.0
Heating capacity(%)
80.0 1,000 1,500 2,000 2,500
Testcondition:NofilterandFanmode.
Air temp
Capacity
AIR FLOW (m3/h)
- (03 - 19) -
COOLING
HEATING
Air temp
Capacity
15.0
14.5
14.0
13.5
13.0
12.5
12.0
11.5
11.0
55
53
51
49
47
45
43
41
39
37
35
°C)
Air temperature(
°C)
Air temperature(
Page 21
3-12. NOISE LEVEL CURVE
3-12-1. OUTDOOR UNIT
MODEL : AO 30L
COOLING HEATING
Condition Fan speed : High Voltage : 230V /50Hz
80
70
µbar)
NC-65
60
50
DUCT TYPE
AR30 - 36
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
0
63 12 5 250 500 1,000 2,000 4,000 8,000
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Old octave-band limiting frequencies, Hz
80
70
µbar)
NC-65
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
0
63 12 5 250 500 1,000 2,000 4,000 8,000
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
DUCT TYPE
AR30 - 36
Old octave-band limiting frequencies, Hz
MODEL : AO 36L
COOLING HEATING
80
70
µbar)
NC-65
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
80
70
µbar)
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
- (03 - 20) -
Page 22
3-12-2. INDOOR UNIT
LO
MODEL : AR 30L
COOLING HEATING
Condition Voltage : 230V /50Hz Static pressure : 30Pa
80
70
µbar)
NC-65
60
50
DUCT TYPE
AR30 - 36
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
0
63 12 5 250 500 1,000 2,000 4,000 8,000
LO
HI
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Old octave-band limiting frequencies, Hz
80
70
µbar)
NC-65
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
0
63 12 5 250 500 1,000 2,000 4,000 8,000
HI
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
DUCT TYPE
AR30 - 36
Old octave-band limiting frequencies, Hz
MODEL : AR 36L
COOLING HEATING
80
70
µbar)
NC-65
60
50
40
30
20
10
LO
HI
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave-band sound-pressure level dB : (0dB=0.0002
80
70
µbar)
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002
NC-65
NC-60
NC-55
NC-50
HI
LO
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 12 5 250 500 1,000 2,000 4,000 8,000
Old octave-band limiting frequencies, Hz
- (03 - 21) -
0
63 125 250 500 1,000 2,000 4,000 8,000
Old octave-band limiting frequencies, Hz
Page 23
SOUND LEVEL CHECK POINT
INDOOR UNIT
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
OUTDOOR UNIT
- (03 - 22) -
Page 24
3-13. ELECTRIC CHARACTERISTICS
Main Fuse (Circuit breaker) Current
A
mm
2
Model Name
AR 30L
AR 36L
AO 30L
AO 36L
Mode
Rated Value Power Supply
50
50
230
2303030
Max Opetating Curent
Starting Current
4.0
4.0
*1) Wiring Spec
-
-
27
21
Outdoor Fan Motor
0.34
0.34
1.52
1.52
Indoor Fan Motor
0.13
0.13
MODELS:
AR 30L / AO 30L AR 36L / AO 36L
Indoor Unit
Outdoor Unit
Voltage V
Frequency Hz
Cooling Heating Cooling Heating
Current A 13.0 11.7 17.9 13.9
Input kW 2.96 2.68 4.08 3.18
A 15.2 15.3 18.4 18.8
DUCT TYPE
AR30 - 36
A 15 15 15 15
Power Cable
*2)Limited wiring length m
Input kW
Full Load Amp.
A
DUCT TYPE
AR30 - 36
Input kW
Full Load Amp.
*1) Wiring Spec :
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
When the wiring length becomes long, please select the wiring of a more larger diameter.
A
- (03 - 23) -
Page 25
PROTECTION FORM AR*30L AR*36L
PROTECTION FORM AO*30L AO*36L
OFF:4.2 ± 0.1MPa ON:3.2 ± 0.15MPa
OFF:4.2 ± 0.1MPa ON:3.2 ± 0.15MPa
OFF:120 ± 5°C
ON:80 ± 15°C
OFF:120 ± 5°C
ON:80 ± 16°C
OFF:130 ± 5°C
ON:80 ± 16°C
OFF:130 ± 5°C
ON:80 ± 17°C
FUSE (SIDE OF POWER SUPPLY TERMINAL)
FUSE ON MAIN PCB
3-14. SAFETY DEVICE
OUTDOOR UNIT
MODEL NAME
FUSE ON POWER PCB - - -
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150°C ± 5°C OFF 150°C ± 5°C OFF
COMPRESSOR - - -
DUCT TYPE
AR30 - 36
HIGH PRESSURE PROTECTION -
LOW PRESSURE PROTECTION - - -
TERMINAL FUSE - - -
- 25A 250V 25A 250V
- 10A 250V 10A 250V
- 3.15A 250V 3.15A 250V
- 5A 250V 5A 250V
DUCT TYPE
AR30 - 36
DISCHARGE THERMOSTAT
COMPRESSOR THERMOSTAT
-
-
INDOOR UNIT
MODEL NAME
PCB FUSE - 3.15A 250V 3.15A 250V
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150°C ± 5°C OFF 150°C ± 5°C OFF
FUSE FOR FAN MOTOR - - -
TERMINAL FUSE - - -
- (03 - 24) -
Page 26
3-15. EXTERNAL INPUT & OUTPUT
PREP
ARA
TION
When the external input / output is used, connect the external signal wire as shown in the figure below.
CONTROL
INPUT
You can control air conditioner on/off by external control. You can select either
DUCT TYPE
AR30 - 36
Edge and Pulse.
[Example]
+
Indoor unit
-
CN114
(White)
Ch1
DUCT TYPE
AR30 - 36
1
2
3
Field supply
DIP Switch (Indoor Unit)
SW state
ON
PulseEdge
SW2
DIP-Switch
NO.
OFF
2
1 Edge
1.The last command has priority.
2.The wire connection is separate from the power cable line.
Ch1 (Input)
Remote controller
Indoor unit
On
Off
On
Operation
Stop
2 Pulse
Ch1 (Input)
Remote controller
Indoor unit
Operation
Stop
200ms 200ms 200ms
On
- (03 - 25) -
Off
Page 27
OPERA
[Example]
TION DISPLA
Y
Operation indicator
Ic
Vc
or
Vc : DC20V or less Ic : 10mA or less
Indoor unit
CN115
(WHITE)
+
2
1
-
Field supply
Indoor
Operation
unit
DUCT TYPE
AR30 - 36
Stop
SHORT
DUCT TYPE
AR30 - 36
CN115
FRESH
(Output)
AIR OUTPUT SETTING
OPEN
You can control sub fan by synchronizaton with fan operation of indoor unit.
[Example]
+
Indoor unit
-
CN14
(GREEN)
1
2
Indoor unit fan
CN14 (Output)
Field supplied
Operation
Stop
14V
0V
Fuse
Power
Fan, other
- (03 - 26) -
Page 28
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation. When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON. When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode. 1 minute delay control set by cutting JM3 on PCB.
[Example]
+
-
CN15
1
2
Power
Field supplied
Operation
Indoor unit
DUCT TYPE
AR30 - 36
(ORANGE)
Indoor
Fuse
External Heater, other.
DUCT TYPE
AR30 - 36
unit
Heating
Indoor
Stop
1min
Operation
unit fan
Stop
14V
CN15 (Output)
0V
<Operation condition>
All conditions shall be met.
Under heating operation.
Fan mode : Either Hi, Med, Low, Quiet.
Cold air prevention function not working (Heat exchanger temperature over 27 C ).
Temperature subtracted set temperature from room temperature is between -10 C to -3 C.
-10 C < *T < -3 C *T=Room temperature
Compressor 3 minutes stop mode is released.
Defrosting mode is released.
<Release condition>
Do not meet above condition , or room temperature is 1 C below from set temperature.
CAUTION!
!
Please locate external a heater between the indoor unit and the ductwork. Please be sure to use delay control of a fan.
External Heater
Supply air
Indoor unit
Return air
- (03 - 27) -
Page 29
Change current capacity No use (OFF)
1
OUTDOOR UNIT
2
3
DIP SW 1
PUSH SW
3-16. FUNCTION SETTING
3-16-1. OUTDOOR UNIT
Pump down switch
SWITCH POSITION
Outdoor unit control circuit board
DUCT TYPE
AR30 - 36
DUCT TYPE
AR30 - 36
DIP SW 1
OFF ON
1
2
3
PUSH SW
- (03 - 28) -
Page 30
3-16-2.
13.5A
12.0A
DIP-SW
CURRENT
(MAX.)
18.0A *1
15.0A *2
OFF
OFF
OFFONON
OFF
ON
OFF
1
OFF
ON23
OFF
OFF
D
*1=36000BTU model's factory setting
DUCT TYPE
AR30 - 36
*2=30000BTU model's factory setting
PU
SWITCH FUNCTION (OUTDOOR UNIT)
G
IN
T
T
SE
H
C
T
I
SW
P
I
Current capacity setting
G
IN
T
ET
S
H
S
H
SWIT
C
DUCT TYPE
AR30 - 36
SW2 setting
Press the this push-button switch, and "PUMP DOWN OPERATION" is starting.
- (03 - 29) -
Page 31
3-16-3. INDOOR UNIT
MODELS:
AR 30L / AO 30L AR 36L / AO 36L
INDOOR UNIT
1
Low static pressure function setting
SW 1
DIP SW
SW 2
Rotary SW SW 3 Indoor unit number setting
DUCT TYPE
AR30 - 36
Jumper Wire
SWITCH POSITION
Duct type Indoor unit control circuit board
2
Forbidden
3
4
1 Room temperature correct coefficient of heating
2 External input select
3 Auto restart validity/invalidity
JM1 Room temperature correct coefficient of cooling
JM2 Commercial mode setting
JM3 Fan delay setting
DUCT TYPE
AR30 - 36
POWER PCB
CN114
CN106
CN115
MAIN PCB
ON
OFF
CN4
CN5
CN16
CN14
CN15
SW1 SW2
1 2 3 1 2 34
SW1 SW2
SW3
ON
OFF
JM1 JM2 JM3
- (03 - 30) -
CN16
Page 32
3-16-4. SWITCH FUNCTION (INDOOR UNIT)
SW1-1 SW state
OFF Normal
ON Low static pressure
SW1-2 OFF
SW1-3 OFF
SW1-4 OFF
SW2-1 SW state
OFF +4 deg (Ceiling setting)
ON 0 deg (Room setting)
SW2-2 SW state
OFF Edge
ON Pulse
SW2-3 SW state
OFF Validity
ON Invalidity
SW3 SW state
0 single
1-15 Indoor unit address
DIP SWITCH SETTING
1. SW1 setting
1-1 Low static pressure function setting
In case of installing in low static , you can minimize air flow and noise.
( Factory setting)
1-2 Dip SW 1-2,1-3,1-4 setting forbidden
DUCT TYPE
AR30 - 36
( Factory setting)
DUCT TYPE
AR30 - 36
2-1 Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
Heat temperature correction
( Factory setting)
2-2 External input select edge/pulse
This switch is used to select the format of external input command as shown in the table below.
( Factory setting)
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTORESTART SETTING
( Factory setting)
ROTARY SWITCH SETTING
This switch can be used when group control system. Set the indoor unit address in the 1,2,-,15 order.
( Factory setting)
- (03 - 31) -
Page 33
JUMPER WIRE SETTING
JM2 JM state
Connect Residencial
Disconnect Commercial
JM3 JM state
Connect Invalidity
Disconnect Validity
Connector INPUT OUTPUT REMARKS
CN114
CONTROL INPUT
(OPERATION/STOP)
-
CN115 - OPERATION DISPLAY
CN14 - FRESH AIR
CN15 - ELECTRICAL HEATER
See external
input/output settings
for details.
JM1 JM state
Connect 0 deg
Disconnect + 2 deg
Room temperature correct coefficient of cooling.
Decide the cooling temperature correct coefficient value of cooling.
Cool temperature corrction
Commercial mode setting
"Hot start" can be canceled,fan operates continously when indoor unit is ON on every mode. When you select "FAN:AUTO"mode fan goes in "HIGH".
DUCT TYPE
AR30 - 36
Fan delay setting
This setting can be used when the auxiliary heater is mounted. When the fan operation is stopped when the indoor unit is operating with an auxiliary heater,the fan operation continues one minutes.
( Factory setting)
( Factory setting)
DUCT TYPE
AR30 - 36
( Factory setting)
EXTERNAL INPUT AND OUTPUT
- (03 - 32) -
Page 34
3-16-5. WIRED, SIMPLE REMOTE CONTROLLER CIRCUIT BOARD
Wired,Simple remote controller
1
Dual remote controller setting
2
Group control setting
DIP SW
3
4
Model setting
Auto changeover setting
5
6
Memory backup setting
AR30 - 36
Wired remote controller
Front case (back side)
OFF
ON
1 2 3 4 5 6
ON
DIP Switch
Simple remote controller
DUCT TYPE
AR30 - 36
DUCT TYPE
SWITCH POSITION
DIP switches
ON
OFF
12345
ON
6
- (03 - 33) -
Page 35
3-16-6. WIRED, SIMPLE REMOTE CONTROLLER
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
( Factory setting)
Number of remote controller
1 (Normal)
2 (Dual)
DUCT TYPE
AR30 - 36
1-2 Group control setting
Number of indoor unit connection (One/Multiple) This is switched according to the number of connected indoor units.
DIP-SW No.3
OFF
Master unit Slave unit
DIP-SW No.1
DIP-SW No.2
ON
OFF
( Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW No.1
ON ON
DIP-SW No.2
DUCT TYPE
AR30 - 36
ON Multiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( Factory setting)
DIP-SW No.4
OFF
ON Cooling only model
Heat Pump model
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
( Factory setting)
DIP-SW No.5
OFF
ON Validity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
( Factory setting)
DIP-SW No.6
OFF
ON Validity
Memory backup
Invalidity
- (03 - 34) -