General ARH24L, ARH24LUAN, ARH30L, ARH30LUAN, ARH36L Installation Manual

...
Refrigerant
e
p
R410A
Duct Type
SPLIT TYPE AIR CONDITIONER
INSTALLATION INSTRUCTION SHEET
(PART NO. 9374318063)
Indoor unit is an appliance not accessible to the general public.
For authorized service personnel only.
WARNING
CAUTION
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant models. However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the piping and installation and service tools are special. (See the table below.) Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with conventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with conventional refrig­erant models. Also, when storing the piping, securely seal the openings by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and always charge from the liquid phase side whose composition is stable.
When moving, if the compressor stops during pump down, close the valve immediately.
Special tools for R410A
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using conventional refrigerant, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table. Never use copper pipes thinner than that in the table even when it is available on the market.
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
Contents of change
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed. It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm2) for high pressure. –0.1 to 3.8 MPa (–76 cmHg to 38 kgf/cm2) for low pressure.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Thicknesses of Annealed Copper Pipes
Pipe outside diameter
9.52 mm (3/8 in)
15.88 mm (5/8 in)
Thickness
0.80 mm
1.00 mm
For authorized service personnel only.
WARNING
For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
Connect the indoor unit and outdoor unit with the air conditioner piping and cords available standards parts. This installation instruction sheet describes the correct connections using the installation set available from our standard parts.
Installation work must be performed in accordance with national wiring standards by authorized personnel only.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a flame, it produces a toxic gas.
Do not use an extension cord.
Do not turn on the power until all installation work is complete.
CAUTION
This installation instruction sheet describes how to install the indoor unit only. To install the outdoor unit, refer to the installation instruction sheet included with the outdoor unit.
•Be careful not to scratch the air conditioner when handling it.
• After installation, explain correct operation to the customer, using the operating manual.
• Let the customer keep this installation instruction sheet because it is used when the air conditioner is serv­iced or moved.
SELECTING THE MOUNTING POSITION
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.
CAUTION
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near heat source of heat, steam, or flammable gas.
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
Decide the mounting position with the customer as follows:
INDOOR UNIT
(1) Install the indoor unit on a place having a sufficient strength so that it withstand against
the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room. (3) Leave the space required to service the air conditioner. (4) Install the unit where the drain pipe can be easily installed. (5) Providing as much space as possible between the indoor unit and the ceiling will
make work much easier. (6) If installing in a place where its humidity exceeds 80%, use heat insulation to prevent
condensation.
Maintenance hole dimension
It shall be possible to install and remove the control box. It shall be possible to install and remove the control box, fan
units and filter.
300 mm
500 mm
Maintenance hole
Control box
100 mm
500 mm
300 mm
500 mm
Control box
300 mm or more
Maintenance hole
1550 mm
150 mm or more
Intake panel
100 mm
INSTALLATION PROCEDURE
Install the air conditioner as follows:
INDOOR UNIT
1
INSTALLATION
RECOMMENDED RANGE OF
EXTERNAL STATIC PRESSURE
30Pa to 150Pa
WARNING
Install the air conditioner in a location which can withstand a load of at least five times the weight
of the main unit and which will not amplify sound or vibration. If the installation location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose. Please take care.
CAUTION
For installation, refer to the technical data.
1. INSTALLING THE HANGERS
WARNING
When fastening the hangers, make the bolt posi­tions uniform.
Hanging bolt installation diagram.
(Example)
(Top side)
AIR
(Left side)
The distance of is adjustable according to the place of the hanging bolts. (MAX : 550 mm, MIN : 410 mm)
740 mm
477 mm
AIR
270 mm
mm
1135
mm
1177
Slide the unit in the arrow direction and fasten it.
Hanging bolt M10 (Obtained locally)
Bolt Strength 9.81 to 14.71 N·m (100 to 150 kgf·cm)
Special nut A
Washer (Obtained locally)
Special nut B
Hanger
WARNING
Fasten the unit securely with special nuts A and B.
2. LEVELING
Base vertical direction leveling on the unit (right and left).
(Left side)
AIR
Base horizontal direction leveling on top of the unit.
0-5 mm
Give a slight tilt to the side to which the drain hose is connected. The tilt should be in the range of 0 mm to 5 mm.
Level meter
AIR
Drain hose
3. INSTALLING DRAIN HOSE
Install the drain hose according to the measurements given in the following figure.
(Left side)
(Right side)
32 mm
Liquid pipe
240 mm
Drain pipe ø 38 mm (O.D.)
240 mm
Gas pipe
Drain pipe ø 38 mm (O.D.) The drain cap is attached at the factory setting.
32 mm
66 mm
114 mm
CAUTION
Install the drain hose in accordance with the instruc­tions in this installation instruction sheet and keep the area warm enough to prevent condensation. Problems with the piping may lead to water leaks.
NOTE: INSTALL THE DRAIN HOSE
• Install the drain hose with downward gradient (1/50 to 1/100) and so there are no rises or traps in the hose.
• Use general hard polyvinyl chloride pipe (VP25) [outside diam­eter 38mm] and connect it with adhesive (polyvinyl chloride) so that there is no leakage.
• When the hose is long, install supporters.
• Do not perform air bleeding.
• Always heat insulate the indoor side of the drain hose.
Outlet air flow
OK
Arrange the drain hose lower than this portion
• When the unit is shipped from the factory, the drain port is on the left side (control box side).
•When using the drain port on the right side of the unit, reinstall the drain cap to the left side drain port.
Drain port
Drain hose
NO
Ris
Supporter
1.5 to 2 m
Air bleeding
Drain cap Nylon fastener
Tr ap
CAUTION
Always check that the drain cap is installed to the unused drain port and is fastened with the nylon fastener. If the drain cap is not installed, or is not sufficiently fastened by the nylon fastener, water may drip dur­ing the cooling operation.
• Cut the drain hose insulation at a position approximately 30mm from the end with cutters, etc.
• Stick the large drain hose insulation at the drain hose installa­tion side.
• Stick the small drain hose insulation at the drain cap side.
450 mm
Cut line
170 mm
Drain hose insulation (large)
unit
Drain hose
Drain hose insulation (small)
Unit
Drain ca
30 mm
420 mm
170 mm
unit
0 mm (0")
Unit
0 mm (0")
30 mm
170 mm
Drain hose insulation (large)
Drain hose
Drain hose insulation (small)
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Hanger
Special nut A (large flange)
Special nut B (small flange)
Coupler heat insulation (large)
Coupler heat insulation (small)
Q’ty
4
4
4
1
1
Application
For suspending the indoor unit from ceiling
For suspending the indoor unit from ceiling
For indoor side pipe joint (large pipe)
For indoor side pipe joint (small pipe)
Name and Shape
Binder
Remote controller
Tapping screw (flush heads)
Remote controller cord
Drain hose insulation
Q’ty
1
(large)
1
(small)
1
2
1
1
Application
For fixing the drain hose
For fixing the remote controller cord
For installing the remote controller
For connecting the remote controller
Insulates the drain hose and vinyl hose
CONNECTING PIPE REQUIREMENT
Diameter
Small
Large
• Use pipe with water-resistant heat insulation.
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks. Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only) In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker. If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insula­tion. In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
9.52 mm (3/8 in.)
15.88 mm (5/8 in.)
CAUTION
ELECTRICAL REQUIREMENT
4. INTAKE DUCT CONNECTION
Follow the procedure in the following figure to the ducts.
1015 mm
240mm
The air inlet duct can be changed by replacing the intake grille and flange.
For the bottom air intake, follow the procedure of for installation. (The factory setting is back air intake.)
CAUTION
When air is taken in from the bottom side, the oper­ating sound of the product will easily enter the room. Install the product and intake grilles where the affect of the operating sound is small.
CAUTION
If an intake duct is installed, take care not to damage the temperature sensor (the tempera­ture sensor is attached to the intake port flange).
Be sure to install the air inlet grille and the air outlet grille for air circulation. The correct tem­perature cannot be detected.
Unit
Air Outlet Grille Air inlet Grille
(Room)
5. OUTLET DUCT CONNECTION
Duct installation pattern ( CUT PART)
(1) Square duct
(
2) Round duct outlet ×4 (This is the factory setting.)
When using as a square duct
(1) Cut the slit seam with a cutter.
(2) Turn up the insulation around the points to be cut according
to the outlet port shape working points so that the insulation does not stick out at the
Cut Cut
part.
6. FRESH AIR INTAKE
(Processing before use)
(1) When taking in fresh air, cut a slit shaped cabinet in the left
side of the outer case with nippers.
Cut
Cut
Cabinet (iron plate) Square hole
CAUTION
When removing the cabinet (iron plate), be care­ful not to damage the indoor unit internal parts and surrounding area (outer case).
When processing the cabinet (iron plate), be careful not to injure yourself with burrs, etc.
(2) Install the round flange (option parts) to the fresh air intake.
OPTIONAL PARTS
When connecting the square duct and round duct, use the optional square flange or round flange and flexible duct.
Square flange Round flange
Model name : UTD–SF045T (P/N 9098180007) Model name : UTD–RF204 (P/N 9093160004)
40 mm
ø225 mm
ø195 mm
ø205 mm
204 mm
1065 mm
85 mm
Flexible duct Long-life filter
Model name : UTD–RD202 (P/N 9074165004) Model name : UTD–LF25NA (P/N9079892004)
ø200 mm L 2 m
507 mm
ø235 mm
239 mm
• Electric wire size :
Connection cord (mm2)
MAX.
MIN.
2.5
1.5
• Install the disconnect device with a contact gap of at least 3 mm nearby the units. (Both indoor unit and outdoor unit)
• Always use H07RN-F or equivalent to the connection cord.
Grills must be fixed so that man cannot touch indoor unit fan, and cannot be removed by only hand operation without tool.
Be sure to install the air filter in the air inlet. If the air filter is not installed, the heat exchanger may be clogged and its performance may de-
crease.
Cut
(3) Cut with nippers and remove the sheet metal.
(4) Since there is a slit in the insulation, use radio pliers, tweez-
ers, etc. to stretch the screw hole part used when installing the round flange and square flange when connecting the duct.
Cut
Round duct
(3) Connect the duct to the round flange.
(4) Seal with a band and vinyl tape, etc. so that air does not leak
from the connection.
Duct
9374318063B2front 05.3.23, 18:291
Simple remote controller
Model name : UTB–YPB (P/N9077582006)
Remote sensor
Model name : UTD–RS100 (P/N9072619004)
e
2
y
e
y
k
CONNECTING THE PIPING
WARNING
Do not use the existing piping and flare nuts.
• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc. (Use the special R410A materials.)
CAUTION
Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
While welding the pipes, be sure to blow dry ni­trogen gas through them.
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe
cutter.
(2) Hold the pipe downward so that cuttings will not enter the
pipe and remove the burrs.
(3) Insert the flare nut (always use the flare nut attached to the
indoor and outdoor units respectively) onto the pipe and per­form the flare processing with a flare tool. Use the special R410A flare tool, or the conventional flare tool. When using the conventional flare tool, always use an allow­ance adjustment gauge and secure the A dimension.
Check if [L] is flared uniformly and is not cracked or scratched
Die
L
Pipe outside
diameter
9.52 mm (3/8 in.)
15.88 mm (5/8 in.)
A (mm)
Flare tool for R410A, clutch type
0 to 0.5
0 to 0.5
A
Pip
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Extend the pipe
unwinding it
b
Do not bend the pipes in an angle more than 90°. When pipes are repeatedly bent or stretched , the material will harden, making it difficult to bend or stretch them any more. Do not bend or stretch the pipes more than three times.
When bending the pipe, do not bend it as is. The pipe will be col­lapsed. in this case, cut the heat insulating pipe with a sharp cutter as shown on the right, and bend it after exposing the pipe. After bend­ing the pipe as you want, be sure to put the heat insulating pipe back on the pipe, and secure it with tape.
Heat insulating Pipe
CAUTION
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of curvature of 150 mm or over.
If the pipe is bent repeatedly at the same place, it will break.
Pipe
Cutter
Cut line
3. CONNECTION PIPES
Indoor unit side
Detach the caps and plugs from the pipes.
CAUTION
Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is im­proper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe.
To prevent gas leakage, coal the flare surface with alkylbenzen oil (HAB). Do not use mineral oil.
Centering the pipe against port on the indoor unit, turn the flare nut with your hand.
CAUTION
Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to tighten the flare nut correctly.
When the flare nut is tightened properly by your hand, use a torque wrench to finally tighten it.
Holding spanner
9.52 mm (3/8 in.) dia.
15.88 mm (5/8 in.) dia.
Torque wrench
Flare nut tightening torque
Flare nut
33 to 42 N·m (330 to 420 kgf·cm)
63 to 77 N·m (630 to 770 kgf·cm)
Unit side
Tightening torque
4. HEAT INSULATION ON THE PIPE JOINTS (INDOOR SIDE ONLY)
Stick coupler heat insulation (large and small) to the place where connecting pipes.
No gaps
Coupler heat insulation
Be sure to overlap the insulation
No gaps
Coupler heat insulation
Be sure to overlap the insulation
CAUTION
There should be no gaps between the insulation and the product.
3
ELECTRICAL WIRING
CAUTION
Do not bundle the remote controller cord, or wire the remote controller cord in parallel, with the in­door unit connection wire (to the outdoor unit) and the power supply cord. It may cause erroneous op­eration.
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to about 25 mm (15/16”) to ex­pose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for
the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board
and tighten securely with the terminal screw using a screw­driver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to about 10 mm (3/8”) to expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal board.
(3) Using a round terminal fastener or pliers, securely clamp
a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten
the terminal screw using a screwdriver.
Strip 25 mm
Insulation
Wire
Loop
Screw with special washer
Te r minal board
Wire
Te r minal block
B. Strand wireA. Solid wire
Strip 10 mm
Screw with special washerRound terminal
Round terminal
Round terminal
1. CONNECTION DIAGRAMS
Remote controller
Black
3
White
2
Red
1
Power line
3 2 1
Indoor unit side terminal
Control line
Outdoor unit
2. INDOOR UNIT SIDE
WARNING
Before starting work, check that power is not being supplied to the indoor unit and outdoor
unit.
Match the terminal board numbers and connec­tion cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the elec­tric parts.
Connect the connection cords firmly to the ter­minal board. Imperfect installation may cause a fire.
Always fasten the outside covering of the con­nection cord with the cord clamp. (If the insula­tor is chafed, electric leakage may occur.)
Always connect the ground wire.
(1) Remove the control box cover and install each connection
wire.
Control box cover
Screw
(2) After wiring is complete, secure the remote controller cord,
connection cord, and power cord with the cord clamps.
Connection cord (to outdoor unit)
45 mm
Cord clamp
Cord clamp
Remote controller cord
1223
Remote controller
Connection cord
31
Outdoor unit
CAUTION
Use care not to mistake the power supply cord and connection wires when installing.
Install so that the wires for the remote control­ler will not come in contact with other connec­tion wires.
If there is a risk of entering insects and small animals into the hole for cords, fill in the gap with putty.
(3) Install control box cover.
Adjust the position of the screws for control box cover according to the installation.
4
REMOTE CONTROLLER SETTING
CAUTION
In order to detect the room tempera­ture correctly when using the tem­perature sensor of the remote con­troller, do not install the remote con­troller in a place where it will be ex­posed to direct sunlight or directly below the air outlet of the indoor unit.
When installing the remote controller and cord near a source of electromagnetic waves, sepa­rate the remote controller from the source of the electromagnetic waves and use shielded cord.
Do not touch the remote controller PC board and PC board parts directly with your hands.
1. INSTALLING THE REMOTE CONTROLLER
(1) Open the operation panel on the front of the remote control-
ler, remove the two screws indicated in the following figure, and then remove the front case of the remote controller.
Front case (back side)
DAY
CLOCK ADJUST
DAY OFF
ENERGY
DELETE SET
Screws
THERMO
SAVE
SENSOR
Connecter
Remote controller wires
Rear case
Connecter
SET BACK
When installing the remote controller, remove the connector from the front case. The wires may break if the connector is not removed and the front case hangs down. When installing the front case, connect the connector to the front case.
(2) Install the rear case to the wall, etc. with the two tapping
screws. Refer to the following information to install the re­mote controller wires.
Front case
Temperature sensor
Rear case
2. ROUTING THE REMOTE CONTROLLER WIRES
(1) Install the remote controller wires to the terminals on the top
of the rear case as shown in the following figure.
(2) Fasten the wires with the binder.
Install the remote controller wires so as not to be direct touched with your hand.
(Example)
1. Red
Binder
2. White
3. Blac
3. SETTING THE DIP SWITCHES
When using a battery (memory backup)
ON
OFF
1 2 3 4 5 6
DIP Switch
Change the DIP switch setting to use batteries. (The DIP switch is not set to use batteries at the factory.) Change DIP switch No. 6 from OFF to ON. If batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
ON
CAUTION
Be sure to connect the gas pipe after connecting the liquid pipe completely.
4. SETTING THE ROOM TEMPERATURE DE­TECTION LOCATION
The detection location of the room temperature can be selected from the following three examples. Choose the detection location that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature sensor.
A
Indoor unit
(1)
When the THERMO SENSOR button is pressed, the lock display flashes because the function is locked at the factory.
B. Remote controller setting
The room temperature is detected by the remote controller tem­perature sensor.
B
Indoor unit
(1) Press the THERMO SENSOR button for 5 seconds or more to
unlock the function. The thermo sensor display flashes and then disappears when the function is unlocked.
(2) Press the THERMO SENSOR button.
The thermo sensor display appears.
(3) Press the THERMO SENSOR button again for 5 seconds or
more to lock the function. The thermo sensor display flashes and then remains on when the function is locked.
(4) Make sure that the function is locked.
C.Indoor unit/remote controller setting (room temperature sensor selection)
The temperature sensor of the indoor unit or the remote control­ler can be used to detect the room temperature.
C
Indoor unit
(1) Press the THERMO SENSOR button for 5 seconds or more to
unlock the function. The thermo sensor display flashes and then disappears when the function is unlocked.
(2) Press the THERMO SENSOR button to select the tempera-
ture sensor of the indoor unit or the remote controller.
NOTES
If the function to change the temperature sensor is used as shown in examples A and B (other than example C), be sure to lock the detection location. If the function is locked, the lock display will flash when the THERMO SENSOR button is pressed.
5
TEST RUN
CAUTION
Supply power to the crankcase heater for at least 12 hours before the start of operation in winter.
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button
simultaneously for 2 seconds or more to start the test run.
Te st run displa
(3) Press the start/stop button to stop the test run.
[SELF-DIAGNOSIS]
When the error indication “E:EE” is displayed, follow the follow­ing items to perform the self-diagnosis. “E:EE” indicates an error has occurred.
REMOTE CONTROLLER DISPLAY
(1) Stop the air conditioner operation.
(2) Press the set temperature buttons simultaneously for 5
seconds or more to start the self-diagnosis. Refer to the following tables for the description of each error code.
Unit number (usually 0)
SUMOTUWETH FR
(3) Press the set temperature buttons simultaneously for 5
seconds or more to stop the self-diagnosis.
Error cod
SA
Error code Error contents
00 01 02
03
04 05
06
08
09
0A
0c
0E
11
Communication error (indoor unit
Communication error (indoor unit
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor short-circuited
Outdoor heat exchanger temperature sensor
Power source connection error
Float switch operated
Outdoor temperature sensor
Discharge pipe temperature sensor
Outdoor high pressure abnormal
Model abnormal
Indoor fan abnormal
remote controller)
outdoor unit)
12 13
Outdoor signal abnormal
Outdoor EEPROM abnormal
14
15
Compressor temperature sensor
16
17
18
19
1A
1b
1c
1d
1E
1F
Pressure switch error
IPM error
CT error
Active filter module (AFM) error
Compressor does not operate
Outdoor unit fan error
Communication error (inverter multicontroller)
2 way valve sensor error
Expansion valve error
Connection indoor unit error
6
SPECIAL INSTALLATION METHODS
CAUTION
When setting the rotary switch and DIP switches, do not touch any other parts on the circuit board directly with your bare hands.
Be sure to turn off the main power.
1. GROUP CONTROL SYSTEM
A number of indoor units can be operated at the same time using a single remote controller.
(1) Wiring method (indoor unit to remote controller)
Indoor unit
No. 0
Remote controller wire
(2) Rotary switch setting (indoor unit)
Set the unit number of each indoor unit using the rotary switch on the indoor unit circuit board. The rotary switch is normally set to 0.
(3) DIP switch setting (remote controller)
Change DIP switch No. 3 on the remote controller from OFF to ON.
Indoor unit
Rotary Switch
2. DUAL REMOTE CONTROLLERS (OPTIONAL)
Two separate remote controllers can be used to operate the in­door units.
(1) Wiring method (indoor unit to remote controller)
Remote controller wire
1 2 3
1 2 3
Indoor unit
No. 1
Remote controller
Indoor unit
No. 2
1 2 3 1 2 3 1 2 3
Remote controller
SW3
Indoor unit
1 2 3
Remote
Master unit Slave unit
controller
Indoor unit
ONOFF
1 2 3 4 5 6
ON
DIP Switch
1 2 31 2 3
No. 3
(2) DIP switch setting (remote controller)
Set the remote controller DIP switch Nos. 1 and 2 according to the following table.
Number of remote controllers
1 (Normal)
2 (Dual)
Number of remote controllers
1 (Normal)
2 (Dual)
Master unit
DIP-SW
No. 1
ON
OFF
DIP-SW
No. 1
ON
DIP-SW
No. 2
OFF
OFF
Slave unit
DIP-SW
No. 2
ON
Remote
controller
1 2 3 4 5 6
3. CANCELING AUTO RESTART
The auto restart function can be canceled.
(1) DIP switch setting (indoor unit)
Change the DIP switch (SW2-3) on the indoor unit circuit board from OFF to ON. The auto restart function will be canceled.
Indoor unit
ON
ON
OFF
DIP Switch
123
SW2
[DIP-SWITCH SETTING]
Indoor unit
NO.
1– Remote sensor setting
SW2
2 Edge Pulse Control input setting
DIP-
Switch
3Validity Invalidity Auto restart setting
Remote controller
NO.
1
2
3One unit Multiple unit
DIP-
Switch
4
5 Invalidity Validity
6 Invalidity Validity
SW state
OFF ON
SW state
OFF ON
Heat &Cool model
Detail
Detail
Dual remote controller setting
Group control setting
Cooling only model
Auto changeover setting
Memory backup
: Factory setting
ONOFF
9374318063B2back 05.3.23, 17:051
Loading...