Refrigerant
R410A
Duct Type
SPLIT TYPE AIR CONDITIONER
INSTALLATION INSTRUCTION
SHEET
(PART NO. 9374318063)
Indoor unit is an appliance not accessible to the general public.
For authorized service personnel only.
WARNING
CAUTION
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the
piping and installation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always
replace the conventional piping and flare nuts with the R410A piping and flare nuts.
Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous
charging with conventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread
diameter for R410A is 1/2 UNF 20 threads per inch.]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with conventional refrigerant models. Also, when storing the piping, securely seal the openings by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of the gas and liquid
phases, and always charge from the liquid phase side whose composition is stable.
When moving, if the compressor stops during pump down, close the valve immediately.
Special tools for R410A
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10m. Do not use copper
pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary
tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using
conventional refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table. Never
use copper pipes thinner than that in the table even when it is available on
the market.
This mark indicates procedures which, if improperly performed, might lead to the death or
serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in
personal harm to the user, or damage to property.
Contents of change
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing
of other refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm2) for high pressure.
–0.1 to 3.8 MPa (–76 cmHg to 38 kgf/cm2) for low pressure.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Thicknesses of Annealed Copper Pipes
Pipe outside diameter
9.52 mm (3/8 in)
15.88 mm (5/8 in)
Thickness
0.80 mm
1.00 mm
For authorized service personnel only.
WARNING
For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
Connect the indoor unit and outdoor unit with the air conditioner piping and cords available standards parts.
This installation instruction sheet describes the correct connections using the installation set available
from our standard parts.
Installation work must be performed in accordance with national wiring standards by authorized personnel
only.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with
a flame, it produces a toxic gas.
Do not use an extension cord.
Do not turn on the power until all installation work is complete.
CAUTION
This installation instruction sheet describes how to install the indoor unit only.
To install the outdoor unit, refer to the installation instruction sheet included with the outdoor unit.
•Be careful not to scratch the air conditioner when handling it.
• After installation, explain correct operation to the customer, using the operating manual.
• Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
SELECTING THE MOUNTING POSITION
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the
units will not topple or fall.
CAUTION
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near heat source of heat, steam, or flammable gas.
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the
unit.
Decide the mounting position with the customer as follows:
INDOOR UNIT
(1) Install the indoor unit on a place having a sufficient strength so that it withstand against
the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) Install the unit where the drain pipe can be easily installed.
(5) Providing as much space as possible between the indoor unit and the ceiling will
make work much easier.
(6) If installing in a place where its humidity exceeds 80%, use heat insulation to prevent
condensation.
Maintenance hole dimension
It shall be possible to install and remove the control box. It shall be possible to install and remove the control box, fan
units and filter.
300 mm
500 mm
Maintenance hole
Control box
100 mm
500 mm
300 mm
500 mm
Control box
300 mm
or more
Maintenance hole
1550 mm
150 mm
or more
Intake panel
100 mm
INSTALLATION
PROCEDURE
Install the air conditioner as follows:
INDOOR UNIT
1
INSTALLATION
RECOMMENDED RANGE OF
EXTERNAL STATIC PRESSURE
30Pa to 150Pa
WARNING
Install the air conditioner in a location which can
withstand a load of at least five times the weight
of the main unit and which will not amplify sound
or vibration.
If the installation location is not strong enough,
the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there
is a risk that the unit will come loose. Please
take care.
CAUTION
For installation, refer to the technical data.
1. INSTALLING THE HANGERS
WARNING
When fastening the hangers, make the bolt positions uniform.
Hanging bolt installation diagram.
(Example)
(Top side)
AIR
(Left side)
The distance of is adjustable according to the place of the
hanging bolts.
(MAX : 550 mm, MIN : 410 mm)
740 mm
477 mm
AIR
270 mm
mm
1135
mm
1177
Slide the unit in the arrow direction and fasten it.
Hanging bolt M10
(Obtained locally)
Bolt Strength 9.81 to 14.71 N·m (100 to 150 kgf·cm)
Special nut A
Washer
(Obtained locally)
Special nut B
Hanger
WARNING
Fasten the unit securely with special nuts A and B.
2. LEVELING
Base vertical direction leveling on the unit (right and left).
(Left side)
AIR
Base horizontal direction leveling on top of the unit.
0-5 mm
Give a slight tilt to the side to which the drain hose is connected.
The tilt should be in the range of 0 mm to 5 mm.
Level meter
AIR
Drain hose
3. INSTALLING DRAIN HOSE
Install the drain hose according to the measurements given in the
following figure.
(Left side)
(Right side)
32 mm
Liquid pipe
240 mm
Drain pipe
ø 38 mm (O.D.)
240 mm
Gas pipe
Drain pipe
ø 38 mm (O.D.)
The drain cap is attached
at the factory setting.
32 mm
66 mm
114 mm
CAUTION
Install the drain hose in accordance with the instructions in this installation instruction sheet and keep
the area warm enough to prevent condensation.
Problems with the piping may lead to water leaks.
NOTE: INSTALL THE DRAIN HOSE
• Install the drain hose with downward gradient (1/50 to
1/100) and so there are no rises or traps in the hose.
• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 38mm] and connect it with adhesive (polyvinyl chloride) so
that there is no leakage.
• When the hose is long, install supporters.
• Do not perform air bleeding.
• Always heat insulate the indoor side of the drain hose.
Outlet
air flow
OK
Arrange the drain hose lower
than this portion
• When the unit is shipped from the factory, the drain port is on
the left side (control box side).
•When using the drain port on the right side of the unit, reinstall
the drain cap to the left side drain port.
Drain port
Drain
hose
NO
Ris
Supporter
1.5 to 2 m
Air bleeding
Drain cap Nylon fastener
Tr ap
CAUTION
Always check that the drain cap is installed to the
unused drain port and is fastened with the nylon
fastener.
If the drain cap is not installed, or is not sufficiently
fastened by the nylon fastener, water may drip during the cooling operation.
• Cut the drain hose insulation at a position approximately 30mm
from the end with cutters, etc.
• Stick the large drain hose insulation at the drain hose installation side.
• Stick the small drain hose insulation at the drain cap side.
450 mm
Cut line
170 mm
Drain hose
insulation
(large)
unit
Drain hose
Drain hose insulation (small)
Unit
Drain ca
30 mm
420 mm
170 mm
unit
0 mm (0")
Unit
0 mm (0")
30 mm
170 mm
Drain hose
insulation
(large)
Drain hose
Drain hose
insulation
(small)
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Hanger
Special nut A
(large flange)
Special nut B
(small flange)
Coupler heat
insulation (large)
Coupler heat
insulation (small)
Q’ty
4
4
4
1
1
Application
For suspending the indoor
unit from ceiling
For suspending the indoor
unit from ceiling
For indoor side pipe joint
(large pipe)
For indoor side pipe joint
(small pipe)
Name and Shape
Binder
Remote
controller
Tapping screw
(flush heads)
Remote controller cord
Drain hose insulation
Q’ty
1
(large)
1
(small)
1
2
1
1
Application
For fixing the drain hose
For fixing the remote
controller cord
For installing the remote
controller
For connecting the remote
controller
Insulates the drain hose
and vinyl hose
CONNECTING PIPE REQUIREMENT
Diameter
Small
Large
• Use pipe with water-resistant heat insulation.
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%,
install heat insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation
that is 15 mm or thicker and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation. In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
9.52 mm (3/8 in.)
15.88 mm (5/8 in.)
CAUTION
ELECTRICAL REQUIREMENT
4. INTAKE DUCT CONNECTION
Follow the procedure in the following figure to the ducts.
1015 mm
240mm
The air inlet duct can be changed by replacing the intake grille
and flange.
For the bottom air intake, follow the procedure of → for
installation.
(The factory setting is back air intake.)
CAUTION
When air is taken in from the bottom side, the operating sound of the product will easily enter the room.
Install the product and intake grilles where the affect
of the operating sound is small.
CAUTION
If an intake duct is installed, take care not to
damage the temperature sensor (the temperature sensor is attached to the intake port flange).
Be sure to install the air inlet grille and the air
outlet grille for air circulation. The correct temperature cannot be detected.
Unit
Air Outlet Grille Air inlet Grille
(Room)
5. OUTLET DUCT CONNECTION
Duct installation pattern ( CUT PART)
(1) Square duct
(
2) Round duct outlet ×4
(This is the factory setting.)
When using as a square duct
(1) Cut the slit seam with a cutter.
(2) Turn up the insulation around the points to be cut according
to the outlet port shape working points so that the insulation
does not stick out at the
Cut Cut
part.
6. FRESH AIR INTAKE
(Processing before use)
(1) When taking in fresh air, cut a slit shaped cabinet in the left
side of the outer case with nippers.
Cut
Cut
Cabinet (iron plate) Square hole
CAUTION
When removing the cabinet (iron plate), be careful not to damage the indoor unit internal parts
and surrounding area (outer case).
When processing the cabinet (iron plate), be
careful not to injure yourself with burrs, etc.
(2) Install the round flange (option parts) to the fresh air intake.
OPTIONAL PARTS
When connecting the square duct and round duct, use the optional square flange or round flange and flexible duct.
Square flange Round flange
Model name : UTD–SF045T (P/N 9098180007) Model name : UTD–RF204 (P/N 9093160004)
40 mm
ø225 mm
ø195 mm
ø205 mm
204 mm
1065 mm
85 mm
Flexible duct Long-life filter
Model name : UTD–RD202 (P/N 9074165004) Model name : UTD–LF25NA (P/N9079892004)
ø200 mm
L 2 m
507 mm
ø235 mm
239 mm
• Electric wire size :
Connection cord (mm2)
MAX.
MIN.
2.5
1.5
• Install the disconnect device with a contact gap of at least 3 mm nearby the units.
(Both indoor unit and outdoor unit)
• Always use H07RN-F or equivalent to the connection cord.
Grills must be fixed so that man cannot touch
indoor unit fan, and cannot be removed by only
hand operation without tool.
Be sure to install the air filter in the air inlet. If
the air filter is not installed, the heat exchanger
may be clogged and its performance may de-
①
crease.
Cut
(3) Cut with nippers and remove the sheet metal.
(4) Since there is a slit in the insulation, use radio pliers, tweez-
ers, etc. to stretch the screw hole part used when installing
the round flange and square flange when connecting the duct.
Cut
Round duct
(3) Connect the duct to the round flange.
(4) Seal with a band and vinyl tape, etc. so that air does not leak
from the connection.
Duct
9374318063B2front 05.3.23, 18:291
Simple remote controller
Model name : UTB–YPB (P/N9077582006)
Remote sensor
Model name : UTD–RS100 (P/N9072619004)
2
CONNECTING THE
PIPING
WARNING
Do not use the existing piping and flare nuts.
• If the existing materials are used, the pressure inside
the refrigerant cycle will rise and cause breakage,
injury, etc. (Use the special R410A materials.)
CAUTION
Do not use mineral oil on flared part. Prevent
mineral oil from getting into the system as this
would reduce the lifetime of the units.
While welding the pipes, be sure to blow dry nitrogen gas through them.
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe
cutter.
(2) Hold the pipe downward so that cuttings will not enter the
pipe and remove the burrs.
(3) Insert the flare nut (always use the flare nut attached to the
indoor and outdoor units respectively) onto the pipe and perform the flare processing with a flare tool.
Use the special R410A flare tool, or the conventional flare
tool.
When using the conventional flare tool, always use an allowance adjustment gauge and secure the A dimension.
Check if [L] is flared uniformly
and is not cracked or scratched
Die
L
Pipe outside
diameter
9.52 mm (3/8 in.)
15.88 mm (5/8 in.)
A (mm)
Flare tool for R410A, clutch type
0 to 0.5
0 to 0.5
A
Pip
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse
them.
Extend the pipe
unwinding it
b
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bent or stretched , the material will
harden, making it difficult to bend or stretch them any more. Do
not bend or stretch the pipes more than three times.
When bending the pipe, do not
bend it as is. The pipe will be collapsed. in this case, cut the heat
insulating pipe with a sharp cutter
as shown on the right, and bend it
after exposing the pipe. After bending the pipe as you want, be sure
to put the heat insulating pipe back
on the pipe, and secure it with
tape.
Heat insulating
Pipe
CAUTION
To prevent breaking of the pipe, avoid sharp
bends.
Bend the pipe with a radius of curvature of 150
mm or over.
If the pipe is bent repeatedly at the same place,
it will break.
Pipe
Cutter
Cut line
3. CONNECTION PIPES
Indoor unit side
Detach the caps and plugs from the pipes.
CAUTION
Be sure to apply the pipe against the port on
the indoor unit correctly. If the centering is improper, the flare nut cannot be tightened
smoothly. If the flare nut is forced to turn, the
threads will be damaged.
Do not remove the flare nut from the indoor unit
pipe until immediately before connecting the
connection pipe.
To prevent gas leakage, coal the flare
surface with alkylbenzen oil (HAB).
Do not use mineral oil.
Centering the pipe against port on the indoor unit, turn the flare
nut with your hand.
CAUTION
Hold the torque wrench at its grip, keeping it in the
right angle with the pipe, in order to tighten the flare
nut correctly.
When the flare nut is tightened properly by your hand, use a torque
wrench to finally tighten it.
Holding
spanner
9.52 mm (3/8 in.) dia.
15.88 mm (5/8 in.) dia.
Torque wrench
Flare nut tightening torque
Flare nut
33 to 42 N·m (330 to 420 kgf·cm)
63 to 77 N·m (630 to 770 kgf·cm)
Unit
side
Tightening torque
4. HEAT INSULATION ON THE PIPE
JOINTS (INDOOR SIDE ONLY)
Stick coupler heat insulation (large and small) to the place where
connecting pipes.
No gaps
Coupler heat insulation
Be sure to overlap
the insulation
No gaps
Coupler heat insulation
Be sure to overlap
the insulation
CAUTION
There should be no gaps between the insulation
and the product.
3
ELECTRICAL WIRING
CAUTION
Do not bundle the remote controller cord, or wire
the remote controller cord in parallel, with the indoor unit connection wire (to the outdoor unit) and
the power supply cord. It may cause erroneous operation.
HOW TO CONNECT WIRING TO THE
TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to about 25 mm (15/16”) to expose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for
the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board
and tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to about 10 mm (3/8”) to expose
the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal board.
(3) Using a round terminal fastener or pliers, securely clamp
a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten
the terminal screw using a screwdriver.
Strip 25 mm
Insulation
Wire
Loop
Screw with
special washer
Te r minal
board
Wire
Te r minal block
B. Strand wireA. Solid wire
Strip 10 mm
Screw with
special washerRound terminal
Round
terminal
Round
terminal
1. CONNECTION DIAGRAMS
Remote controller
Black
3
White
2
Red
1
Power line
3
2
1
Indoor unit
side terminal
Control line
Outdoor unit
2. INDOOR UNIT SIDE
WARNING
Before starting work, check that power is not
being supplied to the indoor unit and outdoor
unit.
Match the terminal board numbers and connection cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric parts.
Connect the connection cords firmly to the terminal board. Imperfect installation may cause a
fire.
Always fasten the outside covering of the connection cord with the cord clamp. (If the insulator is chafed, electric leakage may occur.)
Always connect the ground wire.
(1) Remove the control box cover and install each connection
wire.
Control box cover
Screw
(2) After wiring is complete, secure the remote controller cord,
connection cord, and power cord with the cord clamps.
Connection cord
(to outdoor unit)
45 mm
Cord clamp
Cord clamp
Remote
controller cord
1223
Remote controller
Connection cord
31
Outdoor unit
CAUTION
Use care not to mistake the power supply cord
and connection wires when installing.
Install so that the wires for the remote controller will not come in contact with other connection wires.
If there is a risk of entering insects and small
animals into the hole for cords, fill in the gap
with putty.
(3) Install control box cover.
Adjust the position of the screws for control box cover according
to the installation.
4
REMOTE CONTROLLER
SETTING
CAUTION
In order to detect the room temperature correctly when using the temperature sensor of the remote controller, do not install the remote controller in a place where it will be exposed to direct sunlight or directly
below the air outlet of the indoor unit.
When installing the remote controller and cord
near a source of electromagnetic waves, separate the remote controller from the source of the
electromagnetic waves and use shielded cord.
Do not touch the remote controller PC board and
PC board parts directly with your hands.
1. INSTALLING THE REMOTE CONTROLLER
(1) Open the operation panel on the front of the remote control-
ler, remove the two screws indicated in the following figure,
and then remove the front case of the remote controller.
Front case
(back side)
DAY
CLOCK ADJUST
DAY OFF
ENERGY
DELETE SET
Screws
THERMO
SAVE
SENSOR
Connecter
Remote controller
wires
Rear case
Connecter
SET BACK
When installing the remote controller, remove the connector
from the front case. The wires may break if the connector is
not removed and the front case hangs down.
When installing the front case, connect the connector to the
front case.
(2) Install the rear case to the wall, etc. with the two tapping
screws. Refer to the following information to install the remote controller wires.
Front case
Temperature
sensor
Rear case
2. ROUTING THE REMOTE CONTROLLER
WIRES
(1) Install the remote controller wires to the terminals on the top
of the rear case as shown in the following figure.
(2) Fasten the wires with the binder.
Install the remote controller wires so as not to be direct touched
with your hand.
(Example)
1. Red
Binder
2. White
3. Blac
3. SETTING THE DIP SWITCHES
When using a battery (memory backup)
ON
OFF
1
2
3
4
5
6
DIP Switch
Change the DIP switch setting to use batteries. (The DIP switch
is not set to use batteries at the factory.)
Change DIP switch No. 6 from OFF to ON.
If batteries are not used, all of the settings stored in memory will
be deleted if there is a power failure.
ON
CAUTION
Be sure to connect the gas pipe after connecting
the liquid pipe completely.
4. SETTING THE ROOM TEMPERATURE DETECTION LOCATION
The detection location of the room temperature can be selected
from the following three examples. Choose the detection location
that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature
sensor.
A
Indoor unit
(1)
When the THERMO SENSOR button is pressed, the lock display
flashes because the function is locked at the factory.
B. Remote controller setting
The room temperature is detected by the remote controller temperature sensor.
B
Indoor unit
(1) Press the THERMO SENSOR button for 5 seconds or more to
unlock the function. The thermo sensor display flashes and
then disappears when the function is unlocked.
(2) Press the THERMO SENSOR button.
The thermo sensor display appears.
(3) Press the THERMO SENSOR button again for 5 seconds or
more to lock the function. The thermo sensor display flashes
and then remains on when the function is locked.
(4) Make sure that the function is locked.
C.Indoor unit/remote controller setting
(room temperature sensor selection)
The temperature sensor of the indoor unit or the remote controller can be used to detect the room temperature.
C
Indoor unit
(1) Press the THERMO SENSOR button for 5 seconds or more to
unlock the function. The thermo sensor display flashes and
then disappears when the function is unlocked.
(2) Press the THERMO SENSOR button to select the tempera-
ture sensor of the indoor unit or the remote controller.
NOTES
If the function to change the temperature sensor is used as shown
in examples A and B (other than example C), be sure to lock the
detection location. If the function is locked, the lock display
will flash when the THERMO SENSOR button is pressed.
5
TEST RUN
CAUTION
Supply power to the crankcase heater for at least
12 hours before the start of operation in winter.
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button
simultaneously for 2 seconds or more to start the test run.
Te st run displa
(3) Press the start/stop button to stop the test run.
[SELF-DIAGNOSIS]
When the error indication “E:EE” is displayed, follow the following items to perform the self-diagnosis. “E:EE” indicates an error
has occurred.
REMOTE CONTROLLER DISPLAY
(1) Stop the air conditioner operation.
(2) Press the set temperature buttons simultaneously for 5
seconds or more to start the self-diagnosis.
Refer to the following tables for the description of each error
code.
Unit number (usually 0)
SUMOTUWETH FR
(3) Press the set temperature buttons simultaneously for 5
seconds or more to stop the self-diagnosis.
Error cod
SA
Error code Error contents
00
01
02
03
04
05
06
08
09
0A
0c
0E
11
Communication error
(indoor unit
Communication error
(indoor unit
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor
short-circuited
Outdoor heat exchanger temperature sensor
Power source connection error
Float switch operated
Outdoor temperature sensor
Discharge pipe temperature sensor
Outdoor high pressure abnormal
Model abnormal
Indoor fan abnormal
remote controller)
outdoor unit)
12
13
Outdoor signal abnormal
Outdoor EEPROM abnormal
14
15
Compressor temperature sensor
16
17
18
19
1A
1b
1c
1d
1E
1F
Pressure switch error
IPM error
CT error
Active filter module (AFM) error
Compressor does not operate
Outdoor unit fan error
Communication error
(inverter multicontroller)
2 way valve sensor error
Expansion valve error
Connection indoor unit error
6
SPECIAL INSTALLATION
METHODS
CAUTION
When setting the rotary switch and DIP switches,
do not touch any other parts on the circuit board
directly with your bare hands.
Be sure to turn off the main power.
1. GROUP CONTROL SYSTEM
A number of indoor units can be operated at the same time using
a single remote controller.
(1) Wiring method (indoor unit to remote controller)
Indoor unit
No. 0
Remote
controller
wire
(2) Rotary switch setting (indoor unit)
Set the unit number of each indoor unit using the rotary switch
on the indoor unit circuit board.
The rotary switch is normally set to 0.
(3) DIP switch setting (remote controller)
Change DIP switch No. 3 on the remote controller from OFF
to ON.
Indoor unit
Rotary Switch
2. DUAL REMOTE CONTROLLERS
(OPTIONAL)
Two separate remote controllers can be used to operate the indoor units.
(1) Wiring method (indoor unit to remote controller)
Remote
controller
wire
1 2 3
1 2 3
Indoor unit
No. 1
Remote
controller
Indoor unit
No. 2
1 2 3 1 2 3 1 2 3
Remote controller
SW3
Indoor unit
1 2 3
Remote
Master unit Slave unit
controller
Indoor unit
ONOFF
1
2
3
4
5
6
ON
DIP Switch
1 2 31 2 3
No. 3
(2) DIP switch setting (remote controller)
Set the remote controller DIP switch Nos. 1 and 2 according
to the following table.
Number of
remote
controllers
1 (Normal)
2 (Dual)
Number of
remote
controllers
1 (Normal)
2 (Dual)
Master unit
DIP-SW
No. 1
ON
OFF
DIP-SW
No. 1
–
ON
DIP-SW
No. 2
OFF
OFF
Slave unit
DIP-SW
No. 2
–
ON
Remote
controller
1
2
3
4
5
6
3. CANCELING AUTO RESTART
The auto restart function can be canceled.
(1) DIP switch setting (indoor unit)
Change the DIP switch (SW2-3) on the indoor unit circuit board
from OFF to ON. The auto restart function will be canceled.
Indoor unit
ON
ON
OFF
DIP Switch
123
SW2
[DIP-SWITCH SETTING]
• Indoor unit
NO.
1–✽ – Remote sensor setting
SW2
2 Edge ✽ Pulse Control input setting
DIP-
Switch
3Validity ✽ Invalidity Auto restart setting
• Remote controller
NO.
1 ✽
2 ✽
3One unit ✽ Multiple unit
DIP-
Switch
4
5 Invalidity Validity ✽
6 Invalidity ✽ Validity
SW state
OFF ON
SW state
OFF ON
Heat &Cool
model
Detail
Detail
Dual remote
controller setting
Group control
setting
Cooling only
model
Auto changeover
setting
Memory backup
✽: Factory setting
ONOFF
9374318063B2back 05.3.23, 17:051