GE Industrial Solutions PowerVac PV-VL 13.8-1000-0 a User Manual

gg
GEH-6468A Instructions
GE PowerVac® VL
Vacuum Circuit Breaker
TYPE
PV-VL 13.8-500-0 and -1 PV-VL 13.8-750-0 and -1 PV-VL 13.8-1000-0 and -1
With ML-18VL Mechanism
Page 2 GEH 6468A - Power/Vac VL Breaker
CONTENTS
1. INTRODUCTION 5
1.1 SAFETY 5 11.4 CLOSE COIL PLUNGER GAP 31
2. DESCRIPTION 5
3. RECEIVING, HANDLING AND STORAGE 6 12. ELECTRICAL CHECKS 31
3.1 RECEIVING 6 12.1 ELECTRICAL OPERATION 31
3.2 HANDLING 6 12.2 HIGH-POTENTIAL TEST 31
3.3 STORAGE 6 12.2.1 PRIMARY CIRCUIT 31
3.4 PACKING LIST 6 12.2.2 SECONDARY CIRCUIT 32
4. INITIAL INSTALLATION PROCEDURES 7
4.1 DOOR WIRING INTERFERENCE 7 12.5 INSULATION TESTS 33
4.2 POSITIVE INTERLOCK TEST PROCEDURES 7
4.3 BY-PASS KIT INSTALLATION 7
4.4 CHECKING FOR PROPER INTER­ LOCK AND TRIP FREE FUNCTIONS 14.1 GENERAL 33 BEFORE LOWERING THE BREAKER 14.2 SERVICE CONDITIONS 34 FROM THE ELEVATED POSITION 8 14.3 FAULT INTERRUPTION 34
5. ADJUSTMENTS TO BREAKERS / SWITCHGEAR INTERFACES 8
5.1 STATIONARY AUXILIARY SWITCH 8 14.7 PRIMARY INSULATION PARTS 35
5.2 PRIMARY CONTACT PENETRATION 9 14.8 LUBRICATION 35
5.3 POSITIVE INTERLOCK 9 14.9 RECOMMENDED MAINTENANCE 35
5.4 SECONDARY COUPLER 10
5.5 SPRING DISCHARGE CAM 10
5.6 STOPS 10
5.7 GROUND 10
5.8 POSITION SWITCH 10
6. TYPICAL WIRING DIAGRAMS 11
7. FEATURES 27
7.1 SAFETY PRECAUTIONS 27 17.4 MECHANISM 37
7.2 INTERLOCKS 27 17.5 CONTROL SWITCHES 37
7.2.1 RATING INTERFERENCE PLATE 27 17.6 TRIP COIL REPLACEMENT 37
7.2.2 POSITIVE INTERLOCK SYSTEM 27 17.7 CLOSING COIL REPLACEMENT 37
7.2.3 SPRING DISCHARGE SYSTEM 27 17.8 AUXILIARY SWITCH
8. OPERATION 28
8.1 CLOSE SPRING CHARGING 28
8.2 CLOSING OPERATION 29
8.3 OPENING OPERATION 29 18.1 ORDERING INSTRUCTIONS 38
8.4 TRIP-FREE OPERATION 29
9. CONTROL CIRCUIT 29
10. MECHANICAL CHECK AND SLOW CLOSE 29
10.1 VISUAL INSPECTION 29 19.5 CLOSE COIL PLUNGER 39
10.2 CLOSING SPRING CHARGING 29 19.6 CLOSE SPRING INTERLOCK 39
10.3 CLOSING SPRING GAG 30 19.7 POSITIVE INTERLOCK 39
10.4 SLOW CLOSING 30
10.5 GAG TOOL REMOVAL 30
11.3 CONTACT GAP 30
11.5 TRIP COIL PLUNGER GAP 31
11.6 CONTROL SWITCH ADJUSTMENT 31
12.3 PRIMARY CIRCUIT RESISTANCE 32
12.4 VACUUM INTEGRITY TEST 32
13. CHECKING AND INSTALLATION 33
14. MAINTENANCE 33
14.4 CONTACT EROSION 34
14.5 TRANSFER FINGER WEAR 35
14.6 MECHANISM 35
15. TIMING 36
16. OPENING AND CLOSING SPEED 36
17. REPAIR AND REPLACEMENT 36
17.1 GENERAL 36
17.2 REPLACING INTERRUPTERS 36
17.3 PRIMARY DISCONNECTS 37
37
REPLACEMENT
17.9 MOTOR REPLACEMENT 38
17.10 “Y” RELAY REPLACEMENT 38
18. RENEWAL PARTS 38
19. MECHANICAL ADJUSTMENTS 38
19.1 GENERAL 38
19.2 WIPE ADJUSTMENT 38
19.3 CONTACT GAP ADJUSTMENT 39
19.4 TRIP COIL PLUNGER 39
11. DIMENSIONAL CHECKS 30
11.1 PRIMARY CONTACT EROSION 30
11.2 SPRING WIPE 30 STATIONARY CUBICLE INFORMATION 62
LIST OF ILLUSTRATIONS 4
INDEX
70
GEH 6468A - Power/Vac VL Breaker Page 3
LIST OF ILLUSTRATIONS
FIGURE PAGE
1 INTERIOR VIEW OF STATIONARY CUBICLE 12 2 INTERLOCK MODIFICATION 13 3 MOTOR OPERATOR SWITCH ACTUATOR 14 4 ELEVATING MOTOR TROUBLESHOOTING 15 5 SCHEMATIC DIAGRAM - VERTICAL LIFT DRIVE MECHANISM 16 6 STATIONARY STRUCTURE WIRING 17 7 BY-PASS KIT INSTALLATION 18 8 BREAKER WIRE DIAGRAM (typical) OLD MS MECHANISM 19 9 BREAKER WIRE DIAGRAM (typical) OLD ML MECHANISM 20 10 ADJUSTMENT OF PLUNGER INTERLOCK 21 11 PRIMARY CONTACT PENETRATION 22 12 POSITIVE INTERLOCK ROLLER 23 13 POSITIVE INTERLOCK 1000 MVA UNITS 24 14 POSITIVE INTERLOCK M-26 UNITS 25 15 POSITIVE INTERLOCK M-36 UNITS 26 16 FRONT VIEW WITH FRONT COVER 44 17 FRONT VIEW WITHOUT COVER 45 18 MANUAL CHARGING HANDLE 46 19 CLOSING SPRING GAG ACCESS 47 20 TOGGLE LINKAGE POSITIONS 48-50 21 CONTACT EROSION INDICATOR 51 22 OPERATING ROD ASSEMBLY 52 23 ML-18VL MECHANISM 53-54 24 TRIP COIL LINKAGE 55 25 CLOSE COIL AND LINKAGE 56 26 FRONT VIEW OF ML-18VL MECHANISM 57 27 CONTACT GAP 58 27a CONTACT GAP ADJUSTMENT 59 28 FLEX CABLE CONNECTION 60 29 SAMPLE OPERATING SPEED GRAPHS 61 30 CLOSE COIL PLUNGER GAP 62 31 CONTROL SWITCHES 63 32 TRIP COIL PLUNGER GAP 64 33 SPRING WIPE 64
INDEX 70 TROUBLE REPORTING FORM 68-69 TABLE OF MEASUREMENTS AND ADJUSTMENTS 40 ADDENDUM TO GEH-1802 (CUBICLE) 62
Page 4 GEH 6468A - Power/Vac VL Breaker
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to the Seller.
To the extent required, the products described herein meet applicable ANSI, IEEE and NEMA standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly.
POWER/VAC® VL
VACUUM CIRCUIT BREAKER
WITH ML-18VL MECHANISM
1. INTRODUCTION
1.1. SAFETY IT IS IMPERATIVE THAT ALL PERSONNEL
ASSOCIATED WITH THIS EQUIPMENT READ AND COMPLETELY UNDERSTAND THE WARNINGS LOCATED THROUGHOUT THIS INSTRUCTION BOOK. FAILURE TO DO SO CAN RESULT IN DAMAGE TO PROPERTY, PERSONAL INJURY OR DEATH.
Each user must maintain a safety program for the protection of personnel, as well as other equipment, from the potential hazards associated with electrical equipment.
The following requirements are intended to augment the user’s safety program but NOT supplant the user’s responsibility for devising a complete safety program. The following basic industry practiced safety requirements are applicable to all major electrical equipment such as switchgear or switchboards. GE neither condones nor assumes any responsibility for practices which deviate from the following:
1. ALL CONDUCTORS MUST BE ASSUMED TO BE ENERGIZED UNLESS THEIR POTENTIAL HAS BEEN MEASURED AS GROUND AND ADEQUATE CAPACITY GROUNDING AS­SEMBLIES HAVE BEEN APPLIED TO PRE­VENT ENERGIZING. Many accidents have been caused by unplanned energization from non-recognized back feeds, equipment malfunc-tions, and from a wide variety of sources.
3. Although interlocks to reduce sone of the risks are provided, the individual’s actions while performing service of maintenance are essential to prevent accidents. Each person’s know-ledge; mental awareness; and planned and executed actions often determine if an accident will occur. The most important method of avoiding accidents is for all associated personnel to carefully apply a thorough understanding of the specific equipment from the viewpoints of its purpose, its construction, its operation and the situations which could be hazardous.
All personnel associated with installation, operation and maintenance al electrical equipment, such as power circuit breakers and other power handling equipment, must be thoroughly instructed, with periodic retraining, regarding equipment in general as well as the particular model of equipment which they are working.
Instruction books, actual devices and appropriate safety and maintenance practices such as OSHA publications, National Electric Safety Code (ANSI) C2), National Electric Code, and National Fire Protection Association (NFPA) 70B Electrical Equipment Maintenance must be closely studied and followed. During actual work, supervision should audit practices to assure conformance.
It is strongly recommended that all equipment be completely de-energized, verified to be “dead”, then grounded with adequate capacity grounding assemblies prior to any maintenance.
2. It is strongly recommended that all equipment be completely de-energized, verified to be “dead”, then grounded with adequate capacity grounding assemblies prior to any maintenance. The rounding cable assemblies must be able to withstand energizing fault levels so that protective equipment may clear the circuit safety. Additional discussion on this concept is covered in Chapter 20 of ANSI/
2. DESCRIPTION
The PowerVac® VL vacuum circuit breaker is a vertical lift, removable and interchangeable inter­rupting element, for use in metal-clad switchgear to provide protection and control of electrical apparatus and power systems. The PowerVac® VL Type PV-VL circuit breaker with ML-18VL mechan-
NFPA 70B, Electrical Equipment Maintenance.
GEH 6468A - Power/Vac VL Breaker Page 5
ism is available in continuous current ratings of 1200, 2000 and 3000 amperes in accordance with industry standards. In addition, extended ratings of 3500, (not part of the original Magnablast offering) and 4000 amperes is available as well as a 5000 ampere fan cooled option. Refer to the breaker nameplate for complete rating information of any particular breaker. The nameplate also describes the control power requirements for that breaker. The application of a breaker must be such that its voltage, current and interrupting ratings are never exceeded. Since this book is written to include all ratings of the breaker, as well as several design variations, the instructions will be of a general character and all illustrations will be typical unless otherwise specified.
3. RECEIVING, HANDLING AND STORAGE
3.1. RECEIVING
Breakers should be carefully protected against con­densation, preferably by storing in a warm, dry room of moderate temperature such as 40 to 100° F. High humidity may have an adverse effect on the insulating parts and should be avoided. Circuit breakers for outdoor metal-clad switchgear should be stored in the equipment only when power is available and the heaters are in operation to prevent condensation.
Rollers, latches, etc. of the operating mechanism should be coated with GE part No. 0282A2048P009 (Mobil 28 red) grease to prevent rusting.
If the breaker is stored for any length of time, it should be inspected periodically to see that corrosion has not started. Should the breaker be stored under unfavorable atmospheric conditions, it should be serviced before being placed on line.
Each breaker is carefully inspected before shipment. Immediately upon receipt of the circuit breaker, an examination should be made for any damage sustained in transit. If injury or rough handling is evident, a claim should be filed immediately with the transportation company, and the nearest GE Sales Office should be notified.
3.2. HANDLING
It is expected that care will be exercised during the unpacking and installation of breakers so that no damage will occur from careless or rough handling, or from exposure to moisture or dirt. Loose parts associated with the breaker are sometimes included in the same crate. Check all parts against the packing list to be sure that no parts have been overlooked.
3.3. STORAGE
It is recommended that the breaker be put into service immediately in its permanent location. If this is not possible, the following precautions must be taken to assure the proper storage of the breaker.
The breaker should be stored in a clean location, free from corrosive gases or fumes. Particular care should be taken to protect the equipment from mois- ture and cement dust, as this combination has a very corrosive effect on many parts.
3.4 PACKING LIST
With your breaker, you should have received:
1. Manual charging handle. (Part No. 0282A7227P001)
2. Gag tool. (Part No. 0209B8043G003)
3. Breaker Instruction Book - Contact your GE office for additional copies or verification of present revision.
4. (1) piece of edge protector (See section 4.1)
5. (12) wire ties. (See section 4.1)
6. Lower blocking plate and screws for lower notch in positive interlock cam plate in existing breaker cell units. (Kit # 254-089) NOTE: This assembly eliminates the test provision for closing the breaker in the cabinet, except in the “connect” position, as has been recommended to improve safety of the VL equipment.
7. Existing unit wiring and device WARNING NOTICE sheet.
8. (1) GE tool parts kit (0282A3060G003) with each breaker order of single or multiple breakers.
9. A spring discharge interlock cam - to be installed if none exists in your switchgear cell. NOTE: Customer option to implement, if required.
10. GE grease Part No. 0282A2048P009.
Contact your local GE office if you have not received the above materials.
Page 6 GEH 6468A - Power/Vac VL Breaker
4. INITIAL INSTALLATION PROCEDURES
Although GE has made every effort to assure interchangability and satisfactory interface with existing equipment, older equipment and field modifications made over the years, may require additional procedures before the new vacuum breaker can be installed in the cubicle.
4.1 DOOR WIRING INTERFERENCE
In some of the older GE Metal-Clad switchgear units, the wiring from the door to the stationary structure was run through a perforated steel wire assembly grill. (Figure 1.)
As the new replacement breaker is elevated, the front cover MAY interfere with the subject wiring grill, approximately 4” to 6” before the final connected position.
The front cover shield on the replacement breaker is wider than all previous AM breaker units. Due to the large forces required to operate the existing stationary auxiliary switches, the operating mechanism cannot be decreased in width.
If this condition exists, use the modification kit shipped with the breaker and make the following modifications to the switchgear cubicle.
The lower “Vee” notch in the positive interlock cam plate allows closing and opening the breaker electrically.
FOR IMPROVED SAFETY, IT IS RECOMMENDED THAT THE ABILITY TO FUNCTIONALLY OPER-ATE THE BREAKER IN THE “TEST” POSITION BE ELIMINATED AND THAT BREAKER FUNC-TIONAL TESTING BE PERFORMED WITH THE BREAKER COMPLETELY REMOVED FROM THE CUBICLE.
4.3 BY-PASS KIT INSTALLATION
(See Figures 2 & 7).
The ability to electrically close and open the breaker in the “Test Position” is eliminated by covering the lower Vee notch in the positive interlock cam plate. Materials for accomplishing this modification are provided in Kit #254-089 furnished with the new vacuum breaker. This by­pass kit should be in-stalled on GE breaker cubicles that have a lower interlock roller Vee notch on the positive interlock cam plate. Some GE breaker cubicles do not have this lower Vee notch on the interlock cam plate. In that case, the by-pass kit is not required. If addi-tional by-pass kits are required for the remainder of the switchgear line-up, order Kit #254-089.
1. Cut out the bottom section of the grill as shown in figure 1 on page 12.
2. Cover the sharp edges with the edge protector furnished with the breaker accessories.
3. Fold any wire back and re-tie with the furnished wire ties.
4. Elevate the replacement breaker in accordance with the instructions.
4.2 POSITIVE INTERLOCK TEST PROCEDURES
The positive interlock system functions to prevent closing the breaker contacts when the breaker is being raised or lowered and prevents raising or lowering the breaker when the breaker contacts are closed. In most AM breaker Metal-Clad Switchgear units, there is a breaker “Test Position” which allows you to functionally test the breaker without connecting to the bus. This position is usually about 5” out from the breaker being fully inserted into the cubicle. When in the “test position”, a secondary coupler cable must be used to connect the secondary control circuits since the breaker is fully lowered position.
WARNING: FAILURE TO FOLLOW THE INSTRUCTIONS BELOW COULD CAUSE A CLOSED BREAKER TO BE RAISED TOWARDS THE CONNECTED POSITION, CAUSING INJURY OR DEATH TO THE OPERATOR AND EXTENSIVE EQUIPMENT DAMAGE.
To make the modification proceed as follows:
1. Remove the existing clutch switch cover plate
and discard (save the mounting hardware).
2. Measure and record the distance from the
bottom of the cam plate to the bottom of the switch operator bracket. See Figure 2.
3. Remove the existing switch operator bracket.
4. Install the new switch operator bracket supplied
with the kit, using the two existing ¼ - 20 screws. Adjust the bracket in the exact same location as the removed bracket, in relation to the motor activation switch lever. Make sure that the lower notch in the positive interlock cam plate is covered and that the edge is even with the front edge of the positive interlock cam plate. (Figures 2 and 7.)
GEH 6468A - Power/Vac VL Breaker Page 7
5. Drill two #22 (.157) diameter holes in the positive interlock cam plate from locations in new bracket supplied with kit. See Figure 2.
6. Install two #10-24 thread cutting screws (supplied with kit).
must remain locked and not allow the motor handle to be moved far enough to engage the clutch and close the clutch switch contacts that energize the motor circuit. There should be 1/16” clearance between the clutch and motor coupler, when the motor handle is pulled forward. See Figure 7(A).
7. Install the new clutch switch cover plate supplied with the kit using the existing hardware.
8. All breaker cubicles that undergo this modi­fication to the positive interlock cam plate must be checked according to the dimensions given in Figure 7. a. The 10-7/8” +1/16” -0” dimension from the breaker to the front edge of the positive interlock cam plate must be verified and maintained prior to inserting a replacement PVVL vacuum breaker into the cubicle. See Figure 7(C).
b. The 1/16” clearance between the stationary flag, just behind the upper “Vee” notch and the interlock roller must be maintained or reset if required. The breaker should be in the fully raised position. See Figure 7(A).
4.4 CHECKING FOR PROPER INTERLOCK AND TRIP FREE FUNCTIONS BEFORE LOWER­ ING THE BREAKER FROM THE ELEVATED POSITION.
When the breaker is in the fully elevated and connected position, releasing the motor operating handle will return the positive interlock roller into the upper notch in the interlock cam plate, closing the interlock switches and energizing the circuit that will charge the springs. The breaker may now be closed.
In order to lower the breaker from the connected position, the breaker must be open. If the breaker is not open, the operator can not, and should not be able to engage the clutch or activate the motor circuit. The positive interlock roller will remain locked and will not allow the interlock cam plate to move vertically far enough to activate the elevating motor.
To test the function of the positive interlock system and trip free function, the following checks should be made:
1. With the breaker closed and in the elevated position, the positive interlock roller on the breaker
2. Disconnect the elevating motor plug from its socket.
3. Trip the breaker to the open position.
4. Using the manual charging handle, charge the closing springs in the breaker until the semaphore shows “charged”.
5. Pull back the elevating handle on the motor so that the interlock roller is at the dimension shown in Figure 7. (11/16” +0 -1/16) Hold it in this position while pressing the manual close push button on the breaker. The main power springs must discharge and the breaker must remain open, as indicated by the semaphores on the front of the breaker. This indicates that the breaker contacts will not close during raising or lowering the breaker.
5. ADJUSTMENTS TO BREAKER/SWITCH­ GEAR INTERFACES.
The interfacing parts on all ratings of type AM breakers and switchgear are functionally the same.
5.1 STATIONARY AUXILIARY SWITCH (MOC)
The Stationary Auxiliary Switch is an optional switch mounted in the switchgear cubicle. When the breaker has been elevated to the fully connected position, the switach will be actuated whenever the breaker is closed. The switch is actuated by the plunger interlock (plunger) mounted on the top of the breaker mechanism. The switch has a number of “a” contacts (closed when the breaker is closed and open when the breaker is open) and “b” contacts (open when the breaker is closed and closed when the breaker is open). The following paragraph defines the essential dimensions relating to the interfacing elements of the breaker and switchgear, to assure reliable performance.
The following elements are important factors which commonly affect the operation of the stationary auxiliary switch.
1. Plunger travel on the breaker.
Page 8 GEH 6468A - Power/Vac VL Breaker
2. The gap between the top of the plunger on the breaker and the bottom of the rod on the stationary auxiliary switch mechanism.
3. Variations between breakers in the distance from the underside of the lift rail and the top of the plunger.
4. Variations in the rotation requirements to “make” and “break” the stationary auxiliary switch contacts.
5. Condition of the plunger interlock components on the breaker.
6. Elevating mechanism limit switch consistency.
7. Breaker elevating mechanism positive stops.
8. Seismic events. Some of these elements also affect the other
important interfaces required for reliable operation of the equipment, such as:
1. Primary disconnect penetration.
2. Secondary coupler penetration.
3. The positive interlock mechanism. A major goal in the design of switchgear has
always been the interchangeabililty of breakers. GE Switchgear has been very successful in achieving that goal for many years. Analysis of instruction book adjustments, shop tolerances, and service advice letters issued in recent years, however, has demonstrated that tolerances in switchgear equipment installed and presently operating can result in situations where it is impossible to meet all adjustments or that an adjustment is brought into specification and it causes a problem with another interface.
With specific reference to the plunger / stationary auxiliary switch interface, the following instructions and recommendations supersede all previous Service Advice Letters and instructions. Refer to Figure 1 for details.
Nominal breaker plunger travel is 1-1/8”. Nominal auxiliary switch rod travel is 1-1/16”. It is imperative that a gap is present between the top of the plunger and the bottom of the rod, when the breaker is in the fully connected position and the breaker is open.
To assure the most reliable switch operation, it is recommended that the plunger travel be measured for each breaker and recorded in maintenance records. It is further recommended that the auxiliary switch mechanism be adjusted, if necessary, to result in a gap that is in accordance with the table given in Figure 10. It may require the roll pin which
secures the auxiliary switch mechanism plate to be removed and a new hole drilled after loosening the two mounting bolts and moving the entire auxiliary switch mechanism up or down.
This action may mean future adjusting when and if different breakers are interchanged. Reliable switch operation is critical and it may require limiting your interchangeability of breakers. At a minimum, the criticality requires adjustment verification when swapping breakers.
Specifically, paragraph (f) on page 11 of Service Advice Letter (S.A.L.) #073-323-1, dated 02-01-78 is rescinded and the instruction in GEH-1802X on gap clearance is rescinded and both are replaced with the gap dimension (“G”) given in the table of Figure 10.
The plunger dimensions given in the breaker instruction books are not rescinded because they are correct nominal dimensions. It is permissible to let the breaker adjustment be out of specification, if it conflicts with the dimensions given in Figure 10.
5.2 PRIMARY CONTACT PENETRATION
The nominal contact penetration is 7/8” as shown in Figure 11. The tolerance on penetration is plus 5/32”, minus 1/8” on non 1E equipment and plus 1/16”, minus 1/8” on 1E equipment.
Reference Service Advice Letter # 073.323.1, which addresses methods to check both the penetration and the contact wipe for 5kV equipment. The same methods and means of adjustment also apply to 15kV equipment. GEH­1802X and the similar illustrations it contains showing proper contact wipe patterns should also be consulted. It is essential to maintain proper contact penetration while maintaining the stationary auxiliary switch adjustment given in Figure 10.
5.3 POSITIVE INTERLOCK
The purpose of the positive interlock it to prevent moving the breaker to or from the connected position while the main contacts are closed, and to prevent closing the contacts unless the breaker is in the fully connected position. These important safety features are achieved by means of the positive interlock roller on the right side of the breaker and positive interlock cam and stationary “flag” on the switchgear, as shown in Figure 7.
GEH 6468A - Power/Vac VL Breaker Page 9
The following adjustments are made at the factory and verified for proper operation per Figure 7. The distance from the top of the stationary flag to the top of the switchgear guide rails is set. This maintains the surface upon which the breaker wheels rest when the breaker is lowered. The upper elevating motor limit switch is then adjusted to achieve a roller to flag clearance of 1/16” to 1/8” as shown in Figure 7. The limit switch de-energizes the elevating motor circuit and should be activated when the primary disconnects and secondary coupler reach their nominal contact penetration position. If the timing of this sequence is off, the cubicle must be adjusted back to factory specifications.
Instructions for positive interlock adjustment are detailed on Figures 13, (1000 MVA Equipment), Figure 14, (M-26 Equipment); and Figure 15, (M-36 Equipment). These adjustments are also detailed in instruction book GEH-1802X.
5.4 SECONDARY COUPLER
The cam has minimal adjustment provision. The holes may be slightly slotted to adjust the cam vertically to allow discharge when the breaker wheels reach 1/8” to ¼” height above the floor.
Refer to GE drawing 0184B7344 for instructions on installing a spring discharge cam in the switchgear cubicle.
5.6 STOPS
The stop pins and stop bolts on the elevating mechanism are emergency mechanical stops which would come into use only if the upper elevating motor switch is completely out of adjustment or has failed. Elevating against these stops may be quite audible and the operator should release the clutch handle, de-energizing the elevating motor circuit or, the elevating motor circuit protective fuse will open to protect the motor. The stop bolts should be set to 3/32 to 1/8” clearance and only set after all other elevating adjustments are made.
On the top front of the breaker, there is a black plastic block which holds male secondary coupler pins. This block should make contact with, and slightly raise a spring loaded black plastic block which holds female secondary coupler sockets on the switchgear. The contact depression should be 1/8”. The stationary block is adjustable in the vertical direction as described in Service Advice Letter 073-323-1. It is not always possible to have the black plastic blocks in contact over their entire flat surface. Often, the rear of the blocks are engaged while a gap exists along the front edge. This is an acceptable condition. The contacting block surfaces should touch and the female block edge move upward between 1/32” to 1/8”.
5.5 SPRING DISCHARGE CAM
The purpose of the spring discharge interlock is to discharge all stored energy in the breaker mechanism whenever the breaker is withdrawn from the cubicle. The discharge interlock is located on the left side of the breaker. The spring discharge cam mounted in the switchgear should discharge the breaker closing spring when the breaker is lowered.
5.7 GROUND
A visual check should be made to observe the ground connection. The ground shoe on the moveable breaker is designed to have a nominal engagement of 1-½” + ¼” vertically with the steel and copper spring loaded disconnects of the ground device in the switchgear.
5.8 POSITION SWITCH (TOC)
The position switch is an optional device mounted in the rear left side of the switchgear cubicle. The switch contacts operate when the lifting mechanism is in either the fully raised or fully lowered position. Switch operation should be checked with the breaker withdrawn manually and the equipment de-energized, and again electrically, with the breaker in the cubicle. Refer to Service Advise Letter 073-326.1, dated 5-23-78 for a description of design changes made to improve the switch operating mechanism in 1978.
6. TYPICAL WIRING DIAGRAMS
Page 10 GEH 6468A - Power/Vac VL Breaker
Figures 8 and 9 show typical wiring diagrams for PowerVac® VL breakers.
Replacement breakers for old units with solenoid mechanisms (AM breakers with MS type mech­anisms) are typically wired per the drawing in Figure 8.
Replacement breakers for old units with stored energy mechanisms (AM breakers with ML type mechanisms). are typically wired per the drawing in Figure 9.
The wiring on your breakers may be different. Consult your nameplate for the correct drawing number and call your local GE office for additional copies of this drawing are required.
GEH 6468A - Power/Vac VL Breaker Page 11
Wire Grill
Stationary Aux Switch
SB Control Switch
FIGURE 1
INTERIOR VIEW OF STATIONARY CUBICLE
Grill Cutout
Edge Protector
Front Door
Page 12 GEH 6468A - Power/Vac VL Breaker
FIGURE 2
INTERLOCK MODIFICATION
New Switch Operator Bracket (Shown Blocking Lower Notch)
Positive Interlock Cam Plate
Record this dimension before removing old switch operator bracket. New bracket should be adjusted to this dimension.
SWITCH OPERATOR BRACKET
GEH 6468A - Power/Vac VL Breaker Page 13
FIGURE 3
MOTOR OPERATOR SWITCH ACTUATOR
Page 14 GEH 6468A - Power/Vac VL Breaker
ELEVATING MOTOR TROUBLESHOOTING
TROUBLE SHOOTING
IF ELEVATING MOTOR DOES NOT OPERATE:
1. Check power supply
2. Check fuses UL
FIGURE 4
CORRECTIONS
3. Check and adjust mechanical clutch linkage to clutch switch LC
4. Check LC for proper performance
5. Check motor switch
6. Check motor
7. Adjust upper LE and lower LF limit switches for proper breaker position
8. Check and adjust leaf springs to provide proper tilt to operate limit switches
9. Check plug and receptacle for proper connections
10. Check clutch and mechanism
GEH 6468A - Power/Vac VL Breaker Page 15
FIGURE 5
SCHEMATIC DIAGRAM
VERTICAL LIFT ELEVATING MECHANISM
DO NOT USE RAISE/LOWER SWITCH TO STOP & START MOTOR.
Page 16 GEH 6468A - Power/Vac VL Breaker
FIGURE 6
STATIONARY STRUCTURE WIRING
GEH 6468A - Power/Vac VL Breaker Page 17
FIGURE 7
BY-PASS KIT INSTALLATION
Page 18 GEH 6468A - Power/Vac VL Breaker
FIGURE 8
TYPICAL BREAKER WIRING DIAGRAM
(REPLACEMENT FOR BREAKERS WITH MS MECHANISMS)
GEH 6468A - Power/Vac VL Breaker Page 19
FIGURE 9
TYPICAL BREAKER WIRING DIAGRAM
(REPLACEMENT FOR BREAKERS WITH ML MECHANISMS)
Page 20 GEH 6468A - Power/Vac VL Breaker
FIGURE 10
ADJUSTMENT OF PLUNGER INTERLOCK
Adjustment of plunger interlock - Breaker raised to connect position. Gap adjustment as a function
of breaker plunger travel to assure proper switch operation.
P G R
Plunger
Interlock
Travel (To be
measured) Min. Max. Min. Max.
1-1/16 .001 1/16 1” 1-1/16
Gap between top of plunger interlock and
bottom of aux. switch rod
Resulting travel of the aux. switch rod
GEH 6468A - Power/Vac VL Breaker Page 21
FIGURE 11
PRIMARY CONTACT PENETRATION
Page 22 GEH 6468A - Power/Vac VL Breaker
Loading...
+ 50 hidden pages