for Allis Chalmers®, Siemens/Allis®, and
Siemens® LA-600, LA-800, and LA-1600 Gold
Low-Voltage Power Circuit Breakers
INTRODUCTION
GE Conversion Kits are designed for
upgrading existing Allis Chalmers®,
Siemens/Allis®, and Siemens® low-voltage
power circuit breakers, rather than replacing
the entire breaker. The Conversion Kits
include ProTrip™ Trip Units, the latest
technological advance in GE trip systems.
ProTrip Conversion Kits are designed and
tested to conform to ANSI Standard C37.59,
allowing the retrofitter to properly install
the kit and acceptance test the breaker.
This publication covers installation of
ProTrip Conversion Kits on Allis Chalmers®,
Siemens/Allis®, and Siemens® LA-600, LA800, and LA-1600 gold low-voltage power
circuit breakers. Each Conversion Kit
contains all the components needed to
convert from the existing trip system.
TABLE OF CONTENTS
SECTION 1. GENERAL INFORMATION....................................................................................................................................................4
SECTION 2. BEFORE INSTALLATION ........................................................................................................................................................4
SECTION 4. INSTALLING THE CONVERSION KIT.......................................................................................................................6
Installing and Adjusting the Flux Shifter Assembly....................................................................................................7
Installing the Flux Shifter Assembly .....................................................................................................................7
Flux Shifter Test ....................................................................................................................................................................8
Installing the Current Sensors ..................................................................................................................................................10
LA-600 and LA-800 Current Sensors ...................................................................................................................10
LA-1600 Current Sensors ............................................................................................................................................. 10
3. Components supplied with the conversion kit. ...........................................................................................................................6
8. Attaching the trip unit to the mounting plate...............................................................................................................................9
9. Trip unit mounted on the breaker (LA-600 shown). .................................................................................................................9
10. Installing the current sensors on an LA-600 or LA-800 breaker....................................................................................10
11. Installing the current sensors on an LA-1600 breaker. ........................................................................................................ 10
12. Neutral sensor outline for LA-600 and LA-800 breakers.....................................................................................................11
13. Neutral sensor outline for LA-1600 breakers...............................................................................................................................12
14. Cabling diagram for ProTrip™ trip units with ground fault on four-wire loads............................................... 15
3
SECTION 1. GENERAL INFORMATION
SECTION 2. BEFORE INSTALLATION
GE Conversion Kit installation is straightforward,
but does require careful workmanship and attention
to these instructions. Familiarity with the breaker is
highly desirable. Then general approach is to first
remove the existing trip devices from the breaker,
then install the ProTrip components. Following this
procedure, the converted breaker is performance
tested before it is returned to service.
The majority of trip unit kit installations do not
require any customized assembly work. However,
some installations may involve unusual mounting
conditions or accessory combinations that require
minor modifications and/or relocation of components. In most instances, this supplementary work
can be done on site.
In preparation for the conversion, the installer
should verify that the appropriate current sensors
and trip unit have been furnished. Whenever a
ProTrip kit is installed on a breaker with a four-wire
system, an associated neutral sensor (CT) is
required for separate mounting in the equipment.
Ensure that retrofitted breakers are applied within
their short-circuit ratings.
Note that all ProTrip trip units supplied with conversion kits are equipped with long-time, shorttime, instantaneous, and defeatable ground fault
(LSIGX) trip functions. The installer should be aware
of how these functions will affect his application
before installing the conversion kit.
As a service-related consideration, the installation
of a ProTrip kit provides an excellent opportunity to
perform normal maintenance on the breaker, particularly when the front and back frames are separated. Such procedures are described in the installation and maintenance manuals supplied with the
breaker and equipment.
Before starting any work, turn off and lock out all
power sources leading to the breaker, both primary
and secondary. Remove the breaker to a clean, welllighted work area.
WARNING: Low-voltage power circuit breakers use
high-speed, stored-energy spring operating
mechanisms. The breakers and their enclosures
contain interlocks and safety features intended to
provide safe, proper operating sequences. For
maximum personnel protection during installation,
operation, and maintenance of these breakers, the
following procedures must be followed. Failure to
follow these procedures may result in personal
injury or property damage.
• Only qualified persons, as defined in the
National Electrical Code, who are familiar with
the installation and maintenance of lowvoltage power circuit breakers and switchgear
assemblies, should perform any work on these
breakers.
• Completely read and understand all instructions before attempting any breaker installation, operation, maintenance, or modification.
• Turn off and lock out the power source feeding
the breaker before attempting any installation,
maintenance, or modification. Follow all lockout and tag-out rules of the National Electrical
Code and all other applicable codes.
• Do not work on a closed breaker or a breaker
with the closing springs charged. Trip a
CLOSED breaker and be sure the stored-energy
springs are discharged. This removes the
possibility that the breaker may trip OPEN or
the closing springs discharge, which could
cause injury.
• Trip the breaker OPEN, then remove the
breaker to a well-lighted work area before
beginning work.
• Do not perform any maintenance that includes
breaker charging, closing, tripping, or any other
function that could cause significant movement
of a draw-out breaker while it is on the drawout extension rails.
• Do not leave the breaker in an intermediate
position in the switchgear compartment.
Always leave it in the CONNECTED , TEST , or
DISCONNECTED position. Failure to do so
could lead to improper positioning of the
breaker and flashback.
4
SECTION 3. BREAKER PREPARATION
The following steps are performed to prepare the
breaker for installation of the new conversion kit.
Unless otherwise indicated, the procedure is the
same for LA-600, LA-800, and LA-1600 breakers.
WARNING: Before installing the conversion kit,
turn the breaker OFF, disconnect it from all voltage
sources, and discharge the closing springs.
1. Open the breaker and remove it from its enclosure. Carefully place the breaker on a suitable
work surface so that the rear of the breaker is
initially accessible.
2. If the conversion kit is to be installed on a fused
breaker (LAF series), remove the fuse structure
from the upper (line) studs to allow easier
access to the load studs.
3. Loosen the two Allen-head screws securing each
of the primary disconnects to the line (upper)
and load (lower) studs and remove the primary
disconnects, as illustrated in Figure 1.
4. Remove the wires from the original current sensors (CTs), if present, and slide off the CTs.
5. Unscrew the knob on the end of the manual
charging handle and pull the handle down part
way. Remove the two bolts holding the escutcheon to the breaker frame and lift off the
escutcheon.
6. Carefully position the breaker so that it is resting
on its back on the line and load studs.
7. Remove the two bolts securing the old flux
shifter mounting bracket (if present) to the
breaker frame, shown in Figure 2. One bolt is
secured with a nut, the other is attached to a
tapped hole in the frame. Disconnect the two
connectors on the leads to the trip unit and
remove the flux shifter.
8. Remove the three bolts securing the trip unit
mounting bracket (if present) to the breaker
frame. Remove the trip unit and its wiring harness.
Figure 1. Primary disconnects removed from the lower studs, showing
the original current sensors (LA-1600 shown).
Trip Unit
Flux
Shifter
Figure 2. Original flux shifter and trip unit (Type LTS1 shown) mounting
locations (LA-1600 shown).
5
SECTION 4. INSTALLING THE
CONVERSION KIT
This section describes the installation of the MicroVersaTrip Plus or MicroVersaTrip PM conversion kit.
The components provided with the kit are shown in
Figure 3.
Wiring
Harness
Trip Unit on
Mounting
Plate
Current
Sensor
Support
Bracket
Figure 3. Components supplied with the conversion kit.
6
Flux
Shifter
Installing and Adjusting the Flux Shifter
Assembly
Use the following procedures to install and adjust
the new flux shifter assembly, shown in Figure 4.
Numbers in brackets in the text refer to the numbered parts in Figure 4. The breaker should still be
resting on its back from the previous procedure
(removing the old components).
Installing the Flux Shifter Assembly
Figures 6 and 7 show two views of the completed
flux shifter installation.
1. Check that the diameters of the two flux shifter
mounting holes, shown in Figure 5, are .30 inch.
If they are less than this size, drill them out to
.30 inch (use an N bit).
2. Loosen the screw on the flux shifter reset link [2]
and move the link to the bottom of its slot.
3. Remove and save the nut, lock washer, and flat
washer from the two mounting studs [6] on the
mounting surface of the flux shifter assembly.
Leave the spacers in place, as they are necessary
to ensure proper alignment with the breaker
reset link [7].
4. Install the flux shifter assembly on the right side
of the breaker frame where the original flux
shifter (if present) was removed. The two
mounting studs should fit through the existing
(or modified) holes in the frame, as shown in
Figure 5. Secure the flux shifter assembly to the
frame with the flat washer, lock washer, and nut
removed in step 3.
Flux Shifter Adjustment
1. With the breaker in the open (reset) position,
depress the flux shifter reset arm [1] so that
dimension A is held at about 0.4 inch.
2. Move the flux shifter reset link [2] up to contact
the breaker reset link [7] and take up any travel
in the breaker link.
3. Tighten the screw on the flux shifter reset link
[2] to secure it in position. The flux shifter is
now in its reset position.
4. Check that there is clearance between the reset
pin [5] and the reset latch [4] with the breaker in
the OPEN (reset) position. When the breaker is
CLOSED, the flat of the reset pin [5] must rest
against the reset latch [4].
Figure 4. Flux shifter assembly.
Breaker
Reset
Link
Trip
Paddle
Mounting
Holes
Figure 5. Flux shifter mounting area (LA-800 shown).
7
Trip Screw Adjustment
With the breaker CLOSED, the trip screw [3] must
have zero clearance with the breaker trip paddle. If
adjustment is necessary, OPEN the breaker, make
the adjustment, then CLOSE the breaker to check
the adjustment. Be sure to retighten the adjusting
nut.
WARNING: Be extremely careful when working on
a CLOSED breaker. Do not reach your hands into
the mechanism while adjusting the flux shifter.
Breaker Reset Linkage.
This following procedure is illustrated in Figures 4,
6, and 7
Place a #10 flat washer over the supplied #10-32
bolt. Insert the bolt through the hole in the breaker
reset link [7]. Place a flat washer over the bolt, then
slide the bolt through the slot in the flux shifter
reset arm [1]. Place a flat washer and the selflocking nut on the bolt. Tighten the nut so that the
bolt is still free to rotate.
Flux Shifter Test
The operation of the flux shifter may be tested by
closing the breaker, then applying 9 Vdc to the flux
shifter leads (red is positive). The breaker should
trip and reset. If necessary, repeat the adjustments
in the previous procedures.
Flux Shifter
Reset Arm [1]
Mounting
Stud [6]
Breaker
Reset
Link [7]
Flux Shifter
Reset Link
Trip
Screw
Figure 6. Flux shifter assembly installed, as viewed from the bottom of
the breaker.
Breaker
Reset Link [7]
Trip
Paddle
Figure 7. Flux shifter assembly installed, as viewed from the right front
of the breaker (LA-800 shown). .
8
Installing the Trip Unit
1. On LA-600 and LA-800 installations, remove the
microswitch adjusting bolt on the trip unit
mounting plate.
2. Remove and the trip unit mounting screw from
the rear of the trip unit. Place the trip unit in
position on the mounting plate, with the 50-pin
connector aligned with the opening in the plate.
Secure with the previously removed trip unit
mounting screw, as shown in Figure 8.
3. Insert the 50-pin female connector on the wiring
harness into the trip unit connector through the
rear of the mounting plate. Secure to the mounting plate with the two #4-40 screws and lock
washers provided, as shown in Figure 8.
4. Place the trip unit and mounting plate in position on the support bracket. Secure with three
1
/4 -20 screws, lock washers, and flat washers
into the tapped holes in the support bracket, as
shown in Figure 9.
5. Place the two slotted mounting holes in the
support bracket behind the two existing holes in
the breaker frame, as shown in Figure 9. Secure
with the 1/4 -20 screws, flat washers, lock
washers, and nuts provided.
6. Pass the current sensor and flux shifter leads
from the front to the rear through the hole on
the lower left side (viewed from the rear) of the
breaker frame.
7. If a neutral sensor is to be used in the equipment, pass the corresponding connector
through the rear-frame hole with the CT leads.
Otherwise, tie it to some convenient point on
the breaker frame with wire ties.
8. On LA-1600 installations, adjust the microswitch
adjusting bolt so that the microswitch is off
when the breaker is open and on when the
breaker is closed.
Trip Unit
Mounting
Screw
50-Pin
Connector
Figure 8. Attaching the trip unit to the mounting plate.
Mounting
Plate
Screws
Support Bracket
Mounting
Screws
Figure 9. Trip unit mounted on the breaker (LA-600 shown).
9
Installing the Current Sensors
E
e
The current sensors must be installed differently in
the two breaker frame sizes.
LA-600 and LA-800 Current Sensors
The following procedure is illustrated in Figure 10.
1. Slide two of the current sensors (CTs) over the
outer load studs with their terminals pointing
upward. Slide the other CT over the center line
stud with its terminals pointing downward.
2. Connect the CT leads from the trip unit to each
of the CTs. The leads are labeled with the letter
of the corresponding pole (A is the right pole
from rear of the breaker, B is the center pole, C is
the left pole), and are also cut to the appropriate
lengths. Attach the white wire to the terminal
marked with a white paint dot on the A and C
(outer) CTs. Attach the black wire to the terminal
marked with a white paint dot on the B (center)
CT. This difference is necessary to maintain
proper polarity.
3. Reattach the primary disconnect assemblies to
all the studs if the breaker is unfused or to only
the load (lower) studs if the breaker is fused.
4. If the breaker is fused, reinstall the fuse assemblies on the upper studs.
CT Wire
Exit Hole
Figure 10. Installing the current sensors on an LA-600 or LA-800
breaker..
LA-1600 Current Sensors
The following procedure is illustrated in Figure 11.
1. Slide the three current sensors (CTs) over the
lower (load) studs, with the terminals pointing
up.
2. Connect the CT lead s from the trip unit to each
of the CTs. The leads are labeled with the letter
of the corresponding pole (A is the right pole
from rear of the breaker, B is the center pole, C is
the left pole), and are also cut to the appropriate
lengths. Attach the white wire to the terminal
marked with a white paint dot.
3. Reattach the primary disconnect assemblies to
all the studs if the breaker is unfused or to only
the load (lower) studs if the breaker is fused.
4. If the breaker is fused, reinstall the fuse asse mblies on the upper studs.
CT Wire
xit Hol
Figure 11. Installing the current sensors on an LA-1600 breaker..
10
SECTION 5. FOUR-WIRE GROUND
FAULT OPTION
The ground fault option for four-wire installations
requires the installation of an additional current
sensor on the neutral bus in the equipment. The
sensor is connected to the trip unit through the
connector provided in the wiring harness.
1. Mount the neutral sensor on the outgoing neutral lead, normally in the bus or cable compartment in the equipment. Figure 12 shows the
sensor outlines for the 600 A and 800 A frame
sizes. Figure 13 shows the sensor for the 1600 A
frame size.
2. Connect the neutral sensor wire harness to the
correct taps on the sensor. To maintain the
same polarity as the phase sensors, connect the
white wire to the common terminal, black to the
tap.
3. Route the wires through the equipment and
connect to the two-pin connector on the trip
unit wiring harness, routed through the rear of
the breaker with the CT wires. The wires should
be tied to the breaker frame in an easily
accessible location.
Figure 12. Neutral sensor outline for LA-600 and LA-800 breakers..
11
Figure 13. Neutral sensor outline for LA-1600 breakers.
12
SECTION 6. TESTING AND TROUBLESHOOTING
WARNING: Do not change taps on the current
sensors or adjust the trip unit settings while the
breaker is carrying current. Failure to adhere to
these instructions will void all warranties.
Testing
Before installing a converted breaker back into
service, perform the following steps:
1. Verify that the trip unit is securely installed by
performing a continuity test on the CT wiring
and the trip unit.
a. Disconnect the black CT wires at each phase
sensor.
b. Check for continuity with a continuity tester
or VOM from the white lead of the phase A
CT to the white lead of the phase B CT.
c. Repeat this continuity test for the white leads
of the phase A and phase C CTs.
d. Measure the resistance across each phase
sensor and compare the values measured to
the values listed in Table 1.
e. Reconnect the black CT leads to all of the
phase sensors. Ensure that this is done
before continuing with performance testing
of the breaker.
wiring harness, flux shifter, and trip unit as a
complete system.
a. A high-current, low-voltage power supply
should be connected across each line and
load terminal to simulate an overcurrent fault.
b. Set the long-time trip at 0.5 to minimize the
breaker stress.
c. When ground fault is installed, the test can be
performed by wiring two adjacent poles in
series or by using the GE Digital Test Kit, cat.
no. TVRMS2. This will prevent the breaker
from tripping because of an unbalanced current flow.
CAUTION: Do not attempt to use GE Test Kit cat.
no. TVTS1 or TVRMS on this trip unit.
Trouble-Shooting
When malfunctioning is suspected, first examine
the breaker and its power system for abnormal
conditions such as the following:
• The breaker is not tripping in response to overcurrent conditions or incipient ground faults.
• The breaker is remaining in a trip-free state
because of mechanical interference along its
trip shaft.
• The shunt trip (if present) is activating improperly.
CAUTION: In addition to the continuity test
described in Step 1 and before performance testing of the converted breaker, each phase of the
breaker should be primary injected with a current
level of about 10%, but no more than 20%, of the
CT rating.
WARNING: If the converted breaker is energized or
tested by primary injection with a sufficiently high
test current with a loose or open circuit between
the CTs and the trip unit, damage will occur to the
trip unit, wire harness, 50-pin trip unit connector,
and CTs. Failure to adhere to these instructions
will void all warranties.
2. Check the insulation on the prim ary circuit with
a 1,000-volt Megger.
3. Measure the resistance across the line and load
terminals for each phase using a micro-ohmmeter or millivolt tester. If the resistance differs
considerably from phase to phase, the electrical
connections may not be properly tightened or it
could also indicate improper contact wipe.
4. To verify that the breaker has been properly
retro fitted, perform a primary injection test on
each phase. This test will check the CTs, bus,
Nuisance Tripping on Ground Fault-Equipped
Breakers
When nuisance tripping occurs on breakers
equipped with ground fault trip, a probable cause is
the existence of a false ground signal. Each phase
sensor is con nected to summing circuitry in the trip
unit. Under no-fault conditions on three-wire load
circuits, the currents add to zero and no ground
signal is developed. This current sum is zero only if
all three sensors have the same electrical characteristics. If one sensor differs from the others (such
as by a different rating or wrong tap setting), the
circuitry can produce an output suffi cient to trip the
breaker. Similarly, a discontinuity between any
sensor and the trip unit can cause a false trip signal.
The sensors and their connections should be
closely examined if nuisance tripping is
encountered on any breaker whose ProTrip trip unit
has previously demonstrated satisfactory
performance. After disconnecting the breaker from
all power sources, perform the follow ing procedure:
1. Check that all phase sensors are the same type
(current range).
2. Verify that the tap settings on all three phase
sensors are identical.
13
3. Verify that the wiring harness connections to the
sensors have the proper polarity (white lead to
common, black lead to tap), as shown in the
cabling diagram in Figure 14.
4. On ground fault breakers serving four-wire
loads, check that the neutral sensor is properly
connected, as indicated in Figure 14. In particular, check the following:
a. Verify that the neutral sensor has the same
rating and tap setting as the phase sensors.
b. Verify continuity between the neutral sensor
and its equipment-mounted secondary
disconnect block. Also check for continuity
from the breaker-mounted neutral secondary
disconnect block through to the trip unit
wiring harness connector.
c. If the breaker’s lower studs connect to the
power source, then the neutral sensor must
have its load end connected to the source.
d. Verify that the neutral conductor is carrying
only the neutral current associated with the
breaker’s load current (the neutral is not
shared with other loads).
5. If the preceding steps fail to identify the problem, then measure the sensor resistances. The
appropriate values are listed in Table 1. Since
the phase and neutral sensors are electrically
identical, their resistances should agree closely.
BreakerCT Rating, AResistance, ohms
LA-600
LA-800
LA-1600
150
225
600
150
400
800
800
1600
10.1–15.2
14.5–22
4–58
10.1–15.2
27–41
51–77
54–81
110–166
Table 1. CT resistance values.
14
Figure 14. Cabling diagram for ProTrip™ trip units with ground fault on four-wire loads.
15
These instructions do not cover all details or variations in equipment nor do they provide for every possi ble
contingency that may be met in connection with installation, operation, or maintenance. Should further
information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s
purposes, the matter should be referred to the GE Company.
g
GE Industrial Systems
General Electric Company
41 Woodford Ave., Plainville, CT 06062