GE Masoneilan 12400 Series Instruction Manual

Page 1
GE Oil & Gas
Masoneilan* 12400 Series Level Transmitter & Controller ATEX Instruction Manual
Advanced Level Measurement
SIL2-capable liquid level
transmitter
Low- and high- level switch
integrated fucntions
Easy installation and simple
operation
Three built-in pushbuttons
Seamless system integration
Page 2
2 | GE Oil & Gas
Contents
1.0 Level Transmitter/Controller Type 12400 Operation ..................................................3
2.0 Type 12400 Number System ........................................................................4
3.0 Technical Specifications ...........................................................................4
3.1 Performances ......................................................................................... 4
3.2 Schematics and parts identification .................................................................... 5
4.0 ATEX Intrinsic Safety Marking for Type 12400 ........................................................6
5.0 ATEX Flameproof Marking for Type 12400 ............................................................6
6.0 Electrical Connections and Conduit Entry............................................................7
6.1 Voltage suppy allowable ............................................................................... 7
6.2 Maximum Power....................................................................................... 7
6.3 Output current and loop resistor ....................................................................... 7
6.4 Intrinsic Safety entity parameters ......................................................................8
6.5 Conduit entry in flameproof application ................................................................ 8
7.0 Assembly and Installation ..........................................................................9
7.1 As s emb l y .............................................................................................. 9
7.2 12400 flameproof instalation ...........................................................................9
7.3 12400 Intrinsic Safety and type n installation............................................................ 9
8.0 Setup and Start Up ...............................................................................10
8.1 Coupling..............................................................................................10
8.2 Configuration.........................................................................................10
8.3 Calibration ...........................................................................................10
8.4 Start up ..............................................................................................10
9.0 Maintenance Service .............................................................................11
9.1 General rules .........................................................................................11
9.2 Before maintenance activity ..........................................................................11
9.3 During maintenance activity ..........................................................................11
9.4 After maintenance activity ............................................................................11
10.0 Special Conditions of Use ........................................................................12
10.1 For Intrinsic Safety and Flameproof...................................................................12
10.2 For Intrinsic Safety...................................................................................13
10.3 For Flameproof ......................................................................................13
ANNEX I ......................................................................................14
ANNEX II .....................................................................................15
Page 3
12400 Series Digital Level Instruction Manual (March/2013) | 3
WARNING
BEFORE installing, using or carrying out any maintenance tasks associated with this instrument, READ THE INSTRUCTIONS CAREFULLY.
These instruments comply with the essential safety requirements of the European Directive ATEX 94/9/CE. It is certified to be used in Gas or Dust explosive atmospheres, groups IIA, IIB, IIC and IIIC:
Category II 1GD – zones 0, 1, 2, 20, 21 and 22 for the protection mode "ia"
Category II 2GD – zones 1, 2, 21 and 22 for the protection mode "d" and “tb”
They also comply with the essential safety requirements of the European Directive EMC 2004/108/CE as amended, for use within an industrial environment.
Products certified as explosion proof equipment MUST BE: a) Installed, put into service, used and maintained in compliance with European and/or national and local
regulations and in accordance with the recommendations contained in the relevant standards concerning potentially explosive atmospheres.
b) Used only in situations those comply with the certification conditions shown in this document and after
verification of their compatibility with the zone of intended use and the permitted maximum ambient
temperature.
c) Installed, put into service and maintained by qualified and competent professionals who have undergone
suitable training for instrumentation used in areas with potentially explosive atmosphere. Such trainings are not supported by GE.
It is the end user's responsibility to:
• Verify material compatibility with the application
• Ensure proper use of fall protection when working at heights, per Safe Site Work Practices
• Ensure use of proper Personal Protective Equipment
• Take the appropriate actions to ensure that site personnel who are performing installation,
commissioning and maintenance have been trained in proper site procedures for working with and
around equipment, per Safe Site Work Practices
GE reserves the right to discontinue manufacture of any product or change product materials, design, or specifications without notice.
Under certain operating conditions, the use of damaged instruments could cause a degradation of the performances of the system which may lead to personal injury or death.
Use only GE's Masoneilan replacement parts to ensure that the products comply with the essential safety requirements of the European Directives mentioned above.
1. LEVEL TRANSMITTER/CONTROLLER TYPE 12400 OPERATION
To be operational, the digital level and controller type 12400 must be mounted on a torque tube and on a
displacer chamber equipped with the displacer.
Any change in the level of liquid or the interface between two liquids will change the apparent weight of the
displacer and cause a change of the angle of rotation in the torque tube.
This angle is measured by a sensor and converted by an electronic module:
• Either to a standardized 4-20mA current, proportional with the change in level, when congured as a level
transmitter,
• Or, to a 4-20mA current, generated by a PID algorithm derived from the error between the actual level of liquid and the local set point, when congured as a level controller.
Page 4
4 | GE Oil & Gas
2. TYPE 12400 NUMBER SYSTEM
12 4 a b
c
d
Model Action Mounting Protection
Housing Material
4 - HART communication protocol,
LCD display and push buttons, SIL certified
1 – Controller with
adjustable switches and second 4-20 mA analogue output signal: AO_1, AO_2, DO_1, DO_2
2 – Transmitter:
AO_1
3 – Transmitter
with adjustable switches and second 4-20 mA analogue output signal: AO_1, AO_2, DO_1, DO_2
O - Top and bottom, Screwed, BW or SW
1 - Top and bottom, Flanged
2 - Side and side, Flanged
3 - Top vessel, Flanged
4 - Side vessel, Flanged
5 - Top and side, Screwed, BW or SW
6 - Side and bottom, Screwed, BW or SW
7 - Side and bottom, Flanged
8 - Top and side, Flanged
9 - Side and side, Screwed BW or SW
1 - FM & FMc SI, NI, DIP, XP and Nema 4X-6P
2 - JIS, Xproof
3 - Rosteknadzor,
IS, Xproof and IP 66/67
4 - Inmetro, IS, Xproof
5 - ATEX & IECEx
IS, Xproof, and IP 66/67
6 - Others approvals
(based on ATEX/IEC approvals)
7 - Other approvals
(not based on ATEX/ IEC approvals)
1- Aluminum with
epoxy painting
2 - Stainless steel
Note: Controller option is pending. Please consult GE Oil & Gas.
3. TECHNICAL SPECIFICATIONS
3.1 Performances
Refer to specific gravities between 0.15 and 1.4 with a standard displacer 907 cm3 @ 1362 g.
• Accuracy : ± 0.5 %
• Hysteresis : ± 0.3 %
• Repeatability : ± 0.2 %
• Dead zone: ± 0.1 %
• Ambient temperature ranges:
• In operation : -50°C to + 80°C
• Storage and transport: -50°C to +93°C
• Water ingress protection: IP66/67
Page 5
12400 Series Digital Level Instruction Manual (March/2013) | 5
3.2 Schematics and parts identification
Page 6
6 | GE Oil & Gas
4. ATEX INTRINSIC SAFETY MARKING FOR TYPE 12400
The marking is on the serial plate stamped on the 12400 housing (rep 124).
• Name and address the manufacturer:
Dresser Produits Industriels S.A.S. 12110 CONDE SUR NOIREAU - FRANCE
• Type designation: 12400
See numbering system for complete codification §2.
• Basic marking:
II 1 G/D for protection mode "ia"
Page 7
12400 Series Digital Level Instruction Manual (March/2013) | 7
Page 8
GEA19100 04/2013
© 2013 General El ectric Comp any. All rights r eserved.
* Masoneilan and ValVue are registered trademarks of the General Electric Company. Other company names and product names used in this document are the registered trademarks or trademarks of their respective owners.
AUSTRALIA Brisbane:
Phone: +61-7-3001-4319 Fax: +61-7-3001-4399
Perth:
Phone: +61-8-6595-7018 Fax: +61 8 6595-7299
Melbourne:
Phone: +61-3-8807-6002 Fax : +61-3-8807-6577
BELGIUM
Phone: +32-2-344-0970 Fax: +32-2-344-1123
BRAZIL
Phone: +55-11-2146-3600 Fax: +55-11-2146-3610
CHINA Phone: +86-10-8486-4515 Fax: +86-10-8486-5305
FRANCE Courbevoie
Phone: +33-1-4904-9000 Fax: +33-1-4904-9010
GERMANY Ratingen
Phone: +49-2102-108-0 Fax: +49-2102-108-111
INDIA Mumbai
Phone: +91-22-8354790 Fax: +91-22-8354791
New Delhi
Phone: +91-11-2-6164175 Fax: +91-11-5-1659635
ITALY
Phone: +39-081-7892-111 Fax: +39-081-7892-208
JAPAN Chiba
Phone: +81-43-297-9222 Fax: +81-43-299-1115
KOREA
Phone: +82-2-2274-0748 Fax: +82-2-2274-0794
MALAYSIA
Phone: +60-3-2161-0322 Fax: +60-3-2163-6312
MEXICO
Phone: +52-5-310-9863 Fax: +52-5-310-5584
THE NETHERLANDS Phone: +0031-15-3808666 Fax: +0031-18-1641438
RUSSIA Veliky Novgorod
Phone: +7-8162-55-7898 Fax: +7-8162-55-7921
Moscow
Phone: +7 495-585-1276 Fax: +7 495-585-1279
SAUDI ARABIA
Phone: +966-3-341-0278 Fax: +966-3-341-7624
SINGAPORE
Phone: +65-6861-6100 Fax: +65-6861-7172
SOUTH AFRICA Phone: +27-11-452-1550 Fax: +27-11-452-6542
SOUTH & CENTRAL AMERICA AND THE CARIBBEAN Phone: +55-12-2134-1201 Fax: +55-12-2134-1238
SPAIN
Phone: +34-93-652-6430 Fax: +34-93-652-6444
UNITED ARAB EMIRATES
Phone: +971-4-8991-777 Fax: +971-4-8991-778
UNITED KINGDOM Wooburn Green
Phone: +44-1628-536300 Fax: +44-1628-536319
UNITED STATES Massachusetts
Phone: +1-508-586-4600 Fax: +1-508-427-8971
Corpus Christi, Texas
Phone: +1-361-881-8182 Fax: +1-361-881-8246
Deer Park, Texas
Phone: +1-281-884-1000 Fax: +1-281-884-1010
Houston, Texas Phone: +1-281-671-1640 Fax: +1-281-671-1735
DIRECT SALES OFFICE LOCATIONS
Loading...