Gaylord PBW User Manual

MAKE-UP AIR PLENUM BOX
MODEL “PBW” Whisper AirTM Series ITEM NO. ________ FOR HOOD ITEM NO._________
Plenum Box
Stainless Steel Perforated Panels
GENERAL SPECIFICATIONS
Furnish Gaylord Plenum Box(s) Model PBW WhisperAir series, for distributing low velocity make-up air down, immediately in front of the ventilator, as shown on the plans. The plenum box shall be capable of delivering up to 150 CFM per lineal ft. of ventilator at a low velocity. The plenum box shall be designed to t in front of the ventilator, either ush with the ceiling or dropped down in front of the ventilator. Plenum Box shall be 12" high by the length of the ventilator, as detailed on the drawings. Plenum Box shall be of all stainless steel construction, not less than 20 gauge. All exposed surfaces shall be a number 4 nish. The box shall have bottom discharge through removable stainless steel perforated panels and shall include internal baing to provide even air distribution along the entire length of the unit. One or more anged duct collars shall be provided as shown on the plans. The box shall have two full length mounting brackets with
5/8” holes on 12” centers to accommodate hanging from the overhead.
Option 1 Insulation: The plenum box shall include ½” matte faced
insulation on all solid interior surfaces. Add MFI sux to model number.
Option 2 Insulation: The plenum box shall include ½” foil backed
insulation an all solid interior sides. Add FBI sux to model number.
Specier Note: Insulation is necessary to prevent condensation from forming on the exposed surfaces of the box. It is recommended when the sides of the Plenum Box are exposed and with the following conditions: 1) The make-up air is coole d, or 2) the make-up air is not heated and outside temperatures are cool.
Matte faced is the standard insulation. Foil faced is re quired i n some jursidic tions to meet indoor air quality requirements. Consult local jurisdictions.
APPLICATION
Properly introduced make-up air into the kitchen space is a key factor in the capture and containment performance of the exhaust ventilator. Make-up air introduced improperly, such as through 4 way diusers located near the ven­tilator, or registers with high velocity discharge, typically results in cross drafts causing smoke loss into the kitchen. As a general rule, make-up air should be delivered into the space at a low velocity, an average of 80 FPM or less, to allow the ventilator to pull the air to itself. Any method of introducing make-up air that is forced to the ventilator typically results in smoke loss.
The use of engineered plenum boxes, also referred to as perforated perimeter supply, is an ideal method of introducing make-up air as it assures the cor­rect air volume, the proper discharge velocity at the proper distance from the ventilator. The plenum box is usually preferred over a front face discharge design as it allows ventilators to be located close to walls, sot walls, other ventilators or any other obstruction that would interfere with discharged air.
Plenum boxes are located immediately in front of the ventilator as illustrated above, at a minimum of 18” above the lower front edge. On back to back cook­ing island applications a plenum box would be located on both sides and in some situations on all four sides. On single island applications a plenum box
would typically be located on both sides.
FEATURES
• WhisperAirTM – Low velocity down discharge
• 20GaugeStainlessSteel-For all exposed surfaces
• AirVolume – Delivers up to 150 CFM per lineal ft.
BENEFITS
• Quiet
• LowProle
• LowCost
GAYLORD INDUSTRIES
10900 SW AVERY ST • TUALATIN, OREGON 97062 U.S.A.
PHONE: 800.547.9696 • FAX: 503.692.6048 • email: info@gaylordusa.com
www.gaylordusa.com
2.5"
9' - 0” OR GREATER
TWO DUCT COLLARS
REQUIRED
UNDER 9' - 0"
ONE DUCT COLLAR
MAKE-UP AIR PLENUM BOX
MAKE-UP AIR PLENUM BOX
FULL LENGTH MOUNTING BRACKETS
OPTIONAL INSULATION
ITEM NO. ________
12"
REMOVABLE STAINLESS STEEL PERFORATED PANELS
SUPPLY DUCT(S) BY OTHERS
HANGING ROD BY INSTALLER
FULL LENGTH MOUNTING BRACKETS
18" MIN. FOR UP TO 150 CFM/LINEAL FT. 24" MIN. FROM 150 TO 275 CFM/LINEAL FT.
SUPPLY DUCT(S) BY OTHERS
HANGING ROD BY INSTALLER
FULL LENGTH MOUNTING BRACKETS
DROP DOWN INSTALLATION
Form No. PBW-0711-30677 © Copyright 2011, Gaylord Industries Litho USA
FLUSH TO CEILING INSTALLATION