Gaylord GX-BDL, C-250 Service Manual

THE
GA YLORD VENTILA TOR
EFFECTIVE DA TE 2-99
TECHNICAL MANUAL
FOR GRAND “GX” SERIES
NON W A TER-W ASH VENTILATORS
WITH
MODEL C-250 START/STOP SWITCH
GAYLORD INDUSTRIES, INC.
1-800-547-9696 • 503-691-2010 • FAX: 503-692-6048 • email: info@gaylordusa.com
An Illinois Tool Works Company
“Undisputed World Leader in
Engineered Systems for
Commercial Kitchens”
tm
GAYLORD INDUSTRIES, INC.
World Headquarters: P .O. Box 1149 • T ualatin, Oregon 97062-1 149 U.S.A.
T o Our Customers. . . Congratulations on your recent purchase of a Gaylord
kitchen exhaust hood system. We are proud to be able to provide you with a quality product that incorporates the latest engineering concepts and is a result of over 50 years of experience in the foodservice kitchen exhaust industry .
If you have other Gaylord equipment such as a Gaylord Utility Distribution System, Quencher Fire Protection System, or Roof Top Air Handling Equipment, etc., please refer to the corresponding supplementary equip- ment manuals.
If you have further questions, please call us toll free at 1-800-547-9696. We are more than happy to help.
Sincerely ,
Gaylord Industries, Inc.
PHONE: 503-691-2010 • 800-547-9696 • FAX: 503-692-6048 • email: gaylord@gaylordusa.com • www.gaylordusa.com
COMMERCIAL KITCHEN EXHAUST SYSTEMS • FIRE PROTECTION • UTILITY DISTRIBUTION • ROOF TOP UNITS • POLLUTION CONTROL
STREET ADDRESS: 10900 S.W. Avery Street, T ualatin, Oregon 97062-8549 U.S.A.
T ABLE OF CONTENTS
OPERATION .......................................................................................................... 1
STANDARD MODELS ........................................................................................... 2
MAINTENANCE AND CLEANING INSTRUCTIONS ............................................ 3
TROUBLESHOOTING ........................................................................................... 3
MEASURING INLET SLOT VELOCITY ................................................................. 5
WIRING DIAGRAMS.............................................................................................. 7
PARTS LIST........................................................................................................... 8
WARRANTY
P ATENT NUMBERS
U.S.A.: 4,266,529
4,281,635 4,356,870
CANADA: 1,139,151
1,155,366
GERMANY: 8,034,240
ALL RIGHTS RESERVED. NO PART OF THIS BOOK MAY BE REPRODUCED, ST ORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM BY AN ELECTRIC, ME­CHANICAL, PHOTOCOPYING, RECORDING MEANS OR OTHERWISE WITHOUT PRIOR WRITTEN PERMISSION OF GAYLORD INTERNATIONAL, INC. COPYRIGHT
1999.
© Copyright 1999, Gaylord Industries, Inc.
The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials.
ADDITIONAL COPIES $10.00
OPERATION
The Gaylord “GX” Series Non Water-Wash Ventila­tor offers simplicity, economy and performance that no other ventilator can offer. The unique “extractor insert” gives a grease extraction efficiency far su­perior to that of a typical mesh or extractor filter. The Gaylord “GX” Series Ventilators are UL Listed and meet all the requirements of NFPA #96.
FAN OPERA TION
To operate the exhaust fan, push the “start” or “stop” button on the Gaylord exhaust fan switch.
GREASE EXTRACTION
The Gaylord “GX” Series Ventilator extracts 90% of the grease, dust, and lint particles from the air­stream passing through it. Grease extraction is accomplished by a unique, removable stainless steel “extractor insert” which incorporates a series of horizontal baffles. As the air moves through the ventilator at high speed, it is forced to make a series of turns around these baffles, forcing the heavier-than-air particles of grease, dust, and lint to be thrown out of the airstream by centrifugal force. The liquefied grease then drains off into a grease cup. The extractor inserts are available in two sizes: 151/2" (5 3/4 lbs.) and 191/2" (6 3/4 lbs.). IMPORTANT NOTE: Never operated ventilator without extractor inserts in place.
CLEANING
At the end of the cooking day, or at periodic inter- vals, the inserts are removed and can be washed either in a dishwasher or soaked and rinsed off. To ease in the removal of the extractor inserts, an “Extractor Removcal Tool” is available which eliminates the need for kitchen personnel to climb up on the cooking equipment.
DUCT TAKE-OFF COLLAR
TRANSITION AREA
BAFFLES
GREASE GUTTER
GREASE CUP
280° F FUSE LINK LIGHT FIXTURE
GREASE EXTRACTION
INLET SLOT EXTRACTOR
INSERT SURFACE FIRE
PROTECTION NOZZLE
EXTRACTOR INSERT
FIRE PROTECTION
NFPA #96 requires the use of surface, duct and plenum protection on all non water-wash hoods. It is these systems that are the first line of defense against equipment fires. If the surface system fails to extinguish the fire, the ventilator's internal fire protection system then acts as a back-up.
This is accomplished by a spring loaded fire damper which is activated by a 280° F fusible link or ther- mostat located at the duct collar. In the event of a fire, should the detection device reach 280° F, the damper would close preventing the flames from entering the duckwork and spreading to other parts of the building. The fire is contained in the kitchen area where it can be properly fought.
Surface, duct collar and plenum fire protection uti- lizing The Gaylord Quencher System or other fire protection systems currently on the market can be factory installed as an option.
EXHAUST FAN
ST ART/STOP SWITCH
Model C-250
FIRE DAMPER IN CLOSED POSITION
PLENUM FIRE PROTECTION NOZZLE
CLEANING
EXHAUST DUCT COLLAR FIRE PROTECTION NOZZLE
MELTED280° FFUSE LINK
SURFACE FIRE PROTECTION NOZZLE
FIRE PROTECTION
EXTRACTOR REMOVAL TOOL
FIGURE 1
1
ST ANDARD MODELS
MODEL “GX-AB”
APPLICATION - Backshelf style for all
types of counter height equipment.
MODEL “GX-BDL-O”
APPLICATION - Eyebrow canopy style for
direct mounting to all types of ovens such
as roast, bake, and reel types.
The make-up air options shown below are available on all BDL Series Ventilators.
MODEL “GX-CE”
APPLICATION - Pass-over style for all
types of counter height equipment.
MODEL “GX-BDL-DS-CL”
APPLICATION - Used for cafeteria lines or
any other single line island arrangement.
FIGURE 2
STANDARD MAKE-UP AIR OPTIONS
FIRE DAMPER
APPLICATION - W all mounted canopy style
MODEL “GX-BDL”
for all types of equipment.
MODEL “GX-BDL-DS”
APPLICATION - Used for typical island
style cooking arrangement.
MODEL “MAW” SERIES
FRONT FACE DISCHARGE
This method of introducing make-up air into the kitchen is flexible and has many advantages. Make-up air is discharged through stainless steel perforated panels as illustrated (MAW Series) or optional registers. Typical supply volume is 80% of the exhaust or more, depending on air bal­ance desired. Supply air temperatures should range from 60 to 65°F (16 to 18°C), but may be as low as 50°F (10°C) depending on air volume, distribution, and internal heat load.
MODEL “MAP” SERIES
DOWN DISCHARGE This method of introducing air into the kitchen area is typically used when “spot cooling” of the kitchen staff is desired to help relieve the ef­fects of severe radiant heat generated from equipment such as charbroilers. Discharge ve­locities must be carefully engineered to avoid air turbulence at the cooking surface, discomfort to personnel and the cooling of foods. The amount of supply air introduced may be up to 80% of exhaust depending upon the type of cooking equipment involved, and the air temperature should be 65° F (18°C) or higher.
2
MODEL “MAI” SERIES
INTERNAL DISCHARGE This method of introducing air into the hood is typically referred to as the “short circuit” method. This design has very limited applications and the amount of supply air able to be introduced varies considerably with the type of cooking equip­ment. This air may be untempered air in most areas depending upon climatic conditions and the type of cooking equipment. The difference between the quantity of air being introduced and the amount of air being exhausted must be sup­plied through a traditional make-up air system.
MAINTENANCE AND CLEANING INSTRUCTIONS
CLEANING
At the end of each cooking day, the exposed interior surfaces of the ventilator should be wiped down and the grease cup emptied. During the course of operation, grease particles are gradually collecting inside the extractor inserts. Daily, or at periodic intervals, depending on the type of cooking, the extractor inserts must be removed and cleaned. To clean, proceed as follows:
1. Remove extractor inserts by hand or by using the extractor re­moval tool. CAUTION: Care should be taken when removing ex­tractors, especially over fryers. It is recommended that the cooking equipment be cooled down and the fryers be covered prior to re­moving extractors. To remove, lift up slightly on extractor insert and pull straight out.
2. Extractor inserts may be cleaned either by using a dishwasher or by washing in a sink using hot water and a degreasing detergent. Formula G-510 is highly recommended for this application. For information contact:
20/10 Products Inc.
P.O. Box 7609 Salem, Oregon 97303
3. With extractor inserts removed, wipe and clean the back wall and the grease gutter with hot detergent water. NOTE: If a steam or hot water pressure washer is used for periodic cleaning of the inte- rior, connect a hose to the gutter drain and lead it to a floor sink or large bucket to drain off water.
4. To replace the extractor inserts, care must be taken to insure that point A rests in the rear clip as illustrated at right.
Phone: 800-286-2010 Fax: 503-363-4296 email:twentyten@juno.com
INSPECTION AND CLEANING REQUIREMENTS
The 1998 edition of NFPA-96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations) require that hoods, ducts and exhaust fans be inspected by a properly trained, qualified and certified company or person(s) in accordance with the following table.
Upon inspection, if found to be contaminated with deposits from grease­laden vapors, the entire exhaust system shall be cleaned by a properly trained, qualified, and certified company or person(s) acceptable to the authority having jurisdiction in accordance.
When a vent cleaning service is used, a certificate showing date of inspection or cleaning shall be maintained on the premises. After clean­ing is completed, the vent cleaning contractor shall place or display within the kitchen area a label indicating the date cleaned and the name of the servicing company. It shall also indicate areas not cleaned.
ELUDEHCSNOITCEPSNIMETSYSTSUAHXE
snoitarepognikoocleufdilosgnivressmetsySylhtnoM
gnikoockowrogniliorbrahc,gnikoocruoh-42
sahcussnoitarepognikoocemulov-hgihgnivressmetsyS
snoitarepognikoocemulov-etaredomgnivressmetsyS yllaunnaimeS
sahcus,snoitarepognikoocemulov-wolgnivressmetsyS
roinesro,sessenisublanosaes,spmacyad,sehcruhc
sretnec
ylretrauQ
yllaunnA
5. If the ventilator(s) has a fuse link operated supply duct fire damper NFPA-96 requires inspection of the fuse link every 6 months and replacement annually.
FIGURE 3
TROUBLESHOOTING
POOR SMOKE CAPTURE
If the ventilator is not exhausting properly and smoke is escaping, first check the extractor inserts to make sure they are in place properly. If they are, the probable cause of smoke loss is a malfunctioning fan. The fan can be checked by taking air readings at the inlet slot. Refer to page 5 for proper method of taking air readings.
If the air velocity is low, check the following:
1. Broken or slipping fan belt.
2. Duct access panels left open.
3. Closed fire damper.
4. Proper exhaust fan size (exhaust fan must be capable of delivering specified CFM and static pressure).
5. Proper rotation of fan wheel.
NOTE: NEVER OPERATE THE VENTILATOR IF THE EXTRACTOR INSERTS ARE NOT IN PLACE.
FIGURE 4
CAUTION: Care should be taken when removing extractors,
especially over fryers. It is recommended that the cooking equipment be cooled down and the fryers be covered prior to removing extractors.
Poor smoke capture may also be caused by inadequately and/or improperly introduced make-up air. Make-up air must be supplied for replacement of air exhaust through all kitchen exhaust systems. Make­up air should be delivered through registers at ceiling height, and distrib­uted throughout the kitchen area. A general “rule of thumb” is that 75% to 80% of the replacement air should be fresh, conditioned (heated or cooled) air brought into the kitchen area, with the remaining 20% to 25% allowed to flow into the kitchen from adjacent areas. Smoke loss may also be caused by too much make-up air or make-up air being blown directly at the ventilator. Make-up air should not exceed 90% of exhaust air and should be introduced into the kitchen evenly and away from the ventilator.
3
TROUBLE SHOOTING
DUCT COLLAR
DAMPER CONTROL SWITCH MODEL C-61/GXB
ACCESSTO DAMPER AND FUSE LINK
ACCESSTO DAMPER CONTROL SWITCH AND DUCT COLLAR ACCESS
FUSE LINK ACTIVATED FIRE DAMPER
DUCT COLLAR
DAMPER CONTROL SWITCH COVER C-61/GXSH
ACCESSTO DAMPER AND THERMOSTAT
ACCESSTO DAMPER CONTROL SWITCH AND DUCT COLLAR ACCESS
THERMOSTATICALLY ACTIVATED FIRE DAMPER
RESET HANDLE
EXHAUST FAN WILL NOT COME ON
If the exhaust fan does not come on when the fan switch is flipped or start button is pushed, check the following:
1. Magnetic starter for exhaust fan - It is possible that the overload protectors within the magnetic starter switch may have actuated and stopped the fan. Push the “reset” button on the magnetic starter, and then restart the exhaust fan.
2. In the event that an H.O.A. (Hands Off/Automatic) type magnetic starter switch is used, check the selector switch to make sure it is in the automatic position.
3. Check exhaust fan motor circuit breaker and check fuses in disconnect switch normally located next to the fan.
4. Check 120 volt control power and 3 phase blower power at circuit breaker panel.
GREASE EXTRACTION
The Gaylord “GX” Series Ventilator extracts up to 90% of the grease, dust, and lint particles from the airstream passing through it, when operated and maintained in accordance with design specifications. If it appears that the ventilator is not extracting properly, check the inlet slot velocity as described on Page 5.
FUSE LINK OPERATED DAMPER
A spring loaded fire damper is standard equipment for all “GX” Series Ventilators. The damper is located at the duct collar and is activated by a 280°F (137°C) fuse link. The damper control switch, which contains the spring, is mounted at the side of the duct collar. In the event of a fire, and if the fuse link reaches 280°F (137°C) , the link will separate, the damper will close, and the exhaust fan will shut off. To resume normal operation, the fuse link must be replaced. Most codes require fuse links to be inspected semiannually and replaced annually. It is recommended that a professional service organization be contracted to perform this service. Normally this could be the same company that services the fire protection system. IMPORTANT NOTE: All replacement fuse links must be UL Listed and rated for 280°F (137°C).
ELECTRICALL Y OPERA TED FIRE DAMPER
An electrically operated damper is optional equipment. Ventilators equipped with this option are easily recognizable in that they have a reset handle with a red knob.
DAMPER CONTROL SWITCH
MODEL C-61 / GXSH
FIG. 6
The electric damper is controlled by a 280°F (137°C) thermostat mounted at the duct collar. In the event of a fire and if the thermostat reaches 280 °F (137°C), the fire damper will automatically close and the exhaust fan will shut off. To resume normal operation, the red knob must be reset until the damper latches open.
DAMPER CONTROL SWITCH
MODEL C-61/GXB
FIG. 5
FIG. 7
FIG. 8
4
SENSING HEAD
HEIGHT OF
INLET SLOT
INLET SLOT PLANE
LOWER LIP OF INLET PLANE
POSITION SENSING HEAD ON INLET SLOT PLANE
SENSING HEAD
HEIGHT OF
INLET SLOT
INLET SLOT PLANE
LOWER LIP OF INLET PLANE
POSITION SENSING HEAD
ON INLET SLOT PLANE CUSTOM AIR BAFFLE
LOWER LIP OF REAR INLET SLOT
PLACE BOTTOM OF SENSING HEAD EVEN WITH LOWER LIP OF INLET SLOT ANDTOP OF PROBE HEAD AGAINST BACKWALL OF VENTILATOR AS SHOWN
MEASURING INLET SLOT VELOCITY
MEASURING INLET SLOT VELOCITY
Smoke capture and grease extraction efficiency are dependent upon the proper air velocity at the inlet slot of the ventilator.
The required average slot velocities are shown on the “Air Velocity Chart” below . If the slot velocity is below the required average, the exhaust fan must be adjusted accordingly.
NOTE: The height of the inlet slot can vary depending upon the design of the ventilator. It is, therefore, important to first measure the inlet slot and compare it to the chart below to determine the required average inlet slot velocity. The designed CFM per lineal foot is related to the velocity as shown on the chart below. The total CFM for the ventilator can be found on the ventilator nameplate. (See Figure 12).
deriuqeR
egarevA
tolStelnI
yticoleV
motsuChtiW
selffaBriA
dengiseD repMFC
.tFlaeniL
deriuqeR
telnIegarevA
yticoleVtolS
tnorF
tolS
deriuqeR
egarevA
tolStelnI
yticoleV
)MPF(
raeR
tolS
AIR VELOCITY CHARTS
FOR ALL “GX” SERIES EXCEPT “GX-DS”
motsuCtuohtiW
lanimoN
thgieH
fo
tolStelnI
"30520001051006
0720801061A/N 5820411071A/N 0030021081027
"40040021042527
0540531072028 0745241082848 0050051003009
FOR “GX-DS” SERIES VENTILA TORS
latoT
htoB
stolS
003051051006086 0040520510001086 0050130910021068
Air velocity readings less than what is specified on the “Air Velocity Chart” may allow smoke and grease to escape the confines of the ventilator and/or reduce grease extraction efficiency. This can result in grease deposits which lead to sanitation problems or fire hazards if left uncorrected. If air velocity readings are higher than those specified, it will require more energy to operate the exhaust fan and exces­sive noise levels will result.
Higher or lower velocities than the required average will normally put the entire heating and ventilating system out of balance.
When measuring the air velocity it is very important to take an average reading across the inlet slot plane as illustrated in Figures 9A, B, or C, or Figure 10. Positioning the sensing head incorrectly will give velocity readings that cannot be compared to the “Air Velocity Chart”. The sensing heads shown in Figure 9 are of the design typically used on an­emometer type instruments.
tolS
selffaBriA
dengiseD repMFC
.tFlaeniL
dengiseD repMFC
.tFlaeniL
tnorF
)MPF(
raeR
tolS
FIGURE 9A
FIGURE 9B
FIGURE 9C
REAR SLOT OF MODEL “BDL-DS” SERIES
AND “BDL-DS-CL” SERIES
FIGURE 9A, B, & C
CROSS SECTION OF TYPICAL
VENTILA TOR INLET SLOT
5
INLET SLOT PLANE
AIRFLOW
LOWER LIP OF INLET PLANE
MEASURING INLET SLOT VELOCITY
PROBE HEAD
NOTE: IF A VELOMETER TYPE INSTRUMENT
THIRD READING
SECOND READING
FIRST READING
FIGURE 10
WITH PROBE HEAD IS USED, AS ILLUSTRATED AT LEFT, A MINIMUM OF THREE (3) READINGS MUST BE TAKEN ACCROSS THE INLET SLOT PLANE, AS SHOWN, AND THEN AVERAGED.
NOTE: THE VELOMETER PROBE HEAD SHOWN IS FROM A DWYER MODEL 460. WHEN THIS MODEL IS USED IT IS IMPORTANT THAT THE METER BASE BE HELD VERTICAL.
SENSING HEAD
APPROXIMATEL Y
EQUAL
LENGTH OF INLET SLOT
APPROXIMATEL Y
EQUAL
APPROX.6" IN FROM ENDS
FOR VENTILATORS UP TO 6'-0" LONG,TAKE A MINIMUM OFTWO (2) READINGS. FOR VENTILATORS LONGER THAN 6'-0",TAKE A MINIMUM OF THREE (3) VELOCITY READINGS AS ILLUSTRATED. IF DAMPER CONTROL SWITCH IS LOCATED IN THE CENTER, TAKE CENTER READING 6"TO EITHER SIDE OF THE CONTROL
1. MINIMUM TOTAL EXHAUST VOLUME FOR THIS HOOD SECTION
2. MAXIMUM TOTAL SUPPLY VOLUME FOR THIS HOOD SECTION
3. EXHAUST STATIC PRESSURE AT DUCT COLLAR
4. SUPPLY STATIC PRESSURE AT DUCT COLLAR
LISTED
U
370Y
L
®
EXHAUST HOOD WITH
EXHAUST DAMPER
THIS EXHAUST HOOD HAS BEEN TESTED TO STANDARD UL 710 "EXHAUST HOODS FOR COMMERCIAL COOKING EQUIPMENT"
THIS EXHAUST HOOD IS LISTED UNDER UL FILE NUMBER MH11403
THIS EXHAUST HOOD MEETS ALL REQUIREMENTS OF THE LATEST EDITION OF NFPA-96
PATENT NUMBERS: USA, 3,247,776; 3,611,909; 3,788,041; 4,072,143; 4,266,529; 4,281,635; 4,356,870; Australia, 481,510; 465,037; Canada, 744,166; 759,710; 926,689; 1,139,151; 968, 559; 940,761; 1,004,155; 1,086,126; France, 7,227,217; 7,332,718; 2,351,362; Germany, 2,346,196; 1,604, 173; 3, 152, 501Great Britain, 1,350,857; 1,396,065; 1,558,537; Japan, 650,269; 797,637; 917, 077; 1,045,507; 726,884; 1, 580, 556; New Zealand, 162,024; 167,964; Switzerland, 560,358; other U.S. and foreign patents pending.
WORLD HEADQUARTERS
GAYLORD INDUSTRIES, INC.
A SUBSIDIARY OF GAYLORD INTERNATIONAL, INC.
10900 S.W. AVERY STREET
TUALATIN, OR 97062-8549 USA
UL-GX/FX/SG-FD 996
5. THIS HOOD SECTION SUITABLE FOR APPLIANCES WITH MAXIMUM COOKING SURFACE TEMPERATURE OF:
6. REFER TO GAYLORD VENTILATOR TECHNICAL MANUAL FOR INLET VELOC- ITY REQUIREMENTS AND METHOD OF CHECKING VELOCITY
7. ELECTRICAL RATING OF LIGHT FIXTURES: 120 VOLT, 60 HZ. OR 220 VOLT, 50 HZ. OVERALL RATING - 12 AMPS OR LESS
8. ON "GX" SERIES VENTILATORS EQUIPPED WITH FUSE LINK OPERATED EXHAUST FIRE DAMPER USE ONLY 280° F (137° C), RATED 30 LBS. (13.6 kg.) MIN. UL LISTED FUSIBLE LINK FOR REPLACEMENT
9. ON "FX" AND "GX" SERIES VENTILATORS EQUIPPED WITH FUSE LINK OPER­ATED EXHAUST FIRE DAMPER USE ONLY 212° F (100° C), RATED 30 LBS. (13.6 kg.) MIN. UL LISTED FUSIBLE LINK FOR REPLACEMENT
10
.IF HOOD IS EQUIPPED WITH INTEGRAL MAKE-UP AIR WITH FUSE LINK OPERATED FIRE DAMPER USE ONLY 165° F (74° C), RATED 30 LBS. (13.6 kg.) MIN. UL LISTED FUSIBLE LINKS FOR REPLACEMENT
11.DUCTWORK AND EXHAUST FAN A. STATIC PRESSURE OF DUCT MUST BE ADDED TO VENTILATOR
B. ALL DUCTWORK MUST BE WELDED WATERTIGHT
HOOD MOUNTING REQUIREMENTS
MINIMUM DISTANCE FROM COOKING SURFACE TO FRONT LOWER EDGE OF HOOD
MAXIMUM DISTANCE FROM COOKING SURFACE TO FRONT LOWER EDGE OF HOOD
MINIMUM OVERHANG FROM FRONT OF HOOD CAVITY TO FRONT OF COOKING SURFACE
MAXIMUM SETBACK FROM FRONT OF HOOD CAVITY TO FRONT OF COOKING SURFACE
MINIMUM OVERHANG FROM SIDE OF HOOD TO EDGE OF COOKING SURFACE
SERIAL NO: GI­MODEL NO:
1. REMOVE, INSPECT AND CLEAN FILTERS ON "SG-FD" OR "CFX" SERIES OR GAYLORD EXTRACTOR INSERTS ON "GX" SERIES AS REQUIRED
2. REMOVE AND EMPTY GREASE CUP AS REQUIRED
3. CAUTION - DO NOT OPERATE VENTILATOR WITHOUT FILTERS OR EXTRAC­TORS IN PLACE
4. REPLACE FILTERS IN "SG" AND "FX" SERIES ONLY WITH UL CLASSIFIED GREASE FILTERS OR GAYLORD EXTRACTOR INSERTS IN "GX" SERIES
5. IF THE VENTILATOR(S) HAS A FUSE LINK OPERATED EXHAUST OR SUPPLY DUCT FIRE DAMPER THE NATIONAL FIRE PROTECTION ASSOCIATION'S PAMPHLET NFPA-96 REQUIRES INSPECTION OF THE FUSE LINK EVERY 6 MONTHS AND REPLACED ANNUALLY. REFER TO THE GAYLORD VENTILATOR TECHNICAL MANUAL FOR DETAILS.
°F FOR LINEAL FT. OF HOOD
°F FOR LINEAL FT. OF HOOD
STATIC FOR TOTAL SYSTEM STATIC
MAINTENANCE INSTRUCTIONS
FIGURE 11
ENGINEERING DATA
C.F.M.
C.F.M.
W.G.
W.G.
TOTAL CFM HERE
FIGURE 12
The total required exhaust volume can be found stamped on the UL nameplate located on each hood section.
6
DAMPER FIRE SWITCH LOCATED AT EACH EXHAUST DUCT COLLAR
ALL EXTERNAL CONTROL WIRING SHALL BE 12 GA. MIN.OR AS PER APPLICABLE CODES.
FIELD WIRING BY OTHERS WIRING BY GAYLORD MFG.
WIRING DIAGRAMS
C-250 FAN ON/OFF SW.FURNISHED BY GAYLORD MFG., INSTALLED BY ELECTRICAL CONTRACTOR
L1 L2 L3
FIELD J-BOX
L1 L2
H
120 OR 220 VOLT
N
SERVICE
STANDARD WIRING DIAGRAM
FOR “GX” SERIES VENTILAT ORS
WITH FUSE LINK ACTIV A TED FIRE DAMPER
T1
T 2
EXHAUST FAN ELECTRICAL SERVICE FOR EXHAUST FAN 120, 220, OR 440V.
MAG.STARTER SWITCH WITH 120 VOLT HOLDING COIL (BY OTHERS)
T3
EXHAUST FAN MOTOR BY OTHERS
DAMPER CONTROL SWITCH MODEL C-61 GXS SERIES
DAMPER COIL TO MATCH SUPPLY
BLOWER SW.
VOLTAGE
THERMOSTAT
WIRED IN PARALLEL
WIRED IN PARALLEL
WIRED IN SERIES
5 3 1 8 4
8 4 5 1
FIELD CONNECTION POINT J-BOXES FOR ELECTRICAL CONTRACTOR. WIRING FROM FIELD J-BOXESTO THERMOSTAT J-BOXES IS DONE BY FACTORYWITH HIGH TEMP. WIRE.
ALL EXTERNAL CONTROL WIRING SHALL BE 12 GA. MIN. OR AS PER APPLICABLE CODES.
DAMPER CONTROL SWITCH MODEL C-61 GXS SERIES
DAMPER COIL TO MATCH
BLOWER SW.
SUPPLY VOLTAGE
THERMOSTAT J-BOX
LOCATED AT DUCT COLLAR
WIRED IN PARALLEL
53 184
8 4 5 1
FIELD WIRING BY OTHERS WIRING BY GAYLORD MFG.
C-250 FAN START/STOP SW. FURNISHED BY GAYLORD MFG., INSTALLED BY
THERMOSTAT
WIRED IN PARALLEL
THERMOSTAT J-BOX
LOCATED AT DUCT COLLAR
WIRED IN SERIES
8 4 5 1
L1 L2 MAIN ELECTRICAL SERVICE TO BE FUSED SEPERATELY.
120 OR 220 VOLT
SERVICE
ELECTRICAL CONTRACTOR
FIELD J-BOX BY OTHER
STANDARD WIRING DIAGRAM
FOR “GX” SERIES VENTILA TORS
WITH THERMOSTATICALLY ACTIVATED DAMPER
WHEN C-250 ST ART/STOP SWITCH IS USED
L1 L2 L3
T1
T 2 T3
L1 L2 L3
T1
T 2 T3
ELECTRICAL SERVICE FOR EXHAUST FAN (BY OTHERS)
MAG.STARTER SWITCH WITH HOLDING COIL TO MATCH SUPPLYVOLTAGE (BY OTHERS)
EXHAUST FAN MOTOR BY OTHERS
ELECTRICAL SERVICE FOR SUPPLY FAN (BY OTHERS)
MAG.STARTER SWITCH WITH HOLDING COIL TO MATCH SUPPLYVOLTAGE (BY OTHERS)
SUPPLY FAN MOTOR BY OTHERS
7
Loading...