World Headquarters: P .O. Box 1149 • T ualatin, Oregon 97062-1149 U.S.A.
T o Our Customers. . .
Congratulations on your recent purchase of a Gaylord
kitchen exhaust hood system. We are proud to be able
to provide you with aquality product that incorporates
the latest engineering concepts and is a result of over
50 years of experience in the foodservice kitchen
exhaust industry.
If you have other Gaylord equipment such as a GaylordUtility Distribution System, Quencher Fire ProtectionSystem, or Roof Top Air Handling Equipment, etc.,please refer to the corresponding supplementary equip-ment manuals.
If you have further questions, please call us toll free at1-800-547-9696. We are more than happy to help.
PARTS LIST...........................................................................................................8
WARRANTY
PATENT NUMBERS
U.S.A.:4,266,529
4,281,6354,356,870
CANADA:1,139,151
1,155,366
GERMANY:8,034,240
ALL RIGHTS RESERVED. NO PART OFTHIS BOOK MAY BE REPRODUCED, ST ORED
IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM BY AN ELECTRIC, MECHANICAL, PHOTOCOPYING, RECORDING MEANS OR OTHERWISE WITHOUT
PRIOR WRITTEN PERMISSION OF GAYLORD INTERNATIONAL, INC. COPYRIGHT
The manufacturer reserves the right to modify the materials and
specifications resulting from a continuing program of product
improvement or the availability of new materials.
ADDITIONAL COPIES $10.00
OPERATION
The Gaylord “GX” Series Non Water-Wash Ventilator offers simplicity, economy and performance that
no other ventilator can offer. The unique “extractor
insert” gives a grease extraction efficiency far superior to that of a typical mesh or extractor filter.
The Gaylord “GX” Series Ventilators are UL Listed
and meet all the requirements of NFPA #96.
FAN OPERA TION
To operate the exhaust fan, push the “start” or
“stop” button on the Gaylord exhaust fan switch.
GREASE EXTRACTION
The Gaylord “GX” Series Ventilator extracts 90%
of the grease, dust, and lint particles from the airstream passing through it. Grease extraction is
accomplished by a unique, removable stainless steel
“extractor insert” which incorporates a series of
horizontal baffles. As the air moves through the
ventilator at high speed, it is forced to make a
series of turns around these baffles, forcing the
heavier-than-air particles of grease, dust, and lint
to be thrown out of the airstream by centrifugal
force. The liquefied grease then drains off into a
grease cup. The extractor inserts are available in
two sizes: 151/2" (5 3/4 lbs.) and 191/2" (6 3/4 lbs.).IMPORTANT NOTE: Never operated ventilator
without extractor inserts in place.
CLEANING
At the end of the cooking day, or at periodic inter-
vals, the inserts are removed and can be washed
either in a dishwasher or soaked and rinsed off.To
ease in the removal of the extractor inserts, an
“Extractor Removcal Tool” is available which
eliminates the need for kitchen personnel to climb
up on the cooking equipment.
DUCT TAKE-OFF
COLLAR
TRANSITION
AREA
BAFFLES
GREASEGUTTER
GREASE CUP
280° F FUSE LINK
LIGHT FIXTURE
GREASE EXTRACTION
INLET SLOTEXTRACTOR
INSERTSURFACE FIRE
PROTECTION NOZZLE
EXTRACTORINSERT
FIRE PROTECTION
NFPA #96 requires the use of surface, duct and
plenum protection on all non water-wash hoods. Itis these systems that are the first line of defenseagainst equipment fires. If the surface system failsto extinguish the fire, the ventilator's internal fireprotection system then acts as a back-up.
This is accomplished by a spring loaded fire damperwhich is activated by a 280° F fusible link or ther-
mostat located at the duct collar. In the event of a
fire, should the detection device reach 280° F, the
damper would close preventing the flames from
entering the duckwork and spreading to other parts
of the building. The fire is contained in the kitchen
area where it can be properly fought.
Surface, duct collar and plenum fire protection uti-
lizing The Gaylord Quencher System or other fire
protection systems currently on the market can be
factory installed as an option.
EXHAUST FAN
ST ART/STOP SWITCH
Model C-250
FIREDAMPERINCLOSEDPOSITION
PLENUMFIREPROTECTIONNOZZLE
CLEANING
EXHAUST DUCT COLLAR
FIRE PROTECTION NOZZLE
MELTED280° FFUSE LINK
SURFACE FIRE
PROTECTION NOZZLE
FIRE PROTECTION
EXTRACTOR
REMOVAL
TOOL
FIGURE 1
1
ST ANDARD MODELS
MODEL “GX-AB”
APPLICATION - Backshelf style for all
types of counter height equipment.
MODEL “GX-BDL-O”
APPLICATION - Eyebrow canopy style for
direct mounting to all types of ovens such
as roast, bake, and reel types.
The make-up air options shown below are available on all BDL Series Ventilators.
MODEL “GX-CE”
APPLICATION - Pass-over style for all
types of counter height equipment.
MODEL “GX-BDL-DS-CL”
APPLICATION - Used for cafeteria lines or
any other single line island arrangement.
FIGURE 2
STANDARD MAKE-UPAIR OPTIONS
FIRE DAMPER
APPLICATION - Wall mounted canopy style
MODEL “GX-BDL”
for all types of equipment.
MODEL“GX-BDL-DS”
APPLICATION - Used for typical island
style cooking arrangement.
MODEL “MAW” SERIES
FRONT FACE DISCHARGE
This method of introducing make-up air into the
kitchen is flexible and has many advantages.
Make-up air is discharged through stainless steel
perforated panels as illustrated (MAW Series) or
optional registers. Typical supply volume is 80%
of the exhaust or more, depending on air balance desired. Supply air temperatures should
range from 60 to 65°F (16 to 18°C), but may be
as low as 50°F (10°C) depending on air volume,
distribution, and internal heat load.
MODEL “MAP” SERIES
DOWN DISCHARGE
This method of introducing air into the kitchen
area is typically used when “spot cooling” of the
kitchen staff is desired to help relieve the effects of severe radiant heat generated from
equipment such as charbroilers. Discharge velocities must be carefully engineered to avoid air
turbulence at the cooking surface, discomfort to
personnel and the cooling of foods. The amount
of supply air introduced may be up to 80% of
exhaust depending upon the type of cooking
equipment involved, and the air temperature
should be 65° F (18°C) or higher.
2
MODEL “MAI” SERIES
INTERNAL DISCHARGE
This method of introducing air into the hood is
typically referred to as the “short circuit” method.
This design has very limited applications and the
amount of supply air able to be introduced varies
considerably with the type of cooking equipment. This air may be untempered air in most
areas depending upon climatic conditions and
the type of cooking equipment. The difference
between the quantity of air being introduced and
the amount of air being exhausted must be supplied through a traditional make-up air system.
MAINTENANCE AND CLEANING INSTRUCTIONS
CLEANING
At the end of each cooking day, the exposed interior surfaces of the
ventilator should be wiped down and the grease cup emptied. During
the course of operation, grease particles are gradually collecting inside
the extractor inserts. Daily, or at periodic intervals, depending on the
type of cooking, the extractor inserts must be removed and cleaned. To
clean, proceed as follows:
1. Remove extractor inserts by hand or by using the extractor removal tool. CAUTION: Care should be taken when removing extractors, especially over fryers. It is recommended that the cooking
equipment be cooled down and the fryers be covered prior to removing extractors. To remove, lift up slightly on extractor insert and
pull straight out.
2. Extractor inserts may be cleaned either by using a dishwasher or
by washing in a sink using hot water and a degreasing detergent.
Formula G-510 is highly recommended for this application. For
information contact:
20/10 Products Inc.
P.O. Box 7609
Salem, Oregon 97303
3. With extractor inserts removed, wipe and clean the back wall and
the grease gutter with hot detergent water. NOTE: If a steam or hot
water pressure washer is used for periodic cleaning of the inte-
rior, connect a hose to the gutter drain and lead it to a floor sink or
large bucket to drain off water.
4. To replace the extractor inserts, care must be taken to insure that
point A rests in the rear clip as illustrated at right.
The 1998 edition of NFPA-96 (Standard for Ventilation Control and Fire
Protection of Commercial Cooking Operations) require that hoods, ducts
and exhaust fans be inspected by a properly trained, qualified and
certified company or person(s) in accordance with the following table.
Upon inspection, if found to be contaminated with deposits from greaseladen vapors, the entire exhaust system shall be cleaned by a properly
trained, qualified, and certified company or person(s) acceptable to the
authority having jurisdiction in accordance.
When a vent cleaning service is used, a certificate showing date of
inspection or cleaning shall be maintained on the premises. After cleaning is completed, the vent cleaning contractor shall place or display
within the kitchen area a label indicating the date cleaned and the name
of the servicing company. It shall also indicate areas not cleaned.
5. If the ventilator(s) has a fuse link operated supply duct fire damper
NFPA-96 requires inspection of the fuse link every 6 months and
replacement annually.
FIGURE 3
TROUBLESHOOTING
POOR SMOKE CAPTURE
If the ventilator is not exhausting properly and smoke is escaping, first
check the extractor inserts to make sure they are in place properly. If
they are, the probable cause of smoke loss is a malfunctioning fan. The
fan can be checked by taking air readings at the inlet slot. Refer to page
5 for proper method of taking air readings.
If the air velocity is low, check the following:
1. Broken or slipping fan belt.
2. Duct access panels left open.
3. Closed fire damper.
4. Proper exhaust fan size (exhaust fan must be capable of
delivering specified CFM and static pressure).
5. Proper rotation of fan wheel.
NOTE: NEVER OPERATE
THE VENTILATOR IF THE
EXTRACTOR INSERTS
ARE NOT IN PLACE.
FIGURE 4
CAUTION: Care should be taken when removing extractors,
especially over fryers. It is recommended that the cooking
equipment be cooled down and the fryers be covered prior to
removing extractors.
Poor smoke capture may also be caused by inadequately and/or
improperly introduced make-up air. Make-up air must be supplied for
replacement of air exhaust through all kitchen exhaust systems. Makeup air should be delivered through registers at ceiling height, and distributed throughout the kitchen area. A general “rule of thumb” is that 75% to
80% of the replacement air should be fresh, conditioned (heated or cooled)
air brought into the kitchen area, with the remaining 20% to 25% allowed
to flow into the kitchen from adjacent areas. Smoke loss may also be
caused by too much make-up air or make-up air being blown directly at
the ventilator. Make-up air should not exceed 90% of exhaust air and
should be introduced into the kitchen evenly and away from the ventilator.
3
TROUBLE SHOOTING
DUCT COLLAR
DAMPER CONTROLSWITCH MODELC-61/GXB
ACCESSTO DAMPER
AND FUSE LINK
ACCESSTO DAMPER
CONTROL SWITCH
AND DUCT COLLAR
ACCESS
FUSE LINK ACTIVATED
FIRE DAMPER
DUCT COLLAR
DAMPER CONTROL
SWITCH COVER
C-61/GXSH
ACCESSTO DAMPER
AND THERMOSTAT
ACCESSTO DAMPER
CONTROL SWITCH
AND DUCT COLLAR
ACCESS
THERMOSTATICALLY ACTIVATED
FIRE DAMPER
RESET HANDLE
EXHAUST FAN WILL NOT COME ON
If the exhaust fan does not come on when the fan switch is flipped or
start button is pushed, check the following:
1. Magnetic starter for exhaust fan - It is possible that the overload
protectors within the magnetic starter switch may have actuated
and stopped the fan. Push the “reset” button on the magnetic
starter, and then restart the exhaust fan.
2. In the event that an H.O.A. (Hands Off/Automatic) type magnetic
starter switch is used, check the selector switch to make sure it
is in the automatic position.
3. Check exhaust fan motor circuit breaker and check fuses in
disconnect switch normally located next to the fan.
4. Check 120 volt control power and 3 phase blower power at
circuit breaker panel.
GREASE EXTRACTION
The Gaylord “GX” Series Ventilator extracts up to 90% of the grease,
dust, and lint particles from the airstream passing through it, when
operated and maintained in accordance with design specifications. If it
appears that the ventilator is not extracting properly, check the inlet slot
velocity as described on Page 5.
FUSE LINK OPERATED DAMPER
A spring loaded fire damper is standard equipment for all “GX” Series
Ventilators. The damper is located at the duct collar and is activated by
a 280°F (137°C) fuse link. The damper control switch, which contains
the spring, is mounted at the side of the duct collar. In the event of a fire,
and if the fuse link reaches 280°F (137°C) , the link will separate, the
damper will close, and the exhaust fan will shut off. To resume normal
operation, the fuse link must be replaced. Most codes require fuse links
to be inspected semiannually and replaced annually. It is recommended
that a professional service organization be contracted to perform this
service. Normally this could be the same company that services the
fire protection system. IMPORTANT NOTE: All replacement fuse links
must be UL Listed and rated for 280°F (137°C).
ELECTRICALL Y OPERA TED FIRE DAMPER
An electrically operated damper is optional equipment. Ventilators
equipped with this option are easily recognizable in that they have a
reset handle with a red knob.
DAMPER CONTROL SWITCH
MODEL C-61 / GXSH
FIG. 6
The electric damper is controlled by a 280°F (137°C) thermostat mounted
at the duct collar. In the event of a fire and if the thermostat reaches
280 °F (137°C), the fire damper will automatically close and the exhaust
fan will shut off. To resume normal operation, the red knob must be
reset until the damper latches open.
DAMPER CONTROL SWITCH
MODEL C-61/GXB
FIG. 5
FIG. 7
FIG. 8
4
SENSING HEAD
HEIGHT OF
INLET SLOT
INLET SLOT PLANE
LOWER LIP OFINLET PLANE
POSITION SENSING HEAD
ON INLET SLOT PLANE
SENSING HEAD
HEIGHT OF
INLET SLOT
INLET SLOT PLANE
LOWER LIP OFINLET PLANE
POSITION SENSING HEAD
ON INLET SLOT PLANE
CUSTOM AIRBAFFLE
LOWER LIP OF
REAR INLET SLOT
PLACE BOTTOM OF SENSING HEAD
EVEN WITH LOWER LIP OF INLET
SLOT ANDTOP OF PROBE HEAD
AGAINST BACKWALL OF VENTILATOR
AS SHOWN
MEASURING INLET SLOT VELOCITY
MEASURING INLET SLOT VELOCITY
Smoke capture and grease extraction efficiency are
dependent upon the proper air velocity at the inlet slot of the
ventilator.
The required average slot velocities are shown on the “Air
Velocity Chart” below . If the slot velocity is below the required
average, the exhaust fan must be adjusted accordingly.
NOTE: The height of the inlet slot can vary depending upon
the design of the ventilator. It is, therefore, important to first
measure the inlet slot and compare it to the chart below to
determine the required average inlet slot velocity. The
designed CFM per lineal foot is related to the velocity as
shown on the chart below. The total CFM for the ventilator
can be found on the ventilator nameplate. (See Figure 12).
deriuqeR
egarevA
tolStelnI
yticoleV
motsuChtiW
selffaBriA
dengiseD
repMFC
.tFlaeniL
deriuqeR
telnIegarevA
yticoleVtolS
tnorF
tolS
deriuqeR
egarevA
tolStelnI
yticoleV
)MPF(
raeR
tolS
AIR VELOCITY CHARTS
FOR ALL “GX” SERIES EXCEPT “GX-DS”
motsuCtuohtiW
lanimoN
thgieH
fo
tolStelnI
"30520001051006
0720801061A/N
5820411071A/N
0030021081027
"40040021042527
054053107202807452410828480050051003009
FOR “GX-DS” SERIES VENTILATORS
latoT
htoB
stolS
00305105100608600405205100010860050130910021068
Air velocity readings less than what is specified on the “Air
Velocity Chart” may allow smoke and grease to escape the
confines of the ventilator and/or reduce grease extraction
efficiency. This can result in grease deposits which lead to
sanitation problems or fire hazards if left uncorrected. If air
velocity readings are higher than those specified, it will
require more energy to operate the exhaust fan and excessive noise levels will result.
Higher or lower velocities than the required average will
normally put the entire heating and ventilating system out of
balance.
When measuring the air velocity it is very important to take an
average reading across the inlet slot plane as illustrated in
Figures 9A, B, or C, or Figure 10. Positioning the sensing
head incorrectly will give velocity readings that cannot be
compared to the “Air Velocity Chart”. The sensing heads
shown in Figure 9 are of the design typically used on anemometer type instruments.
tolS
selffaBriA
dengiseD
repMFC
.tFlaeniL
dengiseDrepMFC
.tFlaeniL
tnorF
)MPF(
raeR
tolS
FIGURE 9A
FIGURE 9B
FIGURE 9C
REAR SLOT OF MODEL “BDL-DS” SERIES
AND “BDL-DS-CL” SERIES
FIGURE 9A, B, & C
CROSS SECTION OF TYPICAL
VENTILA TOR INLET SLOT
5
INLET SLOT PLANE
AIRFLOW
LOWER LIP OF
INLET PLANE
MEASURING INLET SLOT VELOCITY
PROBE HEAD
NOTE: IF A VELOMETER TYPE INSTRUMENT
THIRD READING
SECOND READING
FIRST READING
FIGURE 10
WITH PROBE HEAD IS USED, AS ILLUSTRATED AT
LEFT, A MINIMUM OF THREE (3) READINGS MUST BE
TAKEN ACCROSS THE INLET SLOT PLANE, AS
SHOWN, AND THEN AVERAGED.
NOTE: THE VELOMETER PROBE HEAD SHOWN ISFROM A DWYER MODEL 460. WHEN THIS MODEL IS
USED IT IS IMPORTANTTHATTHE METER BASE BE
HELD VERTICAL.
SENSING HEAD
APPROXIMATELY
EQUAL
LENGTH OF INLET SLOT
APPROXIMATELY
EQUAL
APPROX.6"IN FROM ENDS
FORVENTILATORS UPTO 6'-0" LONG,TAKE A MINIMUM OFTWO (2) READINGS.FORVENTILATORS
LONGERTHAN 6'-0",TAKE A MINIMUM OFTHREE (3)VELOCITY READINGS AS ILLUSTRATED.IF DAMPER CONTROL SWITCH IS LOCATED INTHE CENTER,TAKE CENTER READING 6"TOEITHER SIDE OFTHE CONTROL
1.MINIMUM TOTAL EXHAUSTVOLUME FOR THIS HOOD SECTION
2.MAXIMUM TOTAL SUPPLYVOLUME FOR THIS HOOD SECTION
3.EXHAUST STATIC PRESSURE ATDUCT COLLAR
4.SUPPLY STATIC PRESSURE ATDUCT COLLAR
LISTED
U
370Y
L
®
EXHAUST HOOD WITH
EXHAUST DAMPER
THIS EXHAUST HOOD HAS BEEN TESTEDTO STANDARD UL 710 "EXHAUST HOODSFOR COMMERCIAL COOKINGEQUIPMENT"
THIS EXHAUST HOOD IS LISTED UNDERUL FILE NUMBER MH11403
THIS EXHAUST HOOD MEETS ALLREQUIREMENTS OF THE LATESTEDITION OF NFPA-96
5.THIS HOOD SECTION SUITABLE FOR APPLIANCES WITH MAXIMUM COOKINGSURFACE TEMPERATURE OF:
6.REFER TO GAYLORD VENTILATOR TECHNICAL MANUAL FOR INLET VELOC-ITY REQUIREMENTS AND METHOD OF CHECKING VELOCITY
7.ELECTRICAL RATING OF LIGHT FIXTURES: 120 VOLT, 60 HZ. OR 220 VOLT,50 HZ. OVERALL RATING - 12 AMPS OR LESS
8.ON "GX" SERIES VENTILATORS EQUIPPED WITH FUSE LINK OPERATED
EXHAUST FIRE DAMPER USE ONLY 280° F (137° C), RATED 30 LBS. (13.6 kg.)
MIN. UL LISTED FUSIBLE LINK FOR REPLACEMENT
9.ON "FX" AND "GX" SERIES VENTILATORS EQUIPPED WITH FUSE LINK OPERATED EXHAUST FIRE DAMPER USE ONLY 212° F (100° C), RATED 30 LBS. (13.6
kg.) MIN. UL LISTED FUSIBLE LINK FOR REPLACEMENT
10
.IF HOOD IS EQUIPPED WITH INTEGRAL MAKE-UP AIR WITH FUSE LINK
OPERATED FIRE DAMPER USE ONLY 165° F (74° C), RATED 30 LBS. (13.6 kg.)
MIN. UL LISTED FUSIBLE LINKS FOR REPLACEMENT
11.DUCTWORK AND EXHAUST FANA.STATIC PRESSURE OF DUCT MUST BE ADDED TO VENTILATOR
B.ALL DUCTWORK MUST BE WELDED WATERTIGHT
HOOD MOUNTING REQUIREMENTS
MINIMUM DISTANCE FROM COOKING SURFACE TO FRONT
LOWER EDGE OF HOOD
MAXIMUM DISTANCE FROM COOKING SURFACE TO FRONT
LOWER EDGE OF HOOD
MINIMUM OVERHANG FROM FRONT OF HOOD CAVITY TO
FRONT OF COOKING SURFACE
MAXIMUM SETBACK FROM FRONT OF HOOD CAVITY TO
FRONT OF COOKING SURFACE
MINIMUM OVERHANG FROM SIDE OF HOOD TO EDGE OF
COOKING SURFACE
SERIAL NO: GIMODEL NO:
1. REMOVE, INSPECT AND CLEAN FILTERS ON "SG-FD" OR "CFX" SERIES OR
GAYLORD EXTRACTOR INSERTS ON "GX" SERIES AS REQUIRED
2. REMOVE AND EMPTY GREASE CUP AS REQUIRED
3. CAUTION - DO NOT OPERATE VENTILATOR WITHOUT FILTERS OR EXTRACTORS IN PLACE
4. REPLACE FILTERS IN "SG" AND "FX" SERIES ONLY WITH UL CLASSIFIED
GREASE FILTERS OR GAYLORD EXTRACTOR INSERTS IN "GX" SERIES
5. IF THE VENTILATOR(S) HAS A FUSE LINK OPERATED EXHAUST OR SUPPLY
DUCT FIRE DAMPER THE NATIONAL FIRE PROTECTION ASSOCIATION'S
PAMPHLET NFPA-96 REQUIRES INSPECTION OF THE FUSE LINK EVERY 6
MONTHS AND REPLACED ANNUALLY. REFER TO THE GAYLORD
VENTILATOR TECHNICAL MANUAL FOR DETAILS.
°F FORLINEAL FT. OF HOOD
°F FORLINEAL FT. OF HOOD
STATIC FOR TOTAL SYSTEM STATIC
MAINTENANCE INSTRUCTIONS
FIGURE 11
ENGINEERING DATA
C.F.M.
C.F.M.
W.G.
W.G.
TOTAL CFM HERE
FIGURE 12
The total required exhaust volume can be
found stamped on the UL nameplate located
on each hood section.
6
DAMPER FIRE SWITCH LOCATED
AT EACH EXHAUST DUCT COLLAR
ALL EXTERNAL CONTROL WIRING
SHALL BE 12 GA. MIN.OR AS
PER APPLICABLE CODES.
FIELD WIRING BY OTHERS
WIRING BY GAYLORD MFG.
WIRING DIAGRAMS
C-250 FAN ON/OFF SW.FURNISHED
BY GAYLORD MFG., INSTALLED BY
ELECTRICAL CONTRACTOR
L1 L2 L3
FIELD J-BOX
L1 L2
H
120 OR 220VOLT
N
SERVICE
STANDARD WIRING DIAGRAM
FOR “GX” SERIES VENTILATORS
WITH FUSE LINK ACTIVATED FIRE DAMPER
T1
T 2
EXHAUST FAN ELECTRICAL
SERVICE FOR EXHAUST
FAN 120, 220, OR 440V.
MAG.STARTER SWITCH
WITH 120 VOLT HOLDING
COIL (BY OTHERS)
T3
EXHAUST FAN MOTOR
BY OTHERS
DAMPER CONTROL SWITCH
MODEL C-61 GXS SERIES
DAMPER COIL
TO MATCH
SUPPLY
BLOWER SW.
VOLTAGE
THERMOSTAT
WIRED IN PARALLEL
WIRED IN PARALLEL
WIRED IN SERIES
5 3 1 8 4
8451
FIELD CONNECTION POINT J-BOXES
FOR ELECTRICAL CONTRACTOR.
WIRING FROM FIELD J-BOXESTO
THERMOSTAT J-BOXES IS DONE BY
FACTORYWITH HIGHTEMP.WIRE.
ALL EXTERNAL CONTROLWIRING
SHALL BE 12 GA. MIN. OR AS
PER APPLICABLE CODES.
DAMPER CONTROL SWITCHMODEL C-61 GXS SERIES
DAMPER COILTO MATCH
BLOWER SW.
SUPPLYVOLTAGE
THERMOSTAT J-BOX
LOCATED AT DUCT COLLAR
WIRED IN PARALLEL
53184
8451
FIELD WIRING BY OTHERS
WIRING BY GAYLORD MFG.
C-250 FAN START/STOP SW.FURNISHEDBY GAYLORD MFG., INSTALLED BY
THERMOSTAT
WIRED IN PARALLEL
THERMOSTAT J-BOX
LOCATED AT DUCT COLLAR
WIRED IN SERIES
8451
L1 L2
MAIN ELECTRICAL SERVICE
TO BE FUSED SEPERATELY.
120 OR 220 VOLT
SERVICE
ELECTRICAL CONTRACTOR
FIELD J-BOXBY OTHER
STANDARD WIRING DIAGRAM
FOR “GX” SERIES VENTILA TORS
WITH THERMOSTATICALLY ACTIVATED DAMPER
WHEN C-250 ST ART/STOP SWITCH IS USED
L1 L2 L3
T1
T 2 T3
L1 L2 L3
T1
T 2 T3
ELECTRICAL SERVICE
FOR EXHAUST
FAN (BY OTHERS)
MAG.STARTER SWITCH
WITH HOLDING COIL
TO MATCH SUPPLYVOLTAGE
(BY OTHERS)
EXHAUST FAN MOTOR
BY OTHERS
ELECTRICAL SERVICE
FOR SUPPLY
FAN (BY OTHERS)
MAG.STARTER SWITCH
WITH HOLDING COIL
TO MATCH SUPPLYVOLTAGE
(BY OTHERS)
SUPPLY FAN MOTOR
BY OTHERS
7
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.