Gaylord GX2-UV-BDL-BB-MA Specifications

Ultima VentTM with UV Technology
MODEL “GX2-UV-BDL-BB-MA”
CARTRIDGE EXTRACTOR VENTILATOR WITH UV
GENERAL SPECIFICATIONS
Furnish Gaylord Ventilator Model “GX2-UV-___-BDL-BB-MA____________” as shown on plans and in accordance with the following specifications:
GENERAL: Ventilator shall incorporate two extraction chambers mounted back-to-back each with an air inlet opening above and parallel to the cooking surface. Each extraction chamber shall contain one or more removable “extractor inserts” with a grease extraction efficiency of 90% of the mechani­cally extractable grease particulate. The extractor insert shall include a built-in particulate separator creating one integral extractor unit to remove for cleaning. Each extractor includes a Gaylord Extractor Monitor ("GEM") to ensure that all cartridges are in place before the UV lamps can operate. It shall also include ultraviolet lamps to remove a majority of the remaining particulate for a total grease extraction efficiency of up to 99% when operated and maintained in accordance with the Gaylord Technical Manual and design specificiations. Extractor inserts shall be constructed of stainless steel and contain full-length, self-draining baffles. Extractors shall be easily removable, for periodic cleaning, from the floor area immediately in front of the equipment by utilizing an extractor removal tool. The grease collecting gutter at the bottom of the extractor housing shall slope to a drain at one end of the ventilator to a removable stainless steel grease cup. The sloped gutter shall be concealed by an apron which extends the full length of the hood. The Ventilator shall include a "Super Capture"TM lip on the front panel for enhancement of smoke and grease capture. Continuous brackets shall be provided to facilitate hanging from the overhead building structure.
(Optional) The ventilator shall include “Custom Air” baffles to reduce the exhaust volume over specific cooking equipment as indicated on the plans (add suffix “CA” to model number). The ventilator shall operate at air quantities and static pressure as indicated on plans.
Fuse Link Activated Fire Damper Option (series prefix “GX2-UV­FDD”) The damper shall be activated by fuse link(s) located at the duct
collar. The ventilator shall be UL listed under the category “Exhaust Hood with Exhaust Damper”.
Ventilator without Fire Damper Option - (series prefix “GX2-UV­ND”) The ventilator shall be UL listed under the category “Exhaust Hood
without Exhaust Damper”.
MAKE-UP AIR OPTIONS: The ventilator shall have an air supply plenum, with duct collar(s) and:
Incorporate registers for front face discharge make-up air. (Add suffix “MAR” to the model number.)
Incorporate stainless steel perforated panels for front face discharge make-up air. (Add suffix “MAW” to the model number.)
ULTRAVIOLET LIGHT SECTION: The ventilator shall include ultraviolet lamps mounted in modules located in the plenum section. There shall be one or more UV modules, as dictated by the ventilator length, and each module shall be on a slide track for easy removal. Access to the modules shall be through keyed hinged doors, and shall include an interlock switch to shut off the lamps in the event the doors are opened during operation. A pressure switch shall be provided to monitor the airflow to prevent operation of the lamps when the airflow is inadequate. A Gaylord Extractor Monitor (“GEM”) shall be provided to shut off the lamps when a cartridge is removed. Mounted on the face of the plenum of each ventilator section shall be indicator lights to monitor “UV System On”, “UV Lamp Failure” and “UV Safety Interlock Activated”. A duplicate set of these lights shall be mounted on the ventilator control cabinet, Model CUV-100. The control panel shall be equipped with an audible alarm indicating there is a lamp failure or one of the safety interlock switches has been activated.
ITEM NO. _______________
APPLICATION
Used for typical island style cooking arrangements where me­dium, heavy, and extra heavy-duty cooking equipment is used on both sides or when the distance between the equipment exceeds 30" regardless of the type of equipment. Refer to the Master Engineering Data Sheet in the Engineering Section of the Gaylord catalog for determining medium, heavy, and extra heavy-duty equipment. Includes built-in make-up front face air discharge.
CONSTRUCTION: The ventilator shall be of all stainless steel con­struction, not less than 18 gauge, type 300 series. All exposed surfaces shall be a number 4 finish. The use of aluminized steel, galvanized steel, or 430 stainless steel is not acceptable.
ELECTRICAL: The ventilator shall be factory pre-wired to single connection points. On multiple section ventilators power for the UV lamps must be supplied to each section. Wiring for controls and light fixtures shall be furnished with coiled flex conduit for interconnecting sections by applicable trades.
LIGHT FIXTURES: The ventilator shall be equipped with 100 watt surface mounted incandescent, ❏ 150 watt recessed incandescent, recessed fluorescent, light fixtures. Light fixtures shall be factory pre-wired to a single connection point. Ventilators built in multiple sections shall be furnished with coiled flex conduit for interconnecting sections.
ACCEPTANCE & APPROVALS: The ventilator shall be UL, CUL and NSF listed. The ventilator shall comply with all requirements of NFPA­96, IMC, UMC, BOCA and SBCCI model codes.
Patent Pending
GAYLORD INDUSTRIES
10900 SW AVERY ST., TUALATIN, OREGON 97062 U.S.A.
PHONE: 800-547-9696 • FAX: 503-692-6048 • email: info@gaylordusa.com
www.gaylordusa.com
Ultima VentTM with UV Technology
ALL STAINLES STEEL
UV STATUS LIGHTS
AUDIBLE ALARM CANCEL BUTTON
HOUR METER
MODEL “GX2-UV-___-BDL-___-BB-___-____”
**
DAMPER OPTION
FDD = Fuse link damper at the duct collar
**
LOW
PROFILE
(LP)
MA
OPTION
WIDTH
OF
VENTILATOR
ND = No damper
For supply air option add one of the following suffixes to the model number: o MAW o MAR Add the overall width of the ventilator after the make-up air designation. Example: “GX2-UV-ND-BDL-BB-MAW-108”
LOW PROFILE (LP) MINIMUM HEIGHT AT FRONT:
Light & Medium Duty Equipment (400°F) 18" Min. Heavy Duty Equipment (600°F) and Extra Heavy Duty Equip­ment (700°F) "LP" Not Available
If low profile add suffix “LP” after BDL.
34"
EXHAUST FAN/ SYSTEM ON/OFF SWITCH
7" DEEP
8"
CUV-100
CONTROL CABINET
ITEM NO. _____________________ EST. WT. ________________________
LENGTH _____________ WIDTH ______________ HEIGHT ______________
LIGHTS
qq
q
100W SURFACE INCANDESCENT
qq qq
q
150W RECESSED INCANDESCENT
qq q q
q
RECESSED FLUORESCENT
q q
The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials.
ENGINEERING DATA
Mechanical Requirements
The amount of exhaust volume required for each side of the cooking line is dependent upon the type of cooking equipment and the type and volume of cooking. Refer to the Master Engineering Data Sheet in the Gaylord catalog for charts on determining exhaust and supply volume, duct sizes, and static pressure.
Electrical
o Provide 120 volt 20 amp, o 220/240 volt, 50-60 Hz., 24 hour service to
Gaylord CUV-100 Control Cabinet (refer to illustration above). To be fused separately. Provide a separate 120 volt 20 amp service to each ventilator section to power UV lamps. Ventilator lights to be on separate circuit, 120 volt standard, 220/240 volt optional.
TYPICAL SECTION VIEW
Ventilator Lengths
Maximum unit length 16'-0". For greater lengths, join two or more sections together. Check to ensure that there is adequate access into building and kitchen area.
*
Note: Ventilators manufactured outside North America; maximum unit length
10'-0".
Hanging Weight
Ventilator Width 9'-0" 10'-0" 11'-0" 12'-0"
Wt. / lineal ft. lbs. 240 250 260 270
Form No. GX2-UV-BDL-BB-MA 706-30816 © Copyright 2006, Gaylord Industries Litho USA