Ultima VentTM with UV Technology
MODEL “GX2-UV-BDL-BB”
CARTRIDGE EXTRACTOR VENTILATOR WITH UV
GENERAL SPECIFICATIONS
Furnish Gaylord Ventilator Model “GX2-UV-___-BDL-BB____________” as
shown on plans and in accordance with the following specifications:
GENERAL: Ventilator shall incorporate two extraction chambers mounted
back-to-back each with an air inlet opening above and parallel to the cooking
surface. Each extraction chamber shall contain one or more removable
“extractor inserts” with a grease extraction efficiency of 90% of the mechanically extractable grease particulate. The extractor insert shall include a
built-in particulate separator creating one integral extractor unit to remove
for cleaning. Each extractor also includes a Gaylord Extractor Monitor
("GEM") to ensure that all cartridges are in place before the UV lamps can
operate. It shall also include ultraviolet lamps to remove a majority of the
remaining particulate for a total grease extraction efficiency of up to 99%
when operated and maintained in accordance with the Gaylord Technical
Manual and design specificiations. Extractor inserts shall be constructed
of stainless steel and contain full-length, self-draining baffles. Extractors
shall be easily removable, for periodic cleaning, from the floor area immediately
in front of the equipment by utilizing an extractor removal tool. The grease
collecting gutter at the bottom of the extractor housing shall slope to a drain at
one end of the ventilator to a removable stainless steel grease cup. The sloped
gutter shall be concealed by an apron which extends the full length of the hood.
The Ventilator shall include a "Super Capture"TM lip on the front panel for
enhancement of smoke and grease capture. Continuous brackets shall be
provided to facilitate hanging from the overhead building structure.
❏ (Optional) The ventilator shall include “Custom Air” baffles to reduce the
exhaust volume over specific cooking equipment as indicated on the plans
(add suffix “CA” to model number). The ventilator shall operate at air
quantities and static pressure as indicated on plans.
❏ Fuse Link Activated Fire Damper Option (series prefix “GX2-UVFDD”) The damper shall be activated by fuse link(s) located at the duct
collar. The ventilator shall be UL listed under the category “Exhaust Hood
with Exhaust Damper”.
❏ Ventilator without Fire Damper Option - (series prefix “GX2-UVND”) The ventilator shall be UL listed under the category “Exhaust Hood
without Exhaust Damper”.
ULTRAVIOLET LIGHT SECTION: The ventilator shall include ultraviolet
lamps mounted in modules located in the plenum section. There shall be
one or more UV modules, as dictated by the ventilator length, and each
module shall be on a slide track for easy removal. Access to the modules
shall be through keyed hinged doors, and shall include an interlock switch
to shut off the lamps in the event the doors are opened during operation.
A pressure switch shall be provided to monitor the airflow to prevent
operation of the lamps when the airflow is inadequate. A Gaylord Extractor
Monitor (“GEM”) shall be provided to shut off the lamps when a cartridge
is removed. Mounted on the face of the plenum of each ventilator section
shall be indicator lights to monitor “UV System On”, “UV Lamp Failure” and
“UV Safety Interlock Activated”. A duplicate set of these lights shall be
mounted on the ventilator control cabinet, Model CUV-100. The control
panel shall be equipped with an audible alarm indicating there is a lamp
failure or one of the safety interlock switches has been activated.
CONSTRUCTION: The ventilator shall be of all stainless steel construction,
not less than 18 gauge, type 300 series. All exposed surfaces shall be a
number 4 finish. The use of aluminized steel, galvanized steel, or 430
stainless steel is not acceptable.
ITEM NO. _______________
APPLICATION
Used for typical island style cooking arrangements where
medium, heavy, or extra heavy-duty equipment is used on both
sides or when the distance between the equipment exceeds 30"
regardless of the type of equipment. Refer to the Master
Engineering Data Sheet in the Gaylord catalog for determining
medium, heavy, and extra heavy-duty equipment.
ELECTRICAL: The ventilator shall be factory pre-wired to single connection points. On multiple section ventilators power for the UV lamps must be
supplied to each section. Wiring for controls and light fixtures shall be
furnished with coiled flex conduit for interconnecting sections by applicable trades.
LIGHT FIXTURES: The ventilator shall be equipped with ❏ 100 watt
surface mounted incandescent, ❏ 150 watt recessed incandescent, ❏
recessed fluorescent, light fixtures. Light fixtures shall be factory prewired to a single connection point. Ventilators built in multiple sections
shall be furnished with coiled flex conduit for interconnecting sections.
ACCEPTANCE & APPROVALS: The ventilator shall be UL, CUL and
NSF listed. The ventilator shall comply with all requirements of NFPA96, IMC, UMC, BOCA and SBCCI model codes.
Patent Pending
GAYLORD INDUSTRIES
10900 SW AVERY ST., TUALATIN, OREGON 97062 U.S.A.
PHONE: 800-547-9696 • FAX: 503-692-6048 • email: info@gaylordusa.com
www.gaylordusa.com
Ultima VentTM with UV Technology
ALL STAINLES STEEL
UV STATUS LIGHTS
AUDIBLE ALARM
CANCEL BUTTON
HOUR METER
MODEL “GX2-UV-_____-BDL-____-BB-____”
**
DAMPER OPTION
FDD = Fuse link damper at the duct collar
**
LOW
PROFILE
(LP)
DEPTH
OF
VENTILATOR
ND = No damper
For exact model designation add depth following the
letters “GX2-UV- -BDL-BB-”.
Example: “GX2-UV-ND-BDL-BB-108”
LOW PROFILE (LP) MINIMUM HEIGHT AT FRONT:
Light & Medium Duty Equipment (400°F) 12" Min.
Heavy Duty Equipment (600°F) 18" Min.
Extra Heavy Duty Equipment (700°F) "LP" Not Available
34"
EXHAUST FAN/
SYSTEM ON/OFF
SWITCH
7" DEEP
8"
CUV-100
CONTROL CABINET
ITEM NO. ______________________ EST. WT. _________________________
LENGTH _____________ WIDTH ______________ HEIGHT ______________
LIGHTS
qq
q
100W SURFACE INCANDESCENT
qq
qq
q
150W RECESSED INCANDESCENT
qq
q q
q
RECESSED FLUORESCENT
q q
The manufacturer reserves the right to modify the materials and specifications resulting
from a continuing program of product improvement or the availability of new materials.
ENGINEERING DATA
Mechanical Requirements
The amount of exhaust volume required is dependent upon the type of
cooking equipment and the type and volume of cooking. Refer to the Master
Engineering Data Sheet in the Engineering Data section of the Gaylord
catalog for the charts on determining exhaust volume, duct sizes, and static
pressure
Electrical
o Provide 120 volt 20 amp, o 220/240 volt, 50-60 Hz., 24 hour service to
Gaylord CUV-100 Control Cabinet (refer to illustration above). To be fused
separately. Provide a separate 120 volt 20 amp service to each ventilator
section to power UV lamps. Ventilator lights to be on separate circuit, 120
volt standard, 220/240 volt optional.
TYPICAL SECTION VIEW
Ventilator Lengths
Maximum unit length 16'-0". For greater lengths, join two or more sections
together. Check to ensure that there is adequate access into building and
kitchen area.
*
Note: Ventilators manufactured outside North America; maximum unit length
10'-0".
Hanging Weight
Ventilator Width 8'-0" 9'0" 10'-0" 11'-0"
Wt. / lineal ft. lbs. 210 220 230 240
Form No. GX2-UV-BDL-BB 706-30815 © Copyright 2006, Gaylord Industries Litho USA