Ultima VentTM with UV Technology
MODEL “GX2-UV-BDL”
CARTRIDGE EXTRACTOR VENTILATOR WITH UV
GENERAL SPECIFICATIONS
Furnish Gaylord Ventilator Model “GX2-UV-___-BDL-________” as
shown on plans and in accordance with the following specifications:
GENERAL: Each ventilator shall be a high velocity centrifugal grease
extractor with an air inlet opening parallel to, and above the cooking
equipment being ventilated. Each ventilator shall contain one or more
removable “extractor inserts” with a grease extraction efficiency of 90%
of the mechanically extractable grease particulate. The extractor insert
shall include a built-in particulate separator creating one integral extractor unit to remove for cleaning. Each extractor insert includes a Gaylord
Extractor Monitor ("GEM") to ensure that all cartridges are in place
before the UV lamps can operate. It shall also include ultraviolet lamps
to remove a majority of the remaining particulate for a total grease
extraction efficiency of up to 99% when operated and maintained in
accordance with the Gaylord Technical Manual and design specifications. Extractor inserts shall be constructed of stainless steel and
contain full-length, self-draining baffles. Extractors shall be easily
removable, for periodic cleaning, from the floor area immediately in front
of the equipment by utilizing an extractor removal tool. The grease
collecting gutter at the bottom of the extractor housing shall slope to a
drain at one end of the ventilator to a removable stainless steel grease
cup. The sloped gutter shall be concealed by an apron which extends
the full length of the hood. The Ventilator shall include a "Super Capture"
lip on the front panel for enhancement of smoke and grease capture. The
ventilator shall include a built-in 3" air space at the rear for compliance
to NFPA-96 when mounting against a limited combustible wall. Continuous front and rear brackets shall be provided to facilitate mounting to the
wall and hanging from the overhead building structure.
❏ (Optional) The ventilator shall include “Custom Air” baffles to reduce
the exhaust volume over specific cooking equipment as indicated on the
plans (add suffix “CA” to model number). The ventilator shall operate at
air quantities and static pressure as indicated on plans.
❏ Fuse Link Activated Fire Damper Option (series prefix “GX2-UVFDD”) The damper shall be activated by fuse link(s) located at the duct
collar. The ventilator shall be UL listed under the category “Exhaust
Hood with Exhaust Damper”.
❏ Ventilator without Fire Damper Option (series prefix “GX2-UVND”) The ventilator shall be UL listed under the category “Exhaust Hood
without Exhaust Damper”.
ULTRAVIOLET LIGHT SECTION: The ventilator shall include ultraviolet lamps mounted in modules located in the plenum section. There shall
be one or more UV modules, as dictated by the ventilator length, and
each module shall be on a slide track for easy removal. Access to the
modules shall be through keyed hinged doors, and shall include an
interlock switch to shut off the lamps in the event the doors are opened
during operation. A pressure switch shall be provided to monitor the
airflow to prevent operation of the lamps when the airflow is inadequate.
A Gaylord Extractor Monitor ("GEM") shall be provided to shut off the
lamps when a cartridge is removed. Mounted on the face of the plenum
of each ventilator section shall be indicating lights to monitor “UV System
On”, “UV Lamp Failure” and “UV Safety Interlock Activated”. A duplicate
set of these lights shall be mounted on the ventilator control cabinet,
Model CUV-100. The control panel shall be equipped with an audible
alarm indicating there is a lamp failure or one of the safety interlock
switches has been activated.
CONSTRUCTION: The ventilator shall be of all stainless steel construc-
tion, not less than 18 gauge, type 300 series. All exposed surfaces shall
be a number 4 finish. The use of aluminized steel, galvanized steel, or 430
stainless steel is not acceptable.
ELECTRICAL: The ventilator shall be factory pre-wired to single
connection points. On multiple section ventilators power for the UV
lamps must be supplied to each section. Wiring for controls and light
fixtures shall be furnished with coiled flex conduit for interconnecting
sections by applicable trades.
ITEM NO. _______________
TM
APPLICATION
For use over all types of equipment; ovens, broilers, griddles,
fryers, ranges, steam equipment, etc. Cannot be used over solid
fuel cooking equipment.
LIGHT FIXTURES: The ventilator shall be equipped with ❏ 100 watt
surface mounted incandescent, ❏ 150 watt recessed incandescent,
❏ recessed fluorescent, light fixtures. Light fixtures shall be factory prewired to a single connnection point. Ventilators built in multiple sections
shall be furnished with coiled flex conduit for interconnecting sections.
ACCEPTANCE & APPROVALS: The ventilator shall be UL and NSF
listed. The ventilator shall comply with all requirements of NFPA-96, IMC,
UMC, BOCA and SBCCI model codes.
Patent Pending
GAYLORD INDUSTRIES
10900 SW AVERY ST. • TUALATIN, OREGON 97062 U.S.A.
PHONE: 800-547-9696 • FAX: 503-692-6048 • email: info@gaylordusa.com
www.gaylordusa.com
Ultima VentTM with UV Technology
48" MINIMUM.
DIMENSION VARIES
WITH DEPTH OF THE
EQUIPMENT
ALL STAINLES STEEL
UV STATUS LIGHTS
AUDIBLE ALARM
CANCEL BUTTON
HOUR METER
NOTE: ONE EXHAUST DUCT COLLAR
REQUIRED FOR EACH UV MODULE.ONE TO
TWO DUCTS REQUIRED ON EACH SECTION
DEPENDING UPON SECTION LENGTH
16' - 0" MAX. UNIT LENGTH. FOR GREATER
LENGTH, JOIN TWO OR MORE SECTIONS
TOGETHER. ALLOW 6" MIN. OVERHANGE AT
EACH END. IF CHARBROILER IS AT END
OVERHANG 12"
HANGING RODS BY OTHERS
CONTINUOUS HANGING
BRACKET
100 WATT INCANDESCENT LIGHT
FIXTURE STANDARD. RECESSED
INCANDESCENT (8" HIGH) OR
RECESSED FLUORESCENT (6.5"
HIGH) OPTIONAL
30" FOR UP TO 300 CFM/LIN. FT.
34" FOR 400 CFM/LIN/ FT. FOR
34"
REDUCED DIMENSION SEE "LOW
PROFILE" NOTE ABOVE
"SUPER CAPTURE"TM LIP
MODEL “GX2-UV-____-BDL-___-____”
**
DAMPER OPTION
FDD = Fuse link damper at the duct collar
**
LOW
PROFILE
(LP)
DEPTH
OF
VENTILATOR
ND = No damper
For exact model designation add depth following the
letters “GX2-UV-FDD-BDL-”.
Example: “GX2-UV-FDD-BDL-48”
LOW PROFILE (LP) MINIMUM HEIGHT AT FRONT:
Light & Medium Duty Equipment (400°F) 12" Min.
Heavy Duty Equipment (600°F) 18" Min.
Extra Heavy Duty Equipment (700°F) "LP" Not Available
If low profile add suffix “LP” after BDL.
2.5" HIGH WITH NO DAMPER.
10" HIGH WITH FUSE LINK DAMPER
6"
MOUNTING FLANGE
MIN. 3" AIR SPACE
UV LAMPS
4.5" MIN. SLOPING
END PANEL WHEN
LP DESIGN IS USED.
REMOVABLE
EXTRACTOR
INSERT
10"
EXHAUST FAN/
SYSTEM ON/OFF
SWITCH
7" DEEP
CUV-100
CONTROL CABINET
The manufacturer reserves the right to modify the materials and specifications resulting
from a continuing program of product improvement or the availability of new materials.
ITEM NO. _____________________ EST. WT. ________________________
LENGTH ___________ WIDTH _____________ HEIGHT _____________
LIGHTS ____________
qq
q
100W SURFACE INCANDESCENT
qq
qq
q
150W RECESSED INCANDESCENT
qq
q q
q
RECESSED FLUORESCENT
q q
8"
NOTE: 18" OVERHANG
REQUIRED OVER UPRIGHT
BROILER
ENGINEERING DATA
Mechanical Requirements
The amount of exhaust volume required is dependent upon the type of
cooking equipment and the type and volume of cooking. Refer to the Master
Engineering Data Sheet in the Engineering Data section of the Gaylord
catalog for the charts on determining exhaust volume, duct sizes, static
pressure, water consumption, hot water requirements, and drain sizes.
Electrical
o Provide 120 volt 20 amp, o 220/240 volt, 50-60 Hz., 24 hour service to
Gaylord UV Control Panel (refer to Control Cabinet specification sheet). To
be fused separately. Provide a separate 120 volt 20 amp service to each
ventilator section to power UV lamps. Ventilator lights to be on separate
circuit, 120 volt standard, 220/240 volt optional.
12" MIN.
6'-8"
MTG. HT.
7'-0" MAX
TYPICAL SECTION VIEW
Ventilator Lengths
Maximum unit length 16'-0" . For greater lengths, join two or more sections
together. Check to ensure that there is adequate access into building and
kitchen area.
Note: Ventilators manufactured outside North America; maximum unit length
*
10'-0".
Hanging Weight
Ventilator Width 48" 54" 60"
Wt. / lineal ft. Lbs. 105 110 115