Garmin EDP70 User Manual

PART NUMBER 10H52152PU9C rev.8
EDP70 PLUS
UNINTERRUPTIBLE POWER SYSTEM
24/36/50/80kVA —
3 phase input / 3 phase output
     
1) SAVE THESE INSTRUCTIONS
This manual contains important instructions for the EDP70 PLUS which should be followed during installation and maintenance of the UPS and associated batteries.
2)
The installation must be inspected by trained technicians.
The instructions must be followed.
3)
When external batteries are provided by the Customer and not Chloride, reference must be made to
the installation instructions provided by the battery supplier.

1)
The AC and DC supplies to the EDP70 PLUS UPS and the AC output from the UPS MUST be fed
through suitably rated circuit breakers or fuses and isolating switches suitable for branch circuit operation.
2)
Any external battery cabinet connected to the UPS MUST be provided with an over-current protection
device per UL1778 Par. No. 28.4
3)
To reduce the risk of fire or electric shock, the equipment must be installed indoors, in a humidity
and temperature controlled environment which is free from conductive contaminants.

1)
DO NOT REMOVE COVERS DURING NORMAL OPERATION. The panels will be removed during installation, however this should only be undertaken by qualified technicians. It should be ensured that the UPS is switched off and that all power sources are disconnected (A.C. mains and Battery) before either the rear or side panels are removed.
FOREIGN OBJECTS MUST NOT BE INTRODUCED INTO THE VENTILLATION GRILLES.
2)
HAZARDOUS VOLTAGES are present within the EDP70 PLUS even when it is switched off.
3)
Fuses must ONLY be replaced with the same type and rating.
The EDP70 PLUS contains a battery which can be DANGEROUS if interfered with. Contact the
4)
supplier for replacement.
The UPS and/or its components must be disposed of as notifiable waste in accordance with local
5)
pollution control (special waste) regulations.
page
2 --
MI00/10056 rev. 8 —05/2006
3
WARNING
The UPS contains hazardous voltages, even when all switches are open.
In case of fire in the installation area, do not use water to extinguish fire.
ELECTRICAL PRECAUTIONS:
If the UPS is in By-pass mode and the Output switch is closed, no indications will be displayed;
fans will however function, and hazardous voltages are present downline from the static switches.
EMERGENCY PROCEDURE
In the case of an emergency, the load supply can be interrupted by switching off all the switches fitted in the UPS.
ELECTRIC SHOCK
Switch off power; use dry insulating material for protection when pulling the injured person clear of conductors. NEVER TOUCH THE INJURED PERSON WITH BARE HANDS UNTIL CLEAR OF CONDUCTORS. SEEK QUALIFIED ASSISTANCE IMMEDIATELY.
INJURIES CAUSED BY CONTACT WITH CORROSIVE LIQUIDS
In normal conditions, installed batteries are sealed. A damaged battery container may however leak electrolyte, or cause the latter to come into contact with battery parts. In the event of electrolyte contact with the eyes, rinse eyes thoroughly with a saline solution or fresh water for at least 10 minutes. In the event of electrolyte contact with skin, rinse the affected area with abundant water. Remove contaminated clothing. Cover affected area with dry gauze.
If electrolyte is swallowed, do not induce vomiting. Administer large quantities of milk
or water.
IN ALL CASES, SEEK MEDICAL ATTENTION IMMEDIATELY
MI00/10056 rev. 8 — 05/2006-- page
Contents
1.0 INTRODUCTION ..................................................................................................9
1.1 Summary of the manual...................................................................................................... 9
1.2 Summary of the equipment ................................................................................................ 9
1.3 Block diagram.................................................................................................................... 10
1.4 Functions ........................................................................................................................... 11
1.5 Operational modes............................................................................................................ 12
2.0 SAFETY..............................................................................................................14
2.1 General safety.................................................................................................................... 14
2.2 Symbols ............................................................................................................................. 14
2.3 Electrical precautions ....................................................................................................... 15
2.4 Battery precautions........................................................................................................... 15
2.5 Battery safety equipment.................................................................................................. 15
3.0 STORAGE ..........................................................................................................16
4.0 INSTALLATION .................................................................................................16
4.1 Mechanical characteristics............................................................................................... 16
4.2 Installation ......................................................................................................................... 26
Recommended wire sizes .......................................................................................................... 27
4.4 Ventilation.......................................................................................................................... 29
5.0 CONNECTION....................................................................................................30
5.1 Electrical connections ...................................................................................................... 32
5.2 24 – 12/18/24kVA ............................................................................................................... 33
5.3 36 – 24/30/36kVA ............................................................................................................... 36
5.3 EDP70 PLUS 50/80kVA...................................................................................................... 39
5.4 Signal connections ........................................................................................................... 42
6.0 CONTROLS........................................................................................................43
6.1 User Controls..................................................................................................................... 43
6.2 Control Panel ..................................................................................................................... 44
7.0 START UP..........................................................................................................45
8.0 MAINTENANCE BYPASS .................................................................................45
9.0 SHUT-DOWN .....................................................................................................46
9.1 Installing the EPO.............................................................................................................. 46
10.0 VISUAL AND AUDIBLE ALARMS ....................................................................47
10.1 Silencing Audible Alarm ................................................................................................... 47
page
4 --
MI00/10056 rev. 8 —05/2006
5
10.2 Mimic .................................................................................................................................. 47
10.3 Liquid Crystal Display....................................................................................................... 47
10.4 Display Page Headings ..................................................................................................... 48
10.5 Abnormal operating mode messages.............................................................................. 55
10.6 Power History .................................................................................................................... 60
10.7 Battery Test........................................................................................................................ 61
10.8 Battery Autonomy Test ..................................................................................................... 61
10.9 Resetting data loss manually ........................................................................................... 61
11.0 COMPUTER INTERFACE .................................................................................62
11.1 AS400.............................................................................................................................. 62
11.2 RS232 ................................................................................................................................. 63
12.0 REMOTE ALARMS............................................................................................63
13.0 BATTERIES .......................................................................................................64
13.1 EDP70 PLUS/24/18/12 : Battery Installation/Start-up...................................................... 64
13.2 EDP70 PLUS/24/18/12 : Optional Battery Cubicle ........................................................... 65
13.3 EDP70 PLUS above 24KVA: Battery Installation/Start-up .............................................. 66
13.4 EDP70 PLUS above 24KVA: Battery Cubicle .................................................................. 66
14.0 MAINTENANCE AND SPARE PARTS .............................................................66
MI00/10056 rev. 8 — 05/2006-- page
Figures
Figure 1 – Block diagrams – 24/36kVA Figure 2 – Block diagram – 50/80kVA Figure 3 – Normal operation Figure 4 – Utility Supply failure Figure 5 – Re-establishing the Utility Supply Figure 6 – Transferring the Load onto the Reserve Supply Figure 7 – 24 Footprint and cabinet dimensions Figure 8 – 36 Footprint and cabinet dimensions Figure 9 – 50/80 Footprint and cabinet dimensions
Figure 10 – “A” Battery Cabinet Drawing for 24/36kVA Ratings
Figure 11 – “B” Battery Cabinet Drawing for 24/36kVA Ratings
Figure 12 – “E” Battery Cabinet Drawing for 50/80kVA Ratings
Figure 13 – “F” Battery Cabinet Drawing for 50/80kVA Ratings
Figure 14 – “C” Battery Cabinet Drawing for 36/50/80kVA Ratings
Figure 15 – “D” Battery Cabinet Drawing for 50/80kVA Ratings
Figure 16 – UPS Ratings Figure 17 – Connection diagrams Figure 18 - 24 – 12/18/24kVA: Switches and Breakers Figure 19 - 24 – 12/18/24kVA: Switches Figure 20 - 24 – 12/18/24kVA: Cable Connections Figure 21 - 36 – 24/30/36kVA: Switches and Breakers Figure 22 - 36 – 24/30/36kVA: Connections Figure 23 - 36 – 24/30/36kVA: Cable Connections Figure 24 – 50/80kVA: Switches and Breakers Figure 25 – 50/80kVA: Connections Figure 26 – 50/80kVA: Cable Connections Figure 27 – Control panel
Figure 28: Power History Structure
Figure 29 EDP 70 Plus Computer Interface Pin Layout
Figure 30 EDP70 PLUS Remote Alarms Pin Layout
Figure 31- EDP70 PLUS/24/18/12: Internal Battery Shelves
12
12
26
43
10
11
13
13 17 18
19
20 21 22
23
25
30
33
34
35
36
37
38
39
40
41
60
62
63
65
24
page
6 --
MI00/10056 rev. 8 —05/2006
7
EQUIPMENT DELIVERY AND STORAGE
Delivery
The equipment and battery are delivered separately. On receipt, the packaging must be checked for any signs of damage. Any damage or missing parts should be reported to the carrier within 24 hours of delivery.
Unpacking
Care should be taken when unpacking to avoid damaging the equipment or battery; in particular, avoid short circuiting battery terminals. All packing materials should be checked before disposal to ensure that no items are discarded. The equipment panel rating plate should be checked to ensure that supply voltage and output rating correspond to the equipment and load and that the mode of operation is correct.
Handling
Keep equipment and battery upright at all times, and handle with care. Either may be damaged if dropped or subject to severe impact. Particular care should be taken to protect the controls and instruments. a) Leave the equipment in its packaging and transport it with a fork lift.
b) Cut the tapes and remove the packing case by lifting it upwards. c) Unscrew the screws fastening the pallet to the cubicle feet.
d) Lift the cubicle and remove the pallet.
Storage
Store the equipment and battery in a clean, dry place, free from water, condensation, dirt and extremes of temperature. Sealed lead acid battery cells which are supplied filled and charged must be given a boost charge at least every 3
months. Sealed Nickel-Cadmium battery cells which are supplied filled and discharged must be charged and discharged before
storage.
Sealed Nickel-Cadmium battery cells which are supplied dry must be filled, charged and discharged before storage.
Sealed spare battery cells must be charged at least every 3 months.
Failure to comply with the Manufacturer’s instructions may result in the battery not reaching its rated performance and having a shortened life.
MI00/10056 rev. 8 — 05/2006-- page
?
page
8 --
MI00/10056 rev. 8 —05/2006
9
1.0 INTRODUCTION
1.1 Summary of the manual
This handbook provides for the safe installation, startup and use of the EDP70 PLUS Uninterruptible Power System (UPS). The Company recommends that the equipment be installed and regularly maintained by a Chloride Authorized personnel.
DO: - read the User Handbook before operating the EDP70 PLUS UPS.
- keep a log of all incidents.
- protect the batteries from damage. Batteries leak acid; avoid contact with skin, clothes or eyes.
DO NOT: - operate the control switches.
- operate the EDP70 PLUS UPS with any covers removed.
- obstruct the ventilation grilles.
1.2 Summary of the equipment
The EDP70 PLUS Uninterruptible Power System (UPS) totally isolates the load from voltage drops, spikes, transients frequency variations in the utility supply.
In the event of failure or brownout of the AC utility supply, an internal audible alarm sounds and an LED on the control panel illuminates, the EDP70 PLUS UPS will continue to provide safe, clean continuous power, without interruption, from the battery, for a duration dependent on battery capacity and output load.
The audible alarm alerts the user to start a safe orderly shutdown of the load. When the AC utility supply returns to normal, the EDP70 PLUS UPS automatically recharges the battery ready for any future power failure.
The microprocessor display panel provides access to very detailed information regarding the status of the supplies and EDP70 PLUS UPS. Refer to current publication for detailed specification.
The block diagram, shows the main functional sub-assemblies of the EDP70 PLUS UPS. The AC three phase utility supply is rectified to provide direct current, which maintains the battery in a fully charged state and also supplies the inverter, which provides the three phase output via an electronic static switch.
Normally the supply of the reserve line is taken from the AC utility input, but special units, with a separate reserve input supply, are available. This allows the inputs to be supplied from independent three phase sources.
Provided the reserve supply is within limits, the inverter will match the output frequency with the reserve supply frequency. The inverter has its own internal crystal control to stabilize the output frequency if the reserve supply frequency is out of limits. The electronic static switch switches the output from the inverter to the reserve supply, without interruption, to meet any load current surges, or to supply the load if the battery is discharged during an AC utility supply failure.
Maintenance and testing can be carried out on the EDP70 PLUS UPS without interrupting the output, by switching the load from the reserve supply to the maintenance bypass circuit. This work should only be carried out by Chloride-trained personnel.
MI00/10056 rev. 8 — 05/2006-- page
1.3 Block diagram
24kVA - STANDARD CONFIGURATION
S3
Reserve Supply
208Y/120V
S2
S1
AC Supply
IN THE ABSENCE OF A SEPARATE RESERVE
SUPPLY THE RESRVE IS DERIVED FROM THE
AC UTILITY INPUT WITH THE JUMPER
CONNECTED AS INDICATED
Reserve Supply
208Y
S1
AC Supply
IN THE ABSENCE OF A SEPARATE RESERVE
SUPPLY THE RESRVE IS DERIVED FROM THE
AC UTILITY INPUT WITH THE JUMPER
CONNECTED AS INDICATED
Maintenance By-pass
290
3
Battery Contactor
208150
1
5
4
144 Cells (Internal)
2
36kVA - STANDARD CONFIGURATION
480
208Y
S2
S3
Battery Contactor
3
250
1
Maintenance By-pass
5
208Y
4
240 Cells (External)
2
S4
S4
page
Reserve Supply
480V
AC Supply
IN THE ABSENCE OF A SEPARATE RESERVE SUPPLY THE RESRVE IS DERIVED FROM THE AC UTILITY INPUT WITH THE JUMPER CONNECTED AS INDICATED
10 --
MI00/10056 rev. 8 —05/2006
36kVA - 480V/208V CONFIGURATION
S1
S3
S2
208Y
250
480
Maintenance By-pass
3
208Y
1
Battery Contactor
240 Cells (External)
2
Figure 1 – Block diagrams – 24/36kVA
5
S4
4
11
S3
Maintenance Bypass
Reserve Supply
480V
AC Supply
S2
S1
IN THE ABSENCE OF A SEPARATE
RESERVE SUPPLY THE RESERVE IS
DERIVED FROM THE AC UTILITY
INPUT WITH THE JUMPER
CONNECTED AS INDICATED
Battery Contactor
240 Cells (External)
3
1
2
S5
5
S4
4
480Y/277V
208Y/120V
Figure 2 – Block diagram – 50/80kVA
The uninterruptible power system consists of the following:
1 - RECTIFIER/INVERTER S1 = Equipment ON/OFF switch 2 - BATTERY S2 = Equipment Reserve switch 3 - BACKFEED PROTECTION S3 = Equipment By-pass switch 4 - INVERTER STATIC SWITCH S4 = Equipment OUTPUT switch 5 - RESERVE STATIC SWITCH (INVERTER OUTPUT switch for 50/80kVA only)
S5 = RESERVE OUTPUT switch for 50/80kVA only
1.4 Functions
   
The rectifier/battery charger transforms the alternating current of the mains supply to direct voltage to maintain the battery in a fully charged state and also supply the inverter.

The battery is an energy reserve that is used by the inverter and the load whenever the mains supply fails.

The inverter changes the direct voltage from the rectifier or from the battery into a three phase sinusoidal alternating voltage for the external supply.
  
The function of the electronic static switch is to select one of the two sources of alternating voltage and to supply it to the external load. The two sources of voltage supplied to the static switch are the output of the inverter and the reserve supply. In normal working conditions, the static switch supplies the load from the inverter.

The switches permits maintenance and repair of the UPS, without interrupting the supply to the load.
MI00/10056 rev. 8 — 05/2006-- page
1.5 Operational modes
S3
S2
Maintenance By-pass
AC Supply
AC Supply
S1
Battery Contactor
S3
S2
S1
Battery Contactor
24/36kVA Ratings
Maintenance By-pass
50/80kVA Ratings
LOAD
S4
S5
S4
480Y/277V
LOAD
208Y/120V
Figure 3 – Normal operation
During normal operation the load is supplied by the mains through the rectifier and inverter. The rectifier also supplies the current for recharging and maintaining the battery in a fully charged state.
Reserve Supply
AC Supply
S3
S2
S1
Maintenance By-pass
S4
LOAD
Battery
Reserve Supply
Contactor
S3
S2
S1
24/36kVA Ratings
Maintenance By-pass
S5
S4
480Y/277V
LOAD
208Y/120V
AC Supply
Battery Contactor
50/80kVA Ratings
Figure 4 – Utility Supply failure
When the utility supply voltage is absent or outside the allowed tolerances, the battery supplies the inverter. This will be indicated on the UPS front panel display and the Remote Alarm Unit (if fitted). The standby time available depends both on the capacity of the battery and on the size of load. It is possible to extend autonomy by reducing the output power by disconnecting non-important loads. In all cases, the alphanumerical display shows the residual autonomy.
page
12 --
MI00/10056 rev. 8 —05/2006
13
Reserve Supply
S3
S2
Maintenance By-pass
S4
S5
S4
480Y/277V
208Y/120V
AC Supply
Reserve Supply
AC Supply
S1
Battery Contactor
S3
S2
S1
Battery Contactor
24/36kVA Ratings
Maintenance By-pass
50/80kVA Ratings
Figure 5 – Re-establishing the Utility Supply
When the utility supply returns within acceptable limits, the UPS returns automatically to normal operation mode as previously described. The rectifier now starts to recharge the battery. However, until recharge has been completed, any further mains failure will result in reduced standby times.
Reserve Supply
AC Supply
S3
S2
S1
Battery Contactor
Maintenance By-pass
S4
24/36kVA Ratings
Reserve Supply
AC Supply
S3
S2
S1
Battery Contactor
Maintenance By-pass
50/80kVA Ratings
S5
S4
480Y/277V
208Y/120V
Figure 6 – Transferring the Load onto the Reserve Supply
Transfer onto the reserve line is caused by two conditions: a) inverter stop b) overload In both instances the load is transferred onto the reserve without interruption. If the overload is temporary, the system will re-transfer from reserve to inverter as soon as the it ceases. This allows for the initial start-up of loads with high or excessive switch-on currents.
MI00/10056 rev. 8 — 05/2006-- page
2.0 SAFETY
Read all instructions carefully before installing or operating the equipment.
2.1 General safety
The procedure described in these instructions is intended for use by persons experienced in the operation of Uninterruptible Power Systems and ancillary equipment. Persons unfamiliar with this type of equipment should seek guidance from experienced personnel. The EDP70 PLUS UPS is designed to be operated in accordance with existing safe operating procedures. These instructions are not intended to replace existing safety practices. If there are any questions regarding the safe operation of the system, contact a Chloride service representative.
This equipment is designed and built for safe operation when used to supply its rated load, providing it is installed as specified by qualified, licensed and competent electricians. Electrical energy can be supplied by the equipment and the battery.
2.2 Symbols
The following symbols appear in this book and in the unit:
Warning -
electrical shock and danger to personal safety.
DIRECT CURRENT SUPPLY
Hazardous voltages are present. If the instructions are not heeded, there is a risk of
ALTERNATING CURRENT SUPPLY
ON position of the switches
OFF position of the switches
Inverter Start Up
Inverter Shutdown
Audible Alarm Cancel Switch
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
page
14 --
MI00/10056 rev. 8 —05/2006
15
Page Right Control
Record Up
Record Down
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
2.3 Electrical precautions
Never handle a component or assembly without first confirming that no voltage is applied or present. Remove only those protective covers that are essential to perform the repairs or adjustment currently required, and replace them as soon as possible.
. Use only insulated tools. . Place a rubber insulating mat in front of all equipment doors. . Keep all door closed and locked at all times during normal operation.
2.4 Battery precautions
Always isolate the load before connecting or disconnecting the batteries or battery cells. Ensure that batteries are fully isolated by disconnecting the battery connectors, opening circuit breakers, or both. Remove all jewellery from hands, wrists and neck before working on batteries or battery cells. Before leaning over batteries, remove any metal object that could fall out of pockets. Do not place tools or other conductive objects on the batteries.
2.5 Battery safety equipment
When working on or handling batteries, ensure that the following items are worn:
. Eye goggles . Rubber gloves . Rubber apron . Rubber boots
When batteries are being moved or worked on, ensure the following items are available in the immediate vicinity:
. An eye bath, eyewash station or equivalent . A clean water source to wash spilled acids . Absorbent materials to soak up spilled acids . Disposal for contaminated materials.
MI00/10056 rev. 8 — 05/2006-- page
3.0 STORAGE
If the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the integral battery becoming discharged thereby sustaining permanent damage and affecting the standby period available and battery life. The date the battery was last recharged and the date the battery is due for its next recharge are both stamped on the packaging accompanying the unit. If you intend to store the unit, please refer to the recharge date. When the EDP70 PLUS is due to be recharged, refer to the Installation instructions and connect the EDP70 PLUS UPS to a temporary AC supply. The battery MUST be recharged for at least 24 hours every 3 months.
4.0 INSTALLATION
4.1 Mechanical characteristics
- Ambient temperature 18°F[-10°C] to 104°F [+40°C ]
- Relative Humidity (w/out condensing @ 68°F[20°C]) < 90%
- Max altitude (w/out derating) 3300 feet [1000 m] above sea-level
- Protection degree (panel fitted)
- Input cables bottom
- Air inlet bottom
- Air outlet rear
UPS model
Description
Size width
Total Weight (UPS +
Battery)
Floor Area
Floor
Loading
(UPS +
Battery)
Air-Flow
Acoustic Noise
100% Linear Load
depth
height
w/out cells 25 Ah cells 30 Ah cells 35 Ah cells
w/out cells 25 Ah cells 30 Ah cells 35 Ah cells
u.m. 24 36 50 80
In
[mm]
Lbs [kg]
2[m2
In
Lbs/in
[kg/m2]
cfm
[mc/h]
dBA 52 55 55 62
28-.5 [700]
28.7 [730] 56 [1420]
880 [400]
1342 [610] 1456 [662] 1526 [694]
] 789 [0.511] 789 [0.511] 1019 [0.657] 1019 [0.657]
2
1.12 [782]
1.70 [1194]
1.85 [1296]
1.93 [1358]
235
[400]
27.5 [700]
28.7 [730] 56 [1420]
1300 [590]
n.a. n.a. n.a.
1.65 [1155] n.a. n.a. n.a.
647
[1100]
35.4 [900]
28.7 [730] 63 [1600]
1342 [610]
n.a. n.a. n.a.
1.32 [930]
n.a. n.a. n.a.
1165
[1980]
35.4 [900]
28.7 [730] 63 [1600]
1800 [818]
n.a. n.a. n.a.
1.77 [1245]
n.a. n.a. n.a.
1553
[2640]
Notes: 1) n.a. = not applicable
2) Longer autonomies, and battery for EDP above 20 kVA are available with external
battery cubicles.
page
16 --
MI00/10056 rev. 8 —05/2006
17
ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES)
6 8 0 ,
700,0 (27.56)
1 4 2 2 ,
0 (
5 6 )
0
(
2 6 .
7 7 )
(28.5)725,0
58,0 (2.28)
N R
4 X
600,0
ø 8
(
ø 0 ,
3 1 )
(23.62)
6 4 5 ,
0
3
(
2
0
5
,
0
.
3
(
1
9
.
)
1 8 )
C
2 6
A
0
B
(
L
1
E
0 .
E
2
N
4 )
T
X
R Y
6 6
(
2 .
6 )
150
(5.9)
(
2 .
6 4 )
(
7 .
8 7 )
SPACE REQUIRED BY THE WHEEL WHEN ROTATING
63,0 (2.48)
Figure 7 – 24 Footprint and cabinet dimensions
730,0 (28.7)
6 7 ,
0
2 0 0
MI00/10056 rev. 8 — 05/2006-- page
N R
4 X
(
ø
0
,
3
1
)
ø
8
ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES)
700,0 (27.56)
1 4 2 2 ,
0 (
5 6 )
6 8 0 ,
0 (
2 6 .
7 7 )
page
6 4 5
3
,
0
0
,
0
(
2
(
1
5
.
.
1
3
8
9
)
)
600,0
18 --
MI00/10056 rev. 8 —05/2006
8 8 ,
0
(
700,0
(27.5)
125,0 (4.92)
530 (20.9)
500 (19.7)
CABLE ENTRY 500 (19.68) X 110 (4.33)
(23.62)
150 (5.9)
3 .
4 6 )
200 (7.87)
SPACE REQUIRED BY THE WHEEL WHEN ROTATING
50,0
(1.97)
730,0 (28.7)
Figure 8 – 36 Footprint and cabinet dimensions
19
N R
4 X
ø
8
(
ø
0
,
3
1
)
ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES)
900,0 (35.4)
1 6 0 0
(
6 3 .
0 )
6 8 ,
0 (
2 .
6 8
100,0
(3.94)
200
6 4 5
3
,
0
0
,
0
(
2
(
1
5
.
.
1
3
8
9
)
)
CABLE ENTRY
700 (27.56) X 110 (4.33)
800,0
(31.5)
Figure 9 –
(7.87)
150
(5.9)
50/80 Footprint and cabinet dimensions
)
SPACE REQUIRED BY THE WHEEL WHEN ROTATING
50,0
(1.97)
730,0 (28.7)
MI00/10056 rev. 8 — 05/2006-- page
Figure 10 — “A” Battery Cabinet Drawing for 24/36kVA Ratings
page
20 --
MI00/10056 rev. 8 —05/2006
21
Figure 11 — “B” Battery Cabinet Drawing for 24/36kVA Ratings
MI00/10056 rev. 8 — 05/2006-- page
Loading...
+ 46 hidden pages