FULTON ICW6 - 60 HP, ICW6, ICW10, ICW30, ICW50 Installation And Operation Manual

...
INSTALLATION AND
OPERATION MANUAL
Vertical Tubeless Design
Gas/Oil-Fired Hot Water Boilers
Model ICW
6 - 60 HP
Serial/ National Board Number
Fulton Order
Sold To
Job Name
Date
ICW-IOM-2012-1001
ICW-IOM-2012-1001 TABLE OF CONTENTS
Introduction 1-1
Overview .............................................................................................................. 1-2
Warnings & Cautions ............................................................................................1-2
Disclaimers and Local Codes ................................................................................1-2
Installation 2-1
Placement & Rigging ........................................................................................... 2-2
Clearances & Serviceability .................................................................................. 2-4
Environment, Ventilation and Combustion Air Requirements ............................ 2-4
Utilities .................................................................................................................2-7
THE GAS SUPPLY ..........................................................................................................................27
THE OIL SUPPLY ...........................................................................................................................27
Electrical Supply ................................................................................................... 2-8
Water Supply ........................................................................................................2-8
INSTALL WATER PIPING ...............................................................................................................28
Water Chemistry Requirements ......................................................................... 2-10
PREVENT OXYGEN CONTAMINATION ........................................................................................210
ELIMINATE SYSTEM AIR ............................................................................................................211
Piping Speci cations .......................................................................................... 2-11
Insulation ........................................................................................................... 2-12
System Interfaces ............................................................................................... 2-12
FILL CONNECTION ......................................................................................................................212
PRESSURE GAUGES ....................................................................................................................213
Stack and Flue ....................................................................................................2-13
EXHAUST SIDE WALL VENTING ................................................................................................214
Testing ................................................................................................................ 2-14
Maintenance 4-1
Daily Maintenance Schedule ................................................................................ 4-2
Weekly Maintenance Schedule ............................................................................4-2
Monthly Maintenance Schedule .......................................................................... 4-2
Recommended Semi-Annual Maintenance Schedule ......................................... 4-3
Recommended Annual Maintenance Schedule ..................................................4-5
Procedure for Primary Air Adjustment/Inspection .............................................. 4-6
Procedure for Secondary Air Adjustment/Inspection ..........................................4-6
Procedure for Flame Scanner Adjustment ...........................................................4-7
GAS UNIT ......................................................................................................................................47
OIL UNIT ......................................................................................................................................47
Procedure for Removing/Cleaning the Burner ....................................................4-8
Procedure for Controls Voltage Transformer Inspection .....................................4-8
Procedure for Soot Cleaning................................................................................. 4-9
After All Repairs or Maintenance .........................................................................4-9
Troubleshooting ...................................................................................................4-9
Warranty & Parts 5-1
Standard Warranty for Fulton Boilers................................................................... 5-3
Parts ..................................................................................................................... 5-4
Operation 3-1
Start-Up Preparation & Installation Review ........................................................ 3-2
Filling The System/Air Removal ..........................................................................3-2
Start-Up Service ................................................................................................... 3-4
Initial Start-Up ..................................................................................................... 3-4
COMBUSTION ...............................................................................................................................34
Flame Programmers ............................................................................................ 3-5
Operating Controls ............................................................................................... 3-6
WATER RELIEF VALVE ...................................................................................................................36
WATER OUTLET VALVE .................................................................................................................36
TEMPERATURE CONTROL ...........................................................................................................36
OPERATING TEMPERATURE AQUASTAT ......................................................................................36
HIGH LIMIT AQUASTAT/HIGH TEMPERATURE LIMIT ..................................................................36
AIR SAFETY SWITCH ....................................................................................................................36
PROBE TYPE LOW WATER CUTOFF .............................................................................................36
Circulating Pump Switch ......................................................................................3-7
Cycle Testing ......................................................................................................... 3-7
Before Leaving the Installation ............................................................................ 3-7
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
0-1
TABLE OF CONTENTS ICW-IOM-2012-1001
0-2
© The Fulton Companies 2012
INTRODUCTION
INTRODUCTION
INSTALLATION
1
2
OPERATION MAINTENANCE WARRANTY & PARTS
3 4 5
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
1-1
INTRODUCTION ICW-IOM-2012-01-04 SECTION 1
Overview
Prior to shipment, the following inspections and tests are made to ensure the highest standards of manufacturing for our customers:
§ Material inspections
§ Manufacturing process inspections
§ American Society of Mechanical Engineers (ASME)
welding inspection
§ ASME hydrostatic test inspection
§ Electrical components inspection
§ Operating test
§ Final engineering inspection
§ Crating inspection
This manual is provided as a guide to the correct operation and maintenance of your Fulton equipment, and should be read in its entirety and be made permanently available to the sta responsible for the operation of the boiler. It should not, however, be considered as a complete code of practice, nor should it replace existing codes or standards which may be applicable. Fulton reserves the right to change any part of this installation, operation and maintenance manual.
Installation, start-up, and maintenance of this equipment can be hazardous and requires trained, quali ed installers and service personnel. Trained personnel are responsible
for the installation, operation, and maintenance of this product, and for the safety assurance of installation, operation, and maintenance processes. Do not install, operate, service or repair any component of this equipment unless you are quali ed and fully understand all requirements and procedures. Trained personnel refers to those who have completed Fulton Service School training speci c to this product.
Warnings & Cautions
WARNINGS and CAUTIONS appear in various chapters of this manual. It is critical that all personnel read and adhere to all information contained in WARNINGS and CAUTIONS.
§ WARNINGS must be observed to prevent serious injury
or death to personnel.
§ CAUTIONS must be observed to prevent damage
or destruction of equipment or loss of operating e ectiveness.
All Warnings and Cautions are for reference and guidance purposes, and do not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes or regulations.
Disclaimers and Local Codes
Installation of the equipment shall conform to all the requirements or all national, state and local codes established by the authorities having jurisdiction or, in the absence of such requirements, in the US to the National Fuel Gas Code ANSI Z2231/NFPA 54 latest edition, and the speci c instructions in this manual. Authorities having jurisdiction should be consulted prior to installation.
When required by local codes, the installation must conform to the American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1).
When working on this equipment, observe all warnings, cautions, and notes in literature, on stickers and labels, and any additional safety precautions that apply. Follow all safety codes and wear appropriate safety protection. Follow all jurisdictional codes and consult any jursidictional authorities prior to installation.
1-2
© The Fulton Companies 2012
INSTALLATION
INTRODUCTION
INSTALLATION
1
2
OPERATION MAINTENANCE WARRANTY & PARTS
3 4 5
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-1
INSTALLATION ICW-IOM-2012-1001 SECTION 2
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
This boiler is certi ed for indoor installation only.
A competent rigger experienced in handling heavy equipment should handle rigging your equipment into position.
The equipment must be installed on a non-combustible surface.
Ensure all labels on the boiler are legible. All connections and safety devices, both mechanical and electrical, must be kept clean, with ease of access for inspection, use and maintenance.
Do not store or use gasoline or other  ammable vapors and liquids or corrosive materials in the vicinity of this or any other appliances.
Placement & Rigging
Proper placement of your Fulton Product (see Figures 1 and 2, and Tables 1 and 2) is essential. Attention paid to the following points will save a great deal
of di culty in the future. Correct placement is the  rst step to trouble-free installation, operation and maintenance.
Adhere to the following for equipment placement and rigging:
1. Consult authorities with jurisdiction over any national or local codes (including but not limited to National Fire Protection Agency (NFPA), American National Standards Institute (ANSI), Underwriters Laboratories (UL), SCA, and ASME, which might be applicable to boiler applications before beginning.
2. Make appropriate determinations for placement, based on the following:
§ Check building speci cations and Table 2 for unit weights.
§ Ensure the equipment is to be placed on a non-combustible level base
with adequate clearances from combustible materials. See Clearances &
Serviceability section.
§ Locate boiler as close as possible to the place where the heat will be used
in order to keep pipe work costs to a minimum.
§ Ensure that there is adequate clearance around the unit to provide
access for operators and maintenance personnel to all parts of the equipment. Ensure also that clearance provides for component removal for maintenance. See Clearances & Serviceability section. The equipment should be placed in a suitable boiler house or well ventilated separate room through which personnel do not normally pass. The layout should eliminate tra c in potentially hazardous areas. For instance, the service engineer or the operator should not have to pass exposed, hot pipe work to make adjustments to the boiler controls.
4 CAUTION
Do not allow weight to bear on equipment components to prevent damage.
2-2
§ Ensure the equipment is to be placed in such a way that the electrical
components are protected from exposure to water or excessive humidity.
§ Ensure the boiler is located a safe distance from the fuel oil tank (if
applicable).
3. Determine rigging procedure, based on the following:
§ Units are shipped and crated for forklift transport. Once uncrated, all units
can be transported with a forklift and/or lifting lugs at the top of the boiler. All skidded units can be moved with forklifts.
§ If means of lifting are not available, place rollers beneath the frame of the
equipment for guidance to the position of where it is to be installed.
§ Under no circumstances allow weight to bear on the jacket, control panel,
burner, fuel train or fan housing of any Fulton boiler.
© The Fulton Companies 2012
SECTION 2 ICW-IOM-2012-1001 INSTALLATION
F
D
C
K
A
J
B
G
O
M
E
H
L
N
I
Side View
Front View
Top View
TABLE 1 DIMENSIONS REFER TO FIGURE 1
Model ICW 6 10 15 20 30 50 60
Unit Size BHP 6 10 15 20 30 50 60
A. Boiler Height
IN
MM
(B) Boiler Height with Trim* and Fuel Train Assembly
IN
MM
(C) Overall Depth Stack to Burner Fan Housing
IN
MM
(D) Boiler Diameter
IN
MM
(E) Flue Outlet Diameter
IN
MM
(F) To Center of Flue Outlet
IN
MM
(G) Return Water Inlet Height
IN
MM
57.5
1461
75
1905
44
1118
26
660
6
152
52
1320
15.5
394
63.5
1613
80.5
2045
46
1168
28
710
6
152
58
1473
16
406
69.5
1765
86.5
2197
47
1194
30
760
8
203
63
1600
16.25
413
72.5
1842
92.5
2350
60
1524
39
990
10
254
66
1675
17.25
438
82.5
2096
102
2591
67
1702
46
1170
12
305
73.5
1867
17.5
445
87.5
2223
106.5
2705
78
1981
55
1400
12
305
79
2007
18.75
476
93.5
2375
120
3048
78
1981
55
1400
12
305
85
2159
18.75
476
(H) Overall Width
IN
MM
(I) Gas Train Extension (CSD-1)
IN
MM
(J) Clearance Required for Trim & Burner Removal*
IN
MM
*This dimension is 6 inches (152.4 mm) less for oil  red units.
31
787
22.5
572
82
2082
33
838
21.5
546
86
2184
35
889
20.5
521
92
2337
42.5
1080
25
635
96
2438
50.5
1283
27
686
106
2692
58
1473
22.5
572
114
2896
58
1473
34
867
124
3150
FIGURE 1 MODEL ICW DIMENSIONS/SPECIFICATIONS REFER TO TABLES 1 AND 2
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-3
INSTALLATION ICW-IOM-2012-1001 SECTION 2
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
Crystalline silica may be present in components of this equipment. Exposure to crystalline silica may pose signi cant health hazards, including but not limited to eye and respiratory system damage. Per the Centers for Disease Control and Prevention (CDC) and Occupational Safety and Health Administration (OSHA), appropriate Personal Protective Equipment must be worn to minimize exposure to hazardous substances. Refer
to most current guidelines o ered by the CDC and OSHA for more information, including Personal Protective Equipment recommendations.
NOTE: ´ When calculating ventilation requirements, heat losses from the Fulton
equipment (and other equipment) should be considered.
Clearances & Serviceability
Adhere to the following for equipment clearances and serviceability:
1. Ensure appropriate front, back, sides and top clearances are met. This will allow access around the equipment to facilitate maintenance and a safe work environment, and ensure technicians will commission the unit. Technicians will not commence commissioning if hazardous conditions exist.
2. Place boiler with clearances to unprotected combustible materials, including plaster or combustible supports, not less than the following:
§ Heater Front: 36 in. (914 mm)
§ Heater Sides and Rear: 18 in. (457 mm)
§ Heater top: 24 in. (610 mm)
§ Allow for additional minimum clearances for personnel access and burner
removal, as necessary.
Failure to provide required and safe access to the equipment could impede commissioning and maintenance. Service technicians are instructed not to commence commissioning if hazardous conditions exist.
Failure to provide proper minimum clearances between equipment and combustible materials may result in  re.
The installation of an exhaust fan in the boiler room is not recommended. An exhaust fan or similar equipment can create a downdraft in the stack or restrict the burner’s air supply and result in poor combustion. It is essential only fresh air be allowed to enter the combustion air system. Foreign substances such as combustible volatiles and lint may create hazardous conditions.
§ Verify that all clearances are acceptable with the local ordinances.
Environment, Ventilation and Combustion Air Requirements
It is critical to provide free access of air to the boiler. To burn fuel properly, it requires one square inch opening for every 3,000 BTU input of fuel (6.4 cm2 for every 756 kCal).
Adhere to the following to meet ventilation and combustion air requirements:
1. Install two fresh air openings, one at a low level, 24” (610 mm) from the
 oor, and one at a higher level on the equipment room wall. This will provide a  ow of air to exhaust the hot air from the equipment room.
2. Ensure the equipment room air supply openings are kept clear at all times.
2-4
© The Fulton Companies 2012
SECTION 2 ICW-IOM-2012-1001 INSTALLATION
TABLE 2  SPECIFICATIONS REFER TO FIGURE 1
Model ICW 6 10 15 20 30 50 60
Boiler Connec ons
K. Safety Valve Outlet IN MM
L. Safety Valve Inlet IN MM
M. Water Inlet Size IN MM
N. Hot Water Outlet Size IN MM
O. Boiler Drain Size IN MM
Approx. Shipping Weights LB KG
Ra ngs* (sea level to 3000  ) Output 1000 BTU/HR 1000 KCAL/HR
0.75 19
0.75 19
1.5 38
1.5 38
1 25
1700 771
201 51
0.75 19
0.75 19
2 51
2 51
1 25
2000 910
335 84
1.5 38
0.75 19
2.5 64
2.5 65
1 25
2380 1080
502 127
1.5 38
1 25
2.5 64
2.5 65
1.25 32
3400 1542
678 171
1.5 38
1 25
3 76
3 76
1.25 32
4780 2168
1017 256
1.5 38
1.25 32
4 102
4 102
1.5 38
6526 2960
1645 427
1.5 38
1.25 32
4 102
4 102
1.5 38
7280 3302
2034 513
Approximate Fuel Consump on at Rated Capacity+
Light Oil GPH LPH
Propane Gas FT3/HR M3/HR
Natural Gas FT3/HR M3/HR
Natural Gas Boiler Connec on Size (Std CSD-1) IN MM
Oil Inlet Connec on Size IN MM
Burner Motor HP 3450 RPM/60 CY 2850 RPN/50 CY 1/3 1/3 1/3
Electric Power Requirements - Burner Only (in amps)
120V 60 CY 1 Phase 7.2 7.2 7.2 7.2 gas
230V 50/60 CY 1 Phase 3.6 3.6 3.6 3.6 gas
208V 50/60 CY 3 Phase 1.9 1.9 1.9 1.9 gas
230V 50/60 CY 3 Phase 1.6 1.6 1.6 1.6 gas
460V 50/60 CY 3 Phase .8 .8 .8 .8 gas
Water Content U.S. GAL LITERS
1.8
6.8
100
2.8
251
7.1
1 25
.25 6
21 80
3
11.4
168
4.8
419
11.9
1 25
.25 6
35 132
4.5 17
251
7.1
629
17.8
1 25
.25 6
54 204
6
22.7
335
9.5
838
23.7
1.25 32
.25 6
1/3 gas 3/4 oil 3/4
13.8 oil
6.9 oil
3.5 oil
3.2 oil
1.6 oil
104 394
9 34
502
14.2
1256
35.4
1.5 38
.25 6
13.8 ____ ____
6.9 10 gas
3.5 6.6 gas
3.2 6.0 gas
1.6 3 gas
208 787
15 57
837
23.7
2093
59.3
1.5** 38
.25 6
1.5 gas 2 oil
12 oil
7.5 oil
6.8 oil
3.4 oil
291 1101
17.9
67.8
1004
28.4
2511
71.1
2 51
.25 6
1.5 gas 2 oil
10 gas 12 oil
6.6 gas
7.5 oil
6.0 gas
6.8 oil
3 gas
3.4 oil
315 1192
+ Consump on based on light oil 140,000 BTU/GAL, Natural Gas 1010 BTU/ 3, Propane 2530 BTU/ 3. ** CSA gas train size is 2 inches (50.8 mm) Natural gas pressure required/main inlet is 7-11” W.C. LP Gas Pressure required main inlet is 14” W.C. Natural Gas Pressure required/last elbow is 3/5” W.C. and back pressure. LP Gas pressure required/last elbow is 11” W.C. No. 2 Oil Pressure required/oil pump is 230 PSI. Notes: Model sizes up to and including ICW30 have threaded inlet and outlet as shown on schema c. All larger sizes have fl anged inlet and outlet. Models ICW50 and ICW60 are provided with an extra plugged safety valve for extra relief capacity. For custom fuel trains, consult Factory for sizing and connec ons.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-5
INSTALLATION ICW-IOM-2012-1001 SECTION 2
Transformer Scroll
Gaskets
Burner Motor
Control Box
High Density Insulation
Outside Jacket
Handhole
Boiler Runners
Flue Outlet
Lifting Hook(s)
Flue Blanket
Flue Rope Gasket
Flue Plate Cover
Top Plate Assembly
Gas Train Assembly
Secondary Air Damper
Burner Plate
Assembly
Stainless Steel Ring (oil only)
Bottom Refractory
Top Refractory
Castable Refractory Insulation
Water Return
3. See Table 3 for minimum make up air openings required for each model.
TABLE 3 MINIMUM MAKE UP AIR OPENING REQUIREMENTS
Model Fresh Air Opening FT2 (M2)
ICW 6 1 (.09)
ICW 10 1 (.09)
ICW 15 1.5 (.14)
ICW 20 4 (.37)
ICW 30 4 (.37)
ICW 50 5 (.46)
ICW 60 7.5 (.69)
4. If positive forced ventilation is adopted, ensure that there will be no appreciable pressure variation in the equipment room.
5. Avoid ventilation which creates a negative pressure
in the building as it will seriously a ect combustion and proper operation of the burner. Please note that exhaust fans or similar equipment can create a down draft in the chimney or starve the burner’s air supply. Either case may result in poor combustion or nuisance failures. A properly designed make-up air system in the equipment room will preclude these possibilities and is required to maintain proper combustion.
2-6
FIGURE 2 COMPONENT VIEW OF THE ICW UNIT
© The Fulton Companies 2012
SECTION 2 ICW-IOM-2012-1001 INSTALLATION
6. Eliminate potential for high risk situations for particulate matter to be in the combustion air supply (e.g., as a result of construction and maintenance activities).
Utilities
¡ The Gas Supply
Adhere to the following for gas supply installation:
1. Install gas piping in accordance with all applicable codes.
2. Ensure pipe and  ttings used are new and free of dirt or other deposits.
3. Ensure piping is of the proper size for adequate gas supply to the gas head assembly. Consult your gas company for speci c recommendations.
4. When making gas piping joints, use a sealing compound resistant to the action of lique ed petroleum gases. Do not use Te on tape on gas line heads.
5. Ensure no piping stresses are transmitted to the equipment. The equipment shall not be used as a pipe anchor.
6. Ensure all vent connections on diaphragms, gas valves, pressure regulators, and pressure switches (gas- red units) are vented per local code.
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
A quali ed installer, service agency or the gas supplier must perform installation and service on the fuel delivery system.
Do not use matches, candles,  ame or other sources of ignition to check for gas leaks.
What to do if you smell gas: Do not try to light the appliance. Do not touch any electrical switch. Do not use any phone in the building. Leave building and contact gas supplier from neighbor’s phone. If you cannot reach gas supplier, phone the  re department.
7. On gas- red units with NFPA 85 valve trains, ensure the vent valve is piped to atmosphere per local code.
8. During any pressure testing of the system at pressures in excess of 1/2 psig (14 inch W.C.), isolate the with the manual shuto valve (located at the end of the supplied gas train) from the gas supply piping system.
9. Ensure the supply pressure is regulated by a non-stacking, tight, shut-o regulator.
10. Arrange gas piping so that it does not interfere with any cover or burner, inhibit service or maintenance, or prevent access between unit and walls or another unit.
11. After gas piping is completed and before wiring installation is started, carefully check all piping connections, (factory and  eld), for gas leaks. Use an appropriate leak test solution.
¡ The Oil Supply
Adhere to the following for installation:
1. Fuel pipes must be of approved materials and of a diameter suitable for the quantity of oil being delivered to the burner. Vacuum must not exceed 10 in. (254 mm) of mercury at the pump inlet. Maximum inlet pressure to oil pump is 3 PSIG.
When making gas piping joints, maintain proper ventilation to reduce breathing hazards.
An exhaust fan may draw products of combustion into the work environment creating a possible hazard to personnel.
4 CAUTION
It is essential that only fresh air be allowed to enter the combustion air system. Foreign substances, such as combustible volatiles and lint in the combustion system can create hazardous conditions. If foreign substances can enter the air stream, the combustion air inlet must be piped to an outside location. Failure to do so will void the warranty.
To avoid failures due to poor combustion, ensure make-up air system is properly designed.
2. Make fuel connection in accordance with the details on the enclosed fuel
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-7
INSTALLATION ICW-IOM-2012-1001 SECTION 2
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
4 CAUTION
Loose  ttings in the fuel oil line will permit air to enter the fuel line and cause improper  ring.
pump cut sheet.
3. Ensure fuel oil piping is in accordance with local/national requirements.
4. Meet the maximum pressure allowed at the fuel oil pump inlet per the National Fire Protection Association (NFPA).
5. Oil burners are of a two-pass design system, requiring a return line and a supply line. The oil pump is factory set per Test Fire Sheet. Do not alter the setting without consulting the factory.
6. A stop valve, a check valve, and an oil  lter must be installed on the oil
supply line.
7. Ensure there are no loose  ttings. Loose  ttings in the fuel oil line will permit air to enter the fuel line and cause improper  ring.
Electrical Supply
Adhere to the following for electrical supply installation:
1. Locate electrical schematic diagram, a copy of which is inside of the panel box.
2. Ensure the information on the electrical drawing corresponds to your voltage and frequency. Check the supply voltage and make sure that there is no over- or under-voltage exceeding 10% of the nominal value.
3. Install a separate fuse switch for the contactor and a separate fuse switch for the circulating pump. If pump motor is 3/4 HP or larger, install an across-the-line starting switch ahead of the circulating pump motor.
4. Install wiring and ground in equipment in accordance with authority having jurisdiction or in absence of such requirements the National Electrical Code, ANSI/NFPA.
5. Provide a fused disconnect sized for the unit. Size fuses according to motor name plates and local electrical codes.
6. Connect power to the terminal strip as supplied on the inside of the panel box.
Water Supply
¡ Install Water Piping
All water supplies contain some solids, dissolved gases or dissolved minerals. These may cause corrosion, deposition and/or fouling of equipment. To prevent these contaminants from impacting boiler performance, valve operation and general pipe longevity, each location must be analyzed and treated accordingly.
2-8
Adhere to the following for water piping installation:
© The Fulton Companies 2012
SECTION 2 ICW-IOM-2012-1001 INSTALLATION
1. Isolation valves and unions are recommended on both water connections for ease of service.
2. Install piping so that the boiler is not supporting any additional piping.
3. Install manual purging valves in all loops and zones. Install a pressure­reducing (automatic  ll) valve in the cold water  ll line to the boiler system. Check that the proposed operation of zone valves, zone circulator(s) and diverting valves will not isolate air separator(s) and/ or expansion tank(s) from the boiler. Clearance from hot water pipes to combustibles must be at least 6 inches (152 mm).
4. Pipe the water supply line to the lower opening on the back of the boiler. Water stop valve should be in line between the boiler and the  rst piece of equipment. Hot water outlet should be piped to process/equipment requiring hot water. Water makeup supply should be installed. Hot water inlet should be piped to the make-up water supply.
5. Pipe the water safety valve from the outlet of the valve to a safe blow-o point.
NOTE: ´ Do not alter water temperature/pressure gauge assembly in any way.
6. Drain valve is connected to the lowest opening at bottom rear of boiler. Carry piping from the outlet of the valve to safe drain point. Provision should be made for easy access to drain valve of boiler.
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
NOTE: ´ The water connection on the top of the boiler is the outlet connection. The
water connection on the rear of the boiler is the inlet connection.
7. Install  ltration to remove particulates if appropriate.
8. Install bypass chemical feeder for corrosion inhibitor maintenance if appropriate.
9. Install corrosion coupon holder to assess corrosion inhibitor performance if appropriate.
NOTE: ´ The boiler is provided with a drain valve connection and a drain valve.
10. Heating system:
» An automatic pressure activated water make up valve with back
 ow preventer. It must be set to maintain required Net Positive Suction Head (NPSH) for re-circulating pumps, a positive system pressure at the highest point of at least 5-10 PSIG, and make up water valve should be designed to add water to the system at the outlet of the boiler and should not be fed directly into the boiler.
» Air removal equipment, including an air separator and automatic
breather valves, along with a functioning expansion tank . Each
must be designed to system speci cations.
11. When used in conjunction with a refrigeration system, install the boiler
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-9
INSTALLATION ICW-IOM-2012-1001 SECTION 2
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
4 CAUTION
A large amount of improperly treated make­up water can cause premature failure of the heat exchanger resulting from scale build
up. Scale build up will reduce the e ciency and useful life of the boiler and is not covered under warranty.
so that the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler. If the boilers are connected to heating coils (located in air handling units where they may be exposed to refrigerated air circulation)
such boiler piping systems must be equipped with  ow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
Water Chemistry Requirements
System water chemistry requirements are as follows:
§ pH: Range of 8.5 - 10.5
§ Oxygen: Less than 250 ppb (operating condition)
§ Total Iron/Copper: Less than 5 ppm
§ Corrosion Inhibitor: Capable of maintaining iron corrosion rates <2
mpy. Due to changing environmental restrictions a non-heavy metal ALL ORGANIC inhibitor is recommended which is designed for multi metal systems including ferrous metals and yellow metals such as copper and brass.
§ Chloride: Less than 250 ppm
Adhere to the following:
1. Refer to your water conditioning or chemical treatment supplier for analysis and recommendations for proper system conditions.
2. Follow a program with appropriate monitoring and maintenance of system water conditions as provided by your water conditioning or chemical treatment supplier.
3. Operate the boiler in a closed-loop system using water or water/glycol (not requiring a make-up water supply). A large amount of improperly treated make-up water can cause premature failure of the heat exchanger resulting from scale build up. Scale build up will reduce the
e ciency and useful life of the boiler and is not covered under warranty.
¡ Prevent Oxygen Contamination
There are several ways to prevent boiler water oxygen contamination:
§ Minimize system leaks to minimize make up water requirement
§ Do not use open tanks or  ttings
2-10
§ Do not use oxygen permeable materials anywhere in the water
system
§ Repair leaks in the system quickly
§ Eliminate  ttings wherever possible
© The Fulton Companies 2012
SECTION 2 ICW-IOM-2012-1001 INSTALLATION
§ Use air elimination devices in system piping
¡ Eliminate System Air
NOTE: ´ There are no built-in boiler air eliminating features.
Adhere to the following for air elimination:
1. The installation of an air separator and air eliminator (air vent) is required.
2. To prevent scale corrosion in boiler and associated piping, make up water must be kept to a minimum. This is best achieved by ensuring immediate repair of all leaks and that system pressure is maintained.
3. If a sealed diaphragm-type expansion tank is used, install an air eliminator in the hot water piping at the air separator.
4. If an air cushion type expansion tank is used, pipe tank directly into boiler supply.
5. On multi-zoned systems (or a system with both space and domestic water heating), air elimination must be provided either in the common piping or on every loop.
6. When the boiler is installed at a higher level than baseboard radiation (if used), air elimination must be provided directly above the unit.
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
The vent line connection on the gas pressure regulator must be piped to outdoor air by the installer in accordance with National Fuel Gas Code, ANSI Z223­1-1991 or latest addenda. In Canada, gas installations must be in accordance with the current CAN/CGA B149.1 and 2 and/or local codes.
4 CAUTION
Some soap used for leak testing is corrosive to certain types of metals. Use an appropriate leak test solution. Clean all piping thoroughly after completing the leak check.
Piping Specifi cations
For piping, the basic considerations are: the design temperature, the pressure
retained by the pipe, the  uid in the pipe, the load resulting from thermal expansion or contraction, impact or shock loads imparted such as water hammer, external loads, wind loads and vibration from equipment.
Adhere to the following for piping installation:
1. Ensure the arrangement of the piping and its appurtenances takes into consideration the location of other structures and equipment adjacent to the piping, which may result in freezing interference and/or damage as a result of expansion, contraction, vibration, or other movements.
2. Consider the appropriate location and orientation of valves necessary for safe operation and isolation of the piping. Valves are used in piping systems to stop and start the  ow of  uids, to regulate  ow, to prevent the back  ow, and to relieve excessive pressure build up in the piping.
3. Ensure all piping and piping components are suitable for the design temperatures, pressure and  uid used in the system.
4. Ensure all pipework is constructed from seamless mild steel pipe, Schedule 40 or Schedule 80 as required by code and/or application; or copper if system parameters allow.
5. During construction of the installation, ensure that no dirt, water, or residue from welding is left in the system.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-11
INSTALLATION ICW-IOM-2012-1001 SECTION 2
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
Hot pipework and vessels must be adequately insulated with material suited to the temperature and application to prevent both heat loss and personnel injury.
6. Provide expansion joints or properly designed and sited loops to accommodate thermal expansion. Thermal expansion should be calculated
using the maximum possible utilization  uid temperature, regardless of whether the pipe considered is in the feed or return circuit. Steel pipe will expand approximately 1 “ per 100’ over a 100° F temperature rise (1 mm per meter over 100 C rise).
7. Provide supports and anchors for all pipes where necessary to prevent undue stresses from being placed on items of equipment, including pumps, valves, and the boiler. Supports and anchors which will not interfere with thermal expansion should be chosen.
8. Screwed joints may be used for connections 2.5 inches (63.5 mm) and smaller. For larger diameters, all pipe joints should be either welded or  anged construction. Flanges should be 150# or 300# raised face  anges.
9. Cut screw threads carefully and accurately. If possible, new tools should be used. It is recommended that GR5 or higher tensile steel bolts be used for all  anged joints.
10. Use gaskets to make all  anged connections. Gasketing material must be suitable for use with the pressure, temperatures and  uids in the system. Ensure that all bolts are tightened evenly and to the torque recommended values provided by the gasket manufacturer.
11. Install high point bleeds at all high points in the system piping. 1/2” x 12” nipples welded in the top of the piping with ball valves and plugs attached are to be used.
12. Install all pipes with a pitch to facilitate draining and venting.
Insulation
After the appropriate system tests have been satisfactorily completed (see Testing section of this manual), all hot pipework and vessels must be adequately insulated with material suited to the temperature and application to prevent both heat loss and personnel injury. For inspection and maintenance purposes,
leave pumps,  anges, valves and  ttings uninsulated but suitably shielded for safety. Removable insulation may also be used over these components.
System Interfaces
Proper selection and installation of the components in the system will ensure proper and safe operation of the boiler. Consult Fulton representative or contact Fulton at (315) 298-5121.
2-12
¡ Fill Connection
The system is usually  lled from the lowest point, with the aid of a pump. On skid­mounted units, a  ll connection is provided in the inlet piping to the pump.
© The Fulton Companies 2012
SECTION 2 ICW-IOM-2012-1001 INSTALLATION
¡ Pressure Gauges
The range in which readings are expected to fall should comprise mid-scale on the pressure gauge chosen. Pressure gauges must be able to withstand overpressure equal to the rating of the safety relief valves, normally 100 psig.
NOTE: ´ The Water temperature pressure gauge should not be altered in any way.
Stack and Flue
An appropriately sized stack should be connected to the  ue gas outlet at the boiler. The proper  ue size and draft control is most important for proper burner operation. See Table 4.
TABLE 4  MINIMUM FLUE SIZES
Model Minimum Flue Size
inches (mm)
6 6 (152)
10 6 (152)
15 8 (203)
20 10 (254)
30 12 (305)
50 12 (305)
60 12 (305)
80 14 (356)
The  ue must be as large or larger than the outlet on the vessel. Avoid  ue piping and elbows by placing the equipment as close as possible to the chimney.
Adhere to the following for stack and  ue installation (see Figure 3):
1. Ensure the stack rises continuously to the connection at the chimney and contains no more than two bends at 45 degree angles or less. If required, as a result of space limitations, one 90 degree elbow (or tee) can be  tted at the back of the vessel.
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
Assure all electrical connections are powered down prior to attempting replacement or service of electrical components or connections of the equipment.
Cements for plastic pipe should be kept away from all sources of ignition. Proper ventilation should be maintained to reduce the hazard and to minimize breathing of cement vapors.
No shuto of any kind may be placed between the safety relief valve and the equipment, or in the discharge pipe between such valve and the atmosphere. Doing so may cause accidental explosion from overpressure.
Discharge from safety relief valve must be con gured so that there is no danger of scalding personnel or causing equipment damage. Provisions must be made to properly drain safety relief valve discharge piping.
2. Ensure 2 feet (0.6 m) of straight, horizontal  ue before any change in direction,  tting or draft regulator. This is to prevent potential pilot or main  ame failures due to back pressure build up during ignition. Any alternative stack arrangement must supply negative 0.02 to 0.04”wc.
3. Ensure the run in the total distance of stack ducting, as measured in a straight line from the outlet of the boiler to the outlet of the stack, does not exceed 25% of the rise. With the exception of the duct run previously described, horizontal sections of ducting must be avoided and should not exceed 4 feet (1.2 m) total. See Figure 3.
4. Ensure the stack, chimney, and any components associated with the stack, such as heat reclaimers or assist fans, are constructed from material that is rated for a 1000 F (538 C) operating temperature.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
For reasons of safety, the hot exhaust gas duct and chimney must be insulated or shielded within the locality of the heater in compliance with local codes and regulations.
4 CAUTION
The stack arrangement and draft conditions should be in accordance with the information in this manual for proper performance of the equipment.
2-13
INSTALLATION ICW-IOM-2012-1001 SECTION 2
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
Non-Fulton product information is for reference purposes only. No Fulton document may substitute for full review of documentation available from the component manufacturer.
4 CAUTION
Boilers damaged due to adverse water conditions are not covered by warranty.
The weight of all piping must be properly supported. Failure to support piping may result in equipment damage and/or system leakage.
5. Ensure the stack and chimney material complies with all applicable codes.
6. Make adequate provisions for the support of the weight of the chimney and stack to avoid having a load imparted to the outlet connection of the equipment.
7. Ensure the draft, when  ring, is negative and constant. A reading of -0.02 to -0.04”wc (-0.508 to -1.016 mm) when the unit and stack are cold usually
indicates su cient draft. When the unit is running and the stack is hot, the draft should read -0.04 to -0.08 “wc (-1.016 to -1.524 mm) negative.
8. The installation of a draft regulator by the client/contractor is recommended at all installations. This will help to maintain the required draft. The placement of the draft regulator should be as shown in Figure 3. Insulate the section of the chimney duct within the building.
9. Concentration levels of only a few ppm of chlorine containing compounds
in combustion air can produce serious corrosion of the  ue over long periods of time. High chlorine containing compounds such as carbon tetrachloride or perchloroethylene would be prime suspects.
¡ Exhaust Side Wall Venting
Boilers for which sidewall venting (Figure 4) may be utilized are propane, natural gas, or combination propane and natural gas sizes 10 to 30 HP.
Adhere to the following for installations requiring sidewall venting:
Piping must take into consideration potential for freezing interference and/ or damage as a result of expansion, contraction, vibration, or other movements.
Dirt, water, and/or other debris in the piping system after welding may result in equipment failure.
To maintain a reasonable temperature in the equipment area and ensure safety to personnel, the section of the chimney duct within the building should be insulated.
10. Flue vent piping must be pitched upward at ¼ in (6.35 mm) per one foot (3.048 m) of length.
11. An UL-approved Fulton factory-supplied draft fan must be installed to provide su cient draft (-0.02 to -0.04” wc) to safely vent products of combustion.
12. The draft fan should be located as close to the  ue outlet as possible.
13. Draft regulation su cient to lower the draft to between -0.02 to -0.04 “ wc may be required. The draft regulator must be between the boiler and the fan.
14. The draft fan shall have an air  ow proving switch wired in series with the boiler air safety switch.
15. The sidewall vent total length from boiler exhaust to termination shall not exceed 35 feet (10.6 m) with 4 elbows maximum.
Testing
Upon completion of the installation, perform the following testing:
1. A pneumatic test of water piping not exceeding 15 psig.
2-14
2. Leak tests at all welds and joints to ensure that the system is free from leaks.
© The Fulton Companies 2012
SECTION 2 ICW-IOM-2012-1001 INSTALLATION
Roof
Minimum
6' Above
Any Structure
Within 30'
Support As
Necessary
Install Appropriate Weather Cap
Horizontal Run 2'
Draft Regulator (If Necessary)
Draft Regulator (If Necessary)
Expansion Joints As Required
Horizontal Run 2'
Cleanout
Door
60°
(45° Min.)
Cleanout
Door
Cleanout
Door
This Distance Must Not Exceed 25% Of Total Rise
Baffle
3'
3'
30°
Max
Stagger
Entrances
A A
A-A
Total
Rise
FIGURE 3  TYPICAL STACK ARRANGEMENT
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-15
INSTALLATION ICW-IOM-2012-1001 SECTION 2
Air Flow Safety Switch
U.L. Approved Induced Draft Fan
Side Wall
Vent
Termination
(By Others)
Side Wall Vent (By Others)
FIGURE 4  TYPICAL SIDEWALL VENTING
2-16
© The Fulton Companies 2012
OPERATION
INTRODUCTION
INSTALLATION
1 2
OPERATION
MAINTENANCE WARRANTY & PARTS
3
4 5
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
3-1
OPERATION ICW-IOM-2012-1001 SECTION 3
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
Do not operate, or allow others to operate, service or repair this equipment unless you (they) fully understand all applicable sections of this manual and are quali ed to operate/maintain the equipment.
Defective or improperly installed equipment is hazardous. Do not operate equipment which is defective or improperly installed.
Defective equipment can injure you or others. Do not operate equipment which is defective or has missing parts. Make sure all repairs or maintenance procedures are completed before using the equipment. Do not attempt repairs or any other maintenance work you do not understand.
Start-Up Preparation & Installation Review
Review the installation section of this manual carefully. Con rm accordance with the Installation guidelines, including:
1. You have read and followed all safety information.
2. The equipment area is in conformance with established boiler room requirements. Review national and local codes.
3. There are no obstructions left in the  uid circuit from pressure leak testing
such as blanking plates in  anged joints.
4. Pipework is free to expand naturally when hot. Open all valves to user circuits including air bleed valves at high points and drains at low points in the piping system, and the liquid level test connections in the expansion section of the combination tank.
5. Boiler is located with the proper clearances as shown in Installation section of this manual.
6. Relief valves have been properly piped to  oor drains.
7. Flue gas from the boiler is properly vented.
8. Combustion air openings are not obstructed in any way and have adequate capacity.
9. There are no  ammable liquids, materials or hazardous fumes present in the environment.
4 CAUTION
Installation in accordance with the guidelines within the manual should be fully completed before performing the initial start-up; and start-up must be complete prior to putting the unit into service. Starting a unit without the proper piping, venting or electrical systems can be dangerous and may void the product warranty.
“Factory Trained Personnel” refers to someone who has attended a Fulton Service School speci cally for the equipment covered in this manual.
10. Nothing was damaged or knocked loose during shipment and installation. Inspect the main gas train and trim assembly to be sure they were not damaged during shipment or installation.
11. Local authorities where approval for start-up is required have been noti ed. In some localities,  nal inspection of services may be required.
12. Installation checklist is complete.
Filling The System/Air Removal
We recommend boil out be accomplished prior to boiler system operation. This procedure ensures that all oils, sealants and other organic compounds are solublized and removed from the boiler and piping. Consequently, if boil out is not accomplished prior to system operation, low water alarm, erratic water level control and surging may occur.
NOTE: ´ Our experience has indicated that if boil out is not performed as
recommended, there is little bene t from boil out once the boilers have been in operation for over 50 hours.
3-2
© The Fulton Companies 2012
SECTION 3 ICW-IOM-2012-1001 OPERATION
} FILL AND AIR REMOVAL PROCEDURE
1. Close combination shuto /purge valve in supply, all drain cocks, the shuto valve for the pressure reducing ( ll) valve, and all manual air vents.
2. Open all other system shuto valves and one of the zone valves, the vent on the combination shuto / purge valve and the shuto valve to the pressure-reducing ( ll) valve.
3. Water will now begin to  ll the system. Air will escape through the vent on the combination shuto / purge valve. Continue  lling until a constant stream of water (no bubbling) is discharged from the vent.
4. Close the zone valve on the purged loop, and open the zone valve on the next loop to be purged. When all air has escaped and only water is discharged, close the zone valve. When all zones have been purged (one at a time), close the vent on the combination shuto /purge valve.
5. At this point, the system has been initially  lled. However, air pockets may still remain at high points in the system and in heating loops above the level of the combination shut/o purge valve. It is quite possible, depending on the particular system that all piping above the combination shuto /purge valve still contains air. If manual vents are installed on the system high points, these should be opened to vent these locations. When only water is discharged from all vents, the initial purging is complete.
6. Open the combination shuto / purge valve (keep the vent closed). With the gas shuto valve closed, turn on power to the boiler and operate the circulator. Circulate the system water for approximately 30 minutes to move all air to the automatic air separation point.
7. Again, open manual air vents at high points of heating loop until a constant stream of water is discharged from the vent. Close the vent and make sure it’s watertight. Repeat procedure for all high points and for every zone.
8. Check temperature/pressure indicator reading, which should equal the pressure-reducing ( ll) valve set pressure. No more water should be entering the system. Close the shuto valve on the cold-water  ll line.
9. Visually inspect all pipe joints and equipment connections for leaks. If necessary, drain system, repair leaks and re ll/purge the system. If no pressure drop is detected for a period of two hours under pressure, the system may be considered watertight.
10. When purging is completed, make sure the following are open— combination shut-o /purge valve, shuto valve to pressure reducing ( ll valve), shuto valve in cold water  ll line, and shuto valve in return line.
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
Crystalline silica may be present in components of this equipment. Exposure to crystalline silica may pose signi cant health hazards, including but not limited to eye and respiratory system damage. Per the Centers for Disease Control and Prevention (CDC) and Occupational Safety and Health Administration (OSHA), appropriate Personal Protective Equipment must be worn to minimize exposure to hazardous substances. Refer to most current guidelines o ered by the CDC and OSHA for more information, including Personal Protective Equipment recommendations.
4 CAUTION
Do not use this equipment if any part has been under water (or subjected to heavy rains/water if the equipment does not have NEMA 4 wiring, controls and instrumentation). Immediately call a quali ed service technician to inspect the equipment and to replace any part of the control system and/or gas control(s) which have been under water.
Please read these instructions and post in an appropriate place near the equipment. Maintain in good legible condition.
11. Make sure the following are closed - all drain cocks, the vent on the combination shuto -purge valve, & all manual vents. Reset zone valves to normal mode of operation and turn o power to boiler.
12. Open fuel shuto valve, allowing fuel to  ow to boiler.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
3-3
OPERATION ICW-IOM-2012-1001 SECTION 3
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
Wear eye and hand protection for your safety.
Use extreme caution when opening circulating pump plug if system temperature is elevated.
When opening any drains on the equipment or piping system, steps should be taken to avoid scalding/ burning of personnel due to hot
 uids. Whenever possible, the system should be cooled prior to opening any drains.
Use only your hand to turn valve handles. Never use tools. If the handle will not turn by hand, don’t try to repair. Forced or attempted repair may result in  re or explosion.
Start-Up Service
If start-up service has been included in the order, the factory should be contacted after the installation has been successfully completed and approved by the client’s representative or engineers. Where possible, contact the factory at least three weeks before a Fulton service engineer is required on site.
Consider the following in preparation for your on-site visit:
1. All procedures covered in manual sections Start-Up Preparation and Fill the System, including installation review, air testing of piping, pump
alignment (where applicable), and  lling the system must be completed before the service person’s arrival.
2. Depending on the size of the system and the amount of service time contracted, start-up service includes  ring the boiler, checking, verifying and adjusting all safety settings.
3. Careful preparation can expedite the commissioning of your boiler. Most delays can be avoided by following the instructions in this manual. Failure to complete required procedures properly can result in the need for further service time, at extra cost to the customer.
4. Service people will not commence start-up if there are obvious system de ciencies. However, start-up service in no way constitutes a system design check or approval of the installation.
5. In addition to commissioning the boiler, the service person will also familiarize heater room personnel with the operation of all Fulton equipment. Personnel must be quali ed to understand the basic operation and function of controls.
Initial Start-Up
Adhere to the following:
1. Turn on the main power fuse switch.
2. Activate the boiler power ON switch, located on the side of the panel box.
NOTE: ´ The Low Water Control will also be activated when the boiler is powered
on. With the unit full of water, the Low Water Relay requires manual reset.
3. If for any reason the water leaves the unit the Low Water Control will automatically shut it down and if audible alarm is installed, alarm will activate.
¡ Combustion
It is critical for all personnel to be familiar with start up, controls, and shutdown procedures.
3-4
© The Fulton Companies 2012
SECTION 3 ICW-IOM-2012-1001 OPERATION
} STARTING THE BURNER  GAS
1. Verify incoming gas pressure.
2. Open the manual gas cocks on the pilot and main lines on the gas head.
3. Switch on the main power to the burner. If the water level relay is equipped with manual reset, depress the button on the box.
4. Check motor rotation.
5. Start the burner by turning on the switch on the outside of the panel box. The blower motor will begin to deliver air into the furnace.
6. When su cient air pressure has built up in the blower housing, the air
switch located on the top side of the blower housing will make contact and after a seven-second delay, will allow the ignition transformer and pilot valve to operate. This creates pilot  re.
7. When the pilot  ame is established, the  ame rod or UV scanner senses the electrical current (microamps). The signal is transmitted to the protectorelay, which opens the main gas valve for full  re.
NOTE: ´ For new installations/burner has been disassembled, the burner may not
 re upon  rst attempt because air must be cleared from gas lines. The burner protectorelay may go into lockout mode; allow a period of one minute to elapse, then repeat procedure for starting the burner.
} STARTING THE BURNER  OIL
1. Open the oil line’s shut-o valves.
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
Do not attempt to start the equipment for any testing prior to  lling and purging the vessel. A dry  re will seriously damage the equipment and may result in property damage or personnel injury and is not covered by warranty. In
case of a dry  ring event, shut o the fuel supply and allow the vessel to cool to room temperature before  uid is reintroduced to the pressure vessel.
4 CAUTION
A quali ed installer, service agency or the gas supplier must perform installation and service on the fuel delivery system.
2. Verify oil is present at the oil pump.
3. Switch on main power to burner. If the water level relay is equipped with manual reset, depress the button on the box.
4. Start the burner by turning on the switch on the outside of the panel box. The blower motor will begin to deliver air into the furnace.
5. As the blower starts, the magnetic oil valve is energized, allowing the oil pump to deliver fuel for ignition.
6. If the protectorelay does not sense ignition via the CAD cell or UV scanner located on the top of the burner in approximately 15 seconds, it will shut down the burner.
Flame Programmers
Refer to inserts provided.
Before commissioning the equipment, verify with authorized personnel that the gas lines have been purged.
Never attempt to operate equipment that has failed to pass all the safety checks.
After checking controls by manual adjustment, make sure they are always reset to their proper settings. Contact your Fulton dealer before modifying the equipment.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
3-5
OPERATION ICW-IOM-2012-1001 SECTION 3
! WARNING
This boiler is equipped with an ignition device which automatically lights the burner. Do not try to light burner by hand.
Operating this equipment beyond its design limits can damage the equipment and can be dangerous. Do not operate the equipment outside of its limits. Do not try to upgrade the equipment performance through unapproved modi cations. Unapproved modi cations may cause injury, equipment damage, and will void the warranty.
Check daily that the equipment area is free and clear of any combustible
materials, including  ammable vapors and liquids.
Do not tamper with safety features provided by the operating controls.
Operating Controls
¡ Water Relief Valve
The Water Relief Valve releases extra pressure.
¡ Water Outlet Valve
The Water Outlet Valve serves as the isolation valve for the system.
¡ Temperature Control
The Temperature Control is a digital indicating control used to turn the boiler on and o , and to control the  ring rate when the boiler is modulated. The digital display will show both the boiler process temperature and the boiler setpoint.
¡ Operating Temperature Aquastat
The Operating Temperature Aquastat controls the working temperature of the boiler. This an ASME CSD-1 code control which will turn the boiler o when the water temperature exceeds its setpoint. It is an auto-reset control.
4 CAUTION
Operation of the circulating pump for any amount of time without  rst bleeding will result in equipment damage.
For all systems containing boilers or un red steam generators, the water chemistry in the boiler (generator) must be kept within required limits. Failure to do so may cause premature pressure vessel failure and poor steam quality and will void the warranty.
¡ High Limit Aquastat/High Temperature Limit
The High Limit Aquastat/High Temperature Limit prevents over-temperature conditions. It is an ASME CSD-1 code control which includes a manual reset feature for over-temperature. Press the manual reset button when the temperature drops to reset the control.
¡ Air Safety Switch
This switch is controlled by the pressure of air entering the burner. This switch proves that the blower fan is delivering combustion air.
¡ Probe Type Low Water Cut-Off
The Low Water Cut-O shuts down the unit when the water level is too low, after a three-second time delay to prevent nuisance shut downs. Fulton boilers are equipped with ASME CSD-1 Code controls which include a manual reset feature on the burner low water cut o relay. Press the low water reset button to reset the control, and the boiler will start.
3-6
© The Fulton Companies 2012
SECTION 3 ICW-IOM-2012-1001 OPERATION
Circulating Pump Switch
The fused switch that controls the circulating pump should be kept in the ON position at all times during boiler operation and non-operating mode of the boiler. It should be placed in the OFF position when repairs or adjustments must be made.
Cycle Testing
The boiler should be cycled tested and automatically allowed to go through its normal starting sequence several times to verify that all components are functioning properly. This will also verify that combustion is set properly so that
boiler light o has a smooth transition from ignition to main  ame.
A minimum of 10 cycles should be met without any  ame failures, with combustion readings comparable to the factory test  re sheet and no interlocks causing the boiler to shutdown.
Before Leaving the Installation
1. Check all controls to insure they are operating properly. Cycle the boiler several times by raising and lowering operating temperature on the thermostat.
2. Make sure the installation complies with all applicable codes.
! WARNING
WHAT TO DO IF YOU SMELL GAS :
Do not use matches, candles,  ame or other sources of ignition to check for gas leaks. Do not try to light the appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach your gas supplier, call the  re department.
Should overheating occur or the gas supply fails to shut o , manually shut o the gas supply external to the equipment .
4 CAUTION
If any “Manual Reset” limit device trips DO NOT reset without determining and correcting the cause. (Manual Reset Limits may include:  ame safeguard, high or low gas pressure, high temperature limit, low water).
3. Turn switch to OFF position.
Never tamper with low water (liquid level) cuto sensors or circuitry.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
3-7
OPERATION ICW-IOM-2012-1001 SECTION 3
3-8
© The Fulton Companies 2012
MAINTENANCE
INTRODUCTION
INSTALLATION
1 2
OPERATION
MAINTENANCE
WARRANTY & PARTS
3
4
5
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4-1
MAINTENANCE ICW-IOM-2012-1001 SECTION 4
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
Follow all proper lockout/tagout procedures for service.
Before beginning any maintenance, ensure area is free of any combustible materials and other dangers.
What to do if you smell gas: Do not try to light the appliance. Do not touch any electrical switch. Do not use any phone in the building. Leave building and contact gas supplier from neighbor’s phone. If you cannot reach gas supplier, phone the  re department.
4 CAUTION
Daily Maintenance Schedule
Daily maintenance and inspection must include the following:
1. Observe operating temperature and general conditions.
2. Make sure that the  ow of combustion and ventilating air to the boiler is
not obstructed.
3. Ensure boiler area is free and clear of any combustible materials, including  ammable vapors and liquids.
Weekly Maintenance Schedule
Weekly maintenance and inspection must include the following:
1. Check inlet gas pressure at the beginning of the gas train.
2. Observe the conditions of the main  ame. A normal high  re  ame shows an orange screen with a blue halo. In Low  re, the burner should display a reddish-orange glow.
3. Correct air adjustment is essential for the e cient operation of this boiler. If an adjustment to the combustion is necessary, the  ue gas composition should be checked with a carbon dioxide (CO2) or oxygen (O2) analyzer to set conditions. Refer to Procedure for Primary Air Adjustment/
Inspection and Procedure for Secondary Air Adjustment/Inspection
sections of this manual.
All maintenance procedures should be completed by trained personnel. Appropriate training and instructions are available from the Fulton Service Department at (315) 298-5121 or your local Fulton Thermal Representative.
In order to meet warranty conditions, ensure all appropriate maintenance activities are performed.
Monthly Maintenance Schedule
The following steps should be carried out monthly:
1. Make sure main power switch is o before starting work. I
2. Test low gas pressure switch and high gas pressure switch.
3. Clean water pump strainers.
4. Check scanner and ignition electrodes.
5. Check starter contacts. Burned or pitted contacts should be replaced. Do not use sand paper or  le to clean.
6. Clean water traps and strainers in fuel lines.
7. View  ame detection strength via the boiler control.
8. Test high-limit temperature control by reducing setting below the operating temperature. Burner should shut o . Return high limit to previous setting. Then press the manual reset.
9. Test operating temperature control by reducing temperature setting as necessary to check burner operation.
4-2
© The Fulton Companies 2012
SECTION 4 ICW-IOM-2012-1001 MAINTENANCE
Recommended Semi-Annual Maintenance Schedule
The following steps should be carried out semi-annually:
1. Clean the gas burner assembly:
» Disconnect the gas head from the burner by disconnecting the
union. Withdraw the burner assembly and clean the ignition electrode.
» Check that the settings of the gap, if applicable, and ignition
electrode are accurate.
» Reassemble the burner assembly and check the scanner setting.
» Check the combustion e ciency of the burner and adjust if
necessary.
2. Check electrical controls and motors for correct operation.
3. Check water pump for correct operation.
4. Shut o the boiler completely and drain.
5. Replace hand hole gaskets as follows:
! WARNING
Crystalline silica may be present in components of this equipment. Exposure to crystalline silica may pose signi cant health hazards, including but not limited to eye and respiratory system damage. Per the Centers for Disease Control and Prevention (CDC) and Occupational Safety and Health Administration (OSHA), appropriate Personal Protective Equipment must be worn to minimize exposure to hazardous substances. Refer to most current guidelines o ered by the CDC and OSHA for more information, including Personal Protective Equipment recommendations.
Never use open  ame or other sources of ignition to check for gas leaks.
» Remove the hand hole assembly using a 1-1/4” tee handle
wrench or 1-1/4” 1/2” drive socket wrench. See Figure 5. Remove the old gasket and thoroughly clean the surface on the boiler and the plate.
4 CAUTION
All maintenance procedures should be completed by trained personnel. Appropriate training and instructions are available from the Fulton Service Department at (315) 298-5121 or your local Fulton Thermal Representative.
In order to meet warranty conditions, ensure all appropriate maintenance activities are performed.
Use caution when using any cleaning solutions. Refer to local regulations for proper cleaning solution disposal.
If the gasket leaks while pressure is being built up, tighten only enough to stop leakage. Never tighten more than necessary to prevent leakage. Excessive tightening may shorten the life of the gasket.
FIGURE 5  REMOVE ASSEMBLY WITH TEE HANDLE WRENCH
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4-3
MAINTENANCE ICW-IOM-2012-1001 SECTION 4
4 CAUTION
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
All maintenance procedures should be completed by trained personnel. Appropriate training and instructions are available from the Fulton Service Department at (315) 298-5121 or your local Fulton Thermal Representative.
In order to meet warranty conditions, ensure all appropriate maintenance activities are performed.
6. Fit the hand hole assembly as follows:
» Place the gasket on the hand hole plate and ensure that it is
seating correctly. Do not use any grease, lubricant, or adhesive.
» Position the plate in the boiler. Set the yoke and tighten the
securing nut su ciently enough to provide a snug  t. Verify the position of the plate in the boiler, then make it hand tight and then snug with wrench about 1/4 turn. Do not compress excessively. See Figures 6 and 7.
» Re ll the boiler with fresh water.
FIGURE 6  CORRECT PRESSURE ON GASKET
FIGURE 7  OVERCOMPRESSED GASKET
4-4
© The Fulton Companies 2012
SECTION 4 ICW-IOM-2012-1001 MAINTENANCE
4 CAUTION
Recommended Annual Maintenance Schedule
All information in this manual is for
The following steps should be carried out annually:
1. Have combustion (CO2, O2, CO) and input checked by appropriate personnel. See Procedure for Primary Air Adjustment/Inspection and Procedure for Secondary Air Adjustment/Inspection sections of this manual.
reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
2. Clean  ues as follows:
» Remove the burner and  ue cover plate.
» Wire brush  ue passages. See Figure 8.
» Remove clean-out plugs at lowest part of unit (See Figure 9) and
clean the bottom of combustion chamber.
» Remove all soot from the top, and from the clean out plugs at the
bottom, with a vacuum cleaner.
» Replace clean out plugs carefully so as not to damage insulation.
NOTE: ´ Dirty  ues can cause air  ow restrictions resulting in poor combustion and
loss of e ciency.
All maintenance procedures should be completed by trained personnel. Appropriate training and instructions are available from the Fulton Service Department at (315) 298-5121 or your local Fulton Thermal Representative.
In order to meet warranty conditions, ensure all appropriate maintenance activities are performed.
If  ame and/or gas is permitted to exist in the blast tube area, back ring and destruction of electrodes may result. Ensure primary air adjustment is adequate to avoid this condition.
FIGURE 8 - WIRE BRUSHING THE FLUE PASSAGES
FIGURE 9 - REMOVING CLEAN OUT PLUGS
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4-5
MAINTENANCE ICW-IOM-2012-1001 SECTION 4
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
Follow proper lockout / tag out procedures for the electrical, gas and water connections. Use caution when lifting heavy parts.
4 CAUTION
All maintenance procedures should be completed by trained personnel. Appropriate training and instructions are available from the Fulton Service Department at (315) 298-5121 or your local Fulton Thermal Representative..
Procedure for Primary Air Adjustment/Inspection
The primary air adjustment control is located at the top righthand side of the burner assembly. This damper-type air controller is used to introduce air to the fuel supply of the burner. The purpose of the primary air adjustment is to
proportionally divide the air to the center or outer  re chamber.
It is important to the combustion process to maintain proper air mixtures between the outer service and the center of the blast tube area. Fire should be on the outside wall and not the blast tube area. Damper positions are as follows:
§ Open: Most of the air is forced down the blast tube, and less air is going
down the outside wall of the de ector face and  re chamber.
§ Closed: Less air is forced down the blast tube, and most of the air is going
down the outside wall of the de ector face and  re chamber.
NOTE: ´ If it is necessary to close the damper due to a rumbling  re, close it slowly
and no more than 1/4th of the distance of the swing of the damper assembly.
Perform inspections as follows:
1. Visually inspect down the blast tube. If heat,  ames, or fumes are backing up through the burner plate area, the damper must be opened up.
After a new Fulton Boiler has been in operation for several months, pieces of burned metal will be found in the space at the bottom of the boiler. These pieces of metal are the remains of a light gauge metal form which was used during manufacture for forming the boiler insulation. This is a normal
condition and does not a ect the e ciency or the life of the boiler in any way.
2. Visually con rm, via the sight glass, that  re is completely covering the
walls. If the  re is tunneling down or is not on the outside wall, e ciency will drop. If required, use a micro-amp meter to verify  re signal as damper is moved. Adjust as necessary.
Procedure for Secondary Air Adjustment/Inspection
The secondary air adjustment, or main air control, is located at the fan housing face. This control is used to supply the burner with excess air needed for good combustion.
It is important to ensure that the lowest level of excess oxygen is present, while still maintaining a high level of carbon dioxide and no carbon monoxide. It is
best to measure the  ue gas burn with the stack in excess of 420 F (216 C).
Perform inspections as follows:
1. Use an O2 or CO2 test kit to determine the percent of excess air in the combustion mixture. Adjust main air control as needed to reach optimal
e ciencies. Generally a boiler stack area is used to measure the percent of oxygen and carbon dioxide in the fuel.
4-6
© The Fulton Companies 2012
SECTION 4 ICW-IOM-2012-1001 MAINTENANCE
2. Adhere to the following:
Gas-Fired Unit It is a good policy to have 3.5-4.0% excess oxygen, which will
provide 10.5-9.5% excess carbon dioxide.
Oil-Fired Unit It is a good policy to have 4.0% excess oxygen, which will
provide 11.0% excess carbon dioxide.
Verify that carbon monoxide level is zero. To do this, use a Bacharach sni er and CO tubes to prove a clean burn.
Note: Actual values may change when boiler is installed and connected to appropriate stack. Refer to
factory test  re sheet for original factory settings.
3. To increase the oxygen in the burner, open air adjustment to right. To reduce the secondary air, move air adjustment to the left.
NOTE: ´ Too much oxygen will blow the pilot out. Too little oxygen will make the
boiler burn dirty.
Procedure for Flame Scanner Adjustment
Flame scanner adjustments are made with the detectors installed and the burner running. It is essential to obtain optimum  ame signal detection for safe and continual operation of the control relay.
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
4 CAUTION
All maintenance procedures should be completed by trained personnel. Appropriate training and instructions are available from the Fulton Service Department at (315) 298-5121 or your local Fulton Thermal Representative.
Ensure that the blower/gas train assembly is fully supported during removal/cleaning or burner, as the transition elbow will be removed.
¡ Gas Unit
Perform adjustment as follows:
1. Close gas cocks on gas train assembly. This will prevent gas from going into the burner.
2. Turn boiler on while microampmeter is in place.
3. During the ignition trial period, determine if the microampmeter exceeds #1. If yes, it is likely picking up ignition interference and realignment is necessary. It may be necessary to place a reduced scanner ori ce plug into the scanner eye area.
4. Repeat steps 1 - 3 until a reading of #1 or less is achieved on the microampmeter.
5. Reopen gas cocks and adjust the scanner signal response to maximum possible signal.
¡ Oil Unit
Perform adjustment as follows:
1. Turn power to panel OFF.
2. Disconnect the hot wire to the oil valves. This will prevent the oil valves from opening.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4-7
MAINTENANCE ICW-IOM-2012-1001 SECTION 4
! WARNING
Extreme caution must be exercised when checking a failing transformer. They are capable of producing very high voltages which may result in personal injury and death.
3. With microampmeter in place, turn power to the panel ON.
4. During the ignition trial period, determine if the microampmeter exceeds
#1. If yes, it is likely picking up ignition interference and realignment is
necessary. It may be necessary to place a reduced scanner ori ce plug into the scanner eye area.
5. Repeat steps 1 - 3 until a reading of #1 or less is achieved on the
microampmeter.
6. Turn power OFF. Hook the wire up again, and turn power ON. Start boiler
to ensure the safety light is o .
Procedure for Removing/Cleaning the Burner
Perform the following steps:
1. Remove all bolts that connect the transition elbow to the burner plate, and to the scroll tube.
2. Pull burner out of unit by  ange.
3. Inspect burner and wipe o (do not scrub or use wire brush) any soot or foreign material that may have accumulated. If available, use compressed air to clear the burner. Wipe out the inside of the burner with a clean cloth.
4. Reverse removal steps for reinstallation of the burner assembly.
5. Test  re the boiler and use a combustion analyzer to ensure that the fuel/ air ratio is set correctly throughout the range. Refer to the Fulton factory test  re sheet for combustion settings.
Procedure for Controls Voltage Transformer Inspection
The controls voltage transformer supplies a suitable power supply to the controls circuit in situations where the mains supply voltage di erent than the controls voltage. The controls voltage can vary depending on application. Refer to the electrical print supplied with the boiler to determine the controls voltage.
To verify controls transformer voltage, use a DMM (digital multi-meter or equivalent):
1. Measure the voltage on the secondary side of the transformer.
2. Compare this voltage to the voltage stated on the electrical drawing.
Typical 120VAC controls allow for a +10% and a -15% voltage  uctuation.
3. Replace the controls voltage transformer as necessary.
4-8
© The Fulton Companies 2012
SECTION 4 ICW-IOM-2012-1001 MAINTENANCE
Procedure for Soot Cleaning
Perform the following:
1. Determine if  ues are dirty by checking stack temperature with a stack
thermometer. If temperatures are in excess of 600 F (315 C) while the boiler is operating, the  ues are likely dirty/restricted in some other manner.
NOTE: ´ Usually soot cleaning is performed annually, unless the burner setting has
been altered and excessive soot has been produced as a result.
2. Remove burner and  ue cover plates.
3. Using a wire brush, carefully remove soot from  ue passages.
4. Clean out plug at lowest part of unit and clean passages between ribs and bottom of combustion chamber.
5. Remove all soot with a vacuum cleaner. This may be carried out from the top and via the inspection doors at the bottom.
6. Replace clean-out plug carefully so as not to damage insulation.
7. Replace burner and  ue cover plates.
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
After All Repairs or Maintenance
1. Follow “Pre-Start Check List” and all Safety Checks.
2. Fire the boiler and perform combustion safety checks.
3. Analyze combustion throughout the range and verify proper operation of safety devices.
Troubleshooting
Please refer to Troubleshooting tables that follow.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4-9
MAINTENANCE ICW-IOM-2012-1001 SECTION 4
Troubleshooting Gas Fired Boilers
Problem Potential Cause Potential Remedy
Burner Cut-O / Ignition Failure/ Flame Failure
Power Supply
Gas Supply
Ignition Electrodes
Bad Air Switch
Dirty or defective UV Scanner
Transformer
Flame Safeguard Control
Contact open on air safety switch
Loose Wire Connection Check connections to all components.
Scanner wiring reversed at panel box
Protectorelay
Check fuse or circuit; reset or replace, as necessary.
§ Check to be sure main gas cock is not
closed. Check coil in gas valve with OHM meter. Replace if faulty. Check gas regulator setting and readjust as necessary. Check inlet gas pressure and increase or decrease as necessary.
§ Check for gas pressure and for intermittent
supply problems. Gas pressure for natural gas should be 4 in to 11 in wc at the head of the train.*
Check electrodes for carbon buildup and clean if necessary. Check for proper adjustment. Readjust if necessary. Check for cracks in porcelain; if found replace.
Check for bad air switch by jumpering the two air switch leads at the terminal block. If the boiler starts and runs with these terminals jumpered, the air switch should be replaced.
Check for debris on  ame scanner and clean or replace as needed. Ensure scanner is properly located.
Check voltage between transformer leads at terminal block to be sure transformer is being powered.
Check voltage between ignition terminal and neutral. Check must be made before control locks out on safety. If no power, replace control.
Adjust to proper setting
Change to correct terminals.
Check voltage between pilot terminal and ignition terminal. Check must be made before control locks out on safety. If zero voltage, clean relay contacts and recheck for power. If no power, replace control.
* For natural gas  red boilers. Refer to the test  re sheet for all other fuels.
4-10
© The Fulton Companies 2012
SECTION 4 ICW-IOM-2012-1001 MAINTENANCE
Troubleshooting Gas Fired Boilers
Problem Potential Cause Potential Remedy
Poor Combustion
Burner back  res
Refractories
Not Enough Air/Build-Up on Fan Wheel (Rich; Burner Hums)
Fuel Valve Adjusted Too High (Rich; Burner Hums)
Too Much Air (Lean; Unstable
Flame)
Gas Valve Adjusted Too Low
(Lean; Unstable Flame)
Draft
Dirty Flue
Negative Room Pressure
Refractories
Ignition Electrodes
UV Scanner
Draft
Negative Room Pressure
Check refractories to see if they are cracked or broken in pieces. Replace as necessary.
Check CO2/O2 levels. If rich, disassemble  lter housing and gas train. Look inside inlet to the fan. If there is build-up on the fan blades, clean fan. Recheck the CO2/O2 and adjust gas valve as necessary for all combustion points.
Check CO2/O2 levels. Check gas pressure at outlet of valve. If the pressure is too high, make an adjustment at the valve. Be sure to check all combustion points.
Check fan discharge pressure. If too high, adjust damper. Check CO2/O2 levels and adjust gas valve as necessary. Be sure to check all combustion points.
Check CO2 and O2 levels. Check pressure at outlet of the valve. If too negative, adjust gas valve as necessary.
Check draft with a gauge. Draft should be a -.02
in to -.04 in wc with burner o or -.04 in to -.06 in when operating. May need to install a barometric damper.
Check  ue for carbon buildup or blockage. Clean  ue passages with brush.
Make sure no exhaust fans are running in the boiler room.
Check refractories to see if they are cracked or broken in pieces. Replace as necessary.
Check electrodes for carbon buildup and clean if necessary. Check for proper adjustment. Readjust if necessary. Check for cracks in porcelain; if found replace.
Check for debris on  ame scanner and clean as needed. Check for proper location of detector.
Check draft with a gauge. Draft should be a -.02
in to -.04 in wc with burner o or -.04 in to -.06 in when operating. May need to install a barometric damper.
Make sure no exhaust fans are running in the boiler room.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4-11
MAINTENANCE ICW-IOM-2012-1001 SECTION 4
Troubleshooting Gas Fired Boilers
Problem Potential Cause Potential Remedy
Check gas pressure coming into gas train. If low, maintain pressure contact gas company. Should
Boiler will not maintain temperature
Gas Supply
Dirty Flue
Aquastat
Scale Built up in boiler
Refractories
Boiler Size Boiler may be undersized.
be 7 in to 11 in wc /natural gas. Check coil in gas valve with AMP meter. Replace if bad. Check gas regulator setting and readjust as necessary.
Check  ue for carbon buildup or blockage. Clean  ue passages with brush.
If power is on, check across aquastats to verify power through the switch. If bad, replace.
Refer to Recommended Daily Maintenance section of this manual.
Check refractories to see if they are cracked or broken in pieces. Replace as necessary.
4-12
© The Fulton Companies 2012
SECTION 4 ICW-IOM-2012-1001 MAINTENANCE
Troubleshooting Oil Fired Boilers
Problem Cause Remedy
Burner Cut O / Ignition Failure/ Flame Failure
Power Supply
Transformer
Cad Cell
Protectorelay
Oil Supply
Ignition Electrodes
Primary air adjustment
Oil Valve
Oil Pump
Aquastat
Loss of oil prime
Oil Nozzle Check for clogged nozzle; clean or replace
Check fuse or circuit breaker and replace as necessary.
Check voltage between transformer leads at terminal block to be sure the terminal is being powered.
Check for ignition interference. To verify cad cell is working, place a lit candle in front of photo cell at the proper time.
Check voltage between pilot terminal and ignition terminal. Check must be made before control locks out for safety. If zero voltage, clean the relay contacts and recheck terminals for power. If no power, replace control.
Check oil level in supply tank to be sure it is not below intake line. Fill tank with oil. Check for clogged nozzle. Clean or replace.
Check electrodes for carbon buildup and clean as necessary. Check for proper adjustment; readjust if necessary. Check for cracks in porcelain; replace if cracked.
Check air adjustment. Air may be blowing  re away from  ame sensor.
Check voltage between oil valve leads at terminal block to be sure oil valve is getting power.
Check for clogged strainer or  lter. Remove and clean. Check for slipping or broken coupling. Tighten or replace. Check for frozen pump shaft. Replace.
If power is on, check across aquastats to verify power through the switch. If bad, replace.
Check all lines for possible air leak in intake line and tighten. Check for possible restricted intake line. Replace.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4-13
MAINTENANCE ICW-IOM-2012-1001 SECTION 4
Troubleshooting Oil Fired Boilers
Problem Cause Remedy
Check refractories to see if they are sooted,
Poor Combustion
Burner Back Fires
Refractories
S.S. Ring
Oil Nozzle Check for clogged nozzle; clean or replace.
Primary air adjustment
Secondary Air Adjustment
Oil Pump
Draft
Dirty Flue
Refractories
Ignition Electrodes
Primary Air Adjustment
Oil Valve Check for leaky oil valve and replace.
Draft
Loss of Prime
cracked or broken in places. Clean or replace as needed.
Check to be sure ring is present and  ts tight against the furnace wall.
Check air adjustment. Air may be blowing  re
away from  ame sensor.
Check main air adjustment to see if it is loose. Adjust as needed and tighten plate in position. Check CO2 and O2 levels.
Check for clogged strainer or  lter. Remove and clean. Check for slipping or broken coupling. Tighten or replace. Check for frozen pump shaft. Replace.
Check draft with a gauge. Draft should be -0.02 to
-0.04 inches of water column with burner o , or
-0.04 to -0.06 when operating. May need to install barometric damper.
Check  ue for carbon buildup or blockage by using a stack thermometer placed within one foot of the stack leaving the boiler area. If stack temperature is in excess of 600 F while the boiler is operating, the  ues are dirty. Clean as necessary.
Check refractories to see if they are sooted or broken in places. Clean or replace as needed.
Check electrodes for carbon buildup and clean as necessary. Check for proper adjustment; readjust if necessary. Check for cracks in porcelain; replace if cracked.
Check air adjustment. Air may be blowing  re away from  ame sensor.
Check draft with a gauge. Draft should be -0.02 to
-0.04 inches of water column with burner o , or
-0.04 to -0.06 when operating. May need to install barometric damper.
Check all lines for possible air leak in intake line and tighten. Check for possible restricted intake line. Replace.
4-14
© The Fulton Companies 2012
SECTION 4 ICW-IOM-2012-1001 MAINTENANCE
Troubleshooting Oil Fired Boilers
Problem Cause Remedy
Check oil level in supply tank to be sure it is not
Boiler will not maintain pressure
Oil Supply
Oil Nozzle Check for clogged nozzle; clean or replace.
Oil Valve
Oil Pump
Aquastat
below intake line. Fill tank with oil. Check for clogged nozzle. Clean or replace.
Check voltage between oil valve leads at terminal block to be sure oil valve is getting power.
Check for clogged strainer or  lter. Remove and clean. Check for slipping or broken coupling. Tighten or replace. Check for frozen pump shaft. Replace.
If power is on, check across aquastats to verify power through switch. If bad, replace.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4-15
MAINTENANCE ICW-IOM-2012-1001 SECTION 4
4-16
© The Fulton Companies 2012
WARRANTY & PARTS
INTRODUCTION
INSTALLATION
1 2
OPERATION MAINTENANCE
WARRANTY & PARTS
3 4
5
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
5-1
WARRANTY & PARTS ICW-IOM-2012-1001 SECTION 5
5-2
© The Fulton Companies 2012
SECTION 5 ICW-IOM-2012-1001 WARRANTY & PARTS
Standard Warranty for Fulton Boilers
Warranty Valid for Models ICS/FB-A, ICW, ICX/FB-F, VMP, VMPW, FB-S, FB-L, FB-W, ICT
Five (5) Year (60 Months) Material and Workmanship Warranty
The pressure vessel is covered against defective material or workmanship for a period of fi ve (5) years from the date of shipment from the factory. Fulton will repair or replace F.O.B. factory any part of the equipment, as defi ned above, provided this equipment has been installed, operated and maintained by the buyer in accordance with approved practices and recommendations made by Fulton. The commissioning agency must also successfully complete and return the equipment Installation and Operation Checklists to Fulton’s Quality Assurance department. This warranty covers any failure caused by defective material or workmanship; however, waterside corrosion or scaling is not covered. Therefore, it is imperative that the boiler water management and chemistry be maintained as outlined in the Installation and Operation Manual.
Parts Warranty
Fulton will repair or replace F.O.B. factory any part of the equipment of our manufacture that is found to be defective in workmanship or material within one (1) year of shipment from the factory provided this equipment has been installed, operated and maintained by the buyer in accordance with approved practices and recommendations made by both Fulton and the component manufacturers and the commissioning agency has successfully completed and returned the equipment Installation and Operation Checklists to Fulton’s Quality Assurance department.
General
Fulton shall be notifi ed in writing as soon as any defect becomes apparent. This warranty does not include freight, handling or labor charges of any kind. These warranties are contingent upon the proper sizing, installation, operation and maintenance of the boiler and peripheral components and equipment. Warranties valid only if installed, operated, and maintained as outlined in the Fulton Installation and Operation Manual. No Sales Manager or other representative of Fulton other than the Quality Manager or an offi cer of the company has warranty authority. Fulton will not pay any charges unless they were pre-approved, in writing, by the Fulton Quality Manager. This warranty is exclusive and in lieu of all other warranties, expressed or implied, including but not limited to the implied warranties of merchantability and fi tness for a particular purpose. Fulton shall in no event be liable for any consequential or incidental damages arising in any way, including but not limited to any loss of profi ts or business, even if the Fulton Companies has been advised of the possibility of such damages. Fulton’s liability shall never exceed the amount paid for the original equipment found to be defective. To activate the warranty for this product, the appropriate commissioning sheets must be completed and returned to the Fulton Quality Assurance department for review and approval.
Effective 09.01.2010
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
5-3
PARTS & WARRANTY ICW-IOM-2012-1001 SECTION 5
! WARNING
Use of non-factory authorized replacement parts is not recommended for this equipment. Use of non-factory authorized parts may jeopardize safety and system performance, and voids the product warranty.
Parts
Spare and replacement parts may be ordered from your local representative or through the Fulton Companies. When ordering replacement parts, please have the model number and serial number of your Fulton boiler ready. Factory-direct replacement parts must be used to ensure proper equipment operation and adherance with warranty requirements. Contact Fulton Companies at (315) 298­5121 for further information.
5-4
© The Fulton Companies 2012
No part of this Installation, Operation, and Maintenance manual
may be reproduced in any form or by any means without
permission in writing from the Fulton Companies.
Fulton Boiler Works, Inc., Fulton Heating Solutions, Inc. & Fulton Thermal
Corporation are part of the Fulton Group of Companies, a global manufacturer
of steam, hot water and thermal  uid heat transfer systems.
© The Fulton Companies 2012
The heat transfer innovators.
The Fulton Companies
972 Centerville Road, Pulaski, NY 13142 Call: (315) 298-5121 • Fax: (315) 298-6390
www.fulton.com
ICW-IOM-2012-1001
Loading...