FULTON ICS 9.5, ICS 4, ICS 6, ICS 10, ICS 15 Instruction, Operation And Maintenance Manual

...
Serial Number: _______________________________
Model Number: _______________________________
Instruction, Operation, and Maintenance Manual
Sold To: _______________________________
Job Name: _______________________________
Date: _______________________________
Fulton Gas Fired Steam Boilers
HP to 60 HP
ProductBulletin
Product Bulletin
2010-001PB
The Fulton Companies 972 Centerville Road Pulaski, N.Y. 13142
Date: January 22, 2010
Subject: Water Chemistry Requirements for Fulton Steam Products
Products: ICS/ICX, FB-A, FB-F, FB-S, VMP, PVLP, PHP, Electric Steam
Boilers and Unfired Steam Generators
Please note that the water chemistry is different for carbon steel vs. stainless steel pressure vessels and vertical vs. horizontal orientation.
Effective immediately, please use the limits below. Should you have any questions, please do not hesitate to contact Fulton at 315-298-5121.
Water Chemistry Requirements for Fulton Steam Products (to 300 psig MAWP)
NOTES:
*This is a minimum temperature. Feedwater temperatures below 200F will require an oxygen scavenger.
** Suspended solids: Take a water sample. After the sample sits for 10 minutes, no solids should be visible.
+ Total Organic Carbon: Take a water sample. Shake vigorously for 30 seconds. No sheen or foam should be visible.
++ Iron: Take a water sample. Hold the sample against a white background. The water should have no visible yellow, red or
orange tinge.
ND: None Detected.
Parameter
Carbon Steel Stainless Steel
Feedwater Vertical
Boiler/Steam
Pac Water
Horizontal
Boiler/Steam
Pac Water
Feedwater Vertical
Boiler/Steam
Pac Water
Horizontal
Boiler/Steam
Pac Water
pH 7.5-9.5 8.5-10.5 8.5-10.5 6.0-9.5 8.5-10.5 8.5-10.5
Feedwater Temperature
140F* --- --- 140F* --- ---
Hardness as CaCO
3
<2ppm <10 ppm <15 ppm <2 ppm <10 ppm <15 ppm
Chlorides --- --- --- --- 50 ppm 50 ppm
Tota l Alkalinity
--- <300 ppm <500 ppm --- <300 ppm <500 ppm
Tota l Dissolved Solids
--- <2000 ppm <3000 ppm --- <2000 ppm <3000 ppm
Suspended Solids
No visual turbidity**
No visual turbidity**
No visual turbidity**
No visual turbidity**
No visual turbidity**
No visual
turbidity**
Total Organic Carbon
No sheen No foam+
No sheen No foam+
No sheen
No foam+
No sheen No foam+
No sheen No foam+
No sheen No foam+
Iron Colorless
liquid++
Colorless
liquid++
Colorless
liquid++
Colorless
liquid++
Colorless
liquid++
Colorless
liquid++
Dissolved Oxygen
<1ppm* ND ND <5ppm ND ND
Visual Oil ND ND ND ND ND ND
Conducivity (uS/cm)
--- <2985 <4477 --- <2985 <4477
Introduction
This manual is provided as a guide to the correct operation and mainte­nance of your Fulton Gas Fired Steam Boiler, and should be perma­nently available to the staff respon­sible for the operation of the gas fired boiler.
These instructions must not be considered as a complete code of practice, nor should they replace existing codes or standards which may be applicable.
The requirements and instructions contained in this section generally relate to the standard Fulton Gas Fired Steam Boiler. When installing a packaged unit, this entire section should be read to ensure that the installation work is carried out correctly.
Prior to shipment the following tests are made to assure the customer the highest standards of manufacturing:
a) Material inspections. b) Manufacturing process
inspections.
c) ASME welding inspections. d) ASME hydrostatic test
inspection.
e) Electrical components
inspection.
f) Operating test. g) Final Engineering Inspection h) Crating inspection.
NOTE
The installation of the Fulton Gas Fired Steam Boiler should be car­ried out by competent personnel in accordance with the standards of the National Fire Protection Association, National or Canadian Electrical Code. All state and juris-
dictional codes beyond the scope of the applicable ASME Boiler and Pressure Vessel Codes, for its corresponding classification, should be followed in all cases. Jurisdictional authorities must be consulted prior to installation.
All units are crated for fork lift trans­port. Once uncrated, all units can be transported with a forklift. Under no circumstances should weight be allowed to bear on the jacket, con­trol panel, or fan housing of any Fulton Boiler.
Rigging your boiler into position should be handled by a competent rigger experienced in handling heavy equipment.
The customer should examine the boiler for any damage, especially the refractories.
1-G 1/01
Contents
Section
Safety Warnings & Precautions
For Boilers with Low Emissions Burner Only
Description/Instructions
Specifications & Dimensions 4-60 HP Locating the Boiler The Gas Supply Boiler, Condensate Tank, and Blow off Separator Piping Boiler Installation The Steam Supply The Steam Safety Valve The Steam Pressure Gauge Assembly The Blow Off Valve The Feed Water Piping The Water Column Water Gauge & Gauge Glass Installation Instructions Water Supply Recommended Water Treatment Glossary of Water Supply Corrosives & Inhibitors Electrical Requirements Fresh Air Supply for Boiler Conventional Venting Combustion Air Intake (UL and MEA Approved) Corrosion of Flue Pipe Installation Checkpoints Cleaning the Pressure Vessel
Operation
Starting the Gas Fired Boiler Gas Burner Set Up Gas Burner Set Up For Boilers Equipped With Modulation Gas Burner Set Up For Boilers Equipped With High-Low-Off Primary Air Adjustment Secondary Air Adjustment Boiler Controls
Maintenance
Cut Away Gas Boiler Procedure for Cleaning Water Probes Flame Rod Adjustment Flame Scanner Adjustments Stainless Steel Combustion Ring Furnace Refractory Replacement Recommended Daily Maintenance Recommended Weekly Maintenance Recommended Monthly Maintenance Recommended Semi Annual Maintenance Procedure to Replace Hand Hole Gaskets Recommended Annual Maintenance Troubleshooting
Parts
Spare Parts Ordering Instructions
Warranty
Component Data Sheets
1
LE
2
3
4
5 6
7
2-G 1/01
Safety Warnings/Precautions
1
3-G 1/01
4-G 1/01
5-G 1/01
Safety Warnings/Precautions
Safety Warnings Cautions & Notes
The following WARNINGS, CAUTIONS, and NOTES appear
in various chapters of this manual. They are repeated on these safety summary pages as an example and for emphasis.
WARNINGS must be observed to prevent serious injury, or death to personnel.
CAUTIONS must be observed to prevent damage or destruction of equipment or loss of operating effectiveness.
NOTES must be observed for essential and effective operating procedures, conditions, and as a statement to be highlighted.
lt is the responsibility and duty of all personnel involved in the opera­tion and maintenance of this equip­ment to fully understand the
WARNINGS, CAUTIONS, and NOTES by which hazards are to be
reduced or eliminated. Personnel must become thoroughly familiar with all aspects of safety and equipment prior to operation or maintenance of the equipment.
CAUTION
Some soaps used for leak testing are corrosive to certain types of metals. Rinse all piping thoroughly with clean water after leak check has been completed.
NOTE
Where a condensate return tank is to be fitted, this should:
1. Be vented and
2. Have a capacity sufficient to satisfy boiler consumption as well as main­tain proper return tank temperature.
3. Vent pipe should not be down­sized (This may cause pressure build up in the condensate tank.)
4. Return pipes must not be insulat­ed. This can cause overheating the return system, causing a vapor lock in the pump.
5. See Return System Instruction Manual for detailed instructions.
NOTE
Care should be taken to ensure that the blow off receptacle used meets the regulations covering such ves­sels. If in doubt consult a Fulton Representative for advice.
NOTE
Only properly trained personnel should install and maintain water gauge glass and connections. Wear safety glasses during installation. Before installing, make sure all parts are free of chips and debris.
NOTE
Keep gauge glass in original packag­ing until ready to install.
WARNING
Improper installation or maintenance of gauge glass and connections can cause immediate or delayed break­age resulting in bodily injury and/or property damage.
NOTE
After installation is complete and prior to operation the pressure ves­sel should be cleaned.
CAUTION
Do not store halogenated hydrocar­bons near or in the boiler room.
NOTE
a) The fused disconnect switch that controls the feed water pump should be kept in the “on” position at all times during the boiler operation as well as during the non-operating period of the boiler.
b) This switch should be turned “off” only when repairs or adjustments should be made.
NOTE
The pump will continue to operate until the water reaches the correct level in the boiler. This level is approximately the center of the water gauge glass.
WARNING
Prior to the commencement of any work requiring the removal of cover plates and the opening of the control panel box, the electrical supply to the boiler must be disconnected.
CAUTION
Do not tamper with the safety fea­tures of the low water safety cut off.
WARNING
When stopping the boiler for any extensive repairs, shut off main dis­connect switches on both the boiler side as well as the feed water side.
NOTE
To ensure that your Fulton Steam Boiler is kept operating safely and efficiently, follow the maintenance procedures set forth in Section 4 of this manual.
NOTE
To ensure the continued safety and efficiency of the boiler, the schedule of maintenance outlined in this sec­tion should be adhered to.
WARNING
Prior to the commencement of any work requiring the removal of cover plates and the opening of the control panel box, the electrical supply to the boiler must be disconnected.
NOTE
The scanner is located on the outside edge of the burner top plate for 20-60 HP.
NOTE
If only the top refractory is to be changed, the bottom refractory need not be broken.
NOTE
If the boiler is being operated auto­matically on a time clock, the blow off operation may be done once dur­ing the working day and once at the end of the day when at 10 PSIG or less.
NOTE
Fulton recommends that the feedwa­ter treatment should be added between the pump and the boiler.
WARNING
Make sure main power switch is off before starting work.
CAUTION
Do not clean the gauge or glass while pressurized or in operation.
NOTE
After a new Fulton Boiler has been in operation for several months, pieces of burned metal will be found in the space at the bottom of the boiler. These pieces of metal are the remains of a light gauge metal form which was used during manufacture for forming the boiler insulation. This is a normal condition and does not affect the efficiency or the life of the boiler in any way.
6-G 1/01
7-G 1/01
Description/Instructions
LE
8-G 1/01
Standard Models ICS/FB-A 9.5 10 15 20 25 30 Models ICX/FB-F 9.5 10 15 20 30
Unit Size: BHP 9.5 10 15 20 25 30 A. Boiler Height IN 67.5 63.5 69 72.5 74.5 82
MM 1715 1613 1753 1842 1892 2083
B. Boiler Height With Trim* IN 85 80.5 93 97 97 106.5
& Fuel Train Assembly MM 2159 2045 2362 2364 2364 2705
C. Overall Depth Stack IN 44 48 50 61 59 65.5
to Burner Fan Housing MM 1118 1219 1270 1549 1499 1664
D. Boiler Diameter IN 26 28 30 39 39 46
MM 660 710 760 990 990 1170
E. Overall Width IN 33 33.5 35.5 43 43 49
with Water Column MM 838 851 902 1091 1091 1244
F. Flue Outlet Diameter IN 6 6 8 10 10 12
MM 152 152 203 254 245 305
G. To Center of Flue Outlet IN 61.5 57.5 63 66 68 73
MM 1562 1465 1600 1675 1728 1854
H. Feedwater Inlet IN 33 33 33 34 34 34
MM 838 838 838 865 865 865
I. Handholes IN 18.5 18.5 19.5 19.5 19.5 19.5
MM 470 470 495 495 495 495
J. Blowdown Outlet IN 15.25 15 15 16.5 16.5 16.5
MM 387 381 381 420 420 420
K. Water Column Extension IN 14 14 14 14 14 14
MM 355 355 355 355 355 355
L. Gas Train Extension IN 25 21.5 20.5 25 25 27
(CSD-1) MM 635 546 521 635 635 686
M. Clearance Required IN 94 86 108 111 110 121
for Burner Removal MM 2388 2184 2743 2819 2794 3073
Weights
Approx. Shipping Weight LB 1900 2000 2280 3400 3500 4780
KG 862 910 1036 1545 1591 2173
All measurements are subject to +/- 0.5”. Please refer to component drawings for actual measurements. NOTE: Recommended minimum clearance is 24” to the side and back of unit; 36” in front
Dimensions
Fulton Gas & Oil Fired Vertical Tubeless Steam Boilers
(Low Emissions Burner)
Product Data Submittal
Fulton Models: ICS/FB-A and ICX/FB-F
9-G 1/01
CLEARANCE REQUIRED FOR
C
D
O
M
Q
G
R
H
J
S
I
A
BURNER REMOVAL
L
P
B
K
ON/OFF GAS HEAD
CAN PIVOT 360°
MODULATED GAS HEAD IS
FIXED ABOVE FAN HOUSING
F
N
E
Top Vi e wFront ViewSide View
Specifications
Models ICS/ICX/FB 9.5 10 15 20 25 30
Boiler Connections
N. Steam Outlet 15 PSI N/A 1.5” 2” 3” 3” 3”
NPT NPT CL150# CL150# CL150#
Flange Flange Flange
N. Steam Outlet 150 PSI 1” 1” 1.25” 1.5” 2” 2”
NPT NPT NPT NPT NPT NPT
O. Safety Valve Outlet 15 PSI IN N/A 0.75 1 1.5 1.5 1.5
MM 19 32 38 38 38
O. Safety Valve Outlet 150 PSI+ IN 1 1 1 1 1 1
(9.5 HP 100 PSI) MM 25 25 25 25 25 25
P. Safety Valve Inlet 15 PSI++ IN N/A 0.75 1 1.25 1.25 1.25
MM 19 25 32 32 32
P. Safety Valve Inlet 150 PSI IN 0.75 0.75 0.75 0.75 0.75 0.75
(9.5 HP 100 PSI) MM 19 19 19 19 19 19
Q. Feedwater Inlet IN 1 1 1 1 1 1
MM 25 25 25 25 25 25
R. Blowdown Outlet IN 1 1 1 1.25 1.25 1.25
MM 25 25 25 32 32 32
S. Water Column Blowdown IN 1 1 1 1 1 1
MM 25 25 25 25 25 25 Ratings* (Sea level to 3000 ft.) Output 1000 BTU/HR 318 335 503 670 838 1005
1000 KCAL/HR 80.1 84.4 127 169 211 253
Steam Output LB/HR 328 345 518 690 863 1035
KG/HR 149 157 235 313 392 470 Approximate Fuel Consumption at Rated Capacity+++ Natural Gas (ICS) FT3/HR 398 419 628 837 1047 1256
(9” - 13” w.c. req’d) M3/HR 11.3 11.9 17.8 23.7 29.7 35.4
Natural Gas (ICX) FT3/HR 384 403 606 807 1009 1210
(9” - 13” w.c. req’d) M3/HR 10.8 11.4 17.2 22.9 28.6 34.3 Natural Gas Boiler IN 1 1 1 1.25 1.25 1.5 Connection Size (Std CSD-1) MM 25 25 25 32 32 38 Oil Inlet Size IN 1/4 1/4 1/4 1/4 1/4 1/4
MM 6 6 6 6 6 6 Burner 3450 RPM/60 CY Motor HP 2850 RPM/50 CY .75 .75 1.5 1.5 1.5 1.5 Electric Power Requirements - Burner Only (in Amps) *** 120V,60 CY, 1 Phase 9.2 9.2 -- -- -- --
240V, 50/60 CY, 1 Phase 4.6 4.6 8.9 8.9 8.9 8.9
208V, 50/60 CY, 3 Phase 3.1 3.1 4.4 4.4 4.4 4.4
240V, 50/60 CY, 3 Phase 2.8 2.8 4.2 4.2 4.2 4.2
480V, 50/60 CY, 3 Phase 1.4 1.4 2.1 2.1 2.1 2.1
Water Content
U.S. GAL 16 24 39 77 82 170
LITERS 61 91 148 292 311 644
Specifications and Dimensions are approximate. We reserve the right to change specifications and/or dimensions..+ High pressure boilers purchased with low pressure openings may have larger than specified opening sizes, consult factory for correct opening sizes.++ 50 and 60 HP have two safety valves on low pressure. +++Consumption based on Natural Gas 1000 BTU/ft.3. *All ratings from 0 PSIG and at 212 degrees F. *** Control circuit electrical requirement will vary with the system voltage, please consult factory. --Consult factory.
ffsle-pds-2011-1223
The Fulton Companies 972 Centerville Road
Pulaski, NY 13142 Call 315-298-5121 Fax 315-298-6390 www.fulton.com
10-G 1/01
11-G 1/01
Operation
LE
12-G 1/01
13-G 1/01
Starting the Gas Fired Boiler
See page 44-G
Gas Burner Set Up
a. Open the manual gas cocks on the pilot and main lines of the gas head.
b. Switch on the main power to the burner. The water level relay is equipped with a manual reset. Depress the button on the box.
c. The flame programmer is the main control in the panel box. The programmer in conjunction with a UV scanner “supervises” the ignition sequence - proves the flame is satis­factory, and finally “monitors” the established flame. Should any fault occur, either during the ignition sequence or during normal running, the programmer will immediately go to “lock-out” and the burner will shut down.
d. When the pilot flame is estab­lished, the ultra-violet scanner sens­es the flame. This signal is transmit­ted back to the flame programmer which opens the main gas valve giv­ing a main flame.
e. If the installation is new or the burner has been disassembled, the burner may not fire at the first attempt due to air which must be purged from the gas lines. This will result in the burner flame program­mer going to lockout. Repeat the procedure for starting the burner.
f. The main gas valve will remain open as long as there is a demand for heat and the flame is carrying a sufficient signal to the flame pro­grammer.
g. If the flame is not established at the start, the safety switch in the flame programmer control will open the contacts and shut off the burner.
h. Push the reset button on the con­trol to reset. If trouble persists, it may be necessary to check the UV scanner. See Maintenance Section for procedure to check UV Scanner.
Air adjustment for Fulton LE Gas Fired Steam Boilers.
a. The primary air adjustment or main air control is located at the fan housing inlet. This control is used to supply the burner with air needed to facilitate good combustion. Too much or too little air will result in poor combustion. Using a CO
2
or O
2
tester, it is possible to determine the percent of excess air in the combus­tion mixture. Refer to Factory Test Fire Report for acceptable ranges.
LE Operation
14-G 1/01
15-G 1/01
Maintenance
LE
16-G 1/01
17-G 1/01
Pilot Adjustment for Fulton LoNOx Burner.
a. Close downstream main shut off valve.
b. Start boiler and check flame sig­nal on pilot, lock programmer into pilot hold.
c. Adjust gas regulator as needed to obtain a strong pilot signal.
d. Slowly open downstream shut off valve and take the flame program­mer off of hold.
Main Flame Adjustment
a. Place a combustion analyzer in the exhaust of the boiler.
b. Adjust main gas regulator until last elbow pressure matches the test fire sheet.
NOTE: Adjust air accordingly to ensure stable combustion during gas adjustments.
c. Adjust air setting until combus­tion readings are within specifica­tions and stable combustion is pre­sent. Refer to Fulton test fire report for acceptable ranges.
Burner Tile Replacement
a. Remove scroll assembly.
b. Break off top holding clips.
c. Remove ceramic fiber burner tile.
d. Replace burner tile bottom hold­ing clips if needed.
e. Replace with new burner tile.
f. Carefully replace scroll assembly so that the ceramic fiber burner tile is not damaged.
LE Maintenance
18-G 1/01
Troubleshooting
a. The following troubleshooting guide will assist in the diagnosis and the correction of minor field prob­lems. It contains instruction and information necessary to locate and isolate possible troubles which occur during normal operation. It
should be used in conjunction with the unit wiring diagram and the component literature provided in Section 7 of this manual.
b. The following lists cover the most common troubles that may occur on the Fulton gas fired boilers. Refer to left hand column of the chart to
locate the problem. Determine which cause, listed in the center col­umn, that represents the problem by performing the corrective action as listed in the right hand column titled “REMEDY”.
Troubleshooting Gas-Fired Boilers
Problem Cause Remedy
Ignition Failure 1. Power Supply Check fuse or circuit breaker. Reset or
replace, as necessary.
2. Ignition Electrodes Check electrodes for carbon buildup and clean if necessary.
Check for proper adjustments. Readjust if necessary. Check for cracks in porcelain. If found, replace.
3. Transformer Check voltage between transformer leads at terminal block to be sure transformer is being powered.
4. Flame Safeguard Check voltage between ignition terminal and neutral.
Control Check must be made before control locks out on safety.
If no power, replace control.
5. Faulty Air Switch Check for bad air switch by jumpering the two air switch leads at the terminal block. If the boiler starts and runs with these terminals jumpered, the air switch should be replaced.
6. Gas Valve Sticking Check for dirt in valve or orifice and clean if necessary.
(Pilot) Check for faulty actuator or valve and replace if necessary.
7. Gas Supply Check for gas pressure and for intermittent supply problems. See test fire sheet for last elbow.
8. Loose wire connection Check connections to all components.
Flame Failure 1. Power Supply Check fuse or circuit breaker. Reset or replace, as
necessary.
2. Gas Supply Check for gas pressure and for intermittent supply problems.
3. Ignition Electrodes Check electrodes for carbon buildup and clean if necessary. Check for proper adjustment. Readjust if necessary. Check for cracks in porcelain; if found, replace.
4. Primary Air Adjustment Check air adjustment. Air may be blowing flame away from burner head.
LE Maintenance
19-G 1/01
Problem Cause Remedy
Flame Failure 5. Scanner Check for dirt on flame scanner and clean. Check for
proper location of detector.
6. Flame Safeguard Control Check voltage at terminal leading to main gas valve. If no power, replace the control.
7. Loose wire at fuel Tighten wiring connections.
valve circuit
8. Contact open on air Adjust to proper setting.
safety switch
9. Scanner wiring reversed Change to correct terminals.
at panel box
Burner Cut-Off 1. Power Supply Check fuse or circuit; reset or replace, as necessary.
2. Gas Supply Check to be sure main gas cock is not closed. Check coil in gas valve with OHM meter. Replace if faulty. Check gas regulator setting and readjust as necessary. Check inlet gas pressure and increase or decrease as necessary.
3. Ignition Electrodes Check electrodes for carbon buildup and clean if necessary.Check for proper adjustment. Readjust if necessary. Check for cracks in porcelain; if found, replace.
4. Scanner Check for dirt on flame scanner and clean. Check for proper location of detector.
5. Air Switch Check for bad air switch by jumpering the two air switch leads as the terminal block. If the boiler starts and runs with these terminals jumpered, the air switch should be replaced.
6. Gas Valve Sticking Check for dirt in valve or orifice and clean if necessary.
(Pilot) Check for faulty actuator or valve and replace if necessary.
7. Weak Amplifier Replace.
8. Weak Pilot Adjust to larger pilot by adjusting pilot gas pressure regulator.
9. Faulty Liquid Level Control Check to see if there is power to terminal number 10 when the sight glass shows the proper water level. If there is no power at this terminal, the control is bad and must be replaced.
10. Dirty or defective Clean or replace.
UV Scanner
LE Maintenance
20-G 1/01
Problem Cause Remedy
Poor Combustion 1. Refractories Check refractories to see if they are plugged with soot or
broken in pieces. Clean or replace as necessary.
2. Air Adjustment Check main air adjustment to see if it is loosened up. Adjust as necessary and tighten plate in position. Check CO2and O2levels.
3. Draft Check draft with a gauge. Draft should be a -.02” to -.04” W.C. with burner off or -.04” to -.06” when operating. May need to install a barometric damper.
4. Dirty Flue Check flue for carbon buildup or blockage. Clean flue passages with brush.
5. Negative Room Pressure Make sure no exhaust fans are running in the boiler room.
Burner back fires 1. Refractories Check refractories to see if they are plugged with soot or
broken in pieces. Replace as necessary.
2. Ignition Electrodes Check electrodes for carbon buildup and clean if necessary. Check for proper adjustment. Readjust if necessary. Check for cracks in porcelain; if found, replace.
3. UV Scanner Check for dirt on flame scanner and clean. Check for proper location of detector.
4. Draft Check draft with a gauge. Draft should be a -.02” to -.04” W.C. with burner off or -.04” to -.06” when operating. May need to install a barometric damper.
5. Negative Room Pressure Make sure no exhaust fans are running in the boiler room.
Boiler will not 1. Gas Supply Check gas pressure coming into gas train. If low, contact maintain pressure gas company. Should be 7” to 11” W.C. Check coil in
gas valve with AMP meter. Replace if bad. Check gas regulator setting and readjust as necessary.
2. Dirty Flue Check flue for carbon buildup or blockage. Clean flue passages with brush.
3. Pressuretrol Disconnect all power to the controller. Disconnect the wires from the controller. Put an OHM meter between the switch terminals. Lower the set point and recheck with OHM meter. Switch should break. If the controller operates improperly, replace it.
4. Scale Built up in boiler Refer to Section 2 “Pressure Vessel Cleaning”.
5. Refractories Check refractories to see if they are cracked or broken in pieces. Replace as necessary.
6. Steam traps Check traps to see if they are clean or replace as necessary.
blowing through
7. Boiler size Boiler may be undersized.
LE Maintenance
21-G 1/01
Problem Cause Remedy
Boiler is Surging 1. Steam traps blowing Check traps to see if they are clean or replace as necessary.
through
2. Perc (cleaning solvent Clean boiler with washing soda per instruction manual. in boiler)
3. Scale build-up or lime Call water treatment professional and consult factory. deposits
4. Too much compound in Dump return tank and flush system. Have water tested by system (water treatment) water treatment company.
5. Too much water Have water tested by water treatment company. softener (high PH)
6. Too much of a load Check total equipment horsepower required against
horsepower of boiler being used. Decrease amount of equipment being used at one time.
7. Boiler new (not Clean per instructions in instruction manual. cleaned)
Boiler Rumbles and 1. Draft problem Check draft with a gauge. Draft should be a -.02” to -.04” Pulsates W.C. with burner off or -.04” to -.06” when operating. May
need to install a barometric damper.
Boiler pushing water 1. Steam Traps Chech traps. Clean or replace as necessary. with the steam
2. Too much boiler Dump return tank and flush system. Have water compound tested by water treatment company.
Pump will not cut off 1. Dirty Probes Clean or replace as necessary.
2. Relay failed Make sure relay is plugged in tightly. If so, replace
water level relay.
3. Ground Connection Check for tightness and clean.
Pump runs but does 1. Vapor locking of pump Allow system to cool down, check steam traps and check not put water into to be sure return lines are not insulated. Check return tank boiler temp. If it is above 180°F., (82°C.) vapor locking of pump
will occur. Inspect check valves. Clean and replace as needed. Replace pump with multistage centrifugal good for 250°F. (121°C.).
2. Impeller Adjustment Check for impeller wear and adjust per component
information in instruction manual (Burks only).
3. Back pressure on pump Need to install repair kit on pump.
4. Plugged feed water Check and clean or replace as necessary. nipple
LE Maintenance
22-G 1/01
Problem Cause Remedy
Water pump will not 1. Scale on probes Check and clean or replace as necessary. come on at times
2. Bad Pump Contactor Check to see if contactor is being powered. Check to see if contactor coil is pulling in. Replace if necessary.
3. Bad Pump Motor Check the incoming power to the pump to be sure it is receiving power. If power is present but motor does not run, replace it.
Low Fuel pressure 1. Gas pressure regulator Check and replace.
Boiler Flooding 1. Pump does not shut off Dirty probes. Clean or replace as necessary.
2. Relay failed Make sure relay is plugged in tightly. If so, replace water level relay.
3. Ground Connection Check for tightness and clean.
4. Vacuum created with As the boiler cools off, it pulls water from the system
boiler off piping. To prevent this, add a 1/4” check valve on the
steam gauge assembly piping, which closes under pressure and opens under vacuum.
LE Maintenance
23-G 1/01
Parts
LE
24-G 1/01
25-G 1/01
Spare Parts
a. It is important that the correct replacement part is fitted to your Fulton Gas Fired Steam Boiler.
b. When ordering replacement or spare parts, make sure that the full
information given in the Parts List is supplied, together with the fol­lowing details as shown on your boiler identification plate:
1. Boiler Number
2. Boiler Type
3. Electrical Specifications
NOTE:
The policy of Fulton Boiler Works, Inc. is one of continuous improvement, and therefore, we reserve the right to change prices, specifications, and equipment without notice.
LE Parts
Replacement Parts Listing (available from authorized Fulton Representative)
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
2-12-219 Furnace Burner Tile (9.5 HP) 2 .91 2-12-253 Furnace Burner Tile (10 HP) 2 .91 2-12-221 Furnace Burner Tile (15 HP) 2 .91 2-12-254 Furnace Burner Tile (20-30 HP) 15 6.8 5-21-6009 Burner Scroll (9.5 HP) 30 13.6 5-21-6010 Burner Scroll (10 HP) 45 20.4 5-21-6015 Burner Scroll (15 HP) 55 24.9 5-21-6030 Burner Scroll (20 HP) 65 29.5 5-21-6031 Burner Scroll (30 HP) 65 29.5 2-30-1330 Blower Assembly (9.5 - 10 HP) 22 9.98 2-30-1331 Blower Assembly (15 - 20 HP) 30 13.6 2-30-1339 Blower Assembly (30 HP) 35 15.9 2-20-18 Ignition Electrode (9.5 - 10 HP) .5 .23 2-20-30 Ignition Electrode (15, 20, 30 HP) .4 .18 5-10-610 Burner Assembly LoNOx (9.5 - 10 HP) 35 15.9 7-30-571 Burner Assembly LoNOx (15 HP) 45 20.4 7-30-672 Burner Assembly LoNOx (20 HP) 55 24.9 7-30-673 Burner Assembly LoNOx (30 HP) 55 24.9 2-30-819 O ring for Pilot Tube LoNOx - 1.76 ID x .070) .01 .005 2-30-813 O ring for Pilot Tube LoNOx - 8.7 mm x 1.78 mm) .01 .005 2-40-631 Temperature Limit LoNOx 3 1.37 2-40-803 Thermocouple High Limit LoNOx .2 .09
26-G 1/01
Boiler Description/Instructions Gas Fired Boiler
2
27-G 1/01
Description/Instructions
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;
;;;;;
;;;;;
;;;;;
;;;;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;
QQQQQQQQQQQQQQQQQQQQ
QQQQQQQQQQQQQQQQQQQQ
¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢
¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢
Transformer Scroll
Gaskets
Steam Gauge Assembly
Gauge Glass Valve
To
O.P .C.
*
To
H.P .C.
*
Burner Motor
Gauge Glass Valve
Gauge Glass And Protector
Water Column
Control Box
High Density Insulation
Outside Jacket
Handhole
Blowdown
Outlet
Boiler Runners
(4-30 HP)
Feedwater
Inlet
Flue Outlet
Lifting Hook(s)
Flue Blanket
Flue Rope
Gasket
Flue Plate
Cover
Top Plate
Assembly
Gas Train
Assembly
Secondary
Air Damper
Burner
Plate
Assembly
Stainless
Steel Ring
Bottom
Refractory
Top
Refractory
Castable Refractory Insulation
*
O.P.C. = Operating Pressure Control
*
H.P.C. = High Pressure Control
28-G 1/01
Standard Models ICS/FB-A 4 6 9.5 10 15 20 25 30 50 60 Models ICX/FB-F 4 6 9.5 10 15 20 25 30
Unit Size: BHP 4 6 9.5 10 15 20 25 30 50 60 A. Boiler Height IN 47.5 57.5 67.5 63.5 69.5 72.5 75 82.5 87.5 93.5
MM 1207 1461 1715 1613 1765 1842 1905 2069 2223 2375
B. Boiler Height With Trim* IN 65 75 85 80.5 86.5 92.5 95 102 106.5 120
& Fuel Train Assembly MM 1651 1905 2159 2045 2197 2350 2413 2591 2705 3048
C. Overall Depth Stack IN 44 44 44 46 47 58 59 67 78 78
to Burner Fan Housing MM 1118 1118 1118 1168 1194 1474 1499 1702 1981 1981
D. Boiler Diameter IN 26 26 26 28 30 39 39 46 55 55
MM 660 660 660 710 760 990 990 1170 1400 1400
E. Overall Width IN 33 33 33 33.5 35.5 43 43 49 57 57
with Water Column MM 838 838 838 851 902 1091 1091 1244 1448 1448
F. Flue Outlet Diameter IN 6 6 6 6 8 10 10 12 12 12
MM 152 152 152 152 203 254 245 305 305 305
G. To Center of Flue Outlet IN 42 52 62 58 63 66 68 73.5 79 85
MM 1070 1320 1575 1473 1600 1675 1728 1867 2007 2159
H. Feedwater Inlet IN 27 33 33.5 33 33.5 34 34 34 35 35
MM 685 840 851 840 851 865 865 865 890 890
I. Handholes IN 19 19 19 19 19 19 19 19 20 20
MM 485 485 485 485 485 485 485 485 510 510
J. Blowdown Outlet IN 15 15 15.5 15.5 15.5 16.5 16.5 16.5 17.5 17.5
MM 380 380 394 394 394 420 420 420 445 445
K. Water Column Extension IN 14 14 14 14 14 14 14 14 14 14
MM 355 355 355 355 355 355 355 355 355 355
L. Gas Train Extension IN 22.5 22.5 25 21.5 20.5 25 25 27 22.5 34
(CSD-1) MM 572 572 635 546 521 635 635 686 572 867
M. Clearance Required IN 72 82 92 86 92 96 98 106 114 124
for Burner Removal* MM 1828 2083 2337 2184 2337 2438 2490 2692 2896 3150
Weights
Approx. Shipping Weight LB 1400 1700 1900 2000 2280 3400 3500 4780 6526 7280
KG 635 773 862 910 1036 1545 1591 2173 2966 330
Approx. Operating Weight LB 1516 1833 2200 2200 2605 4042 4184 6197 8569 9531
KG 688 831 998 998 1182 1833 1898 2811 3887 4323
*This dimension is 6” less for oil fired units 4-50 HP and 12” less for oil fired units 60 HP.
NOTE: Recommended minimum clearance is 24” to the side and back of unit; 36” in front
Dimensions
Fulton Gas & Oil Fired Vertical Tubeless Steam Boilers
(Standard Burner)
Product Data Submittal
Fulton Models: ICS/FB-A and ICX/FB-F
29a-G 1/01
O
CLEARANCE REQUIRED FOR
C
D
BURNER REMOVAL
ON/OFF GAS HEAD
CAN PIVOT 360°
MODULATED GAS HEAD IS
FIXED ABOVE FAN HOUSING
L
F
N
M
Q
G
R
H
J
S
I
A
B
P
K
E
Top ViewFront ViewSide View
ffsstd-pds-2011-1222
Specifications
Models ICS/ICX/FB 4 6 9.5 10 15 20 25 30 50 60
Boiler Connections
N. Steam Outlet 15 PSI 1” 1” N/A 1.5” 2” 3” 3” 3” 4” 4”
25 NPT NPT NPT CL150# CL150# CL150# CL150# CL150#
Flange Flange Flange Flange Flange
N. Steam Outlet 150 PSI 0.75” 0.75” 1” 1” 1.25” 1.5” 2” 2” 3” 3”
19 NPT NPT NPT NPT NPT NPT NPT CL150# CL150#
Flange Flange
O. Safety Valve Outlet 15 PSI IN 0.75 0.75 N/A 0.75 1 1.5 1.5 1.5 2 2
MM 19 19 19 32 38 38 38 38 38
O. Safety Valve Outlet 150 PSI+ IN 1 1 1 1 1 1 1 1 1.25 1.25
(9.5 HP 100 PSI) MM 25 25 25 25 25 25 25 25 32 32
P. Safety Valve Inlet 15 PSI++ IN 0.75 0.75 N/A 0.75 1 1.25 1.25 1.25 1.5 2
MM 19 19 19 25 32 32 32 32 32
P. Safety Valve Inlet 150 PSI IN 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1 1
(9.5 HP 100 PSI) MM 19 19 19 19 19 19 19 19 25 25
Q. Feedwater Inlet IN 0.75 0.75 1 1 1 1 1 1 1 1
MM 19 19 25 25 25 25 25 25 25 25
R. Blowdown Outlet IN 1 1 1 1 1 1.25 1.25 1.25 1.5 1.5
MM 25 25 25 25 25 32 32 32 38 38
S. Water Column Blowdown IN 1 1 1 1 1 1 1 1 1 1
MM 25 25 25 25 25 25 25 25 25 25 Ratings* (Sea level to 3000 ft.) Output 1000 BTU/HR 134.40 201 318 335 503 670 838 1005 1674 2009
1000 KCAL/HR 33.8 50.7 80.1 84.4 127 169 211 253 422 506
Steam Output LB/HR 138 207 328 345 518 690 863 1035 1725 2070
KG/HR 63 94 149 157 235 313 392 470 785 942 Approximate Fuel Consumption at Rated Capacity+++ Light Oil GPH 1.2 1.8 2.8 3.0 4.5 6.0 7.5 9.0 15.0 17.9
LPH 4.5 6.8 10.6 11.4 17 22.7 28.4 34.1 56.8 67.8
Propane Gas (ICS) FT3/HR 67.2 100 159 168 251 335 419 502 837 1004
(14” w.c. req’d) M3/HR 1.9 2.8 4.5 4.8 7.1 9.5 11.9 14.2 23.7 28.4
Propane Gas (ICX) FT3/HR 63 97 161 242 323 404 484
(14” w.c. req’d) M3/HR 2.2 2.7 N/A 4.6 6.9 9.1 11.4 13.7
Natural Gas (ICS) FT3/HR 168 257 398 419 628 837 1047 1256 2093 2511
(7” - 11” w.c. req’d) M3/HR 4.8 7.1 11.3 11.9 17.8 23.7 29.7 35.4 59.3 71.1
Natural Gas (ICX) FT3/HR 159 242 384 403 606 807 1009 1210
(7” - 11” w.c. req’d) M3/HR 5.6 6.9 10.8 11.4 17.2 22.9 28.6 34.3 Natural Gas Boiler IN 1 1 1 1 1 1.25 1.25 1.5 1.5 2 Connection Size (Std CSD-1) MM 25 25 25 25 25 32 32 38 38 51 Oil Inlet Size IN 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
MM 6 6 6 6 6 6 6 6 6 6 Burner 3450 RPM/60 CY 1/3 gas 1/3 gas 1.5 gas 1.5 gas Motor HP 2850 RPM/50 CY 1/3 1/3 1/3 1/3 1/3 3/4 oil 3/4 oil 3/4 2 oil 2 oil Electric Power Requirements - Burner Only (in Amps) *** 120V,60 CY, 1 Phase 5.2 5.2 5.2 5.2 5.2 5.2 gas 5.2 gas 9.2 -- --
9.2 oil 9.2 oil
240V, 50/60 CY, 1 Phase 2.6 2.6 2.6 2.6 2.6 2.6 gas 2.6 gas 4.6 8.9 gas 8.9 gas
4.6 oil 4.6 oil 9.5 oil 9.5 oil
208V, 50/60 CY, 3 Phase 1.9 1.9 1.9 1.9 1.9 1.9 gas 1.9 gas 3.1 4.4 gas 4.4 gas
3.1 oil 3.1 oil 5.7 oil 57 oil
240V, 50/60 CY, 3 Phase 1.6 1.6 1.6 1.6 1.6 1.6 gas 1.6 gas 2.8 4.2 gas 4.2 gas
2.8 oil 2.8 oil 5.4 oil 5.4 oil
480V, 50/60 CY, 3 Phase 0.8 0.8 0.8 0.8 0.8 0.8 gas 0.8 gas 1.4 2.1 gas 2.1 gas
1 .4 oil 1.4 oil 2.7 oil 2.7 oil
Water Content
U.S. GAL 14 16 16 24 39 77 82 170 245 270
LITERS 53 61 61 91 148 292 310 644 927 1022
Specifications and Dimensions are approximate. We reserve the right to change specifications and/or dimensions..+ High pressure boilers purchased with low pressure openings may have larger than specified opening sizes, consult factory for correct opening sizes.++ 50 and 60 HP have two safety valves on low pressure. +++Consumption based on light Oil 140,000 BTU/G; Natural Gas 1000 BTU/ft.3; Propane 2500 BTU/ft3. *All ratings from 0 PSIG and at 212 degrees F. *** Control circuit electrical requirement will vary with the system voltage, please consult factory. --Consult factory.
The Fulton Companies 972 Centerville Road
Pulaski, NY 13142 Call 315-298-5121 Fax 315-298-6390 www.fulton.com
29b-G 1/01
30-G 1/01
Description/Instructions
K
K
F
K
D
C
I
E
J
H
B
A
G
Description/Instructions
31-G 1/01
SEE PRODUCT DATA SUBMITTAL ON PREVIOUS PAGES
72
1828
4
Locating the Boiler
a) The boiler should be located in dry
surroundings on a level base, making sure that there is sufficient room around the boiler to enable the opera­tor and/or the maintenance engineer to gain access to all parts of the boiler. Check location for ease of water sup­ply and electrical connections.
b) Place the boiler on a non combus­tible floor with clearances to unpro­tected combustible materials, includ­ing plaster or combustible supports.
c) It is necessary to have the follow­ing vertical clearance from the floor to the ceiling for removal of the burner for servicing:
Minimum Vertical Clearances
BHP IN MM
6 82 2083
9.5 86 2184 10 86 2184 15 92 2337 20 92 2438 30 106 2692 40 104 2642 50 114 2896 60 124 3150
The Gas Supply
a) Gas Piping should be installed in
accordance with National Fuel Gas Code, ANSI-Z223-1-1984 or latest addenda and any other local codes which may apply. In Canada gas installations must be in accordance with the current CAN/CGA B149.1 and .2 and/or local codes.
b) Install a dirt trap ahead of all of the gas valves.
c) The pipe and the fittings used must be new and free of dirt or other deposits.
d) The piping must be of the proper size to ensure adequate gas supply to the gas head assembly. Consult your gas company for specific recommen­dations.
e) For natural gas a pressure of 7" to 11" (178mm to 279mm) of water col­umn pressure at the gas train is required with burner firing. Do not exceed 13" of water column.
f) For propane or butane gas the pressure required is 11" (279 mm) of water column pressure. Again, do not exceed 13" of water column.
g) When making gas piping joints, use a sealing compound resistant to
the action of liquefied petroleum gases. Do not use teflon tape on gas line threads.
h) The main and the pilot gas pres­sure regulators must be vented to the atmosphere.
i) After gas piping is completed care­fully check all piping connections, (fac­tory and field), for gas leaks. Use a soap and water solution.
CAUTION
Some soaps used for leak testing are corrosive to certain types of metals. Rinse all piping thoroughly with clean water after leak check has been completed.
j) The boiler must be disconnected at
the boiler shut off valve from the gas supply piping system during any pres­sure testing of the system at pressure in excess of 1/2 PSIG--14" W.C.
k) The boiler must be isolated from the gas supply piping system by clos­ing the shut-off cock during any pres­sure testing of the gas supply piping system at pressures equal to or less than 1/2 PSIG--14" W.C.
32-G 1/01
Description/Instructions
Vent
Vent
Return
Cold Water Supply
Sight
Glass
Union
Pump/
Strainer
Thermometer
Aquastat
Drain
Condensate
Return
T ank
Blowdown
Separator
Outlet To Drain
Check
Valve
Shut
Off
Valve
Cold Water Inlet
Basic Boiler, Condensate Tank, and Blow off Separator
NOTE
Where a condensate return tank is to be fitted, this should:
1) Be vented to a safe location, and
2) Have a capacity sufficient to satisfy boiler consumption as well as maintain proper return tank temperature.
3) Vent pipe should not be down­sized (this may cause pressure build up in the condensate tank).
4) Return pipes must not be insu­lated. This can cause overheating the return system, causing a vapor lock in the pump.
5) See Return System Instruction Manual for detailed instructions.
Description/Instructions
Safety
Valve
Water Column and Sight Glass
Electric Control Panel
Gas Fired
Steam Boiler
Shut
Off
Valve
Check Valves
Fast
Opening
Valve
Blowdown Valve
Union
NOTE
Care should be taken to ensure that the blow off receptacle used meets the regulations covering such vessels. If in doubt consult a Fulton Representative for advice.
a) Make sure two check valves are
installed between the boiler and pump (one check valve is supplied with the unit).
b) In a closed system an end of the line trap should be installed.
c) There are three blow off valves on the boiler: the main valve at the rear of the boiler, the gauge glass blow off valve, and the water col­umn blow off valve. The boiler blow off valve supplied with the boiler should be screwed to the blow off pipe at the rear of the boiler and
connected to a blow off receptacle of approved design.
All these procedures should be done in accordance with state and/or local codes. The water col­umn blow off valve and the gauge glass blow off valve should be con­nected to the main blow off line.
33-G 1/01
Description/Instructions
Boiler Installation
The Steam Supply — Pipe the
steam supply line from the top right side of the boiler.
The Steam Safety Valve
1) Before installing, be sure that all
pipes and connections have been blown clean. Pipe compound or dope is used on external threads only. Be sure inlet of valve is free of any foreign material.
2) Do not use a pipe wrench! When making installation, use proper type and size wrench.
3) The valve should be installed in a vertical upright
position in the connection provided
on the top left side of the boiler
with no unnecessary inter-
vening pipe. Under no cir­cumstances should there be
a shut off valve or restriction
of any kind between the
safety valve and the con-
nection provided.
4) Do not cap or plug drain hole in the side of valve body.
5) Since the purpose of this safety valve is to protect against an overpressure situa­tion, it will loudly discharge hot
steam in doing so. Therefore, it is recommended that a discharge pipe be securely installed and run to a safe point of disposal.
6) When a discharge pipe is used, it must be of a pipe size equal to or greater than that of the valve outlet. Use schedule 40 discharge pipe only. Do not use schedule 80, extra strong or double extra strong dis­charge pipe or connections. It must
be as short and straight
as possible and so
arranged as to avoid undue
stress on the valve. It must have an ample provision for drain­ing condensate at or near the valve outlet. It must terminate freely to atmosphere with no intervening valve of any description and it must be securely anchored and supported.
The Steam Pressure Gauge Assembly — The gauge should be
facing front towards the panel box and/or operator of the boiler.
Except as noted, each assembly or any of its component parts may be oriented, other than as shown to provide improved operating clear­ances and/or view of gauge. Before installing steam gauge on the siphon, add a small amount of water to the siphon to create a water seal to buffer the gauge ele­ment. This must be done to prevent inaccurate pressure readings and /or premature failure of the gauge. Install the steam gauge into the siphon on the water column.
Saftey Valve Outlet
Steam Outlet
Steam
Pressure
Gauge
Inspection/
Test Valve
(Shown Open)
Steam
Siphon Loop
To
High Limit
Pressure
Control
To
Operating
Pressure
Control
Ball
Valve
(Open)
(Closed)
34-G 1/01
Description/Instructions
35-G 1/01
4
1/2
12.5
The Blow-Off Valve — There are two blow off valves on the boiler: The main valve at the rear of the boiler and the water gauge glass blow off valve. The boiler blow off valve sup­plied with the boiler should be screwed to the blow off pipe at the rear of the boiler and connected to a blow off receptacle of approved design. This should be done in accor­dance with state and local codes.
4) Do not use the pump as a piping support. It is critical that the pipe be independently supported near the pump so no strain will be transmit­ted to the unit.
5) Connect the feed water stop valve to the feed water pipe at the rear of the boiler and pipe it to the return system.
The Water Column
Install the piping from the water column and water gauge glass to a safe blow-off point.
The Feed Water Piping
1) Provisions must be made for ade-
quate water supply and properly sized piping. Piping must be done in compliance with all local codes. The following chart may be used as a guideline for sizing.
BHP Minimum Water
Supply Piping Size
Inches Millimeters
6 1/2 12.5
9.5 1/2 12.5 10 1/2 12.5 15 3/4 19 20 3/4 19 30 1 25 40 1 25 50 1 25 60 1 25
2) When feeding the boiler using a return system, the city water pressure should not exceed 40 PSI. A pres­sure reducing valve should be installed a head of the return tank when above this pressure.
3) It is important that all piping be lined up and not forced into place. It is recommended that you begin pip­ing at the pump. If the lines are ended at the pump, particularly if the last piece is cut too short or long, the pump will be forced to meet the pipe and strain or distortion will result.
36-G 1/01
Water Gauge & Gauge Glass Installation instructions
NOTE
Only properly trained personnel should install and maintain water gauge glass and connections. Wear safety glasses during installation. Before installing, make sure all parts are free of chips and debris.
NOTE
Keep gauge glass in original pack­aging until ready to install.
1) Verify the proper gauge has been
supplied.
2) Examine the gauge glass and packings carefully for damage before installation. Do not use the glass if it contains any scratches, chips, or any other visible signs of damage.
3) Do not subject the gauge glass to bending or torsional stresses.
4) Apply teflon tape or pipe dope to pipe threads. Install top gauge fitting (fitting without a drain valve) into the uppermost tapping. Wrench tighten the fitting until it is snug and the glass outlet is pointing at five o’clock (about 1/8 turn from its final downward verti­cal position).
5) Install the bottom gauge fitting (the fitting with a drain valve) until it is snug and the glass outlet is pointing directly upward. Verify top and bot­tom fittings are threaded into the tap­pings the same number of turns (dis­tance A=distance B).
6) Remove glass packing nut, friction washer and glass packing from the fittings, and place them, in the same order, on to both ends of the gauge glass. Push both packings about an inch up the gauge glass.
7) Gently insert one end of the glass into the top gauge fitting. Keeping the glass inside the top fit­ting, gently rotate the top gauge fit­ting clockwise until vertically aligned with the bottom gauge fitting, then inset glass into bottom fitting until glass bottoms out on the shoulder inside the bottom fitting.
8) Carefully raise glass about 1/16” and slide lower glass packing down until the glass packing contacts the lower gauge fitting. DO NOT allow the glass to remain in contact with any metal!
9) Carefully slide upper glass pack­ing up as far as possible.
10) Hand tighten both glass packing nuts, then tighten 1/2 turn more by wrench. Tighten only enough to pre­vent leakage. DO NOT OVER TIGHTEN! If any leakage should occur, tighten slightly, a quarter turn at a time, checking for leakage after each turn.
11) Install the protective guard, and utilize automatic ball checks where necessary to help prevent injury in case of glass breakage.
WARNING
Improper installation or mainte­nance of gauge glass and connec­tions can cause immediate or delayed breakage resulting in bod­ily injury and/or property damage.
Description/Instructions
Top Gauge
Fitting
Gauge Glass
Guard Rod
Glass Packing Nut
Friction Washer
Glass Packing Bottom Gauge
Fitting
A
Vessel
Wall
B
Drain
Valve
Water Supply
a) Feed water contains solids and
dissolved gases. These may promote incrustation of scale; foaming, prim­ing, surging, and solids in steam; cor­rosion and pitting; or caustic embrittle­ment. To prevent this, feedwater must be studied individually and treated accordingly by reputable profession­als specializing in this field. It is strongly recommended that a compe­tent water treatment company be con­sulted prior to the installation of the boiler.
b) The purpose of this treatment should be to provide quality feedwater to the boiler such that corrosion and deposition in the boiler will be mini­mized. Dissolved oxygen, high chlo­ride levels and low pH can all be major causes of corrosion. Untreated hardness is the major cause of deposits. Poor quality feedwater requires increased blow off and increased chemical treatment costs to prevent boiler corrosion and scaling.
c) One way to lower the amount of dissolved oxygen in the boiler feed water is the sparge tube option. This option injects live steam into the feedwater to increase the water temperature to 180 degrees F (82 degrees C) which removes oxygen from the water.
d) Chlorides can be controlled by increasing the number of blow downs per day from one to four.
e) The Fulton Warranty does not cover damage or failure that can be attributed to corrosion, scale or dirt accumulations. Oxygen is a cor­rosive. See the Warranty Section of
this manual for full details.
Recommended Water Treatment
a) Following are recommendations
for feed water and boiler water. Contact your local water treatment professional for testing and treatment recommendations. It is very important that a strict water treatment program be followed.
Feedwater:
Dissolved Oxygen.............less than 0.05 ppm
pH Value............................9-11 (tested at room
temperature)
*Hardness..........................less than 70 ppm
in the form of CACO
3
Oil.......................................none
Suspended Solids.............none
Organic Matter ..................less than 5.0 ppm
Chloride .............................less than 50.0 ppm
Total Dissolved Solids .......less than 300ppm
Boiler Water:
Phosphate....................30 to 50 ppm
in the form of PO
4
Alkalinity .......................less than 300 ppm in
the form of CACO3
Chloride ........................less than 500 ppm
pH Value.......................9 to 11 tested
at room temperature) Total Dissolved Solids..400 to 2,000 ppm
Iron................................1 ppm maximum
Silica .............................180 ppm max. as SIO
2
Hardness......................less than 50.0 ppm
Dissolved Oxygen........none
ppm = parts per million; CACO3=Calcium Carbonate; PO4=Phosphate; SiO2=silicon dioxide; * 1 Grain Hardness = 17.118 ppm Therefore: 70 ppm = 4.10 grains hardness
b) It is critical that the boiler pH be alkaline (9-11) whenever water is in the boiler. Solids that enter in with the feed water concentrate in the boiler. Daily boiler blow down is recommend­ed to prevent corrosion and/or deposits from forming.
Glossary of Water Supply Corrosives and Inhibitors
Dissolved Oxygen: Oxygen that is
dissolved in the feedwater will cause the steel in the boiler and the feedwa­ter system to be attacked by the water in a manner described as “pitting”. The pits that are produced can vary from tiny depressions to holes large enough to penetrate the boiler metal and are usually covered with tuber­cles of iron oxide. Once pitting starts, it may be extremely hard to arrest. Pitting can proceed at a surprisingly rapid rate and can occur not only in the boiler proper, but also in pre-boiler equipment such as economizers, feedwater heaters, and feedwater lines.
Sodium Sulfite: Its purpose is to chemically remove the dissolved oxy­gen left in the feedwater.
Sodium Sulfite reacts chemically with dissolved oxygen, producing sodium sulfate. Since it is desirable to remove dissolved oxygen from the feedwater before it reaches a boiler. Sodium sulfite is best introduced con­tinuously at some suitable point in the feedwater system. Chemical residual control is based on the maintenance of a specific excess of sodium sulfite in the boiler water. The essential requirement being to maintain in the feedwater at all times slightly more than enough sodium sulfite to con­sume all of the dissolved oxygen. When sodium sulfite is not fed contin-
uously, protection of the boiler against oxygen attack must depend on the reserve of sodium sulfite that is pre­sent in the boiler water. In this case, it is important that the feedwater and the boiler water are mixed thoroughly and as quickly as possible so that boiler water sodium sulfite may con­sume feedwater oxygen before the latter can cause damage to the boiler.
Sulfite as a treatment represents a second line of defense against oxy­gen corrosion. A vigorous mainte­nance program to safe guard against oxygen leakage into the pre-boiler system should be followed.
Suspended Solids: Suspended solids are the undissolved matter in water, including dirt, silt vegetation, and any other insoluble organic mat­ter. Normally suspended solids are expressed in terms of turbidity.The presence of suspended solids in cool­ing water can increase impingement type corrosion. Suspended solids may also deposit in low velocity areas and create differential aeration cells. Pitting can result. The most common cause of high suspended solids is high hardness feedwater. Of the agents which cause foaming, sus­pended solids probably have the least effect. Reasons for the increased hardness or other suspended solids should be determined.
In line filters, or various types of pretreatment can be used to lower the suspended solids level. Various polymers assist in holding solids in suspension.
Alkalinity: Alkalinity is the capacity of a water to neutralize acids. Common water alkalinities consist of bicarbonate, carbonates, hydroxide, phosphate, and silicate. These alka­linities, especially bicarbonates and carbonates, break down to form car­bon dioxide in steam, which is a major factor in the corrosion on condensate lines. High alkalinity also causes foaming and carry over in boilers.
Both foaming and carry over cause erratic boiler operation. When foaming occurs an anti-foam should be added or increased. The reason for the high alkalinity should be determined. It may result from lack of sufficient blow off. Pretreated makeup water and condensate should also be checked. Quite often the source of alkalinity is an overdose of alkaline internal water treatment chemical.
Description/Instructions
37-G 1/01
38-G 1/01
pH: pH is a measure of the degree of acid or base of solution. Normal pH ranges of 6.5-9.0 will have little influence on the corrosion rate of cooling waters. If for some reason, pollution, etc., the pH is lowered into the acid range, increased corrosion can be expected. The solution lies in determining the cause of the low pH and correcting that condition. A low pH can result in corrosion of metals, while a high pH can result in scale formation.
In order to control boilers and equipment used for the external treatment of make up water, it is essential that reliable pH measure­ments be made.
Phosphates: Ground or surface waters seldom contain large amounts of phosphates. If present, it generally indicates fertilizer runoff or pollution. Phosphate from raw water can be the cause of scale problems in open recir­culating cooling water systems after the water is concentrated.
Chlorides: Chlorides are involved in most cooling water corrosion cells. Other factors being equal, it can be assumed the higher the chloride con­tent, the more corrosive the water. When pits or cracks occur on stain­less steel or other metals, chlorides are always suspect.
High chloride levels can cause severe corrosion. Corrosion from chlorides can be controlled by increasing the amount of corrosion inhibitor or changing to a more effective inhibitor.
Oil: Oil is not a natural constituent of boiler water; still it can frequently enter a system through leaks in a con­denser or other heat exchanger. Oil can also enter a system through the lubrication of steam driven reciprocat­ing equipment. Whatever the source, the presence of oil in boiler water is undesirable. Oil can act as a binder to form scale. In high heat-transfer areas oil can carbonize and further contribute to the formation of scale.
Foaming is one indication of oil in boiler water. Its presence can also be confirmed by first shaking a bot­tle containing boiler water. If oil is present foam will result. To ensure the foaming is being caused by oil, add a small amount of powdered activated carbon to the bottle con­taining the boiler water and shake. Little or no foam will appear if the foaming is caused by oil.
Often oil in boiler water will origi­nate in the condensate. This conta­minated condensate should be directed to the sewer until the source of the oil is determined and corrective steps taken.
Silica: Silica in boiler deposits is usu­ally combined with other constitutents. Silicates form a number of different scale complexes with calcium, mag­nesium, aluminum, sodium, and iron. Since there is at present no effective dispersant for silicate deposits, the scale problem can be alleviated by maintaining close control of calcium, aluminum, and iron as well as silica.
Iron (oxides): Iron in any of its oxide or complex forms is undesirable in boiler water. It is very difficult to dis­perse so that it can be removed the bottom blow off lines.
Iron in its various forms can originate in the raw water makeup, condensate return water, or form directly in the boiler as a result of corrosion. Most iron oxide originates outside the boil­er. It does not concentrate in the boil­er and it tends to collect in stagnant areas. If a boiler is using raw water makeup, iron is almost certain to be a major component of developing scale.
Water Hardness: Water hardness is the measure of calcium and mag­nesium content as calcium carbon­ate equivalents. Water hardness is a primary source of scale in boiler equipment.
Feedwater: Feedwater is the com­bination of fresh makeup and return­ing condensate that is pumped to the boiler.
Condensate: Condensate is con­densed steam that is normally low in dissolved solids. Hence, it does not contribute to the dissolved solid con­tent of the feedwater. In addition, con­densate is very expensive to waste. It's been chemically treated, heated, pumped, converted to steam, and condensed. This costs money and when condensate is returned to the boiler, money is saved.
Description/Instructions
39-G 1/01
Description/Instructions
41.09
Electrical Requirements
a) Connect wiring as shown in
the wiring diagram which is furnished inside the electrical control panel box.
b) Be sure to install a separate fused disconnect for each. The dis­connects should be installed in com­pliance with the NEC (National Electric Code) and all local codes.
c) Connections for an optional audible alarm are provided in the control panel and are clearly indicat­ed on the diagram.
Fresh Air Supply for Boiler
a) It is most important to provide
free access of air to the boiler. To burn fuel properly, it requires one square inch opening of fresh air for every 3,000 BTU input of fuel. (6.4cm2for every 756 Kcal).
b) Proper ventilation of the boiler room is essential for good combustion. Install two fresh air openings, one at a low level (24”— 610mm from floor) and one at a high­er level in the boiler room wall.This will provide a flow of air to exhaust the hot air from the boiler room.
Room temperature not to exceed 100°F.
c) The following openings are
recommended for each size boiler:
Make Up Air Openings
BHP FT
6 1 .09 10 1 .09 15 1.5 .14 20 4 .37 30 4 .37 40 5 .46 50 5 .46 60 7.5 .69
2
M
2
Be sure total BHP = proper make up air opening size. For instance if you have three 10 BHP boilers, it is a total BHP of 30, and the 30 BHP make up air opening size is recommended.
These measurements are subject to state and local regulations. The installation of exhaust fans in a boil­er room is not recommended. An exhaust fan, or similar equipment can create down draft in the stack or restrict the burner’s air supply which will result In poor combustion. It is essential that only fresh air is allowed to enter the combustion air system. Foreign substances, such as combustible volatiles and lint, in the combustion system can create hazardous conditions.
40-G 1/01
Description/Instructions
46152
Conventional Venting
a) The stack should rise continuously
to the connection with the chimney, and should contain no more than two bends at 45 angles or less. If required as the result of space limitations, one 90 elbow can be fitted at the back of the boiler. There should be two feet of straight, horizontal flue before any bends or turns. Any alternative stack arrangement must supply a negative .02 to.04” W.C. pressure (0.508 to
1.016 mm) with the burner off.
b) The run in the total distance of stack ducting, as measured in a straight line from the outlet of the boiler to the outlet of the stack, should not exceed 25% of the rise. With the exception of a duct run described in Item a, horizontal sec­tions of ducting must be avoided, and should not exceed four feet of total run.
Install Appropriate Weather Cap
c) The stack and chimney material shall comply with all local codes.
d) Adequate provision must be made for the support of the weight of the chimney and stack to avoid hav­ing too great a load imparted to the flue outlet connection of the boiler.
e) The proper flue size and draft control is most important for proper burner operation. The flue must be as large or larger than the outlet on the boiler. Avoid flue piping and elbows by placing the boiler as close as pos­sible to the chimney.
f) A mechanical draft regulator should be installed in the flue outlet. Do not install the draft regu­lator prior to the first turn of the flue.
BHP Boiler Flue Size
Inches Millimeters
6 6 152
9.5 6 152 10 6 152 15 8 203 20 10 254 30 12 305 40 12 305 50 12 305 60 12 305
g) The installer should check the draft with a meter at negative .02 to .04” W.C. pressure (0.508 to 1.016 mm) with the burner off.
Cleanout
Door
Draft Regulator (If Necessary)
Horizontal Run 2'
Support As
Necessary
60°
(45° Min.)
Cleanout
Door
This Distance Must Not Exceed 25% Of Total Rise
Roof
A-A
Expansion Joints As Required
Stagger
Entrances
Draft Regulator (If Necessary)
Horizontal Run 2'
Minimum
6' Above
Any Structure
Within 30'
AA
30°
Max
Baffle
Cleanout
Door
Total
Rise
3'
3'
41-G 1/01
Description/Instructions
Exhaust Side Wall Venting (UL and MEA Approved- MEA File Number 68-79-E Vol. 2 )
a) Boilers for which sidewall venting
may be utilized are No. 2 oil, natural gas, or combination No. 2 oil and nat­ural gas,sizes 4 to 30 H.P. The fol­lowing criteria is required for installa­tions using sidewall venting:
1) Flue vent piping shall be pitched upward at 1/4" per foot of length.
2) A U.L. Approved draft fan must be installed to provide sufficient draft (-.02 to -.04 inches WC pressure -
0.508 to -1.016 mm) to safely vent the products of combustion.
3) The draft fan should be located as close to the flue outlet as possible.
4) Draft regulation sufficient to lower the draft to between -.02 and
-.04 inch WC pressure (-.508 to -
1.016mm) may be required. The draft regulator(s) must be between the boiler and draft fan.
5) The draft fan shall have an air flow proving switch wired in series with the boiler air safety switch.
6) The sidewall vent total length from boiler exhaust to termination shall not exceed 35 feet (10.7 m) with 4 elbows maximum.
Combustion Air Intake (UL and MEA Approved- MEA File Number 68-74-E Vol. 3 )
a) Vertical boilers as described in
MEA 68-79-E Vol. 3 applied with combustion air intake assembly. This shall be applicable only to gas fired units, sizes 4-30 boiler horsepower. The following criteria is required for installations using combustion air intake assemblies.
1) Outside air intake inlet shall be equipped with a vent cap in order to prevent flame blow out from exces­sive wind. This vent cap shall have a minimum cross sectional opening equal to an 8 inch vent pipe.
2) All intake ducting shall have a cross sectional area equal to or greater than 50 square inches.
3) A mesh screen shall be affixed to the air inlet with openings of approxi­mately 1/2" x 3/4".
4) The total length from outdoors to the boiler intake shall not exceed 35 feet (10.7 m) with four elbows maximum.
Corrosion of flue pipe
a) In the case of a combustion flue
pipe, acid may develop over a long period of time by the following process. Chlorine containing gases, such as halocarbon refrigerants, car­bon tetrachloride, trichloroethylene,
or perchloroethylene, when drawn into combustion air are broken down into elemental chlorine gas which exits up the flue pipe. If the flue pipe is cold, as it would be if the combus­tion process had been off for some time, the water vapor condenses in the flue pipe during the first few min­utes of ignition and the chlorine in the combustion gas dissolves in the water forming hydrochloric acid. As the combustion system flue line increases in temperature, the water vapor no longer condenses because the flue temperature is above the dew point of the combustion gas.
The combustion gas then dries out (dehydrates) the hydrochloric acid solution leaving behind dry chloride salt.
b) When the next cold start-up occurs, the process repeats except that more and more chloride collects and concentrates along the flue. As the quantity of chloride increases it does not dehydrate completely as the flue heats up and a corrosive poultice develops which attacks the steel and will also attack the boiler.
c) Concentration levels of only a few ppm of chlorine containing compounds in combustion air can produce serious corrosion over long periods of time. High chlorine con­taining compounds such as carbon tetrachloride or perchloroethylene would be prime suspects .
Air Flow Safety Switch
U.L. Approved Induced Draft Fan
Side Wall
Vent
Termination
(By Others)
Side Wall Vent (By Others)
Installation Check Points
1) Make sure all piping connections
are complete and tight.
2) Make sure the pressure controls are adjusted properly.
3) Make sure all electrical connections in the control panel box, the water col­umn, and elsewhere are secure.
4) Make sure the door in the boiler room is closed. Combustion air cont­aminates can cause damage to the boiler jacket and stack.
NOTE
After installation is complete and prior to operation the pressure vessel should be cleaned.
Cleaning the Pressure Vessel
a) After the boiler has been installed
and before it is placed in service it is advisable to purge the pressure vessel of any oil film,dirt, or other impurities. Clean the pressure vessel as follows:
1) Isolate the boiler from the system by shutting off the main steam valve.
2) Remove the steam safety valve.
3) Mix washing soda with water in a
one-gallon container and pour it into the boiler through the steam safety valve opening.
4) The mixture of washing soda to water is as follows:
Boiler Size Soda
4 - 6 1 lb. (454g)
10 - 15 2 lb (908g)
20 - 30 3 lb (1362g)
40 - 50 3-1/2 lb (1589g)
60 4 lb (1816g)
5) Replace the steam safety valve.
6) Fill the boiler with water. Water
level is about center in the water gauge glass.
7) Generate 15 PSI (1.054 kg/cm2) of steam and shut off the boiler. Allow this hot solution to remain in the boiler for 10 minutes.
8) Drain and flush the boiler twice with fresh water.
9) To remove all the oil and dirt from the main steam and the condensate return lines, allow the returns to go into a floor drain or a safe discharge point for the first week of operation.
CAUTION
Do not store halogenated hydro­carbons near or in the boiler room.
In general, ensure that the boiler area is in conformance with established boiler room requirements. Review national and local codes.
As a final checkpoint, again,
Water Treatment
We cannot emphasize enough the importance of proper water treat­ment: Water analysis should be made by a competent water treat­ment concern and their recom­mendations should be followed.
Description/Instructions
42a-G 1/01
42b-G 1/01
Operation
3
43D-G 1/01
43b-G 1/01
44-G 0/01
Starting the Gas Fired Boiler
Stop! Make sure you have read and followed all previous safety information.
Check with local authorities where approval for start-up is required. In some localities, final inspection of services may be required.
In general, ensure that the boiler area is in conformance with estab­lished boiler room requirements. Review national and local codes.
Carry out the following procedure on the initial start up of the boiler and on every subsequent occasion when restarting the boiler after a shut down.
1) Close the blow-off valve.
2) Close the water gauge drain
valve.
3) Open main steam stop valve at the top of the boiler.
4) Open the water feed valve on the boiler.
5) Open valves on makeup water line to return if return system is used.
6) Place feedwater pump fused switch in the "on" position.
NOTE
a) The fused disconnect switch that controls the feed water pump should be kept in the "on" position at all times during the boiler opera­tion as well as during the non­operating period of the boiler.
b) This switch should be turned "off" only when repairs or adjust­ments should be made.
NOTE
The pump will continue to operate until the water reaches the correct level in the boiler. This level is approximately the center of the water gauge glass.
7) Activate the boiler power on
switch, located on the side of the panel box.
8) With the unit full of water the low water safety relay(s) will be in a lock­out mode. Press the low water safety relay manual reset button located on the side of the control panel box.
Operation
Operation
Gas Burner Set Up
NOTE: Refer to Section LE for LOW EMISSIONS BURNERS
a) Open the manual gas cocks on the
pilot and main lines of the gas head.
b) Switch on the main power to the burner. The water level relay is equipped with a manual reset. Depress the button on the box.
c) The flame programmer is the main control in the panel box. The program­mer in conjunction with a sensing device, either a flame rod or a UV scanner, "supervises" the ignition sequence - proves the flame is satis­factory, and finally"monitors" the estab­lished flame. Should any fault occur, either during the ignition sequence or during normal running, the program­mer will immediately go to "lock-out" and the burner will shut down.
d) When the pilot flame is estab­lished, the flame rod (or ultra-violet scanner) senses the voltage which is created in the flame between the flame rod and the gas nozzle (ground). This signal is transmitted back to the flame programmer which opens the main gas valve giving a main flame.
e) Fulton 4 - 30 h.p. natural gas fired boilers can be equipped with flame rods or UV scanners.
f) All Fulton propane or butane boil­ers and 50 and 60 HP Fulton natural gas boilers are standardly furnished with UV Scanners.
1) If the installation is new or the burner has been disassembled, the burner may not fire at the first attempt due to air which must be purged from the gas lines. This will result in the burner flame programmer going to lockout. Repeat the procedure for starting the burner.
2) The main gas valve will remain open as long as there is a demand for heat and the flame is carrying a suffi­cient signal to the flame programmer.
3) If the flame is not established at the start, the safety switch in the flame programmer control will open the contacts and shut off the burner.
4) Push the reset button on the control to reset. If trouble persists, it may be necessary to check the flame rod setting or the UV scanner. See Maintenance Section 4 for pro­cedure to check flame rod setting or UV Scanner.
60 HP – 7800 flame safeguard control
45-G 1/01
4-50 HP – 7895 flame safeguard control
4-30 HP with flame rods 50 and 60 HP with UV Scanner
46-G 0/01
Operation
Gas Burner Set Up For Boilers Equipped with Modulation
a) Modulation is available as an
option on Fulton gas fired steam boil­ers for 30 -100 HP units only.
b) Boilers equipped with modulation will have the linkage rod disconnected between the modulation motor and the gas butterfly valve for shipment.
c) Mount the gas train on the pipe nipple of the burner plate with the gas train inlet directly facing over the panel box. Reconnect the linkage from the butterfly valve to the modula­tion motor.
d) The end of the linkage arm that attaches to the butterfly valve will have a notch on both sides of it, where the swivel collar should be centered. This setting was based on factory test fire conditions.
e) Combustion analysis should be done at the installation to make any changes to insure proper combustion characteristics.
f) The modulating burner will have a modulation lock switch in the panel box to enable you to lock the firing sequence anywhere along the firing rate from low to high.
g) Depending on the combustion characteristics, it may be necessary to adjust both linkage arms. To adjust the linkages, unscrew the swivel col­lar and move the linkage rod in the appropriate direction.
h) Modulating burners will have a pro­portioning pressure control in addition to the standard operating pressure control that will send a 0-135 ohm sig­nal to the modulation motor to adjust the firing rate. Both pressure controls should have the same setting.
i) NEMA 4 units will use a digital pressure controller with transducer as the operating pressure control which sends a 4-20 ma signal to the modu­lation motor to control firing rate.
Modulating Gas Fired Burner
Panel Box for Modulating Gas Fired Boilers
Proportioning Pressure Control
Night Heating Pressure Control (Optional)
Modulation Hold/Lock Switch
47-G 1/01
Operation
Gas Burner Set Up For Boilers Equipped with High-Low-Off
a) A gas fired burner equipped for
high-low-off firing is available as an option on Fulton gas fired steam boilers for 30 -100 HP units only.
b) Boilers that have a high-low-off firing rate will have a linkage between the high-low gas valve and the primary air gate. This valve is equipped with a spring return.
c) The linkage will be disconnected from the gas valve for shipment.
d) Mount the gas train on the pipe nipple of the burner plate with the gas train inlet directly facing over the panel box. Reconnect the linkage from the primary air gate to the high­low gas valve.
e) The end of the linkage arm that goes to the gas valve will have a notch on both sides of where the swivel collar should be centered. This setting was based on factory test fire conditions.
f) Combustion analysis should be done at the installation to make any changes to insure proper combus­tion characteristics.
g) To adjust the linkage, unscrew the swivel collar and move the link­age rod in the appropriate direction. The high-low-off configuration comes with two operating pressure controls.
h) Set the low operating pressure control to approximately 60% of your desired set point and the main oper­ating pressure control to your desired set point.
Gas burner equiped with high-low-off firing
Panel Box for Boilers equiped with high-low-off firing
Low firePressure Control
Night Heating Pressure Control (Optional)
48-G 0/01
Operation
WARNING
Prior to the commencement of any work requiring the removal of cover plates and the opening of the control panel box, the electrical supply to the boiler must be dis­connected.
Primary Air Adjustment for Fulton Gas Fired Steam Boilers
a) The primary air adjustment or main
air control is located at the fan hous­ing face. This control is used to sup­ply the burner with excess air needed to facilitate good combustion. Too much or too little air will result in poor combustion. It is important to make sure the lowest level of excess oxy­gen is present while still maintaining a high level of carbon dioxide and neg­ligible carbon monoxide. Using a CO2or O2tester it is possible to determine the percent of excess air in the combustion mixture.
b) It is a good policy on a gas fired unit to have between 3.5% and 4% oxygen present in the combustion. This will give you 10.5% to 9.5% car­bon dioxide. The carbon monoxide level should always be less than 400 PPM.
Secondary Air Adjustment Procedure for Fulton Gas Fired Steam Boilers
a) The secondary air control adjust-
ment is located on the top, right-hand side of the burner assembly. This damper type air controller is used to introduce air to and through the blast tube of the burner. The purpose of the secondary air adjustment is to proportionately divide the air to the center or outer fire chamber. By mov­ing the damper closed, the air is forced to the outside of the fire chamber with less air going down the
blast tube area. By pulling the damper open more air is forced down the blast tube and less on the outside wall of the deflector face and fire chamber.
b) It is important in the combustion process to maintain proper air mix­tures between the outer surface and center of the blast tube area. On most boilers the damper is locked in a wide open position. However, if it is necessary to close the damper, care should be taken to close the damper slowly and no more than 1/4 of the distance of the swing of the damper assembly.
c) A visual examination down the blast tube should reveal that no heat, flames or fumes are backing up through the burner plate area. If they are, the secondary damper must be opened up once again. Failure to
remove the flame or gases from the blast tube area can cause a backfire as well as cause premature failure of electrodes, flame rods, and other burner components.
d) A visual inspection down the burn­er view port should also show the fire completely covering the furnace walls. If the fire is tunneling down or is not to the outside wall of the fur­nace, the efficiency will drop off. Close the secondary air damper until tunneling stops.
Primary Air Adjustment is located at the fan housing face
Blast Tube Viewing Port
Burner Viewing Port
Secondary Air Adjustment 40-60 HP
Secondary Air Adjustment 4-30 HP
49-G 1/01
Operation
Boiler Controls
a) Flame safeguard burner control–
This is the main control in the panel box. The programmer in conjunction with a sensing device, either a flame rod or an ultra violet scanner,"super­vises" the ignition sequence - proves the flame is satisfactory - and finally "monitors" the established flame. Should any fault occur, either during the ignition sequence or during normal running, the programmer will immedi­ately go to "lock-out" and the burner will shut down.
b) Low Water Cut-Off--probe type– Cuts off the unit when water level is too low after a 3 second time delay to avoid nuisance shut downs. As a standard feature, Fulton boilers are equipped with ASME CSD-1 Code controls which include a manual reset feature on the burner low water cut off relay and ASME CSD-1 Code controls also feature an independent second low water cut off relay. Press the low water reset button and the boiler will start.
CAUTION
Do not tamper with the safety fea­tures of the low water safety cut out.
c) Pressure Relief Valve– limits
maximum operating pressure of the boiler.
d) Operating Steam Pressure Control– located in the control panel
box and connected to the steam pres­sure gauge assembly by means of a copper tube. The pressure control reg­ulates the on/off cycle of the burner, shutting the burner off when maximum pressure is reached and switching on when the steam pressure falls below a
predetermined level.
e) Sight Glass Isolation Valves--
The brass sight glass isolation valves are equipped with an internal ball check. In the event that a sight glass should break, the ball will seat, pre­venting the discharge of steam and water. The brass valve stem must be opened fully to enable this feature. If the valve is in any other position than full open, the ball will not seat. For added safety all Fulton boilers are
equipped with gauge glass protectors. f) High limit pressure control– locat­ed in the control panel box and con­nected to the steam pressure gauge assembly by means of a copper tube. The pressure is usually set 10 to 15 PSI (.703 - 1.054 kg/cm2) above the operating pressure, but below the
maximum pressure of the pressure relief valve. If the pressure exceeds the high limit pressure control setting, the boiler will automatically shut off.
The high limit pressure control must be manually reset by depressing the
plunger located on top of the control. f) Air Pressure Switch– mounted on the burner scroll, this switch is operated by the pressure of air enter­ing the burner through the throat of the scroll. Absence of air, or insuffi­cient pressure, will prevent the switch completing the circuit, thus
preventing the burner from operating.
WARNING
When stopping the boiler for any extensive repairs, shut off main dis­connect switches on both the boiler side as well as the feed water side.
NOTE
To ensure that your Fulton Steam Boiler is kept operating safely and efficiently, follow the maintenance procedures set forth in Section 4 of this manual.
Maintenance
4
5-G 1/01
51-G 1/01
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;
;;;;;
;;;;;
;;;;;
;;;;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;
QQQQQQQQQQQQQQQQQQQQ
QQQQQQQQQQQQQQQQQQQQ
¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢
¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢¢
52-G 1/01
Maintenance
Gas Train
Assembly
Burner
Plate
Assembly
Secondary
Air Damper
Top Plate Assembly
Flue Plate
Cover
Flue Rope
Gasket
Flue Blanket
Lifting Hook(s)
Stainless
Steel Ring
Transformer Scroll
Gaskets
O.P .C.
To
To
H.P .C.
Burner Motor
*
*
Steam Gauge Assembly
Gauge Glass Valve
Gauge Glass And Protector
Water Column
Flue Outlet
Top
Refractory
Feedwater
Inlet
Bottom
Refractory
Blowdown
Outlet
Boiler Runners
(4-30 HP)
Gauge Glass Valve
Control Box
High Density Insulation
Outside Jacket
Handhole
Castable Refractory Insulation
O.P.C. = Operating Pressure Control
*
H.P.C. = High Pressure Control
*
Maintenance
NOTE
To ensure the continued safety and efficiency of the boiler, the sched­ule of maintenance outlined in this section should be adhered to.
WARNING
Prior to the commencement of any work requiring the removal of cover plates and the opening of the con­trol panel box, the electrical supply to the boiler must be disconnected.
Procedure for Cleaning Water Probes
Clean probe on top of boiler shell and probes in water column. Make sure there is no pressure on the boiler during the removal of the probes. Remove one probe (using a 7/8" socket), clean with very fine emory cloth and replace it before removing another to assure no probe mix-ups that would change the control functions.
For replacement purposes, installed probe lengths are indicated in the chart below. For a universally adapt­able plug and probe which can be cut to length in the field to fit all boilers, order Part No. 2-20-017.
*A = 7-1/4” -- 184 mm *B = 9-1/4” -- 235 mm *C = 11-1/4” -- 286 mm
D = 17-1/8” -- 435 mm
*For 4 HP boilers only, water column probes are 2” shorter.
53-G 1/01
ABCD
Flame Rod Adjustment for Fulton Gas Fired Steam Boilers
a) The flame rod adjustment is made
by loosening the lock nut and turning the porcelain portion of the flame rod clockwise or counter clockwise. Whenever a flame rod is moved, care should be taken to ensure that the flame rod does not ground out by touching the metal surface of the blast tube assembly. A keyboard display module can be used to determine proper signal response. It is neces­sary to establish pilot so that the main gas valve will engage. The main flame should be adjusted to an acceptable flame signal to ensure con­tinued performance. A poor signal will result in the boiler flame programmer going off on safety.
b) A single flame rod is used on 4-15 HP Fulton Boilers, and two flame rods on 20 and 30 HP. If the boiler has two flame rods, adjust the flame rod in the burner plate first, with the outside one disconnected. After a good pilot signal is established on the inside flame rod, then the outside flame rod can be hooked up and the signal adjusted for proper responses.
c) If a signal is erratic after adjusting the flame rod, the main and secondary air supplies may need adjusting. If a flame rod is cracked or broken, the porcelain will have to be replaced to get a proper signal.
Flame Scanner Adjustments for Fulton Gas Fired Steam Boilers
a) Flame scanner adjustments are
made with the detectors installed and the burner running. It is essential to obtain optimum flame signal detection for safe and continual operation of the control relay.
b) If a scanner is inoperable, it may prove the detector is working and only an adjustment to the pilot flame is needed to improve the signal.
c) If the scanner is found to be defective, replace.
NOTE:
The scanner is located on the out­side edge of the burner top plate for 20-60 HP.
d) For the RM7800 Series use a key-
board display module or volt meter,the flame safeguard will require a 1.25 VDC signal to pull in the main flame. Then a maximum signal should be obtained on main flame (5.0 VDC).
e) Adjustments to establish a good signal may include the following items:
1) Primary and secondary air adjustments.
2) Increasing the pilot gas through the pilot gas regulator.
Checking the Stainless Steel Combustion Ring on Fulton Gas Fired Steam Boilers
a) The stainless steel combustion
ring in Fulton gas fired boilers (50-60 HP only) are designed to bring quick and effective flame transfer to the fire wall. The ring should fit securely and tight against the furnace wall for best results.
b) The ring should be inspected for distortion in the event of poor com­bustion which could result in flame failures.
54-G 1/01
Maintenance
Stainless Steel Combustion Ring
Primary Air Gate
Gas Head
Flame Rod(s)
Scanner Location (20–60 HP)
*
Scanner (4–15 HP)
Burner Plate
Secondary Air Gate
Blast Tube
Viewing Port
Burner
Viewing Port
Blast Tube
Top Plate
Air Deflector
If Applicable
*
Furnace Refractory Replacement Procedure
a) Remove the burner plate and top
plate assembly up and out of the scroll assembly.
b) Remove the stainless steel com­bustion ring from the furnace (50 and 60 HP only).
c) Remove the clean-out plugs from the bottom sides of the boiler. 4-15 HP boilers have one clean out plug located at the bottom of the boiler directly below the panel box. 20-60 HP boilers have one clean out plug located at the bottom of the boiler to the right side of the panel box. 10-30 HP Energypak Boilers have one clean out to the right of the lower right side hand hole and one clean out to the right of the rear bottom blow down.
d) Break off the top holding clips that were used to keep the refractory in position during shipping. The 4-50 HP boilers also have holding clips beneath the top refractory. There is no need to cut the holding clips located beneath the top refractory as the refractory may be rotated to avoid these clips during installation of the lower refractory. The 60- HP boiler has welded flat bars beneath the top refractory. These bars will have to be cut to change the lower refractory. Rewelding of the bars will be required prior to installation of the top refractory. For the lower refractory you will also need to break off the top holding clips that were used to keep the refractory in position during ship­ment.
e) Break up the top and/or bottom refractories and remove the pieces from the boiler through the clean-out plugs.
NOTE
If only the top refractory is to be changed, the bottom refractory need not be broken.
f) Round and bevel the outer edges of
the new refractories.
g) The bottom refractory has the largest hole, while the top refractory has the smallest.
h) Lower the bottom refractory down the furnace with wire fastened around the refractory in three positions. When the refractory is close to position, it can be tipped by maneuvering the wire to drop it flat on the holding clips. If the refractory will not tip, it may have to be removed and again rounded and beveled.
i) Install the top refractory in the same manner as the bottom refractory. When installed the outer edges must be sealed with insulcrete - a castable refractory mix available from the Fulton factory.
It is not necessary to reinstall the ship­ping clips.
j) Install the stainless steel combus­tion ring, (50-and 60 HP only) burner assembly, and clean out plug.
k) normal operation can be resumed immediately.
55-G 1/01
Maintenance
Gas Train Assembly
Air
Deflector
Gas Orifice
Assembly
Stainless Steel
Combustion
Chamber
Ring
Stainless Steel Ring
Supporting Clips
Holding Clips For
Shipping Only
Stainless Steel
Supporting Clips
Top Castable
Refractory
Bottom
Castable
Refractory
Holding Clips For
Shipping Only
Stainless Steel
Supporting Clips
56-G 1/01
Recommended Daily Maintenance Schedule
a) The following procedures should be
carried out daily. They are designed to prevent the build up of scale, silt, or sludge in the bottom of the boiler and in the pipes leading to the water gauge. In addition to these proce­dures, the advice of a water treatment supplier should be sought and fol­lowed. An ASME Section VIII blow off receptacle must be provided for the appropriate pressure.
b) Blow down the boiler each morning by starting the boiler and generating not more than 10 PSI (.703 kg/cm2) of steam. Turn on tap water to blow-off separator, then open the boiler blow off valve for approximately 10 seconds, then close the valve. Shut off tap water to blow-off separator.
Blow Down Boiler Daily. Shown is the blow down "Y" valve.
NOTE
If the boiler is being operated auto­matically on a time clock, the blow off operation may be done once during the working day and once at the end of the day when at 10 PSIG or less.
c) Blow down water column each
morning when boiler is at 10 PSI (.703 kg/cm2) by opening the water column and the water gauge blow off valves for approximately 5 seconds, then close the valves.
Blow down water column each morning by opening the water column and the water gauge blow-off valves.
d) If the feed water is being treated by
compounds, make sure that this treat­ment is carried out carefully and according to the manufacturer's instructions.
NOTE
Fulton recommends that the feed­water treatment should be added between the pump and the boiler.
e) When first starting the boiler each
day, make sure ignition and burner are working properly.
f) Check water level in sight glass.
g) Check to be sure feed water pump
is working.
h) For float type water level control, blow-down float chamber.
Recommended Weekly Maintenance Schedule
a) Check that the low water cut-off
relay is operating correctly in the following manner:
1) Make sure that the boiler is cool with little or no pressure showing on the steam pressure gauge.
2) With the burner operating, open the boiler blow off valve. When the water drops below the required level (note the level in the water gauge glass) the burner should shut off; this is when the water level falls below the low water electrode in the water column assem­bly and/or the boiler shell. Manual reset of the low water relay is required.
Recommended Monthly Maintenance Schedule
WARNING
Make sure main power switch is off before starting work.
a) Clean the water gauge glass.
CAUTION
Do not clean the gauge or gauge glass while pressurized or in opera­tion.
1) Clean the water gauge glass using
a commercial non-abrasive glass cleaner. Use diluted acids such as hydrochloric (muriatic) acid when regu­lar cleaners do not seem to work. Do not use wire brushes or any other abrasive materials which could scratch the glass. If any leakage is evident, replace the gaskets.
Clean Glass; Replace Gaskets If Leaking
2) Always replace the high impact
plastic gauge glass protector which is standard on all Fulton Boilers.
b) Clean water pump strainers.
c) Check scanner or flame rod and
ignition electrodes.
d) Check starter contacts. Burned or pitted contacts should be replaced. Do not use sand paper or file to clean.
e) Clean water traps and strainers in fuel lines.
f) Check operation of all steam traps on condensate return system.
Maintenance
57-G 1/01
Maintenance
g) Remove brass pipe plug at the
cross connection below water column and clean nipple into boiler. Boiler must be cold and water level below pipe.
Remove plug at cross section; clean nipple to boiler.
Recommended Semi-Annual Maintenance Schedule
a) Cleaning the gas burner assembly
1) Disconnect the gas head from the
burner by disconnecting the union. Remove the burner plate screws. For 4-15 HP boilers with scanner, discon­nect scanner from burner plate.
Withdraw the burner assembly and clean the flame rod and ignition elec­trode.
2) Check that the settings of the flame rod, if applicable, and ignition electrode correspond to those in the illustration below.
3) Reassemble the burner assembly and check the flame rod setting or scanner setting.
4) Check the combustion efficiency of the burner and adjust if necessary.
5) Clean probe on top of boiler shell and probes in water column. There must be no pressure on the boiler dur­ing the removal of the probes.
6) Check refractories for soot or breakage and inspect the stainless steel ring (50 and 60 HP only).
7) With the boiler under no more than 15 PSI pressure, check that the steam safety valve is operating by lifting the lever.
b) Drain condensate tank and clean tank by flushing with hose. Check float valve operation.
c) Check electrical controls and motors for correct operation.
d) Check water pump for correct operation.
e) Shut off the boiler completely and drain.
f) Remove the hand holes and inspect the interior of the vessel for scale or sludge deposits. The
amount of deposits will indicate the efficiency of the water treatment being used. The frequency of the inspection will depend on the condition of the water side of the boiler.
Inspect hand holes for scale or sludge buildup.
Test
Pressure
Tapping
Flame Rod
Orifice
Pipe
Grounding
Fins
Gas Burner Ignition
Electrode gap setting is same on 4 - 100 HP units whether Flame Rod or Scanner is utilized.
Ignition Electrode Ignition Electrode
Holder Burner
Plate
Gap to Pipe 1/8" ±1/16" (Ignition Gap)
Gap to Pipe 1/8" ±1/16"
g) Replace hand hole gaskets using the following procedure:
1) Remove the hand hole assembly
using a 1-1/4" tee handle wrench or 1-1/4" 1/2" drive socket wrench.
Removing hand hole assembly with a Tee Handle Wrench
2) Remove the old gasket and thor-
oughly clean the surface on the boiler and the plate.
3) Fit the hand hole assembly as follows:
a) Place the gasket on the hand hole plate and ensure that it is seating cor­rectly. Do not use any grease, lubri-
cant, or adhesive.
b) Position the plate in the boiler. Set
the yoke and tighten the securing nut sufficiently enough to provide a snug fit. Verify the position of the plate in the boiler, then make it hand tight and then snug with wrench about 1/4 turn. Do not compress excessively.
Illustration shows correct pressure on gasket.
c) If the gasket leaks while pressure is
being built up, tighten only enough to stop leakage.
Never tighten more than necessary to prevent leakage. Excessive tightening may shorten the life of the gasket.
Illustration shows over compressed gasket.
d) Refill the boiler with fresh water.
NOTE
After a new Fulton Boiler has been in operation for several months, pieces of burned metal will be found in the space at the bottom of the boiler. These pieces of metal are the remains of a light gauge metal form which was used during manu­facture for forming the boiler insula­tion. This is a normal condition and does not affect the efficiency or the life of the boiler in any way.
Recommended Annual Maintenance Schedule
a) Have combustion (CO2, O2, CO)
and input checked by responsible per­sonnel.
b) Dirty flues can cause air flow restrictions resulting in poor combus­tion and loss of efficiency.
Clean flues as follows:
1) Remove the burner and flue
cover plate.
2) Wire brush flue passages.
Wire brushing the flue passages.
3) Remove clean out plugs at lowest
part of unit and clean the bottom of combustion chamber.
Removing clean out plugs.
4) Remove all soot from the top, and
from the clean out plugs at the bottom with a vacuum cleaner.
5) Replace clean out plugs carefully so as not to damage insulation and replace burner and flue cover plates.
c) Flush boiler out if necessary. See Section 2 for proper procedure for "Cleaning the Pressure Vessel."
d) Provide annual inspection by a qualified ASME Boiler inspector.
Maintenance
Remove burner and flue cover plate
58-G 1/01
59-G 1/01
Maintenance
Troubleshooting
a) The following trouble shooting
guide will assist in the diagnosis and the correction of minor field prob­lems. It contains instructions and information necessary to locate and isolate possible troubles which occur during normal operation. It
should be used in conjunction with the unit wiring diagram and the component literature provided in Section 7 of this manual.
b) The following lists cover the most common troubles that may occur on the Fulton gas fired boilers. Refer to left hand column of the chart to
locate the problem. Determine which cause, listed in the center col­umn, that represents the problem by performing the corrective action as listed in the right hand column titled “REMEDY”.
Troubleshooting Gas-Fired Boilers
Problem Cause Remedy
Ignition Failure 1. Power Supply Check fuse or circuit breaker. Reset or
replace, as necessary.
2. Ignition Electrodes Check electrodes for carbon buildup and clean if necessary. Check for proper adjustment. Readjust if necessary. Check for cracks in porcelain. If found,replace.
3. Transformer Check voltage between transformer leads at terminal block to be sure transformer is being powered.
4. Flame Safeguard Check voltage between ignition terminal and neutral.
Control Check must be made before control locks out on safety.
If no power, replace control.
5. Faulty Air Switch Check for bad air switch by jumpering the two air switch leads at the terminal block. If the boiler starts and runs with these terminals jumpered, the air switch should be replaced.
6. Gas Valve Sticking Check for dirt in valve or orifice and clean if necessary.
(Pilot) Check for faulty actuator or valve and replace if necessary.
7. Gas Supply* Check for gas pressure and for intermittent supply problems. Gas pressure for natural gas should be 3-1/2" W.C. plus fan pressure at the elbow to the burner and 7" to 11" W.C. at the head of the train.
8. Loose wire connection Check connections to all components.
Flame Failure 1. Power Supply Check fuse or circuit breaker. Reset or replace, as
necessary.
2. Gas Supply* Check for gas pressure and for intermittent supply problems. Gas pressure for natural gas should be 3-1/2" W.C. plus fan pressure at the elbow to the burner and 7" to 11" W.C. at the head of the train.
3. Ignition Electrodes Check electrodes for carbon buildup and clean if necessary. Check for proper adjustment. Readjust if necessary. Check for cracks in porcelain; if found, replace.
4. Primary Air Adjustment Check air adjustment. Air may be blowing flame away from flame rod.
* For natural gas fired boilers. Refer to the test fire sheet for all other fuels.
60-G 1/01
Problem Cause Remedy
Flame Failure 5. Flame Rod Adjustment Check flame rod for carbon buildup and clean if
or UV Scanner necessary. Check flame rod adjustment via a
display module. Flame signal should be 5 VDC. Check for cracks in porcelain. If found, replace. Check for dirt on flame scanner and clean. Check for proper location of detector.
6. Flame Safeguard Control Check voltage at terminal leading to main gas valve. If no power, replace the control.
7. Loose wire at fuel Tighten wiring connections.
valve circuit
8. Contact open on air Adjust to proper setting.
safety switch
9. Scanner wiring reversed Change to correct terminals.
at panel box.
Burner Cut-Off 1. Power Supply Check fuse or circuit; reset or replace, as necessary.
2. Gas Supply Check to be sure main gas cock is not closed. Check coil in gas valve with OHM meter. Replace if faulty. Check gas regulator setting and readjust as necessary. Check inlet gas pressure and increase or decrease as necessary.
3. Ignition Electrodes Check electrodes for carbon buildup and clean if necessary. Check for proper adjustment Readjust if necessary. Check for cracks in porcelain; if found replace.
4. Flame Rod Adjustment Check flame rod for carbon buildup and clean if
or UV Scanner necessary. Check flame rod adjustment via a
display module. Flame signal should be 5 VDC. Check for cracks in porcelain. If found, replace. Check for dirt on flame scanner and clean. Check for proper location of detector.
5. Air Switch Check for bad air switch by jumpering the two air switch leads at the terminal block. If the boiler starts and runs with these terminals jumpered, the air switch should be replaced.
6. Gas Valve Sticking Check for dirt in valve or orifice and clean if necessary.
(Pilot) Check for faulty actuator or valve and replace if necessary.
7. Weak Ampl;ifier Replace.
8. Weak Pilot Adjust to larger pilot by adjusting pilot gas pressure regulator.
9. Faulty Liquid Level Control Check to see if there is power to terminal number 10 when the sight glass shows the proper water level. If there is no power at this terminal, the control is bad and must be replaced.
10. Dirty or defective Clean or replace.
UV Scanner.
Maintenance
61-G 1/01
Maintenance
Problem Cause Remedy
Poor Combustion 1. Refractories Check refractories to see if they are plugged with soot or
broken in pieces. Clean or replace as necessary.
2. S.S. Ring Check to be sure ring is present and fits tight against the furnace wall (50-100 HP).
3. Primary Air Check air adjustment. Air/fuel mixture may be off. Open
Adjustment primary air so fire is to outside wall of furnace.
4. Secondary Air Check main air adjustment to see if it is loosened up.
Adjustment Adjust as necessary and tighten plate in position. Check
CO2and O2levels.
5. Draft Check draft with a gauge. Draft should be a -.02 " to -.04" W.C. with burner off or -.04" to -.06" when operating. May need to install a barometric damper.
6. Dirty Flue Check flue for carbon buildup or blockage. Clean flue passages with brush.
7. Negative Room Pressure Make sure no exhaust fans are running in the boiler room.
Burner back fires 1. Refractories Check refractories to see if they are plugged with soot or
broken in pieces. Replace as necessary.
2. Ignition Electrodes Check electrodes for carbon buildup and clean if necessary. Check for proper adjustment Readjust if necessary. Check for cracks in porcelain; if found replace.
3. Flame rode adjustment Check flame rod for carbon buildup and clean if
or UV Scanner necessary. Check flame rod adjustment via a
display module. Flame signal should be 5 VDC. Check for cracks in porcelain. If found, replace. Check for dirt on flame scanner and clean. Check for proper location of detector.
5. Draft Check draft with a gauge. Draft should be a -.02 " to -.04" W.C. with burner off or -.04" to -.06" when operating. May need to install a barometric damper.
6. Negative Room Pressure Make sure no exhaust fans are running in the boiler room.
Boiler will not 1. Gas Supply Check gas pressure coming into gas train. If low, maintain pressure contact gas company. Should be 7" to 11" W.C. Check
coil in gas valve with AMP meter. Replace if bad. Check gas regulator setting and readjust as necessary.
2. Dirty Flue Check flue for carbon buildup or blockage. Clean flue passages with brush.
3. Pressuretrol Disconnect all power to the controller. Disconnect the wires from the controller. Put an OHM meter between the switch terminals. Lower the set point of the controller. Switch should make. Raise the set point and recheck with OHM meter. Switch should break. If the controller operates improperly, replace it.
62-G 1/01
Maintenance
Problem Cause Remedy
Boiler will not 4. Scale Built up in boiler Refer to Section 2 “Pressure Vessel Cleaning”. maintain pressure
5. Refractories Check refractories to see if they are cracked or broken in pieces. Replace as necessary.
6. Steam traps Check traps to see if they are clean or replace as
blowing through. necessary.
7. Boiler size. Boiler may be undersized.
Boiler is Surging 1. Steam traps blowing Check traps to see if they are clean or replace as
through necessary.
2. Perc (cleaning solvent Clean boiler with washing soda per
in boiler) instruction manual.
3. Scale build-up or lime Call water treatment professional and consult factory.
deposits.
4. Too much compound in Dump return tank and flush system. Have water tested by
system (water treatment) water treatment company.
5. Too much water Have water tested by water treatment company.
softener (high PH)
6. Too much of a load Check total equipment horsepower required against horsepower of boiler being used. Decrease amount of equipment being used at one time.
7. Boiler new (not Clean per instructions in instruction manual.
cleaned).
Boiler Rumbles and 1. Draft problem Check draft with a gauge. Draft should be a -.02 " to -.04" Pulsates W.C. with burner off or -.04" to -.06" W.C. when
operating. May need to install a barometric damper.
2. Too much primary air (See primary air adjustment)
Boiler pushing water 1. Steam Traps Check traps. Clean or replace as necessary. with the steam
2. Too much boiler Dump return tank and flush system . Have
compound water tested by water treatment company.
Pump will not cut off 1. Dirty Probes Clean or replace as necessary.
2. Relay failed Make sure relay is plugged in tightly. If so, replace water level relay.
3. Ground Connection Check for tightness and clean.
63-G 1/01
Maintenance
Problem Cause Remedy
Pump runs but does 1. Vapor locking of pump. Allow system to cool down, check steam traps not put water into boiler and check to be sure return lines are not insulated. Check
return tank temp. If it is above 180 deg. F, (82 deg. C) vapor locking of pump will occur. Inspect check valves. Clean and replace as needed. Replace pump with multistage centrifugal good for 250 degrees F (121 deg.C).
2. Impeller Adjustment Check for impeller wear and adjust per component information in instruction manual (Burks only).
3. Back pressure on pump Need to install repair kit on pump.
4. Plugged feed water Check and clean or replace as necessary.
nipple
Water pump will not 1. Scale on probes. Check and clean or replace as necessary. come on at times.
2. Bad Pump Contactor Check to see if contactor is being powered. Check to see if contactor coil is pulling in. Replace if necessary.
3. Bad Pump Motor Check the incoming power to the pump to be sure it is receiving power. If power is present but motor does not run, replace it.
Low Fuel pressure 1. Gas pressure regulator Check and replace.
Boiler Flooding 1. Pump does not Dirty Probes. Clean or replace as necessary.
shut off
2. Relay failed Make sure relay is plugged in tightly. If so, replace water level relay.
3. Ground Connection Check for tightness and clean.
4. Vacuum created with As the boiler cools off, it pulls water from the system
boiler off. piping. To prevent this, add a 1/4" check valve on the
steam gauge assembly piping, which closes under pressure and opens under vacuum.
Parts
5
6-G 1/01
ICS (FB-A) Classic & ICX (FB-F) Edge manual update:
For all new ICS (FB-A) Classic boilers manufactured 2018 and after, the following updates have occurred:
The ICX (FB-F) Edge model boiler has been discontinued.
The ICS (FB-A) Classic is now configured as follows:
The ICS (FB-A) Classic boilers initially configured as natural gas or propane boilers are
configured with the ICX (FB-F) Edge second flue gas pass rib heat transfer pattern and cannot be converted to fire #2 oil. These boilers will also require use of the Edge cleanout brush in lieu of the standard. The Edge cleanout brush part number is 2-60-
000155.
The ICS (FB-A) Classic boilers initially configured as #2 oil boilers or combination natural
gas/propane and #2 oil boilers are configured with the further spaced Classic second flue gas pass rib heat transfer pattern. These boilers will also require use of the Classic cleanout brush. The Classic cleanout brush part number is 2-60-000112.
66-G 1/01
Parts
Spare Parts
a) It is important that the correct
replacement part is fitted to your Fulton Gas Fired Steam Boiler.
b) When ordering replacement or spare parts, make sure that the full information given in the Parts List is supplied, together with the following details as shown on your boiler identification plate:
1. Boiler Number
2. Boiler Type
3. Electrical Specifications
Note:
The policy of Fulton Boiler Works, Inc. is one of continuous improvement, and therefore, we reserve the right to change prices, specifications, and equip­ment without notice.
Parts
5-60-100 Instruction Manual, Fuel-Fired 2 0.91 5-60-165 Certification Papers 5-60-164 Boiler Documentation for Export Boilers
Boiler Shell Parts
5-12-004 Furnace Refractory 8" OD x 2" ID (9.5 HP Top) 10 4.55 5-12-005 Furnace Refractory 8" OD x 21/2" ID (4 HP Gas Top - Old Style) 10 4.55 5-12-006 Furnace Refractory 8" OD x 3" ID (9.5 HP Bottom ) 10 4.55 5-12-007 Furnace Refractory 10" OD x 3" ID (4-10 HP Top) 18 8.18 5-12-008 Furnace Refractory 10" OD x 31/2" ID (15 HP Top) 18 8.18 5-12-009 Furnace Refractory 10" OD x 5" ID (4-15 HP Bottom) 18 8.18 5-12-010 Furnace Refractory 15" OD x 51/2" ID (20 HP Top) 35 15.91 5-12-011 Furnace Refractory 15" OD x 6" ID (30 HP Top) 35 15.91 5-12-012 Furnace Refractory 15" OD x 7" ID (20 & 30 HP Bottom) 35 15.91 5-12-015 Furnace Refractory 24" OD x 8" ID (40 - 60 HP Top) 125 56.82 5-12-016 Furnace Refractory 24" OD X 10" ID (40- 60 HP Bottom) 125 56.82 5-12-017 Furnace Refractory 30" OD x 91/2" ID (80 HP Top) 225 102.27
2-12-000 Furnace Cement- 2 Ib. can 2 0.91 2-12-001 Furnace Cement - 8 Ib. can 8 3.64 2-12-002 Furnace Cement - 15 Ib. can 15 6.82
5-10-353 Flue Cover Ring - 4 & 6 & 9.5 HP 19 8.64 5-10-354 Flue Cover Ring -10 HP 20 9.09 5-10-355 Flue Cover Ring - 15 HP 20.5 9.32 5-10-357 Flue Cover Ring - 20 HP 21 9.55 5-10-359 Flue Cover Ring - 30 HP 25 11.36 5-10-360 Flue Cover Ring - 40-60 HP 40 18.18
5-12-001 Bottom Cleanout Access Plate with Plug 4-30 HP 10 4.55 5-12-002 Bottom Cleanout Access Plate with Plug 40-60 HP 20 9.09 5-12-003 Square Cleanout Plug (Not for Series E) 15 6.82
2-12-064 Flexitalic (HHG) Extra Heavy High Pressure 0.5 0.23 2-12-088 Blue Max HHG 0.05 0.02
5-10-800 Handhole Welding Patch 4-60 HP 1.1 0.5 2-12-004 Handhole Gasket 4-60 HP 0.05 0.02 2-11-105 HandholeYoke 1.5 0.68
2-11-100 3 x 4 Handhole Cover 4-10 HP (White) 2 0.91 2-11-101 3 x 4 Handhole Cover 15 HP (Red) . 2 0.91 2-11-102 3 x 4 Handhole Cover 20 HP (Green) 2 0.91 2-11-103 3 x 4 Handhole Cover 30 HP (Yellow) 2 0.91 2-11-104 3 x 4 Handhole Cover 40-100 HP (Blue) 2 0.91
4-11-010 10 HP Handhole Assembly (White) 7 3.18 4-11-012 15 HP Handhole Assembly (Red) 7 3.18 4-11-014 20 HP Handhole Assembly (Green) 7 3.18 4-11-016 30 HP Handhole Assembly (Yellow) 7 3.18 4-11-018 40 -60 HP Handhole Assembly (Blue) 7 3.18
2-12-504 Blanket Insulation (Sq. ft.) 0.5 0.23
5-21-300 Steel Jacket 4 HP - No Holes Cut 80 36.36 5-21-301 Steel Jacket 6 HP - No Holes Cut 80 36.36
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
67-G 1/01
Replacement Parts Listing (available from authorized Fulton Representative)
Parts
5-21-302 Steel Jacket 10 HP - No Holes Cut 100 45.45 5-21-303 Steel Jacket 15 HP - No Holes Cut 115 52.27 5-21-304 Steel Jacket 20 HP - No Holes Cut 125 56.82 5-21-305 Steel Jacket 30 HP - No Holes Cut 125 56.82 5-21-306 Steel Jacket 40-60 HP - No Holes Cut 125 56.82
5-21-5064 Bottom Handhole Funnel 4 & 6 HP 6.5 2.95 5-21-5066 Bottom Handhole Funnel 10 HP 6.5 2.95 5-21-5068 Bottom Handhole Funnel 15 HP 6.5 2.95 5-21-5070 Bottom Handhole Funnel 20 HP 6.5 2.95 5-21-5072 Bottom Handhole Funnel 30 HP 6.5 2.95 5-21-5074 Bottom Handhole Funnel 40 & 60 HP 6.5 2.95
5-21-5063 Top Handhole Funnel 4 & 6 HP 6.5 2.95 5-21-5065 Top Handhole Funnel 10 HP 6.5 2.95 5-21-5067 Top Handhole Funnel 15 HP 6.5 2.95 5-21-5069 Top Handhole Funnel 20 HP 6.5 2.95 5-21-5071 Top Handhole Funnel 30 HP 6.5 2.95 5-21-5073 Top Handhole Funnel 40 - 60 HP 6.5 2.95
123 Bottom Funnel Repair Kits 4-15 HP 9.5 4.32 123 Bottom Funnel Repair Kits 20-30 HP 9.5 4.32 123 Bottom Funnel Repair Kits 40-60 HP 9.5 4.32
123 Top Funnel Repair Kits 4-15 HP 9.5 4.32 123 Top Funnel Repair Kits 20-30 HP 9.5 4.32 123 Top Funnel Repair Kits 40-60 HP 9.5 4.32
2-21-053 6" Stack Connection 4-10 HP 6.5 2.95 2-21-054 8" Stack Connection 15 HP 7 3.18 2-21-055 10" Stack Connection 20 HP 7.5 3.41 2-21-056 12" Stack Connection 30-60 HP 8 3.64
2-21-058 6" Stack to Pipe Adaptor 4-10 HP 6.5 2.95 2-21-059 8" Stack to Pipe Adaptor 15 HP 7 3.18 2-21-060 10" Stack to Pipe Adaptor 20 HP 8 3.64 2-21-061 12" Stack to Pipe Adaptor 30-60 HP 9 4.09 2-12-501 Castable Block Mix - per Ib. (10 Ibs. min.)-Use for top of bottom handhole up 2-12-498 Castable Block Mix - 25 Ib. bag -Use for top of bottom handhole up 2-12-502 Kast Set - per Ib. (10 Ibs. minimum) - Use for making refractories 2-12-500 Insulcrete - per Ib. (10 Ibs. min.) - Use for top of bottom handhole down
2-12-497 Insulcrete - 50 Ib. bag - Use for top of bottom handhole down
5-12-020 Kaowool Sleeve for Bottom Funnel 0.9 0.41 4-12-018 Kaowool Insulation per sq. ft. 2-12-507 Kaowool (panels) 7"
2-21-015 Buckeye Stamping for Bottom Handhole 4-100 HP 1 0.45 2-21-092 Buckeye Stamping for Upper Handhole 4-15 HP 1 0.45 2-21-093 Buckeye Stamping for Upper Handhole 20-100 HP 1 0.45
2-23-171 Touch Up Paint - MICA Spray 1 0.45 4-23-014 Mica Paint - Quart 2 0.91 4-23-044 Mica Paint - Gallon 7.8 3.55 2-12-504 TIW Filler Insulation per sq ft
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
68-G 1/01
Parts
Burner Assembly - Parts (Common)
2-40-605 1/3 HP 115/230/60/1 Burner Motor 3450 RPM 21 9.55 2-40-606 1/3 HP 230/460/60/3 Burner Motor 3450 RPM 20 9.09 2-40-603 1/3 HP 110/220/50/1 Burner Motor 2850 RPM 25 11.36 2-40-770 1/3 HP 380/50/3 Burner Motor 2850 RPM 28 12.73
2-40-608 3/4 HP 115/230/60/1 Burner Motor 3450 RPM 25 11.36 2-40-611 3/4 HP 230/460/60/3 Burner Motor 3450 RPM 22 10 2-40-609 3/4 HP 110/220/50/1 Burner Motor 2850 RPM 28 12.73 2-40-610 3/4 HP 380/50/3 Burner Motor 2850 RPM 22 10
2-40-613 1.5 HP 115/230/60/1 Burner Motor 3450 RPM 40 18.18 2-40-614 1.5 HP 110/220/50/1 Burner Motor 2850 RPM 45 20.45 2-40-615 1.5 HP 230/460/60/3 Burner Motor 2850/3450 RPM 31 14.09 2-40-771 1.5 HP 380/50/3 Burner Motor 2850 RPM 48 21.82
2-40-773 2.0 HP 380/50/3 Burner Motor 2850 RPM 48 21.82 2-40-616 2.0 HP 115/230/60/1 Burner Motor 3450 RPM 43 19.55 2-40-618 2.0 HP 230/460/60/3 Burner Motor 3450 RPM 33 15 2-40-617 2.0 HP 110/220/50/1 Burner Motor 2850 RPM 48 21.82
2-12-014 Pyrex Plate Glass 1 " - 4 -100 HP 0.1 0.05 2-45-025 Bakelite Terminal 90° for Electrode 0.05 0.02 2-45-026 Bakelite Terminal Straight for Electrode 0.05 0.02 2-45-017 Ignition Wire - per foot 0.01 0
2-11-116 Burner Scroll Casting - 9.5 HP 14 6.36 2-11-123 Burner Scroll Casting- 4-15 HP 30 13.64 5-20-059 Burner Scroll Casting - 20 HP 35 15.91 5-20-060 Burner Scroll Casting - 30 HP 40 18.18 5-20-061 Burner Scroll Casting - 40, 50 & 60 HP 50 22.73
Burner Fans:
Size HP Applicable Fuel Hz.
2-30-407 5-1/2 x 1-1/2 x 5/8 4 HP Propane or Nat. Gas 50/60 HZ 1.40 0.64
6 HP Propane 50/60 HZ 1.40 0.64 2-30-410 6-1/4 x 1-1/2 x 5/8 6 HP Combination or Natural Gas 50/60 HZ 1.60 0.73 2-30-412 7 x 1-1/2 x 5/8 9.5-10 HP Propane or Nat. Gas 50/60 HZ 2.00 0.91 2-30-414 7-11/16 X 1-1/2 x 5/8 15-20 HP Propane or Nat. Gas 50/60 HZ 2.30 1.05 2-30-418 8-3/8 x 2 x 5/8 30 HP Propane or Nat. Gas 50/60 HZ 3.15 1.43 2-30-421 8-3/8 x 2-1/2 x 1 40-50 HP Propane or nat. Gas 50/60 HZ. 3.00 1.36
60 HP Propane or nat. Gas 50/60 HZ. 3.00 1.36 *When ordering burner fans, check for the correct part number on the back of the fan plate.
Burner Assembly - Gas
2-40-082 Ignition Transformer - Gas 115/60 9.5 4.32 2-40-083 Ignition Transformer - Gas 240/60 9.5 4.32 2-40-084 Ignition Transformer - Gas 120/50 10.3 4.68 2-40-085 Ignition Transformer - Gas 220/50 10.2 4.64 2-45-026 Straight Bakelite Terminal 0.03 0.01
4-45-010 Ignition Cable with 90° Bakelite Terminal 0.5 0.23 4-45-012 Flame Rod Cable with 90° Bakelite Terminal 0.5 0.23 2-20-019 Ignition Electrode 0.4 0.18 2-20-020 Flame Rod 0.4 0.18
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
69-G 1/01
Parts
2-30-118 Air Switch 4-100 HP 0.72 0.33
5-20-019 Burner Plate Gas - 4 HP 1 0.45 5-20-007 Burner Plate Gas - 6 & 10 HP 1 0.45 5-20-055 Burner Plate Gas - 9.5 HP 2 0.91 5-20-013 Burner Plate Gas - 15 & 20 HP 1 0.45 5-20-018 Burner Plate Gas - 30-60 HP 1 0.45
2-11-112 Air Deflector - Gas - 6 & 10 HP 11 5.00 2-11-075 Air Deflector - Gas - 9.5 HP 11 5.00 2-11-113 Air Deflector - Gas -15 HP 11 5.00 7-20-088 Air Deflector - Gas - 20 HP 24 10.91 7-20-090 Air Deflector - Gas - 30 HP 24 10.91 7-20-092 Air Deflector - Gas 40 - 60 HP 45 20.45
2-40-533 Gas Pressure Switch High-Low 3.25 1.48 2-40-211 Gas Pressure Switch - Low 4.9 2.23 2-40-212 Gas Pressure Switch - High 4.8 2.18
2-30-298 1/2" Pilot Gas Valve (4-100 HP) 1.5 0.68 2-30-301 1 " Main Gas Valve - V48A 3.2 1.45 2-30-302 1-1/4 " Main Gas Valve - V48A 4 1.82 2-30-303 1-1/2" Main Gas Valve - V48A 4.5 2.05
2-30-312 1-1/2" Gas Valve V5055A 4 1.82 2-30-313 2" Gas Valve V5055A 9.2 4.18
2-40-249 Gas Valve Body - P.O.C V5055C 1" 5 2.27 2-40-252 Gas Valve Body - P.O.C V5055C 1-1/4" 5.1 2.32 2-40-253 Gas Valve Body - P.O.C V5055C 1-1/2" 4.7 2.14 2-40-254 Gas Valve Body - P.O.C V5055C 2" 9.3 4.23
2-40-214 Actuator for 2", 2-1/2" and 3" Valve Body 13.70 6.23 2-40-220 Actuator for 2", 2-1/2" and 3" Valve Body w/Proof of Closure Switch 12.8 5.82
2-30-400 3/4" Vent Valve - 120V Normally Open 3.2 1.45 2-30-401 1" Vent Valve - 120V Normally Open 4.3 1.95 2-30-402 1-1/4" Vent Valve - 120V Normally Open 4.7 2.14
2-30-305 3/4" Solenoid GasValve 1.8 0.82 2-30-306 1" Solenoid Gas Valve 3.9 1.77 2-30-307 1-1/4'' Solenoid Gas Valve 3.9 1.77 2-30-308 1-1/2" Solenoid Gas Valve 4.4 2.00
2-30-198 1/8" Gas Cock (Pet Cock) 0.25 0.11 2-30-111 1/2" Pilot Gas Cock 0.6 0.27 2-30-112 3/4" Main Gas Cock 1.5 0.68 2-30-113 1" Main Gas Cock 2 0.91 2-30-114 1-1/4 " Main Gas Cock 3 1.36 2-30-115 1-1/2 " Main Gas Cock 4.8 2.18 2-30-116 2" Main Gas Cock 4.8 2.18 2-30-021 1" Lubricated Gas Cock 5 2.27 2-30-022 1-1/4" Lubricated Gas Cock 6.5 2.95 2-30-013 1-1/2" Lubricated Gas Cock 7 3.18 2-30-012 2" Lubricated Gas Cock 10 4.55
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
70-G 1/01
Parts
2-30-102 1/2" Gas Pressure Regulator RV 48 0.7 0.32 2-30-104 1" Gas Pressure Regulator - RV 53 1.5 0.68 2-30-105 1-1/4 " Gas Pressure Regulator - RV 61 5 2.27 2-30-106 1-1/4" Gas Pressure Regulator - RV 81 5 2.27 2-30-107 1-1/2"Gas Pressure Regulator - RV 81 4.8 2.18 2-30-108 2" Gas Pressure Regulator - RV 91 8.3 3.77
2-20-002 CSA Air Gas Mixing Valve 1 0.45 7-20-060 Natural Gas Orifice - 4 HP Pre 2/89 3/4" 2 0.91 7-20-050 Natural Gas Orifice - 4 HP - Post 2/89 1" 2 0.91 7-20-051 Natural Gas Orifice - 6 HP 2 0.91 7-20-078 Natural Gas Orifice - 9.5 HP 2 0.91 7-20-052 Natural Gas Orifice -10 HP 2 0.91 7-20-023 Natural Gas Orifice - 15 HP - Post 2/89 1" 2 0.91 7-20-053 Natural Gas Orifice -15 HP - Pre 2/89 1-1/4" 2.5 1.14 7-20-054 Natural Gas Orifice - 20 HP 3 1.36
7-20-055 Natural Gas Orifice - 30 HP 3 1.36 7-20-265 Natural Gas Orifice - 40 HP 3.5 1.59 7-20-056 Natural Gas Orifice - 50 HP 3.5 1.59 7-20-057 Natural Gas Orifice - 60 HP 3.5 1.59
7-20-060 Propane Orifice - 4 HP - Pre 2/89 3/4" 2 0.91 7-20-030 Propane Orifice - 4 HP - Post 2/89 1" 2 0.91 7-20-061 Propane Orifice - 6 HP 2 0.91
7-20-062 Propane Orifice - 10 HP 2 0.91 7-20-033 Propane Orifice - 15 HP - Post 2/89 1" 2 0.91 7-20-063 Propane Orifice -15 HP - Pre 2/89 1-1/4" 2.5 1.14 7-20-064 Propane Orifice - 20 HP 3 1.36 7-20-065 Propane Orifice - 30 HP 3 1.36 7-20-275 Propane Orifice - 40 HP 3.5 1.59 7-20-066 Propane Orifice - 50 HP 3.5 1.59 7-20-067 Propane Orifice - 60 HP 3.5 1.59
2-30-177 Propane Spring RV48 0.05 0.02 2-30-178 Propane Spring RV53 0.05 0.02 2-30-179 Propane Spring RV61 0.05 0.02 2-30-180 Propane Spring RV81 0.05 0.02 2-30-181 Propane Spring RV91 0.05 0.02
7-30-001 Top Plate Assembly - 4 HP - Natural Gas 10 4.55 7-30-002 Top Plate Assembly - 6 & 10 HP - Natural Gas 15 6.82 5-30-001 Top Plate Assembly 9.5 HP - Natural Gas 15 6.82 7-30-003 Top Plate Assembly - 15 HP - Natural Gas 15 6.82 7-30-004 Top Plate Assembly - 20 HP - Natural Gas 35 15.91 7-30-005 Top Plate Assembly - 30 HP - Natural Gas 35 15.91 7-30-006 Top Plate Assembly - 40, 50 & 60 HP - Natural or Propane Gas 65 29.55
7-30-020 Top Plate Assembly - 4 HP - Propane Gas 10 4.55 7-30-021 Top Plate Assembly - 6 & 10 HP - Propane Gas 15 6.82 7-30-022 Top Plate Assembly - 15 HP - Propane Gas 15 6.82 7-30-023 Top Plate Assembly - 20 HP - Propane Gas 35 15.91 7-30-024 Top Plate Assembly - 30 HP - Propane Gas 35 15.91
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
71-G 1/01
Parts
7-30-025 Burner Plate Assembly - 4 HP - Natural Gas 7 3.18 7-30-026 Burner Plate Assembly - 6 HP - Natural Gas 8 3.64 7-30-123 Burner Plate Assembly - 9.5 HP Natural Gas 8 3.64
7-30-027 Burner Plate Assembly - 10 HP - Natural Gas 8 3.64 7-30-028 Burner Plate Assembly - 15 HP - Natural Gas 8 3.64 7-30-029 Burner Plate Assembly - 20 HP - Natural Gas 10 4.55 7-30-030 Burner Plate Assembly - 30 HP - Natural Gas 10 4.55 7-30-031 Burner Plate Assembly - 40, 50 HP - Natural Gas 12 5.45 7-30-032 Burner Plate Assembly - 60 Hp - Natural Gas 12 5.45
7-30-053 Burner Plate Assembly - 4 HP - Propane Gas 7 3.18 7-30-054 Burner Plate Assembly - 6 HP - Propane Gas 8 3.64 7-30-055 Burner Plate Assembly - 10 HP - Propane Gas 8 3.64 7-30-056 Burner Plate Assembly - 15 HP - Propane Gas 8 3.64 7-30-057 Burner Plate Assembly - 20 HP - Propane Gas 10 4.55 7-30-058 Burner Plate Assembly - 30 HP - Propane Gas 10 4.55 7-30-059 Burner Plate Assembly - 40, 50 HP - Propane Gas 12 5.45 7-30-060 Burner Plate Assembly - 60 HP - Propane Gas 12 5.45
7-54-1000 Gas Train Assembly- 4 HP - Natural Gas 20 9.09 7-54-1001 Gas Train Assembly - 6 HP- Natural Gas 23 10.45 7-54-1002 Gas Train Assembly -10 HP - Natural Gas 23 10.45 7-54-1003 Gas Train Assembly - 15 HP - Natural Gas - 1" 23 10.45 7-54-1004 Gas Train Assembly - 20 HP - Natural Gas - 1-1/4" 27 12.27 7-54-1005 Gas Train Assembly - 30 HP - Natural Gas 27 12.27 7-54-1006 Gas Train Assembly - 40 - 50 HP - Natural Gas 70 31.82 7-54-1007 Gas Train Assembly- 60 HP- Natural Gas 70 31.82
7-54-1050 Gas Train Assembly - 4 HP - Propane Gas 20 9.09 7-54-1051 Gas Train Assembly - 6 HP - Propane Gas 25 11.36 7-54-1052 Gas Train Assembly -10 HP - Propane Gas 25 11.36 7-54-1053 Gas Train Assembly -15 HP - Propane Gas 25 11.36 7-54-1054 Gas Train Assembly - 20 HP - Propane Gas 30 13.64 7-54-1055 Gas Train Assembly - 30 HP - Propane Gas 30 13.64 7-54-1056 Gas Train Assembly - 40 - 50 HP - Propane Gas 70 31.82 7-54-1057 Gas Train Assembly - 60 HP - Propane Gas 70 31.82
Water Column
5-20-022 Fulton Water Column Bottle Casting -4-100 HP 20 9.09 2-30-151 MM 150 Pump Control 25 11.36 2-30-193 MM 150 - M/R Control 25 11.36 2-30-152 MM 150 HD Assembly 25 11.36 2-30-192 MM 150-M-HD M/R Head 25 11.36 2-12-125 MM 150-14 Gasket 0.05 0.02 2-30-136 MM 157 Pump Control and Low Water Cutoff 39.7 18.05 2-30-137 MM 53-2 Boiler Feeder and Low Water Cutoff 38.5 17.5 2-45-144 MM Mercury Switch - 2 Wire 1 0.45 2-45-143 MM Mercury Switch - 3 Wire 1 0.45
2-30-149 Water Gauge Glass Valves w/Ball Checks 1.5 0.68 2-30-047 Try Cocks 0.4 0.18 2-12-065 8-5/8" Extra Heavy Gauge Glass 0.05 0.02 2-12-008 9-1/4 Water Gauge Glass - standard 0.05 0.02 2-12-007 9-1/4" Extra Heavy Gauge Glass 0.1 0.05 2-12-017 9-1/4" Water Gauge Glass -Corning 0.05 0.02
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
72-G 1/01
Parts
2-12-018 10" Water Gauge Glass- MM 0.06 0.03 2-12-071 12" Water Gauge Glass 0.07 0.03 2-12-063 14"Water Gauge Glass 0.08 0.04 2-30-155 Conbraco 250# GG Valve w/Ball Check (9.5 HP) 1.5 0.68
2-12-020 Brass Water Gauge Glass Gasket 0.0018 0 2-12-019 Rubber Water Gauge Glass Gasket 0.004 0 2-12-080 Teflon Water Gauge Gaskets 0.01 0
2-35-514 Brass Packing Nut for Gauge Glass Valve 0.1 0.05 2-30-330 Gauge Glass Protector Rods 0.04 0.02 2-12-022 Lucite Gauge Glass Guard for 9-1/4" Glass 0.4 0.18 2-12-024 Lucite Gauge Glass Guard for 10" Glass 0.5 0.23
2-12-021 Lucite Gauge Glass Guard for 12" Glass (53MM) 0.06 0.03 2-12-204 Lucite Gauge Glass Guard - 9.5 HP 0.045 0.02
4-21-010 Water Column Electrode Basket & Cover 0.5 0.23
4-30-050 Set of four (4) Water Level Probes & Plugs - 4 HP 1.3 0.59 4-30-052 Set of four (4) Water Level Probes & Plugs - 6-60 HP 1.3 0.59 4-30-042 Set of 3 Water Column Probes 0.8 0.36 2-20-010 Pump Off Probe - 7-1/4 " 0.2 0.09 2-20-011 Pump On Probe - 9-1/4" 0.2 0.09 2-20-012 Low Water Probe in Water Column -11-1/4” 0.3 0.14 2-20-017 Low Water Probe in Boiler- 17-1/8” 0.5 0.23 2-21-012 Probe Cover - 2" 1 0.45 2-21-013 Probe Cover - 4" 1 0.45 2-30-398 1/4"Male-Female Ball Valve for Water Column 0.6 0.27 2-40-021 Probe Basket 0.05 0.02
Panel Box Parts
2-40-420 Fulton Pump Relay-120V 0.5 0.23 2-40-421 Fulton Burner Relay - 120V 0.5 0.23 2-40-422 Base for Fulton Pump Relay 0.25 0.11 2-40-423 Base for Fulton Burner Relay 0.25 0.11
2-40-405 Fulton Pump Relay - 220v 0.5 0.23 2-40-406 Fulton Burner Relay - 220v 0.5 0.23 2-12-090 Spring Retainer for burner/pump relay 0.001 0
2-40-403 IDlDO-120VRelay 2 0.91 2-40-402 IGIDO - 120V Relay 2 0.91 2-40-400 IGlDO-A-120VRelay 2 0.91 2-40-401 ID2DO - 220V Relay 2 0.91 4-45-050 Set of three (3) Coils for ID or IG Type Relay 1 0.45 4-45-051 Set of three (3) Coils ID2D0 - 220V 1 0.45 2-40-131 General Purpose Relay (Ice Cube) - AB 0.8 0.36 2-40-096 Base for Ice Cube Relay 0.1 0.05
2-45-091 On/Off Switch 0.05 0.02 2-45-092 Manual Reset Switch 0.05 0.02 2-45-090 Night Switch for two (2) Pressuretrols 0.05 0.02 2-40-552 4" Alarm Bell 1 0.45 2-40-551 120V Transformer for Bell 1 0.45 2-40-550 220V Transformer for Bell 1 0.45
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
73-G 1/01
Parts
2-45-106 Green Panel Box Indicating Light - 120V 0.1 0.05 2-45-107 White Panel Box Indicating Light -120V 0.1 0.05 2-45-108 Amber Panel Box Indicating Light - 120V 0.1 0.05 2-45-110 Red Panel Box Indicating Light -120V 0.1 0.05 2-45-112 Green Panel Box Indicating Light - 220V 0.1 0.05 2-45-115 White Panel Box Indicating Light - 220V 0.1 0.05
2-45-116 Amber Panel Box Indicating Light - 220V 0.1 0.05 2-45-114 Red Panel Box Indicating Light - 220V 1 0.45
2-45-412 AB Green Panel Light 120 V - NEMA 4 0.02 0.01 2-45-413 AB Amber Panel Light 120 V - NEMA 4 0.02 0.01 2-45-411 AB Red Panel Light 120 V - NEMA 4 0.02 0.01 2-45-410 AB White Panel Light 120 V - NEMA 4 0.02 0.01
2-40-567 Motor Contactor - AB - 100 - A09ND3- 120V - 4-60 HP 0.8 0.36 2-40-568 Motor Contactor - AB - 100 - A09NA3- 220V - 4-60 HP 0.8 0.36
2-40-565 Overload - AB - BSB 16 0.45 0.2 2-40-657 Overload - AB - BSB 15 0.45 0.2 2-40-648 Overload - AB - BSB 22 0.45 0.2 2-40-571 Overload - AB - BSB 30 0.45 0.2 2-40-575 Overload - AB - BSC 10 0.45 0.2 2-40-643 Overload - AB - BSC 15 0.45 0.2 2-40-652 Overload - AB - BSC 24 0.45 0.2 2-40-572 Overload - AB - BSB 42 0.45 0.2 2-40-573 Overload - AB - BSB 60 0.45 0.2 2-40-574 Overload - AB - BSB 80 0.45 0.2 2-40-566 Overload - AB - BSB 90 0.45 0.2
2-40-200 Motor Starter Relay -120V - 20 AMP 0.6 0.27 2-40-202 Motor Starter Relay - 120V - 30 AMP 0.5 0.23
2-40-201 Motor Starter Relay - 220V - 20 AMP 0.4 0.18 2-40-203 Motor Starter Relay - 220V - 30 AMP 0.5 0.23
4-40-050 Night Heating Pressuretrol Set Up 3.5 1.59 2-40-227 Pressuretrol L404A - 2-15 PSI 1.7 0.77 2-40-228 Pressuretrol L404A - 5-50 PSI 2 0.91 2-40-229 Pressuretrol L404A - 10-150 PSI 2 0.91 2-40-230 Pressuretrol L404A - 20-300PSI 2.7 1.23 2-40-231 Pressuretrol L404C - 2-15 PSI 2 0.91 2-40-232 Pressuretrol L404C - 5-50 PSI 2 0.91 2-40-233 Pressuretrol L404C - 10-150 PSI 2 0.91 2-40-234 Pressuretrol L404C - 20-300 PSI 2.7 1.23
2-40-161 Flame Scanner (Mini-Peeper) 0.5 0.23
2-40-260 RM7895A Programmer 20-50 HP - 120 V 2 .91 2-40-262 RM7800M Programmer 60-100 HP - 120 V 2.5 1.14
2-40-265 7 Second Prepurge Timer 0.1 0.05 2-40-266 30 Second Prepurge Timer 0.1 0.05 2-40-267 60 Second Prepurge Timer 0.1 0.05 2-40-268 RM7800 Amplifier - For Flame Rod 0.3 0.14 2-40-269 RM7800 Amplifier - For UV Amp 0.2 0.09
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
74-G 1/01
Parts
2-40-161 Mini Peeper For All 7800 0.5 0.23 2-40-270 Base For All 7800 0.5 0.23 2-40-272 Display Module for 7800 Controls English (Also Available in Spanish) 0.5 0.23 2-40-247 Remote Mounting Bracket for 7800 0.65 0.3
2-40-248 Extension Cable
2-40-261 EC7830A Programmer 220/50 2 0.91 2-40-276 Timer 7 for EC7830/50 0.1 0.05 2-40-273 Timer 30 for EC7830/50 0.1 0.05 2-40-274 UV - Amplifier for EC7830/50 0.2 0.09
Boiler Trim
5-35-100 9.5 HP Steam Orifice 2 0.91 2-30-396 1" Spring Loaded Check Valve - 200# 2.55 1.16 2-30-397 1-1/4" Spring Loaded Check Valve - 200# 3.8 1.73
2-30-019 1/4" Ball Valve - 200# 0.6 0.27 2-30-008 1/2" BallValve-200# 0.7 0.32 2-30-027 3/4" BallValve-200# 1.4 0.64 2-30-026 1" Ball Valve - 200# 1.75 0.8 2-30-001 1" MxF Ball Valve 200# 2 0.91 2-30-017 1-1/4" Ball Valve - 200# 3.1 1.41 2-30-018 1-1/2" Ball Valve - 200# 4.7 2.14 2-30-025 2" Ball Valve - 200# 6.35 2.89 2-30-208 3" Ball Valve - 200# 18 8.18
2-30-391 1"Y Type Blowdown Valve - 200# 4 1.82 2-30-392 1-1/4" Y Type Blowdown Valve - 200# 5.5 2.5 2-30-393 1-1/2" Y Type Blowdown Valve - 200# 8.4 3.82
2-30-007 1" Quick Action Blowdown Valve 13 5.91 2-30-014 1-1/4" Quick Action Blowdown Valve 14 6.36 2-30-023 1-1/2" Quick Action Blowdown Valve 23 10.45
2-40-133 Timer for Automatic Blowdown System 0.8 0.36 2-30-386 1" Motorized Valve for Automatic Blowoff 9.8 4.45 2-30-387 1-1/4" Motorized Valve for Automatic Blowoff 10.7 4.86 2-30-403 1-1/2" Motorized Valve for Automatic Blowoff 12.6 5.73
2-30-1066 1/2" Steam Solenoid Valve - 120V 2.3 1.05 2-30-122 3/4" Steam Solenoid Valve - 120V 2.5 1.14 2-30-146 1" Steam Solenoid Valve - 120V 4.5 2.05 2-30-147 1-1/4 " Steam Solenoid Valve - 120V 4.9 2.23 2-30-148 1-1/2" Steam Solenoid Valve - 120V 6.3 2.86
2-30-214 3/4" 15# Series 19 V-Stamped Safety Valve 1 0.45 2-30-215 1" 15# Series 19 V-Stamped Safety Valve 1.1 0.5 2-30-216 1-1/4" 15# Series 19 V-Stamped Safety Valve 1.85 0.84 2-30-016 1-1/2" 15# Series 19 V-Stamped Safety Valve 2 0.91 2-30-217 2" 15# Series 19 V-Stamped Safety Valve 2.5 1.14
2-30-062 1/2"-100# Safety Valve 1.2 0.55 2-30-063 1/2"-125# Safety Valve 1.3 0.59 2-30-064 3/4"-15# Safety Valve 1 0.45 2-30-065 3/4"-30# Safety Valve 1.8 0.82 2-30-067 3/4"-75# Safety Valve 3.2 1.45
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
75-G 1/01
Parts
2-30-068 3/4"-100# Safety Valve 2 0.91 2-30-069 3/4"-125# Safety Valve 2 0.91 2-30-070 3/4"-150# Safety Valve 1.4 0.64 2-30-071 3/4"-200# Safety Valve 5.1 2.32 2-30-073 3/4"-300# Safety Valve 2.35 1.07
2-30-074 1"-15# Safety Valve 1.1 0.5 2-30-075 1"-75# Safety Valve 4 1.82 2-30-076 1"-100# Safety Valve 4.1 1.86 2-30-077 1"-125# Safety Valve 4.1 1.86 2-30-078 1"-150# Safety Valve 4.1 1.86 2-30-079 1"-200# Safety Valve 4 1.82 2-30-081 1"-300# Safety Valve 5 2.27
2-30-082 1-1/4 "-15# Safety Valve 1.85 0.84 2-30-083 1-1/4"-100# Safety Valve 6.6 3
2-30-084 1-1/4"-125# Safety Valve 6.75 3.07 2-30-085 1-1/4"-150# Safety Valve 6.8 3.09
2-30-086 1-1/2"-15# Safety Valve 2 0.91 2-30-087 1-1/2"-100# Safety Valve 12.4 5.64 2-30-088 1-1/2"-125# Safety Valve 10.9 4.95 2-30-089 1-1/2"-150# Safety Valve 12.3 5.59 2-35-518 1/4" Steel Pigtail Syphon for Steam Gauge Assembly- Long 0.6 0.27
2-30-202 Pressure & Temp Gauge 1 0.45 2-30-326 0-30 PSI Steam Pressure Gauge 0.5 0.23 2-30-334 0-60 PSI Steam Pressure Gauge 0.5 0.23 2-30-333 0-200 PSI Steam Pressure Gauge 0.5 0.23 2-30-332 0-300 PSI Steam Pressure Gauge 0.5 0.23 2-30-327 0-600 PSl Steam Pressure Gauge 0.5 0.23
2-12-025 Teflon Disc for 1" Y Valve 0.2 0.09 2-11-015 Brass Seat for 1" Y Valve 0.1 0.05 2-12-026 Teflon Disc for 1-1/4 " Y Valve 0.5 0.23 2-11-016 Brass Seat for 1-1/4 " Y Valve 0.1 0.05 2-12-027 Teflon Disc for 1-1/2" Y Valve 0.2 0.09 2-11-017 Brass Seat for 1-1/2" Y Valve 0.1 0.05 2-12-028 Teflon Disc for 2" Y Valve 0.2 0.09 2-11-018 Brass Seat for 2" Y Valve 0.1 0.05
Test Equipment/Tools
2-40-090 Test Leads 0.6 0.27 2-40-215 Microampmeter - W136 2 0.91 2-60-100 Jr. Amprobe - Y25 1 0.45 2-60-102 Pocket Draft Meter 1 0.45 2-60-103 All Purpose Draft Meter 3 1.36 2-60-104 CO Tester-Gas 15 6.82 2-60-105 CO Tubes 0.25 0.11 2-60-106 StackThermometer 4 1.82 2-60-108 SmokeTester-Oil 2 0.91 2-60-110 Fisher Gauge - 50 PZ 1 0.45
2-60-112 Flue Cleanout Brush 0.8 0.36 2-60-247 Flue Brush - Pipe Type - 2-1/2" - 100 HP 1 0.45 2-60-248 Flue Brush - Pipe Type - 2" - 80 HP 1 0.45
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
76-G 1/01
Parts
5-10-397 Tee Handle Wrench 2.7 1.23 2-20-110 Fan Puller - 5/8" Hub 2 0.91 2-20-115 Fan Puller - 1" Hub 2 0.91
Barometric Controls
2-30-092 6" MGI 4, 6 & 10 HP - Gas 3 1.36 2-30-095 8" MG1 15 HP - Gas 4 1.82 2-30-097 10" M&MG2 20 HP - Oil, Gas, Comb 8 3.64 2-30-098 12" M&MG2 30 HP - Oil, Gas, Comb. 12 5.45 2-30-099 14" M&MG2 50 - 100 HP - Oil, Gas, Comb. 16 7.27 2-30-0415 16" M&MG2 25 11.36
Spare Parts Kits
4-50-000001 Spare Parts Kit No. 1 4-30 BHP Gas Consists of: 4 1.82
Qty Part No. Description 6 2-12-000004 Handhole Gaskets 1 2-12-000017 9-1/4" Gauge Glass 2 2-12-000019 Water Gauge Glass Rubber 2 2-12-000020 Water Gauge Glass Fiber 1 2-20-000019 Ignition Electrode 1 2-20-000020 Flame Rod 1 5-10-000397 Tee Handle Wrench 1 4-30-000052 Set of (4) Plugs and Probes
4-50-000002 Spare Parts Kit No. 2 50-100 BHP Gas 4 1.82
6 2-12-000004 Handhole Gaskets 1 2-12-000017 9-1/4" Gauge Glass 2 2-12-000019 Water Gauge Glass Rubber 2 2-12-000020 Water Gauge Glass Fiber 1 2-20-000019 Ignition Electrode 1 5-10-000397 Tee Handle Wrench 1 4-30-000052 Set of (4) Plugs and Probes
2-12-515 Burner Plate Gasket 4 HP Gas 0.05 0.02 2-12-516 Burner Plate Gasket 6-20 HP Gas 0.05 0.02 2-12-517 Burner Plate Gasket 30-100 HP Gas 0.06 0.03 2-12-023 Screws (11) 0.001 0.00 2-12-513 Bottom Cleanout Gasket Only 0.5 0.23 2-12-514 Combination Gasket 0.05 0.02
4-12-100 Flue Cover Plate Gasket - 4 HP 1.5 0.68 4-12-102 Flue Cover Plate Gasket - 6 HP 1.5 0.68 4-12-104 Flue Cover Plate Gasket -10 HP 1.5 0.68 4-12-106 Flue Cover Plate Gasket -15 HP 1.8 0.82 4-12-108 Flue Cover Plate Gasket - 20 HP 2 0.9 4-12-110 Flue Cover Plate Gasket - 30 HP 2 0.91 4-12-112 Flue Cover Plate Gasket - 40-60 HP 2.5 1.14
2-12-210 1/4" Braided Rope Gasket 4-100 HP - price per foot 0.25 0.11
0.00
2-12-077 Handhole Funnel Gasket 20-100 HP Top 0.05 0.02
2-12-078 Handhole Funnel Gasket 4-15 HP Top 0.05 0.02 2-12-079 Handhole Funnel Gasket 4-100 HP Bottom 0.05 0.02
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
77-G 1/01
Parts
2-12-528 Scroll Gasket - 4 HP 1 0.45 2-12-529 Scroll Gasket - 6-15 HP 1 0.45 2-12-530 Scroll Gasket- 20-30 HP 1 0.45 2-12-531 Scroll Gasket- 40-60 HP 1 0.45
2-12-537 Stack Extension Gasket 6" 4-10 HP 1 0.45 2-12-538 Stack Extension Gasket 8" 15 HP 1 0.45 2-12-539 Stack Extension Gasket 10" 20 HP 1 0.45 2-12-540 Stack Extension Gasket 12" 30-60 HP 1 0.45
2-12-518 Top Plate Gasket - 4 HP (Old Style) 1 0.45 2-12-519 Top Plate Gasket - 4-15 HP 1 0.45 2-12-520 Top Plate Gasket - 20-30 HP 1 0.45 2-12-521 Top Plate Gasket - 40-60 HP 1 0.45
4-12-522 9.5 HP Gas, Oil, & Comb Gasket Kit 5 2.27 4-12-500 4-15 HP Gas, Oil, & Comb Gasket Kit 5 2.27 4-12-506 20-30 HP Gas, Oil, & Comb Gasket Kit 6 2.73 4-12-512 40-60 HP Gas, Oil, & Comb Gasket Kit 10 4.55
See the following component assembly drawings to assist with parts identification.
Approx. Approx.
Part No. Description Net Weight Net Weight
(lbs.) (kgs.)
78-G 1/01
79-G 1/01
Parts
Parts
Part No.* Burner Motor
2-40-605 1/3 HP 115/230/60/1 3450 4-15
2-40-606 1/3 HP 230/460/60/3 3450 4-15
2-40-603 1/3 HP 110/220/50/1 2850 4-15
2-40-770 1/3 HP 380/50/3 2850 4-15
2-40-608 3/4 HP 115/230/60/1 3450 20-30
2-40-611 3/4 HP 230/460/60/3 3450 20-30
2-40-609 3/4 HP 110/220/50/1 2850 20-30
2-40-771 1.5 HP 380/50/3 2850 40-60
2-40-613 1.5 HP 115/230/60/1 3450 40-60
2-40-615 1.5 HP 230/460/60/3 3450 40-60
2-40-614 1.5 HP 110/220/50/1 2850 40-60
*The correct part number is located on the burner motor.
Part No. Burner Scroll Casting
2-11-123 Burner Scroll Casting 4-15
5-20-059 Burner Scroll Casting 20
5-20-060 Burner Scroll Casting 30
2-11-126 Burner Scroll Casting 40 -60
(1)
RPM HP
(2)
HP
Part No.
(8)
(9)
(6)
HP
HP
50-100
4-30
Nat. Gas Orifice LP Gas Orifice
7-20-050 7-20-030 4
7-20-051 7-20-061 6
2-20-078 consult factory 9.5
7-20-052 7-20-062 10
7-20-023 7-20-033 15
7-20-054 7-20-064 20
7-20-055 7-20-065 30
7-20-265 7-20-275 40
7-20-056 7-20-066 50
7-20-057 7-20-067 60
Part No. Air Switch
2-30-118 4-100
Part No. Flame Detectors HP
2-40-161 Scanner for 7800 Series
2-20-020 Flame Rod
(7)
Part No.* Burner Fan
2-30-407 5-1/2 x 1-1/2 x 5/8 LP/N.Gas 50/60 4
2-30-410 6-1/4 x 1-1/2 x 5/8 N.Gas 50/60 6 2-30-412 7 x 1-1/2 x 5/8 LP/N. Gas 50/60 9.5-10 2-30-414 7-11/16 X 1-1/2 x 5/8 LP/N. Gas 50/60 15-20 2-30-418 8-3/8 x 2 x 5/8 LP/N. Gas 50/60 30 2-30-421 8-3/8 x 2-1/2 x 1 LP/N. Gas 50/60 40-50. 2-30-425 9 -3/16 X 2-1/2 x 1 LP/N. Gas 50/60 60
*The correct part number is located on the back of the fan plate.
Part No. Ignition Transformer
2-40-082 120/60/1
2-40-083 240/60/1
2-40-084 120/50/1
2-40-085 240/50/1
Part No. Air Deflector
2-11-112 Air Deflector 4-10
2-11-075 Air Deflector 9.5
2-11-113 Air Deflector 15-20
7-20-090 Air Deflector 30
7-20-092 Air Deflector 40-60
(3)
Fuel HZ HP
LP 50/60 6
(4)
(5)
HP
(11)
(10)
(12)
(13)
(14)
HP
HP
4-60
40-100
4-100
Part No. Burner Plate
5-20-019 Gas Burner Plate 4
5-20-007 Gas Burner Plate 6-10
5-20-055 Gas Burner Plate 9.5
5-20-013 Gas Burner Plate 15-20
5-20-018 Gas Burner Plate 30-60
Part No. Air Gate
5-20-017 Air Gate 4-10
5-20-012 Air Gate 15
5-20-011 Air Gate 20-30
5-20-066 U.K. Air Gate 40-100
Part No. Electrode Parts HP
2-20-019 Ignition Electrode
2-20-033 Ignition Electrode - VMP
2-12-014 Pyrex Plate Glass 1"
80-G 1/01
-G 1/01
Parts
Gas Burner Ignition Assembly
Gas Burner Components
81
82-G 1/01
Parts
Gas Head Assemblies
Part No. Complete Gas Head Assembly HP
7-54-1000 Natural Gas 4 7-54-1001 Natural Gas 6 7-54-1002 Natural Gas 10
7-54-1003 Natural Gas 15 7-54-1004 Natural Gas 20 7-54-1005 Natural Gas 30 7-54-1006 Natural Gas 40-50 7-54-1007 Natural Gas 60 7-54-1050 Propane Gas 4 7-54-1051 Propane Gas 6 7-54-1052 Propane Gas 10 7-54-1053 Propane Gas 15 7-54-1054 Propane Gas 20 7-54-1055 Propane Gas 30 7-54-1056 Propane Gas 40-50 7-54-1057 Propane Gas 60
Gas Train Components
Part No. Description HP
2-30-113 Main Gas Manual Shut Off Valve (1) 4-15 2-30-114 Main Gas Manual Shut Off Valve 20 2-30-115 Main Gas Manual Shut Off Valve 30-50 2-30-116 Main Gas Manual Shut Off Valve 60 2-30-104 Main Gas Pressure Regulator (2) 4-15 2-30-105 Main Gas Pressure Regulator 20 2-30-107 Main Gas Pressure Regulator 30-50 2-30-108 Main Gas Pressure Regulator 60
2-30-301 Main Automatic Gas Valve (3) 4-15 2-30-302 Main Automatic Gas Valve 20 2-30-303 Main Automatic Gas Valve 30-50
2-40-220 Main Automatic Gas Valve Actuator
w/Proof of Closure (4) 60-100
2-40-254 Main Automatic Gas Valve Body (5) 60
2-30-198 Leak Test Valve (6) 4-100
2-40-533 High/Low Gas Pressure Switch (7) 60-100
Part No. Description HP
2-30-113 Final Manual Shut-off Valve (8) 4-15 2-30-114 Final Manual Shut-off Valve 20 2-30-115 Final Manual Shut-off Valve 30-50 2-30-116 Final Manual Shut-off Valve 60
2-30-111 Pilot Gas Manual Shut-off Valve (9) 4-100
2-30-102 Pilot Gas Pressure Regulator (10) 4-100
2-30-298 Pilot Gas Automatic Shut-off Valve (11) 4-100
83-G 1/01
Parts
Gas Head Assembly (CSD-1) 4 to 50 HP
Gas Head Assembly (CSD-1) 60 HP
2
1
8
3
6
11
4
5
2
10
8
9
6
7
11
10
9
1
84-G 1/01
Parts
Water Level
Relay
Contactor/
Overload–3 Phase
(Upon Request) or
Starter Relay–1 Phase
For Feed Water
Pump Motor
Flame
Safe Guard/
Burner Control
Low Limit
Pressuretrol
(Optional)
Operating Pressuretrol
Terminal Block Low Water
Safety Relays
Low Water Manual Reset Switch
4-50 HP:
1 Phase Motor Starter Standard
60 HP:
3 Phase Contactor/ Overload Standard
3 Phase Available On 4-50 HP As Option
Power On/Off Switch
High Limit Pressuretrol With Manual Reset
Panel Box Parts
Part No. Relays HP
2-40-420 Fulton Pump Relay - 120V 4-100 2-40-421 Fulton Burner Relay - 120V 4-100 2-40-422 Base for Fulton Pump Relay 4-100 2-40-423 Base for Fulton Burner Relay 4-100 2-40-405 Fulton Pump Relay 220V 4-100 2-40-406 Fulton Burner Relay 220V 4-100 2-40-403 IDlDO-120V Relay 4-100 2-40-402 IGIDO - 120V Relay (manual reset) 4-100 2-40-400 IGlDO-A-120V Relay 4-100 2-40-401 ID2DO - 220V Relay 4-100
Part No. Switches HP
2-45-091 On/Off Switch 4-100 2-45-092 Manual Reset Switch 4-100 2-45-090 Night Switch for two (2) Pressuretrols 4-100
Part No. Motor Starter Relays (Single Phase) HP
2-40-200 Motor Starter Relay - 120V - 20 AMP 4-50 2-40-202 Motor Starter Relay - 120V - 30 AMP 4-50 2-40-201 Motor Starter Relay - 220V - 20 AMP 4-50 2-40-203 Motor Starter Relay - 220V - 30 AMP 4-50
Part No. Flame Safeguard Control HP
2-40-260 RM7895F Programmer 4-50 2-40-262 RM7800M Programmer 60-100 2-40-272* Display Module For 7800 Series Controls 60-100
*Standard on 60-100 HP; optional 4-50 HP.
Part No. Motor Contactors (Three Phase) HP
2-40-568 Contactor -AB -100- A09NA3- 220V 4-60 2-40-567 Contactor- AB -100- A09ND3-120V 4-60 2-40-641 Contactor -AB -100- A12NA3- 220V 80-100 2-40-642 Contactor- AB -100- A12ND3-120V 80-100 2-40-565 Overload - AB - BSB 16 2-40-657 Overload - AB - BSB 15 2-40-648 Overload - AB - BSB 22 2-40-571 Overload - AB - BSB 30 2-40-575 Overload - AB - BSC 10 2-40-643 Overload - AB - BSC 15 2-40-652 Overload - AB - BSC 24 2-40-572 Overload - AB - BSB 42 2-40-573 Overload - AB - BSB 60 2-40-574 Overload - AB - BSB 80 2-40-566 Overload - AB - BSB 90 Note: Contactor Overload depends on motor h.p. and voltage
Part No. Pressuretrols HP
4-40-050 Night Heating Pressuretrol Set Up 4-100 2-40-227 Pressuretrol L404A - 2-15 PSI 4-100 2-40-228 Pressuretrol L404A - 5-50 PSI 4-100 2-40-229 Pressuretrol L404A - 10-150 PSI 4-100 2-40-230 Pressuretrol L404A - 20-300 PSI 4-100 2-40-231 Pressuretrol L404C - 2-15 PSI 4-100 2-40-232 Pressuretrol L404C- 5-50 PSI 4-100 2-40-233 Pressuretrol L404C - 10-150 PSI 4-100 2-40-234 Pressuretrol L404C - 20-300 PSI 4-100 Note: Correct pressuretrol is based on boiler trim pressure.
85-G 1/01
Parts
14
12
(Located
In
Boiler)
9
13
11 10
1
2
6
15
8
4 5
3
7
3
Water Column - Parts
Part No. Water Column Bottle Casting (1) HP
5-20-022 Water Column Bottle Casting 4-30 5-20-048 Water Column Bottle Casting 50-100
Part No. Water Gauge Glass (2) HP
2-12-017 9-1/4" Water Gauge Glass - Corning 4-100 2-12-065 8-5/8" Extra Heavy Gauge Glass 9.5
Part No. Water Gauge Glass Trim HP
2-30-149 Water Gauge Glass Valves w/Ball Checks (3) 4-100 2-30-155 Conbraco 250 w/Ball Check (3) 9.5 2-12-020 Brass Water Gauge Glass Gasket (4) 4-100 2-12-019 Rubber Water Gauge Glass Gasket (5) 4-100 2-35-514 Brass Packing Nut for Gauge Glass Valve (6) 4-100 2-30-330 Gauge Glass Protector Rods (7) 4-100 2-12-022 Lucite Gauge Glass Guard -9-1/4" Glass (8) 4-100 2-12-204 Lucite Gauge Glass Guard -8-5/8" Glass (8) 9.5
Part No. Water Level Probes & Plugs HP
2-20-010 *Pump Off Probe - 7-1/4 " (9) 6-100 2-20-011 *Pump On Probe - 9-1/4" (10) 6-100 2-20-012 *Low Water Probe in Water Column-11-1/4" (11) 6-100 2-20-017 Low Water Probe in Boiler- 17-1/8" (12) 6-100 2-21-012 Probe Cover (13) 4-100 2-21-013 Probe Basket (14) 4-100 2-30-398 1/4" Ball Valve for Water Column (15) 4-100
*For 4 HP boilers only, the water column probes are 2” shorter.
Warranty
6
8-G 1/01
87-G 1/01
Standard Warranty for Fulton Boilers
88-G 1/01
Warranty Valid for Models ICS, ICX, ICW, ICXW, VMP, VMPW, FB-A, FB-F, FB-L, FB-S, FB-W
Five (5) Year (60 Months) Material and Workmanship Warranty
The pressure vessel is covered against defective material or workmanship for a period of five (5) years from the date of shipment from the factory. Fulton will repair or replace F.O.B. factory any part of the equipment, as defined above, provided this equipment has been installed, operated and maintained by the buyer in accordance with approved practices and recommendations made by Fulton. The commissioning agency must also successfully complete and return the equipment Installation and Operation Checklists to Fulton’s Quality Assurance department. This warranty covers any failure caused defective material or workmanship; however, waterside corrosion or scaling is not covered. Therefore, it is imperative that the boiler water management and chemistry be maintained as outlined in the Installation and Operation Manual.
Parts Warranty
Fulton will repair or replace F.O.B. factory any part of the equipment of our manufacture that is found to be defective in workmanship or material within one (1) year of shipment from the factory provided this equipment has been installed, operated and maintained by the buyer in accordance with approved practices and recommendations made by both Fulton and the component manufacturers and the commissioning agency has successfully completed and returned the equipment Installation and Operation Checklists to Fulton’s Quality Assurance department.
General
Fulton shall be notified in writing as soon as any defect becomes apparent. This warranty does not include freight, handling or labor charges of any kind.
These warranties are contingent upon the proper sizing, installation, operation and maintenance of the boiler and peripheral components and equipment. Warranties valid only if installed, operated, and maintained as outlined in the Fulton Installation and Operation Manual.
No Sales Manager or other representative of Fulton other than the Quality Manager or an officer of the company has warranty authority. Fulton will not pay any charges unless they were pre­approved, in writing, by the Fulton Quality Manager.
This warranty is exclusive and in lieu of all other warranties, expressed or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose. Fulton shall in no event be liable for any consequential or incidental damages arising in any way, including but not limited to any loss of profits or business, even if the Fulton Companies has been advised of the possibility of such damages. Fulton’s liability shall never exceed the amount paid for the original equipment found to be defective.
To activate the warranty for this product, the appropriate commissioning sheets must be completed and returned to the Fulton Quality Assurance department for review and approval.
9/9/09
89-G 1/01
Extended Warranty for Fulton Skid Mounted Steam Boilers
90-G 1/01
Warranty Valid for Models ICS, ICX, VMP, FB-A, FB-F, FB-L, FB-S
Ten (10) Year Material and Workmanship Warranty
The pressure vessel is covered against defective material or workmanship for a period of ten (10) years from the date of shipment from the factory. Fulton will repair or replace at our option, F.O.B. factory any part of the equipment, as defined above, provided this equipment has been installed, operated and maintained in accordance with the Installation, Operation and Maintenance Manual. The commissioning agency must also successfully complete and return the equipment Installation and Operation Checklist to Fulton’s Service Department. This warranty covers any failure caused by defective material or workmanship, however, waterside corrosion or scaling is not covered. Therefore, it is imperative that the boiler water management and chemistry be maintained as outlined in the Installation, Operation and Maintenance Manual.
The extended warranty is valid only for steam boilers that are purchased as part of a skid mounted boiler system. Generally, this system MUST include ALL of the following equipment in order for the warranty to apply.
1. Fulton boiler with model number as listed above.
2. Fulton DA or condensate return system with preheat kit.
3. Fulton blowdown tank/separator
4. Water softener
5. Chemical feed system
6. Automatic surface or bottom blowdown, which must operate to maintain TDS levels as specified in the Installation,
Any deviation or additional equipment specified by Fulton Engineering must be used and maintained per the Installation, Operation and Maintenance Manual
There is a $1,000 labor allowance for any failed pressure vessel that is covered under the above warranty.
Parts Warranty
Fulton will repair or replace FOB factory any part of the equipment of our manufacture that is found to be defective in workmanship or material within twelve (12) months of shipment from the factory provided this equipment has been installed, operated and maintained by the buyer in accordance with approved practices and recommendations made by both Fulton and the component manufacturers.
General
Fulton shall be notified in writing as soon as any defect becomes apparent. This warranty does not include freight, handling or labor charges of any kind.
No Sales Manager or other representative of Fulton other than the Quality Manager or an officer of the company has warranty authority. Fulton will not pay any charges unless they were pre-approved, in writing, by the Fulton Quality Manager.
This warranty is exclusive and in lieu of all other warranties, expressed or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose. Fulton shall in no event by liable for any consequential or incidental damages arising in any way, including but not limited to any loss of profits or business, even if Fulton has been advised of the possibility of such damages. Fulton’s liability shall never exceed the amount paid for the original equipment found to be defective.
Conditions of Warranty Warranties are only valid if the boiler is installed, operated and maintained as outlined in the Installation, Operation and Maintenance Manual. Fulton shall accept no responsibility if the equipment has been improperly installed, operated or maintained or if the buyer has permitted any unauthorized modification, adjustment, and/or repairs to the equipment. The use of replacement parts not manufactured or authorized by Fulton will void any warranty express or implied.
Warranty coverage for all components and equipment in said warranty are not valid unless the boiler is started up by a factory certified technician. The commissioning agency must successfully complete and return the equipment Installation and Operation Checklist to Fulton’s Service department.
The boiler must be maintained in accordance with the product manual and annual combustion and maintenance reports must be produced for warranty consideration.
The warranty is valid for the original installation only in the U.S.A and Canada.
Operation and Maintenance Manual.
08/20/10
91-G 1/01
Loading...