Questions? Call (315)298-5121, or visit us online at www.fulton.com
1-1
INTRODUCTIONHPN-IOM-2014-0416 SECTION 3
Overview
Prior to shipment, the following inspections and tests are
made to ensure the highest standards of manufacturing for
our customers:
Material inspections
Manufacturing process inspections
American Society of Mechanical Engineers (ASME)
welding inspection
ASME hydrostatic test inspection
Electrical components inspection
Operating test
Final engineering inspection
Crating inspection
This manual is provided as a guide to the correct operation
and maintenance of your Fulton equipment, and should be
read in its entirety and be made permanently available to the
sta responsible for the operation of the heater. It should not,
however, be considered as a complete code of practice, nor
should it replace existing codes or standards which may be
applicable. Fulton reserves the right to change any part of
this installation, operation and maintenance manual.
Installation, start-up, and maintenance of this equipment
can be hazardous and requires trained, quali ed
installersand service personnel. In order to meet Fulton
warranty requirements, this unit must be commissioned
by a Fulton Factory Technician. Trained personnel are
responsible for the operation and maintenance of this
product, and for the safety assurance of operation and
maintenance processes.
Warnings & Cautions
WARNINGS and CAUTIONS appear in various chapters of this
manual. It is critical that all personnel read and adhere to all
information contained in WARNINGS and CAUTIONS.
WARNINGS must be observed to prevent serious injury
or death to personnel.
CAUTIONS must be observed to prevent damage
or destruction of equipment or loss of operating
e ectiveness.
All Warnings and Cautions are for reference and guidance
purposes, and do not substitute for required professional
training, conduct, and strict adherence to applicable
jurisdictional/professional codes or regulations.
Disclaimers and Local Codes
Installation of the equipment shall conform to all the
requirements or all national, state and local codes established
by the authorities having jurisdiction or, in the absence
of such requirements, in the US to the National Fuel Gas
Code ANSI Z223.1/NFPA 54 latest edition, and the speci c
instructions in this manual. Authorities having jurisdiction
should be consulted prior to installation.
The boiler heat exchanger is manufactured and stamped
in accordance with ASME Boiler and Pressure Vessel Code,
Section I or Section VIII, Div. 1.
Do not install, operate, service or repair any component
of this equipment unless you are quali ed and fully
understand all requirements and procedures.
When working on this equipment, observe all warnings,
cautions, and notes in literature, on stickers and labels, and
any additional safety precautions that apply. Follow all safety
codes and wear appropriate safety protection. Follow all
jurisdictional codes and consult any jursidictional authorities
prior to installation.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-1
INSTALLATIONHPN-IOM-2014-0416 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Unless otherwise noted, this heater is
certi ed for indoor installation only.
A competent rigger experienced in
handling heavy equipment should
handle rigging your equipment into
position.
The equipment must be installed on a
non-combustible surface.
Ensure all labels on the heater are
legible. All connections and safety
devices, both mechanical and
electrical, must be kept clean, with
ease of access for inspection, use and
maintenance.
Do not store or use gasoline or other
ammable vapors and liquids or
corrosive materials in the vicinity of
this or any other appliances.
Placement & Rigging
Proper placement of your Fulton Product (see Figure 2, and Table 1) is essential.
Attention paid to the following points will save a great deal of di culty in the
future. Correct placement is the rst step to trouble-free installation, operation
and maintenance.
Adhere to the following for equipment placement and rigging:
1. Consult authorities with jurisdiction over any national or local codes
(including but not limited to National Fire Protection Agency (NFPA),
American National Standards Institute (ANSI), Underwriters Laboratories
(UL), SCA, and ASME, which might be applicable to heater applications
before beginning.
2. Make appropriate determinations for placement, based on the following:
Check building speci cations and Table 2 for permissible oor loading.
Ensure the equipment is to be placed on a non-combustible level base
with adequate clearances from combustible materials. See Clearances
& Serviceability section.
Locate heater as close as possible to the place where the heat will be
used in order to keep pipe work costs to a minimum.
Ensure that there is adequate clearance around the unit to provide
access for operators and maintenance personnel to all parts of the
equipment. Ensure also that clearance provides for component removal
for maintenance. See Clearances & Serviceability section. The
equipment should be placed in a suitable heater house or well ventilated
separate room through which personnel do not normally pass. The
layout should eliminate tra c in potentially hazardous areas. For
instance, the service engineer or the operator should not have to pass
exposed, hot pipe work to make adjustments to the heater controls.
4 CAUTION
Do not allow weight to bear on
equipment components to prevent
damage.
2-2
Ensure the equipment is to be placed in such a way that the electrical
components are protected from exposure to water or excessive
humidity.
3. Determine rigging procedure, based on the following:
Units are crated for forklift or crane transport. Once uncrated, all units
can be transported with a forklift or crane. All skidded units can be
moved with forklifts. Some stand-alone heaters are supplied with lifting
lugs.
If means of lifting are not available, place rollers beneath the frame of the
equipment for guidance to the position of where it is to be installed.
Under no circumstances allow weight to bear on the jacket, control
panel, burner, fuel train or fan housing of any Fulton heater.
4. Install a 4 inch (102 mm) curb completely around the unit. In the event of a
large spill, this will help contain the uid.
Adhere to the following for equipment clearances and serviceability:
1. Ensure appropriate front, back, sides and top clearances are met. This
will allow access around the equipment to facilitate maintenance and a
safe work environment, and ensure technicians will commission the unit.
Technicians will not commence commissioning if hazardous conditions
exist.
2. Place heater with clearances to unprotected combustible materials,
including plaster or combustible supports, not less than the following:
Heater Front 36” (1m) or more, depending on burner requirements
Heater Sides 18” (0.5 m), 36” (1 m) on side where panel located
Heater Rear: enough room for coil to be pulled
Flue Pipe 18” (0.5 m)
3. Pipes must not be run within 10” (254 mm) of any control cabinets or
combustible material.
4. Verify that all clearances are acceptable with the local ordinances.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Failure to provide required and
safe access to the equipment
could impede commissioning and
maintenance. Service technicians
are instructed not to commence
commissioning if hazardous
conditions exist.
Failure to provide proper minimum
clearances between equipment and
combustible materials may result in
re.
Environment, Ventilation and Combustion Air
Requirements
Ventilation must be su cient to maintain a building temperature of 120°F (49°C)
or less. Consistent proper ventilation of the equipment room is essential for good
combustion.
NOTE: When calculating ventilation requirements, heat losses from the Fulton
equipment (and other equipment) should be considered.
Adhere to the following to meet ventilation and combustion air requirements, if
installed indoors:
1. Install two fresh air openings, one at a low level, 24” (610 mm) from the
oor, and one at a higher level on the equipment room wall. This will
provide a ow of air to exhaust the hot air from the equipment room.
2. Ensure the burner has an adequate supply of air. Based on NBIC
recommendations, unobstructed air openings must be sized on the basis
of 0.5 square inch of free area per 1,000 BTU/hr input maximum fuel
input of the combined burners in the equipment room or as speci ed by
applicable codes.
3. Ensure the equipment room air supply openings are kept clear at all times.
4. See Table 3 for minimum make-up air required and the recommended area
of each opening for each model.
Questions? Call (315)298-5121, or visit us online at www.fulton.com
TABLE 3 MINIMUM MAKEUP AIR REQUIREMENTS AND RECOMMENDED AREA OF OPENING
FOR VENTS
ModelMinimum Make-Up
Air (SCFM)*
100300600200
2006001200400
35010002000667
600180036001200
800230046001534
1000290058001934
1200350070002334
1400400080002667
1600460092003067
20005800116003867
24006900138004600
30008600172005734
400011500230007667
* Minimum make-up air requirements are based on 25% excess air at high re.
** Opening areas are calculated based input of a single heater and do not
account for the ventilation needs of the equipment room. These measurements
are subject to state and local regulations.
Opening Area (in2)**
Lower Vent
Opening Area (in2)
Upper Vent
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-5
INSTALLATIONHPN-IOM-2014-0416 SECTION 2
! WARNING
A quali ed installer, service agency
or the gas supplier must perform
installation and service on the fuel
delivery system.
Do not use matches, candles, ame or
other sources of ignition to check for
gas leaks.
What to do if you smell gas:
Do not try to light the appliance.
Do not touch any electrical switch.
Do not use any phone in the building.
Leave building and contact gas
supplier from neighbor’s phone. If you
cannot reach gas supplier, phone the
re department.
When making gas piping joints,
maintain proper ventilation to reduce
breathing hazards.
An exhaust fan may draw products
of combustion into the work
environment creating a possible
hazard to personnel.
Assure all electrical connections are
powered down prior to attempting
replacement or service of electrical
components or connections of the
equipment.
5. If positive forced ventilation is adopted, ensure that there will be no
appreciable pressure variation in the equipment room.
6. Avoid ventilation which creates a negative pressure in the building as it
will seriously a ect combustion and proper operation of the stack. Please
note that exhaust fans or similar equipment can create a down draft in the
chimney or starve the burner’s air supply. Either case may result in poor
combustion or nuisance failures. A properly designed make-up air system
in the equipment room will preclude these possibilities and is required to
maintain proper combustion.
NOTE: A properly designed make-up air system in the equipment room will
preclude these possibilities and is required to maintain proper combustion.
7. Eliminate potential for high risk situations for particulate matter to
be in the combustion air supply (e.g., as a result of construction and
maintenance activities).
Utilities
The Gas Supply
Adhere to the following for gas supply installation:
1. Install gas piping in accordance with all applicable codes.
2. Ensure pipe and ttings used are new and free of dirt or other deposits.
3. Ensure piping is of the proper size for adequate gas supply to the gas head
assembly. Consult your gas company for speci c recommendations.
4. When making gas piping joints, use a sealing compound resistant to the
action of lique ed petroleum gases. Do not use Te on tape on gas line
heads.
4 CAUTION
It is essential that only fresh air be
allowed to enter the combustion air
system. Foreign substances, such
as combustible volatiles and lint in
the combustion system can create
hazardous conditions. If foreign
substances can enter the air stream,
the combustion air inlet must be piped
to an outside location. Failure to do so
will void the warranty.
To avoid failures due to poor
combustion, ensure make-up air
system is properly designed.
2-6
5. Ensure no piping stresses are transmitted to the equipment. The
equipment shall not be used as a pipe anchor.
6. Ensure all vent connections on diaphragms, gas valves, pressure regulators,
and pressure switches (gas- red units) are vented per local code.
7. On gas- red units with NFPA valve trains, ensure the vent valve is piped to
atmosphere per local code.
8. During any pressure testing of the system at pressures in excess of 1/2 psig
(14 inch W.C.)., disconnect the heater at the heater manual shuto valve
(located at the end of the supplied gas train) from the gas supply piping
system.
9. Ensure the supply pressure is regulated by a non-stacking, tight, shut-o
regulator.
10. Arrange gas piping so that it does not interfere with any cover or burner,
inhibit service or maintenance, or prevent access between unit and walls
or another unit.The burner assembly and gas controls
terminate at a manual stop valve to which the gas
supply should be connected. Piping must be sized
for a gas ow consistent with the required BTU/Hr
input. Large pressure drops must be avoided. Fulton
recommends that the supply piping between the
pressure regulator and the inlet to the heater be kept to
a minimum. The minimum required gas pressure at the
stop valve varies with the model of heater.
NOTE: Even when the unit is shut down, the gas supply
pressure must never exceed these values.
11. Some fuel train con gurations are require a safety relief
valve which must be piped to a safe area in accordance
with local codes.
12. After gas piping is completed and before wiring
installation is started, carefully check all piping
connections, (factory and eld), for gas leaks. Use a soap
and water solution.
The Oil Supply
the fuel oil pump inlet per the National Fire Protection
Association (NFPA).
NOTE: If for some reason the pressure of the fuel supply will
exceed NFPA maximum, tting a regulator to the fuel line
must be considered, e.g. when there is a tank situated with an
oil level eight feet (2.4 m) or more above the pump.
5. On units tted with NFPA controls, ignition is obtained by
means of a gas pilot. A natural gas or LP supply is required
for these units. The required gas supply pressure is 7” w.c.
If a guaranteed supply of natural gas is not available, then
a supply of bottled gas at 11“w.c. is required. For details
contact a local liquid propane dealer.
Instrument Air
Instrument air provision for pneumatically actuated control
devices should meet the minimum and maximum ow rate
and delivery pressures speci ed by the individual equipment.
Additionally, it should be a dry, dust-free,water-free, and oilfree supply with a dew point of -40°F (-40°C).
Fuel Oil ViscositySpeci c GravitySulfur Content
#2Less than
31.9 Seconds
Redwood #1 at
100°F (38°C)
#4Less than
81 Seconds
Redwood #1 at
100°F (38°C)
#6Less than 3000
Seconds Redwood #1 at 100°F
(38°C)
0.824 to 0.852 at
59 C (15°C)
0.90 to 0.93 at 59
C (15°C)
0.95 to 0.98 at
59°F (15°C)
less than 0.40%
by weight
less than 0.1.6%
by weight
less than 2.12%
by weight
Adhere to the following for installation:
1. Fuel pipes must be of approved materials and of a
diameter suitable for the quantity of oil being delivered to
the burner and the static head available.
2. Make fuel connection in accordance with the details on
the enclosed fuel pump cut sheet.
3. Ensure fuel oil piping is in accordance with local and/or
national requirements. In addition, if a two pipe system
is employed, a check valve must be tted into the return
pipe.
4. Do not exceed the 3 psi maximum pressure allowed at
Electrical Supply
Adhere to the following for electrical supply installation:
1. Install wiring and ground in equipment in accordance
with authority having jurisdiction or in absence of such
requirements the National Electrical Code, ANSI/NFPA 70.
2. Provide a wall-mounted, fused disconnect sized for
the unit. This must be tted by the client/contractor if
disconnect is not supplied on the panel.
3. Size fuses according to motor name plates and local
electrical codes.
4. Connect power to the terminal strip as supplied on the
inside of the panel box.
NOTE: Single skid systems are generally shipped completely
prewired.
NOTE: The liquid level switch on the expansion tank, when
supplied, will be shipped in the parts box and must be
installed in the eld.
5. Determine multiple skid systems wiring requirements
(between the skids). Fulton will run conduit and wire
the devices on each skid. For the devices that have to
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-7
INSTALLATIONHPN-IOM-2014-0416 SECTION 2
2” NPT Gas Connection
Manual Gas Valve
Pilot Gas Valve
Pilot Gas Valve
HI/LOW Gas Pressure Switch
Main Gas Regulator
Gas Safety Shutoff Valve
FIGURE 3 TYPICAL GASFIRED FUEL TRAIN
come down for shipping, the wire will be left at the end
Locate electrical schematic diagram, a copy of which is inside
of the panel box. Ensure the information on the electrical
drawing corresponds to your voltage and frequency. Check
the supply voltage and make sure that there is no over-or
under-voltage exceeding 10% of the nominal value.
NOTE: Normal supply will be 460 volts, 3 phase, 60 Hz, AC
unless otherwise speci ed.
Thermal Fluids
Thermal Fluids at Elevated Temperatures
Personnel must be familiar with the nature of potential
hazards when working with thermal uids at operating
temperatures. Unlike steam or high-pressure water systems,
thermal uid attains extremely high temperatures without a
corresponding increase in pressure.
Manual Gas Valve
Adhere to the following:
1. Be aware that certain types of thermal uid may have
operating temperatures reaching 650°F (345°C) and
above, so all exposed pipework is hazardous and should
be insulated.
2. Check that anged joints are tight during and after the
rst warming up of the system. Turn burner and pump
o before ttings are tightened. After these checks,
exposed hot anges, pumps, valves and ttings should
be tted with some sort of shield.
3. Remember that there is pressure generated in the
system by the circulating pump. Care should be
exercised when opening any drain or vent valves
in the system. This is especially important during
commissioning, when any air trapped in the system is
vented at high points, and when water, which will ash
into steam, is either expelled from the deaerator vent or
drained o at low points.
The selection of the thermal uid most suited to your application is very
important. Factors to be considered include e ciency, thermal stability,
adaptability to various systems, and physical properties, including vapor
pressure, freezing point, and ash and re points.
Heat transfer uids of both mineral and synthetic origin have been specially
developed to give thermal stability over a very wide range of temperature. A
wide variety of thermal uids have been used successfully in Fulton Thermal Fluid
Heater systems, however, your nal selection should be made in conjunction
with recommendations from Fulton or the uid manufacturer.
Consider the following for thermal uid selection:
1. The Fulton coil design heater is a red heat exchanger and the safe
control and monitoring of the thermal uid temperature is of paramount
importance.
2. The safe maximum bulk temperature of the uid must be strictly adhered
to. The safe maximum temperature of the uid varies.
3. Special care must be taken when consulting uid manufacturers’ literature,
as maximum uid temperatures quoted are the actual limit to which any
of the uids may be subjected. It is important to remember that in any
red heater there exists a “ lm temperature” which is higher than the
temperature of the “bulk” of the uid. It is the BULK uid temperature and
NOT the FILM temperature that is indicated by the instruments.
4. As a general guide, the following list of uids that have given satisfactory
service over many years is provided. This is by no means a complete list.
Any uid speci cally designed for heat transfer use may be considered;
multipurpose oils are not acceptable.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
The vent line connection on the
gas pressure regulator must be
piped to outdoor air by the installer
in accordance with National Fuel
Gas Code, ANSI Z223-1-1991 or
latest addenda. In Canada, gas
installations must be in accordance
with the current CAN/CGA B149.1 and
2 and/or local codes.
If a re does occur, extinguish using
CO2 foam or dry chemical. Do not use
water.
4 CAUTION
Proper selection of thermal uid is
critical to system performance.
AMOCO Transfer Oil 4199
CHEVRON
DOW G
EXXON 43
MOBIL
MONSANTO
MULTITHERM
PARATHERM
PETROCANADA T
SHELL
TEXACO
5. Any uid speci cally designed for heat transfer use must also exhibit these
characteristics:
Be a stable and homogenous liquid to a temperature of at least 100°F
(38°C) over and above the maximum intended temperature of utilization,
compatible with metals used in the installation, and tolerating contact
Questions? Call (315)298-5121, or visit us online at www.fulton.com
2-9
INSTALLATIONHPN-IOM-2014-0416 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
4 CAUTION
Some soap used for leak testing is
corrosive to certain types of metals.
Clean all piping thoroughly after
completing the leak check.
Some plastics can be dissolved by
thermal uid.
If excessive amounts of thermal uid
are vented from the system, additional
thermal uid may be required in the
system. Contact Fulton for further
assistance.
with atmospheric air.
No solid matter in suspension.
Non-toxic in the case of leakage.
Su cient lubricity, i.e. not likely to cause seizure.
6. The thermal uid manufacturer must guarantee the characteristics of the
product, and verify that the uid bulk temperature limitation exceeds
the expected operating temperature. After a uid is selected, refer to the
manufacturer’s recommendations, published in compliance with the
Occupational Safety and Health Administration (OSHA).
7. If the uid expansion volume from 50°F to 600°F (10°C to 316°C) exceeds
20% of the initial uid volume, consult Fulton.
Routine Analysis of Heat Transfer Fluid
Nearly all leading manufacturers of heat transfer uids provide an after
sales service to monitor the condition of the uid in operation and make
recommendations when replacement becomes necessary.
Each uid manufacturer has procedures for regular testing and analysis of the
uid. These usually allow for a sample to be taken and analyzed at least once a
year, although actual frequency will depend on operating temperature, number
of hours operated weekly, and the results of tests made during the rst weeks of
system operation.
Fulton recommends that the thermal uid in your system be analyzed within the
rst two months after startup and annually thereafter.
During the rst few months of operation, sampling may be carried out at
frequent intervals to con rm that system performance has been predicted
correctly.
If the supplier of your thermal uid does not contact you within four weeks of
commissioning, contact the supplier and make certain that the “ ll” is registered
for routine analysis.
Thermal Fluid Breakdown
The possibilities of thermal uid breakdown are very slim in a typical closed loop
thermal uid system. Fulton’s combination expansion/deaerator/thermal bu er
tank creates a “cold seal” of uid that is slightly above ambient temperature. This
prevents oxidation that will otherwise happen when high temperature uid
contacts air.
Oxidation of the uid will also occur when hot thermal uid contacts air at a leak
in the system piping. Oxidized thermal uid becomes acidic and will damage the
thermal uid system. Thermal uid breakdown can occur in sections of piping
where there is a low ow condition. A low ow rate through the heater will result
in high lm temperatures leading to breakdown of the thermal uid.
Multiple pressure switches and a di erential pressure switch are used to
prevent this condition from occurring. These safeties must not be bypassed
at any time.
Exceeding the maximum operating temperature of the thermal uid will
also result in thermal uid breakdown. Fulton heaters are equipped with a
temperature limit switch (located on the front of the panel box) to prevent
this from occurring.
A high temperature limit switch is an over temperature safety device.
If the high temperature limit shuts down the unit, the manual reset
button on the limit switch must be pressed. The reset button on the
ame programmer must also be pressed to reset the unit before it can be
restarted. Refer to Maintenance section of this manual for troubleshooting
activities.
Piping Specifi cations
For piping, the basic considerations are: the design temperature, the pressure
retained by the pipe, the uid in the pipe, the load resulting from thermal
expansion or contraction, impact or shock loads imparted such as water hammer,
external loads, wind loads and vibration from equipment.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Fulton is not responsible for any
injury or damage caused by the use of
inadequate uid.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
Adhere to the following for piping installation:
1. Ensure the arrangement of the piping and its appurtenances takes into
consideration the location of other structures and equipment adjacent to
the piping, which may result in freezing interference and/or damage as a
result of expansion, contraction, vibration, or other movements.
2. Consider the appropriate location and orientation of valves necessary
for safe operation and isolation of the piping. Valves are used in piping
systems to stop and start the ow of uids, to regulate ow, to prevent the
back ow, and to relieve excessive pressure build up in the piping.
3. Ensure all piping and piping components are suitable for the design
temperatures, pressure and uid used in the system.
4. Ensure all components exposed to thermal uid ow, including pipe,
valves, and screens, are not copper, copper alloys, bronze, brass,
aluminum, or cast iron. Cast iron is porous to thermal uids, and copper
and aluminum act as catalysts in the degradation of some thermal uids.
Carbon or stainless steel, or ductile iron, are recommended.
5. Ensure all pipework is constructed from seamless mild steel pipe,
conforming to ASME SA 106B or SA 53B, Schedule 40 or Schedule 80 or
equal, as required based on the design temperature and pressure of the
system.
6. If an isolating valve is completely closed, the pressure in the system will
rise to the deadhead pressure of the pump. Suitably sized pipe will enable
the system to withstand the total head generated by the circulating
Questions? Call (315)298-5121, or visit us online at www.fulton.com
2-11
INSTALLATIONSECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
If a re does occur, extinguish using
, foam or dry chemical. DO NOT
CO
2
USE WATER.
4 CAUTION
Some plastics may be dissolved by
thermal uid.
pump, should this occur. In applications where it is desirable to design
to pressures lower than 100 psig, an alternative safeguard is to install
appropriately sized safety valves.
7. Where secondary circulating pumps are installed, ensure the system is
suitable for the aggregate head, against a closed valve, of both pumps.
8. During construction of the installation, ensure that no dirt, water, or
residue from welding is left in the system.
9. Consider expansion joints or pipe loops to accommodate thermal
expansion. Design should be per latest edition of ASHRAE Systems and
Equipment Handbook to prevent detrimental forces and stresses at
connected equipment. Thermal expansion should be calculated using the
maximum possible utilization uid temperature, regardless of whether the
pipe considered is in the feed or return circuit. Steel pipe will grow axially
and can be expected to expand approximately 1” over 100ft @ 100dg°F
temperature rise (1mm per meter over 100 C rise).
10. Provide properly designed supports and anchors for all piping where
necessary to prevent undue stress from being imparted on equipment
such as pumps, valves and the heater. Care should be taken as end
reactions transmitted to rotating equipment, such as pumps, may deform
the equipment. Therefore equipment manufacturers’ recommendations
on allowable forces and movements should be followed. Ensure all pipe
joints are of either welded or anged construction. Screwed joints must be
avoided where possible. In no instance should screwed joints be used in
the ow circuit. All anges should be welded to the pipe and not screwed.
Depending on the size, anges should be 150# or 300# raised face anges,
SA105. See Figure 4.
11. Ensure heaters that are skid mounted with pumps and tanks are equipped
with a y-strainer, a ex connector and a valve in the inlet run between the
pump and the combination tank. Piping between the discharge of the
pump and the inlet of the heater will include a ex connector and a valve.
12. If screwed connections have to be made, e.g., to items of control
equipment, use a thread sealant suitable for use with uids at elevated
temperature. Te on tape, standard pipe sealant, or hemp and paste are not
acceptable.
13. Cut screw threads carefully and accurately. If possible, new tools should
be used. Threaded connections larger than 1” are not to be used. It is
recommended that GR5 or higher tensile steel bolts be used for all anged
joints.
14. Use gaskets to make all anged connections. Gasketing material must be
suitable for use with the pressure, temperatures and uids in the system.
Flexible graphite gaskets are suited for most applications. Recommended
gasket thickness is 1/10 - 1/8 inch. Ensure that all bolts are tightened
evenly and to the torque recommended values provided by the gasket
manufacturer. Refer to Tables 4 - 7 and Figure 5 for guidelines.
NOTE: Typical gaskets used by Fulton include JM Clipper Elastograph gaskets and
Flexitallic gaskets. Adhere to installation instructions and torque requirements for
these gaskets.
15. Install high point bleeds at all high points in the system piping. 1/2” x 12”
nipples welded in the top of the piping with ball valves and plugs attached
are to be used.
NOTE: It will save a considerable amount of time during the cold ltration if the
system piping is cleaned prior to assembly. The mill scale (the results of oxidation)
on the inside of the piping as well as construction debris can foul the uid and
cause the need for the lters (strainers) to be cleaned more than need be. This can
range from simply using a rag to ordering pickled pipe. (“Pickling” is a process
where the piping is rst soaked in an acid bath, then soaked in a neutralizing bath,
then given a protective oil coating.)
16. Install all pipes with a pitch to facilitate draining and venting.
TABLE 4 RECOMMENDED GASKET LOADS FOR FLEXITALLIC SPIRAL WOUND CLASS 150#
GASKETS SAE GRADE 5 BOLTS OR EQUAL
Nominal Flange
Size (in.)
1/241/245
3/441/245
141/245
1 1/44 1/2 45
1 1/2 4 1/2 45
2 4 5/890
2 1/24 5/890
3 4 5/890
3 1/285/890
485/890
583/4150
683/4150
883/4150
10127/8240
Number of BoltsDiameter of Bolts
(in.)
Preferred Torque
Req. Per Bolt (ft-lb)
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Fulton is not responsible for any
injury or damage caused by the use of
inadequate uid.
4 CAUTION
The weight of all piping must be
properly supported. Failure to support
piping may result in equipment
damage and/or system leakage.
Piping must take into consideration
potential for freezing interference and/
or damage as a result of expansion,
contraction, vibration, or other
movements.
Dirt, water, and/or other debris in the
piping system after welding may result
in equipment failure.
Questions? Call (315)298-5121, or visit us online at www.fulton.com
2-13
INSTALLATIONHPN-IOM-2014-0416 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
TABLE 5 RECOMMENDED LOADS FOR FLEXITALLIC SPIRAL WOUND CLASS 300# GASKETS
SAE GRADE 5 BOLTS OR EQUAL
Nominal Flange
Size (in.)
1/241/245
3/445/890
145/890
1 1/44 5/890
1 1/2 4 3/4150
2 8 5/890
2 1/283/4150
3 83/4150
3 1/283/4150
483/4150
583/4150
6123/4150
8127/8240
10161368
Number of BoltsDiameter of Bolts
(in.)
Preferred Torque
Req. Per Bolt (ft-lb)
TABLE 6 RECOMMENDED LOADS FOR JM CLIPPER ELASTOGRAPH 150# GASKETS SAE
TABLE 7 RECOMMENDED LOADS FOR JM CLIPPER ELASTOGRAPH 300# GASKETS SAE
GRADE 5 BOLTS OR EQUAL
Nominal Flange
Size (in.)
1/241/230
3/445/860
145/860
1 1/44 5/860
1 1/2 4 3/4100
2 8 5/860
2 1/283/4100
3 83/4100
483/4100
583/4100
6123/4160
8127/8245
10161160
Number of BoltsDiameter of Bolts
(in.)
Preferred Torque
Req. Per Bolt (ft-lb)
Insulation
After the appropriate system tests have been satisfactorily completed (see
Testing section of this manual), all hot pipework and vessels must be adequately
insulated with material suited to the temperature and application to prevent
both heat loss and personnel injury.
Adhere to the following for insulation installation:
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
To maintain a reasonable
temperature in the equipment area
and ensure safety to personnel, the
section of the chimney duct within
the building should be insulated.
Due to extremely high operating
temperatures of the thermal uid,
all exposed pipework should be
insulated, and exposed hot anges,
pump, valve, and ttings should be
shielded. Refer to Insulation section of
this manual for details.
1. For inspection and maintenance purposes, leave pumps, anges, valves
and ttings uninsulated but suitably shielded for safety.
2. Insulate the deaerator section of the combination tank.
3. Do not insulate the thermal bu er and expansion sections of the
combination tank. On units operated with inert gas blankets above the
uid in the expansion tank, the entire combination tank, including the
expansion and thermal bu er sections, may be insulated but it is not
necessary.
4. Ensure hot oil pipe insulation is a minimum of 2” (51 mm) thick,
high temperature, laminated, foamglass cellular glass insulation as
manufactured by Pittsburgh Corning Corporation or equal.
System Interfaces
Proper selection and installation of the components in the hot oil system will
ensure proper and safe operation of the heater.
Questions? Call (315)298-5121, or visit us online at www.fulton.com
2-15
INSTALLATIONHPN-IOM-2014-0416 SECTION 2
Heater Connections
Adhere to the following for heater connections:
1. Connect the outlet of the pump directly to the inlet of
the heater via an isolating valve (preferably a throttling
valve) and pump exible connector.
2. Pipe heater outlets directly to the system via an isolating
valve.
3. A safety relief valve may be shipped in the parts box
accompanying the fuel- red heater, and must be installed
in the outlet manifold. On all units, the outlet must be
piped to a safe discharge area. The piping from the outlet
of the safety valve must be piped to a catch tank. The
discharge ow must not be restricted, i.e. no valve should
be installed. The weight of the piping must be properly
supported in order to prevent damage to the safety valve.
If the valve body becomes warped, leakage may result.
Thermal Fluid Circulating Pump
Installing the pump in accordance with the manufacturer’s
speci cations and these instructions will prolong the life
of the pump and contribute signi cantly to the successful
operation of your Fulton heater system. The pump
manufacturer’s installation and operation instructions can be
obtained from the manufacturer.
Adhere to the following for pump installation:
1. Locate pump adjacent to the heater. Its base must be
rm, level (preferably concrete), and free from vibration.
2. Route pump per the manufacturer’s requirements. It
should be equipped with exible connections at the
suction and discharge sides. The primary function of
these connections are to prevent stresses due to pipe
expansion from being placed on the pump and to
isolate pump vibrations from the pipe work and the
heater. They also allow for expansion and de ection of
the pipe work. These connections should be rated for
high temperature since they are considered part of the
piping system.
3. Connect suction pipe work directly to the deaerator
section via a vertical run with as few elbows as possible.
It should contain the strainer and an isolating valve.
The discharge pipe work must be connected directly to
the heater inlet, and should contain an isolating valve.
See that pipe work connections match up accurately
with pump anges. Refer to the pump manufacturer’s
recommendations for the speci c pump inlet piping
requirements. Typically these requirements are that:
It be a straight run of pipe.
The straight run from the pump inlet to the rst
tting, valve, or ex connector be a minimum of 6-10
pipe diameters in length.
The pipe used should be the same size as the inlet of
the pump.
The piping in the immediate vicinity of the pump
must not be supported by the pump. The pump is
not designed to bear the weight of the piping, and
weight on any part of the pump will throw it out of
alignment.
and seal life expectancy. The pump is properly aligned
before it leaves the factory. Because the system
expands in operation, pump must be realigned when
the system is at operating temperature.
The coupling alignment of the pump and driver must
be carefully checked for angular and axial alignment.
Check pump manufacturers instructions for these
speci cations. The use of a dial indicator to check the
axial and angular alignment is recommended.
An air cooled pump does not have an oiler. This type
of pump has a sleeve bearing which is, like the seals,
lubricated by thermal uid. An air cooled pump
has a grease nipple located at the drive end of the
pump near the coupling connection. This comes
pre-greased, and should be greased at intervals as
recommended by the manufacturer.
An oiler is shipped with each water cooled pump and
it should be lled with a lubricating oil recommended
by the manufacturer. The suggested lubricant is
usually SAE-30 non-detergent oil.
Thermal uid is not su cient lubrication for bearings.
All seals on air cooled pumps are lubricated by
thermal uid, therefore the pump must never be run
dry, i.e., without thermal uid in it.
Filling a pump equipped with either a Grafoil packed
or mechanical seal with thermal uid will ensure
lubrication. However, in order to be certain that all
seals on an air cooled pump are coated with thermal
uid, the pump must be bled.
Grafoil packings require a run-in procedure. Typically,
Pipe Support Must Be
Provided (Not To Be
Welded On Both Ends)
6 - 10 Pipe Diameters
FIGURE 4 TYPICAL PUMP PIPING
From Outlet of Deaerator
ve rings installed and several rings loose. These
extra rings must be on hand for the initial run-in
procedure. See manufacturer’s instruction manual
for this procedure.
1
5
3
First
Fitting
7
2
FIGURE 5 BOLTING SEQUENCE FOR 4 AND 8 BOLT FLANGES
8
6
2. Check local codes regarding disposal of hot water.
Combination Deaerator/Thermal Buff er/
Expansion Tank
4
Requirements for Air Cooled Pumps
Adhere to the following for air cooled pumps (See Figure
6):
1. Allow for free air ow around the entire pump casing
at all times.
2. Maximum room temperature should be 100°F (38°C).
3. In no case should any part of the drive side of the
pump be insulated.
4. Maximum operating temperature for air cooled
pumps varies by manufacturer. Consult instruction
manual to verify.
Requirements for Water Cooled Pumps
Adhere to the following for water cooled pumps (See
Figure 7):
1. Requirements for water cooled pumps will vary with
manufacturer. Consult manufacturer’s instructions
for ow rate and temperature requirements.
Fulton’s e cient design combines the operation of the
expansion, deaerator, and thermal bu er tanks. Installation is
considerably simpli ed by virtue of this arrangement.
The expansion section is vital to the thermal uid system.
From ambient to operating temperature, the thermal uid in
the system will typically expand in the range of 25% to 50%,
and a vessel capable of handling this expansion is mandatory.
The customer should con rm the expansion rate of the
chosen uid and system volume.
At start up, the primary purpose of the deaerator section
is to remove all volatiles from the system to avoid pump
cavitation. The deaerator section also allows air to be vented
from the system on a continuous basis during operation
to avoid oxidation of the thermal uid, and removes other
volatile particles generated by the uid itself during system
operation. This section of the tank must be insulated.
A system of interconnecting pipe work in the thermal bu er
tank section prevents the movement of any oil that has not
cooled su ciently into the expansion section. This avoids
contact of very high thermal uid temperature with oxygen
contained in the atmosphere, which causes uid breakdown.
DO NOT insulate this section.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-17
INSTALLATIONHPN-IOM-2014-0416 SECTION 2
Sizing The Expansion Tank For The System
Expansion tank capacity is the total volume of the tank
(see Figures 8 and 9). It is necessary to have some air space
available at the top of the tank to avoid spillage or over ow.
At initial ll (for system volume calculations) the deaerator
and cold seal sections must be lled completely and the
expansion section must be lled to a level of 4 inches (102
mm) to “make” the liquid level switch.
The volume between the initial ll level and the safe “full” level
is the amount available for expansion. That volume is used to
decide which tank is suitable for the system expansion.
SIZING EXAMPLE
A system contains 175 gallons, including the heater, but not
the tank. You select the FT-200-L, so you add 25 gallons to 175
for a total of 200 gallons.
You look up the expansion rate for the thermal uid.
(Assuming it is 25%), 200 gal. x 1.25 = 250 gallons, 250-200 =
50 gallon expansion.
may be used at start-up to remove air and water from the
system, and then valved appropriately during operation to
provide expansion capacity for the system.
Pressurized Systems
Nitrogen pressurization may be used if the total system
content is very large, or in a system operating near or above
the vapor pressure of the uid employed, or if the inlet of the
DA tank is not the highest point in the piping system, or at
any time to further protect the uid from oxidation.
In conjunction with this system, adhere to the following:
1. An automatic venting device must be tted to the
system expansion tank. Consult Fulton for further
details.
2. The location for the liquid level switch (Figure 10) is a
2-1/2” NPT connection on the same end of the tank as
the inlet. The liquid level switch is supplied and shipped
with the unit, and must be installed by the customer and
then wired to the control panel.
The FT-200-L has only 46 gallons available for expansion, so
the correct selection is the FT-500-L.
Adhere to the following for installation:
1. Install tank in accordance with Fulton’s speci cations.
2. Unless the system is pressurized, the inlet to the
deaerator section must be higher than or equal to the
highest point in the system to prevent pockets of air
from collecting in system piping.
3. Take into account the head required at the circulation
pump suction inlet to avoid the possibility of pump
cavitation.
4. In systems operating close to maximum uid
temperature, ensure the tank is elevated enough,
possibly well above the highest point in the system, to
prevent pump cavitation by increasing the static head.
An inert pressurizing blanket may be considered as an
alternative. See Pressurized Systems section of this
manual.
5. Provide supports for tank mounting. These should be
suited for supporting the tank by the side rails. The
eyelets tted to the tank are for lifting only.
3. If the tank is located outdoors, nitrogen is required.
Vent Connections
Adhere to the following for vent connections:
1. Make vent connection in a manner that will prevent
penetration of water or foreign bodies into the tank.
This connection must always terminate in a safe, well
ventilated area and has to be free of obstruction, open
to atmosphere, and arranged in such a manner that,
in the event of discharge from the system, thermal
uid could drain into a catch tank without danger to
personnel or property.
2. Make the vent run the same size as the tank outlet. It
should run pitch down from the outlet of the tank to
the catch tank.
3. If nitrogen is used on the system, the vent can be
reduced to 2” (51 mm) and should be piped with a
positive closing valve at the catch tank.
4. Ensure the connection between the tank outlet and the
horizontal pump inlet is as close to a vertical drop as
possible. It should have the minimum bends and length
of pipe.
Two-Pipe Expansion Tank
An alternate con guration is the 2-pipe expansion tank. This
2-18
5. Ensure the inlet to the deaerator is higher than or equal
to the highest point in the system, or a pressurized
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
FIGURE 7 TYPICAL WATER COOLED PUMP
system must be used.
6. Field-install the liquid level switch (supplied and shipped with the unit).
This must be wired to the control panel.
7. Ensure test connections are accurate. The high and low level test
connections are 1/2” NPT, and are located on the end of the tank opposite
the inlet. The low level is on the center line of the expansion tank, the high
level is next to it, slightly o center. The high level rises up from the bottom
of the tank and ends 4” (102 mm) below the top; the low level rises 2” (51
mm) from the bottom of the tank.
8. Both the high and low level connections should be piped to a safe
catchment. Valves should be installed in these lines at the catch tank.
Installation of the valves should be accomplished in such a manner that
any ow will be visible when the valves are open.
9. Flow from the high level test connection indicates a tank that is too full; no
ow from the low level test connection indicates too little uid.
10. There is a 300 #, raised face, anged drain on the bottom of the thermal
bu er section, for the purpose of draining the tank when necessary. This
should be piped with a valve in the line, to a safe catchment. The valve
speci cations outlined above apply to this valve as well.
Questions? Call (315)298-5121, or visit us online at www.fulton.com
2-19
INSTALLATIONHPN-IOM-2014-0416 SECTION 2
11. An inspection opening is located at the highest point
on the tank. Access to this port is recommended but
not required.
12. Refer to the maintenance schedule for
recommendations on draining the bu er tank. For
positioning of all connections on tank, see Figure 9.
Catch Tank
Adhere to the following for the catch tank:
1. Ensure the heater safety relief valve outlet and
connections on the DA tank are piped to a safe catch
tank. The catch tank must be appropriately sized based
on the system volume and con guration.
2. Under normal operating conditions, the catch tank
should be empty. Fluid that is expelled into the tank
should not be reintroduced into the system.
3. Ensure the vent from the catch tank is located and
installed in such a manner as to protect personnel and
property from discharge of steam, water, and thermal
uid. Vent outlet should be positioned in a safe location
outside the heater room.
Drain/Fill Connection
The system is usually lled from the lowest point, with the aid
of a pump. On skid-mounted units, a drain and ll connection
is provided in the inlet piping to the pump. See Figure 11.
Vent for Piping
to Safe Catchment
Expansion
Tank
Expansion
Volume
Liquid
Level
Switch
ModelCapacity (gallons)Initial Fill (gallons)Available for