FULTON FHE-250 Installation, Operation & Maintenance Manual

Page 1
FHE-250 MANUAL 09 2014 ISSUE 2
Fulton Ltd
FHE-250 Gas Fired Condensing Boiler
250 kW
This Manual must be available to the boiler operator at all times.
INSTALLATION, OPERATION & MAINTENANCE
MANUAL
Page 2
FHE-250 MANUAL 09 2014 ISSUE 2
The Pressure System Safety Regulations 2000
Fulton Boilers fall within the scope of the Pressure Systems Examination Scheme. Regular inspections are therefore required by a ‘Competent Person’. The scope of the examination and the actual intervals between examinations is at the discretion of the competent person. It is the responsibility of the user to provide a written scheme of examination for those parts of the system in which a defect may give rise to danger. Instructions in this manual are provided for the safe operation and maintenance of the boiler and do not cover periodic statutory inspections.
For further information contact:-
(a) SAFed SAFETY ASSESSMENT FEDERATION Limited. Nutmeg House, 60 Gainsford Street, Butlers Wharf, London, SE1 2NY.
(b) Health and Safety Executive local ofce.
(c) Your Competent Person.
For your Safety!
The following WARNINGS, CAUTIONS and NOTES appear in various sections of this manual.
WARNINGS must be observed to prevent
serious injury or death to personnel.
CAUTIONS must be observed to prevent damage or destruction of equipment or loss of operating effectiveness.
NOTES: must be observed for essential and effective operating procedures, conditions and as a statement to be highlighted.
It is the responsibility and duty of all personnel involved in the operation and maintenance of this equipment to fully understand the WARNINGS, CAUTIONS and NOTES by which hazards are to be eliminated or reduced.
Personnel must become familiar with all aspects of safety and equipment prior to operation or maintenance of the equipment.
WARNING
Hot Water Boilers are a potential hazard, possibly fatal if not properly
maintained.
CAUTION
It is vitally important that the instructions
given in this manual are strictly adhered to.
Failure to carry out the routine maintenance
checks could result in a drastic reduction in the
life expectancy of the boiler.
CAUTION
Incase of Emergency
This boiler has been designed and constructed to meet all of the essential requirements of the applicable European Directives and subject to proper maintenance should not give occasion to any hazardous conditions.
If such a condition should occur during commissioning or during subsequent operation of this product, what so ever the cause, then the fuel supply to the boiler should be isolated immediately, until such time that the fault
has been investigated by a competent person and rectied.
!
!
!
!
!
Page 3
FHE-250 MANUAL 09 2014 ISSUE 2
LIST OF CONTENTS
INTRODUCTION 1
General 1.1 Technical Data 1.2 Optional Extras 1.3 Safety 1.4
- Safe Handling 1.4.1
- Safe Handling of Substances 1.4.2
INSTALLATION 2
General 2.1 Siting 2.2 Water Circulation System 2.3 Water Piping Installation 2.4 Water Treatment 2.5 Frost Protection 2.6 Preventing Oxygen Contamination 2.7 Eliminating System Air 2.8 Filling the Boiler with Water 2.9 Gas Supply 2.10
- Gas Connection 2.10.1 Sealed System Requirements 2.11 Ventilation 2.12
- Common Air Intake and Exhaust Venting of Multiple Boilers
2.12.1
- Intake Duct Sizing 2.12.2 Exhaust Venting Terminations (Flues) 2.13
- Horizontal Exhaust Vent Termination 2.13.1 Flue Installation 2.14
- Flue System Design 2.14.1
- Flue Gas Conditions 2.14.2 Condensate Drain 2.15 Water and Gas Header Installation (Optional Extra) 2.16 Electrical Supply 2.17 Hydraulic Resistance 2.18 Electrical Connections 2.19
- External Wiring 2.19.1
- Terminal Connections for External Wiring 2.19.2
OPERATION 3
General 3.1 Perform Pre-Start-Up Inspection 3.2 Fill and Purge the System 3.3 Commissioning the Boiler 3.4
- Electrical Installation 3.4.1
- Gas Installation 3.4.2
- Flue Commissioning 3.4.3 Test of Ignition Safety System 3.5 Perform Test of Low Gas Pressure Switch 3.6 Test of Condensate Pressure Switch 3.7 Normal Operation of the Boiler 3.8
- Boiler Test Fire 3.8.1
- Disabling the Boiler 3.8.2
- Changing the Temperature Setpoint for DHW 3.8.3
- Changing the Temperature Setpoint for CH 3.8.4
- Finding the Master Boiler 3.8.5
- Boiler Operation 3.8.6
- Auto Detection 3.8.7 Shutdown Procedures 3.9
- Normal Shut off Procedures 3.9.1
- Emergency Shut off Procedures 3.9.2
- Shutting the Boiler Down for an Extended Period of Time
3.9.3
- Starting the Boiler after Prolonged Shutdown 3.9.4 Display Operation 3.10 Symbols on the LCD 3.11 Push-buttons 3.12 Backlight 3.13 User Interface Operating Modes 3.14
- Initial Mode 3.14.1
- Standby Mode on Master DSP 3.14.2
- Standby Mode on Slave DSP 3.14.3
- Suspend Mode 3.14.4
- CH Setpoint Adjust Mode 3.14.5
- Auto Detection Mode 3.14.6
- Cascade Test Mode 3.14.7
- Local Test Mode 3.14.8
- Local Installer Mode 3.14.9
- History Mode 3.14.10
- Installer+ Mode 3.14.11
MAINTENANCE 4
General 4.1 Safety 4.2 Partial Isolation of Boilers in Cascade Systems 4.3 Servicing Schedule 4.4
- Daily 4.4.1
- Weekly 4.4.2
- Monthly 4.4.3
- Annual 4.4.4 Procedure for Cleaning the Air Inlet Filter 4.5 Examine the Flue System 4.6 Inspect Heating System for Other Problems 4.7 Procedure for Removing/Cleaning the Burner 4.8 Procedure for Cleaning the Heat Exchanger 4.9 Gas Valve Adjustment 4.10 After All Repairs and Maintenance 4.11 Handing Over 4.12 Error Codes and Troubleshooting 4.13 Maintenance Log 4.14
GENERAL DATA 5
Boiler Dimensions 5.1
Boiler Specication 5.2 Seasonal Efciencies 5.3
Recommended Water Conditions 5.4 Name Plates and Packaging Label 5.5
Electrical Diagrams (Supplied Separately)
Page 4
FHE-250 MANUAL 09 2014 ISSUE 2
LIST OF CONTENTS
WARNING
Do not try to do repairs or any other maintenance work you do not understand. Obtain a Service Manual from Fulton or
call a Fulton Service Engineer.
WARNING
It is the responsibility of the installer to ensure all parts
supplied with the boiler are tted in a correct and safe
manner.
WARNING
Understand the electrical circuit before connecting or
disconnecting an electrical component. A wrong connection
can cause injury and or damage.
WARNING
A defective boiler can injure you or others. Do not operate
a boiler which is defective or has missing parts. Make sure
that all maintenance procedures are completed before using
the boiler.
CAUTION
Obey all laws and local regulations which affect you and
your boiler.
WARNING
Do not change the boiler fuel without consulting the boiler
manufacturer.
WARNING
LIFTING EQUIPMENT
Make sure that lifting equipment complies with all local
regulations and is suitable for the job. You can be injured
if you use faulty lifting equipment. Make sure the lifting
equipment is in good condition.
WARNING
Operating the boiler beyond its design limits can damage
the boiler, it can also be dangerous.
Do not operate the boiler outside its limits.
Do not try to upgrade the boiler performance by unapproved
modications.
WARNING
Non-approved modications can cause injury and damage.
Contact your Fulton dealer before modifying the boiler.
WARNING
Only qualied persons should be allowed to operate and
maintain the boiler and its equipment. Boilers should always
be drained through an approved Blowdown Vessel.
WARNING
The installation of Gas appliances including the ue system
should only be carried out by Gas Safe Registered
Engineers.
CAUTION
HYDRAULIC TEST - RISK OF BRITTLE FRACTURE Hydraulic testing requires specialist equipment and is
normally only required by engineering
surveyors / inspectors. In order to ensure the material / pressure vessel does not suffer from brittle fracture, hydraulic testing should not be
carried out below 7°C.
WARNING
DANGER FROM HOT SURFACES
Hot Water Boilers have high temperature surfaces, that if
touched may cause serious burns. Only competent and
qualied personnel should work on or in the locality of a
steam boiler and ancillary equipment. Always ensure the
working area and oor are clear of potential hazards, work
slowly and methodically.
Do NOT store inammable materials near the boiler.
WARNING
DANGER FROM INCOMPLETE COMBUSTION
The importance of correct burner adjustment to achieve low
emissions, safe, clean and efcient combustion is
paramount. Poor combustion, where unburnt gas forms carbon monoxide is both a health hazard, and the potential risk to the boiler from overheating, caused by re-burning of
the un-burnt gas in the secondary ue passes.
WARNING
The importance of correct boiler water and feedwater
cannot be over emphasised, see the relevant section in this
manual.
CAUTION
LOW FEEDWATER TEMPERATURE
Low feedwater temperature can result in thermal shock to
the boiler pressure vessel. Return the maximum amount of
condensate and if necessary pre-heat the feedwater. If in
doubt consult Fulton Ltd.
CAUTION
WATER SOFTENER and CHEMICAL TREATMENT
The chemicals required to operate the water softeners and
chemical treatment plants CAN BE SUPPLIED by Fulton.
It is the responsibility of the operator to ensure adequate
supplies of chemical are available at all times (including
commissioning).Costly repairs could be required should
the plant operate without chemicals or the wrong dosage of
chemicals.
SAFETY
The instructions provided for the operation and maintenance of the boiler MUST be observed. Failure to do so could result in damage to the boiler and serious personal injury.
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Page 5
FHE-250 MANUAL 09 2014 ISSUE 2
TITLE FIG. NO.
General Arrangement 1
General Arrangement with Panels Removed 2
Typical Gas Train 3
Flue Gas Conditions 4
Boiler Hydraulic Resistance 5
Boiler Communication Cables 6
Electrical Terminals 3-13 Disconnected 7
Jumper 8
Inserted Jumper Between Terminals 19 and 20 9
LCD Glass Layout 10
Push-button Layout 11
Boiler Dimensions 12
Name Plates 13
LIST OF ILLUSTRATIONS
Page 6
FHE-250 MANUAL 09 2014 ISSUE 2
FIG.1 GENERAL ARRANGEMENT
Boiler Control Panel
Adjustable Feet
Page 7
FHE-250 MANUAL 09 2014 ISSUE 2
Page 1
1
The boilers are fully automatically controlled, oor standing and efcient condensing appliances.
The FHE-250 comprises of a single module capable of delivering 250 kW.
Up to 12 FHE-250 modules can be cascaded (for simplicity, only 250-1000 kW models are shown in this manual), being stacked either vertically or horizontally.
The boiler controls built into the appliance include:
Volt free ‘alarm’ contacts
Burner hours run meters
System temperature indication
The boilers can draw combustion air from the room or via ducting from outside.
Each module provides a maximum of 250 kW heat output and will modulate down to 41.66 kW (see the table in Section 5.2 - Boiler Specication, for efciencies at different temperatures). Boilers comprising of more than one module will share the heating load equally among modules, switching modules off individually once the heating load drops below 16.67% of the total boiler
capacity. This way, a decreasing load is continuously matched for optimum efciency. The minimum
output from all models is 41.66 kW, providing a turndown ration of 6:1 for the 250 kW, 12:1 for the
500 kW, 18:1 for the 750 kW and 24:1 for the 1000 kW. Modules will re on the basis of least hours
run under the dictates of lead/lag sequencing from the onboard controller.
Each module includes a ap which only opens when the fan is running. This prevents energy wastage when the boiler module is not ring.
The boilers are capable of high operating efciencies and low emissions (see Section 5) through
the combination of a sophisticated control system with premix burner and a stainless steel heat exchanger.
These boilers are certied to meet the requirements of the EC Gas Appliance Directive, Boiler
Efciency Directive, EMC and Low Voltage Directive.
CAUTION
WATER SOFTENER and CHEMICAL TREATMENT
The chemicals required to operate the water softeners and chemical
treatment equipment CAN BE SUPPLIED by Fulton. It is the responsibility
of the operator to ensure adequate supplies of chemical are available at all times
(including commissioning). Costly repairs could be required should the plant operate
without chemicals or the wrong dosage of chemicals.
!
SECTION 1 - INTRODUCTION
1.1
GENERAL
1.2
TECHNICAL DATA
For a full specication refer to Section 5.2 - Boiler Specication.
Page 8
FHE-250 MANUAL 09 2014 ISSUE 2
Page 2
1
y Air Inlet Ducting Kit
For FHE-500 and above:
y Water and Gas Header Assembly - Packaged y Water and Gas Header Assembly c/w Valves - Packaged y Flue Header Kit
Note: Please contact Fulton Ltd for further details of all optional extras.
1.3
OPTIONAL EXTRAS
1.4
SAFETY
Current Gas Safety (Installation and Use) Regulations or rules in force.
The appliance is suitable for installation in any EU country and should be installed in accordance with
the rules in force.
In the UK, the installation must be carried out by a Gas Safe Registered Engineer or in IE by a competent person. It must be carried out in accordance with the relevant requirements of the:
y Gas Safety (Installation and Use) Regulations
y The appropriate Building Regulations either The Building Regulations, The Building Regulations
(Scotland), Building Regulations (Northern Ireland).
y The Water Fittings Regulations or Water by-laws in Scotland.
y The Current I.E.E. Wiring Regulations.
Where no specic instructions are given, reference should be made to the relevant British Standard
Code of Practice.
In IE, the installation must be carried out by a Competent Person and installed in accordance with the current edition of I.S.820:2000 “Non Domestic Gas Installations”, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
The boilers have been tested by a notied body and conform to EN656 and EN15417 for use with
Natural Gas. Detailed recommendations are contained in the following Standards and Codes of Practice:
BS. 5854 Flue and ue Structures in Buildings.
BS. 6644 Installation of gas red hot water boilers of rated inputs between 70 kW and
1.8 MW (net) (2nd and 3rd family gases).
BS. 6880 Low temperature hot water heating systems of output greater than 45 kW.
Part 1 Fundamental and design considerations. Part 2 Selection of equipment. Part 3 Installation, commissioning and maintenance.
IGE/UP/1 Soundness testing and purging of industrial and commercial gas installations.
IGE/UP/2 Gas installation pipework, boosters and compressors on industrial and
commercial premises.
IGE/UP/10 Installation of gas appliances in industrial and commercial premises.
Page 9
FHE-250 MANUAL 09 2014 ISSUE 2
Page 3
1
The FHE-250 may require 2 or more operatives to move it to its installation site, and when moving
into its installation location. Manoeuvring the boiler will include the use of a pallet truck or forklift and may involve pushing and pulling.
Caution should be exercised during these operations.
Operatives should be physically capable, and knowledgeable in handling techniques, when performing these tasks. The following precautions should be reinforced:
y Be physically capable.
y Use personal protective equipment as appropriate, e.g. gloves, safety footwear.
During all manoeuvres, every attempt should be made to ensure the following:
y Keep back straight.
y Avoid twisting at the waist.
y Avoid upper body/top heavy bending.
y Always grip with the palm of the hand.
y Use designated hand holds.
y Keep load as close to the body as possible.
y Always use assistance if required.
1.4.1
SAFE HANDLING
1.4.2
SAFE HANDLING OF SUBSTANCES
No asbestos, mercury or CFCs are included in any part of the boiler or its manufacture.
Page 10
FHE-250 MANUAL 09 2014 ISSUE 2
Page 4
FIG. 2 GENERAL ARRANGEMENT WITH PANELS REMOVED
Venturi
Fan
Electrical Plate
Heat Exchanger
Return Pipe
Flow Pipe
Gas Valve
Condensate
Pipe
Automatic
Air Vent
Page 11
FHE-250 MANUAL 09 2014 ISSUE 2
Page 5
2
The installation of the FHE-250 Hot Water Boiler should be carried out by competent personnel in
accordance with all relevant safety regulations. It is the responsibility of the installer to ensure that these regulations are complied with.
WARNING
Maintenance on the burner assembly requires that the area directly in front of the boiler must
not be obstructed with pipework or equipment which would interfere with the removal of
the complete burner unit. Care should be taken on installation of the boiler to ensure this area
remains clear of obstructions.
!
WARNING
Do not allow weight to bear on equipment components to prevent damage.
!
SECTION 2 - INSTALLATION
2.1
GENERAL
2.2
SITING
(Reference should be made to Utilisation Procedures as stated in IGE/UP/10 Part 1 Communication 1676, and in particular to Section 5, Location of Appliances).
The boiler house should be sufciently large to allow easy and safe access to all parts of the boiler
for operational and maintenance purposes.
1. The boiler must stand on a oor which must be at, non-combustible, level and of a suitable load bearing capacity to support the weight of the boiler (when lled with water) and any ancillary equipment.
2. The boiler must not be tted outside.
3. Install so that all system components are protected from water (dripping, spraying, rain etc) during boiler operation and service.
4. Minimum clearance for access should be maintained at 600 mm at the front and at least one side of the boiler/modular installation.
5. Ensure all labels on the boiler will be fully visible for maintenance and inspection.
Page 12
FHE-250 MANUAL 09 2014 ISSUE 2
Page 6
2
A circulation pump MUST be connected to the boiler.
The boiler may be used for indirect hot water supply: wherever it is used for this type of system, an
additional heat exchanger must be provided to ensure hydraulic separation between primary and secondary circuits.
Each boiler installation should incorporate a safety valve to ensure maximum pressure is not exceeded.
The appliances are NOT suitable for gravity central heating nor gravity domestic hot water as system
pressure must be a minimum of 1 bar.
The boiler MUST be vented, there is an internal automatic air vent included for this purpose.
Draining taps MUST be located in accessible positions, which allow the draining of the whole system - including the boiler and hot water storage vessel. They should be at least 1/2” BSP nominal size and be in accordance with BS. 2879.
The central heating system should comply with the relevant standards on page 2.
Due to the compact nature of the boiler, the heat stored within the heat exchanger at the point of shutdown of the burner must be dissipated into the water circuit in order to avoid overheating. To allow pump operation after burner shutdown, the boiler control incorporates a pump overrun facility. In order to make use of this, a pump must be controlled via the terminals inside the boiler.
When sizing pumps, reference should be made to hydraulic resistances given in Section 2.18, which
shows the boiler resistance against ow rates, to achieve the required temperature differential.
Flow rate using a 20°C temperature differential is 3.0 l/s (10.7 m³/hr) for each FHE-250 boiler/module.
The boilers MUST be installed in a closed loop system, it is the installers responsibility to ensure
adequate sized pressurisation units and expansion vessels are included for the system.
Note: With the boiler ring at maximum rate, the temperature differential should not be less than 20°C.
With the boiler ring at minimum rate, the temperature differential should not be greater than 35°C. Lower ow rates generating higher temperature differentials will lead to poor system performance.
The lower the return temperature to the boiler, the higher the efciency. At return temperatures of 55°C and below,
the difference becomes marked because the water in the ue gases starts to condense, releasing its latent heat.
System designs should ensure the boiler minimum ow rates, as detailed in Section 5.2 - Boiler Specication, are always maintained.
WARNING
If the water supply must be disconnected, the boilers must be turned off to prevent
accidental ue gas emission into the boiler room.
!
2.3
WATER CIRCULATION SYSTEM
Page 13
FHE-250 MANUAL 09 2014 ISSUE 2
Page 7
2
All water supplies contain some solids, dissolved gases or dissolved minerals. These may encourage
corrosion, deposition and/or fouling of equipment. To prevent these contaminants from impacting boiler performance, valve operation and general pipe longevity, each location must be analysed and treated accordingly.
Adhere to the following for water piping installation.
1. The boiler requires a minimum temperature differential across the heat exchanger at high re, and has a minimum ow requirement.
2. Ensure piping arrangements allow for heat-up times at or below 30 seconds; this will reduce condensation which may contribute to equipment failure.
3. Pipe unions and isolation valves are recommended on both water connections for ease of service.
4. Install piping so that the boiler is not supporting any additional piping.
5. The top water connection on the back of the boiler is the hot water inlet and must be connected as the return from the system. The bottom connection is the ow/boiler outlet.
6. Install a hot water circulator, remote mounted from the boiler. Do not attach directly to the boiler.
7. If the boilers are connected to heating coils, located in air handling units where they may be
exposed to refrigerated air circulation, such boiler piping system shall be equipped with ow
control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
8. The boiler is not provided with a drain valve directly on the boiler. A drain valve should be installed near the system return (water inlet) connection to the boiler and piped to a drain.
9. Before installing a FHE-250 boiler into a hydronic loop, be sure that the system piping and any other components of the system are clean and free of debris and any foreign matter. The
hydronic system should be completely ushed prior to installing the boiler itself. Install a strainer
upstream of each boiler to ensure that no foreign matter will have the opportunity to get inside the heat exchanger.
WARNING
The boiler must be disconnected at the boiler shut off valve from the
gas supply piping system during any pressure testing of the system.
!
CAUTION
Small levels of chlorides and/or sulphur presence in the combustion air or fuel will negatively impact
the heat exchanger components. Any presence of these contaminants will void the warranty.
!
CAUTION
Some soaps used for leak testing are corrosive to certain types of metals. Rinse all piping thoroughly
with clean water after leak check has been completed.
!
2.4
WATER PIPING INSTALLATION
Page 14
FHE-250 MANUAL 09 2014 ISSUE 2
Page 8
2
These boilers incorporate a STAINLESS STEEL heat exchanger. For water conditions, please refer
to Section 5.4 - Recommended Water Conditions.
CAUTION
Heat exchanger failure due to inappropriate water quality, foreign matter or debris damage is not
covered under the warranty.
CAUTION
If the piping system attached to this unit will be chemically cleaned, the boiler must
be disconnected from the system and a bypass installed so that the chemical cleaning
solution does not circulate through the boiler.
CAUTION
The hydronic system should never be ushed while the boiler is attached to the system
since the debris could accumulate in the boiler and block water from passing through the heat
exchanger. This will lead to premature boiler failure.
!
!
!
Frost protection mode will be initialised when the boiler temperature sensor readings drop to 5°C.
The boilers will re until the water temperature reaches 15°C. Upon reaching 15°C the pumps will
continue to run for the pre-set duration of their overrun (specied by parameter “P 07” in Installer+
mode).
!
WARNING
The application of any other treatment to this product other than those recommended by Fulton Ltd
may render the guarantee of Fulton Ltd invalid.
!
CAUTION
Care needs to be taken to eliminate oxygen from the water system as excess oxygen in the system will
reduce the life of any boiler. The boiler warranty does not cover heat exchanger replacement due to
oxygen contamination of boiler water.
2.5
WATER TREATMENT
1. It is most important that the correct concentration of the water treatment products is maintained in accordance with the manufacturers’ instructions.
2. If the boiler is installed in an existing system any unsuitable additives MUST be removed by thorough cleansing.
3. In hard water areas, treatment to prevent limescale may be necessary.
4. Under no circumstances should the boiler be red before the system has been thoroughly
ushed.
2.6
FROST PROTECTION
2.7
PREVENTING OXYGEN CONTAMINATION
1. There are several ways to prevent boiler water oxygen contamination:
2. Minimise system leaks to minimise make up water requirement
3. Do not use open tanks or ttings
4. Do not use oxygen permeable materials anywhere in the water system
5. Repair leaks in the system quickly
6. Eliminate ttings wherever possible
Page 15
FHE-250 MANUAL 09 2014 ISSUE 2
Page 9
2
There is a factory-installed AAV (automatic air vent) on the heat exchanger. The AAV must not be altered or removed.
The local gas supplier should be consulted at the installation planning stage in order to establish
the availability of an adequate supply of gas. An existing service pipe must NOT be used without prior consultation with the local gas supplier.
A gas meter can only be connected by the local gas supplier, in UK by a Gas Safe Registered
Engineer or in IE by a competent person.
An existing meter should be checked, preferably by the gas supplier, to ensure that the meter is
adequate to deal with the dynamic rate of gas supply required. A minimum working gas pressure of
6.5 mbar MUST be available at the boiler inlet for Natural Gas.
Do not use pipes of a smaller size than the boiler inlet gas connection.
The complete installation MUST be tested for gas soundness and purged in accordance with the
appropriate standards.
Gas Boosters
A gas booster is required if the gas pressure available at the boiler is lower than 6.5 mbar. Boosted
gas supplies should not exceed 20 mbar. Location of the booster requires careful consideration but should preferably be closer to the burner rather than the gas meter. Ventilation should also be considered to ensure ambient temperatures do not exceed designed recommendations. Further guidance is provided in IGEM/UP/2 (Institution of Gas Engineers and Managers-Installation pipework on industrial and commercial premises. Communication number 1729).
2.8
ELIMINATING SYSTEM AIR
2.9
FILLING THE BOILER WITH WATER
2.10
GAS SUPPLY
Adhere to the following:
1. Once the boilers have been installed and connected to the distribution system, open the isolating valves on each boiler, the AAV’s (automatic air vents) will vent any excess air in the system.
2. Visually inspect all pipe joints and equipment connections for leaks. If necessary, drain system,
repair leaks and rell/purge the system. If no pressure drop is detected for a period of two hours
under pressure, the system may be considered watertight.
3. When purging is completed, make sure the following are open: combination shut-off/purge valve,
shutoff valve to pressure reducing (ll valve), shutoff valve in cold water ll line, and shutoff
valve in return line.
4. Make sure the following are closed: all drain cocks, the vent on the combination shutoff purge valve, and all manual vents.
5. Open fuel shut-off valve, allowing fuel to ow to boiler.
Page 16
FHE-250 MANUAL 09 2014 ISSUE 2
Page 10
2
WARNING
Do not use any source of ignition to check for gas leaks
!
CAUTION
Some soap used for leak testing is corrosive to certain types of metals.
Clean all piping thoroughly after completing the leak check.
!
CAUTION
Never leave an opened manual air vent unattended.
In the event that an opened vent is left unattended, water damage could occur.
!
CAUTION
The presence of chlorides and/or sulphur in the combustion air or fuel
will negatively impact the heat exchanger and void the warranty.
!
The gas supply pipe terminates in a 28 mm copper pipe connection on each 250 model. Common
gas supply pipe sizes for connection to multiple boiler modules are available on request from Fulton.
1. A minimum working gas pressure of 6.5 mbar must be available at the boiler inlet with the
boiler ring.
2. Fit a gas supply pipe at an appropriate size in order to limit the pressure drop between the meter outlet and connection to the boiler(s) to 1 mbar (100 Pa) max.
3. All gas supply pipework must be independently supported.
4. The boiler and all gas piping connections must be pressure-tested and checked for leaks before being placed into service. Test with compressed air or inert gas if possible.
5. The boiler must be disconnected at the boiler manual shutoff valve (located near the end of the supplied gas train at the front of the boiler) from the gas supply piping system during any pressure testing of the system at pressures in excess of 35 mbar (3.5 Pa).
6. Gas piping must be installed in accordance with all relevant gas codes and any other local codes which may apply.
7. The pipe and the ttings used must be new and free of dirt or other deposits.
8. After gas piping is completed and before wiring installation is started, carefully check all
piping connections, (factory and eld), for gas leaks. Use a soap and water solution.
2.10.1
GAS CONNECTION
Page 17
FHE-250 MANUAL 09 2014 ISSUE 2
Page 11
2
FIG. 3 TYPICAL GAS TRAIN
Modulating Gas Valve
Inlet to Modulating Gas Valve
Isolating Valve
Page 18
FHE-250 MANUAL 09 2014 ISSUE 2
Page 12
2
Working pressure 6 bar maximum, 1 bar minimum.
Particular reference should be made to BS. 6644, Guidance note BG01 “Guidance on safe operation of boilers” and “INDG436 “Safe management of industrial steam and hot water boilers”, published by the Health and Safety Executive.
The information and guidance given below is not intended to override any requirements of either of
the above publications or the requirements of the local authority, gas or water undertakings.
In general commercial closed pressurised systems are provided with either manual or automatic water make up.
In both instances it will be necessary to t automatic controls intended to protect the boiler, circulating system and ancillary equipment by shutting down the boiler plant if a potentially hazardous situation should arise.
Examples of such situations are low water level and operating pressure or excessive pressure within the system. Depending on circumstances, controls will need to be either manual or automatic reset. In the event of a shutdown both visual and audible alarms may be necessary.
Expansion vessels used must comply with EN 13831 and must be sized on the basis of the total system volume and initial charge pressure.
Initial minimum charge pressure should not be less than 1.0 bar (100 kPa) and must take account of
the static head and specication of the pressurising equipment.
When make up water is not provided automatically it will be necessary to t controls which shut down
the plant in the event of the maximum system pressure approaching to within 0.35 bar (35 kPa) of the safety valve setting. Other British Standards applicable to commercial sealed systems are: BS. 6880: Part 2 BS. 1212 BS. 6281: Part 1 BS. 6282: Part 1 BS. 6283: Part 4
2.11
SEALED SYSTEM REQUIREMENTS
Page 19
FHE-250 MANUAL 09 2014 ISSUE 2
Page 13
2
Adequate fresh, clean air is necessary for safe and efcient combustion, and should be provided at
high and low level in accordance with BS 6644 1991 and IGE/UP/10 Part 1 Communication 1676.
Note:
a) Ensure there is adequate ventilation in the boiler room. Lack of ventilation will create a high temperature and
cause control lockout.
b) Where mechanical ventilation is provided for plantrooms, ensure positive pressurisation of the space is
always maintained - hazardous interlock with the boiler may be required for this purpose.
c) Do not store chemicals such as perclorethylene in the boiler house, the fumes may damage the boiler and
ue and cause the burner to lock out on ame failure. The ventilation requirements of these boilers are dependant on the type of ue system used, and their heat input. All vents must be permanent with no means
of closing, and positioned to avoid accidental
obstructions by blocking or ooding.
Detail reference should be made to BS. 6644 for inputs between 70 kW and 1.8 MW (net).
In IE refer to the current edition of I.S.820:2000. The following notes are for general guidance only:
Dust contamination in the combustion air may cause blockage of the burner slots. Unless the boiler room provides a dust free environment then direct connection of the air intake via ducting to clean outside air should be used.
IMPORTANT NOTE: If combustion air is drawn from within the boiler room, ensure no dust or airborne debris can be ingested into the appliance. Dusty concrete ooring should be sealed to reduce the presence of dust.
The temperature within a boiler room shall not exceed 25°C within 100 mm of the oor, 32°C at mid
height and 40°C within 100 mm of the ceiling.
Open Flued Installations
If ventilation is to be provided by means of permanent high and low vents communicating direct with outside air, then reference can be made to the sizes below. For other ventilation options refer to BS.
6644. In IE refer to the current edition of I.S.820.
Required area (cm2) per kW of total rated input (net)
Note: Where a boiler installation is to operate in summer months (e.g. DHW), additional ventilation requirements
are stated within BS6644 if operating for more than 50% of the time.
Boiler Room Enclosure
Low Level (Inlet) 4 10
High Level (Outlet) 2 5
2.12
VENTILATION
Required area (cm2)
Boiler Room
FHE-250 FHE-500 FHE-750 FHE-1000
Low Level (Inlet) 1020.4 2040.8 3061.2 4081.6
High Level (Outlet) 510.2 1020.4 1530.6 2040.8
Enclosure
FHE-250 FHE-500 FHE-750 FHE-1000
Low Level (Inlet) 2551 5102 7653 10204
High Level (Outlet) 1275.5 2551 3826.5 5102
Page 20
FHE-250 MANUAL 09 2014 ISSUE 2
Page 14
2
Combining multiple FHE-250 boilers into a common ue or duct for combustion air supply,
exhaust, or both is only permitted on a case by case basis and must be accomplished with an engineered solution. Please contact Fulton for details/designs.
Adhere to the following:
1. There is an integral combustion air supply damper within the unit, complete with a magnetic
switch that is fully integrated into the standard boiler controls, to prevent ue gases from entering the plantroom.
2. FHE-250 boilers should not be common vented with other types of equipment.
WARNING
Fulton cannot assume responsibility for an air intake or exhaust
arrangement where FHE-250 boilers are common vented with any other type of equipment.
!
1. Air intake ducting must be sized in conjunction with the exhaust venting to provide no greater
than a 2 mbar (200 Pa) combined pressure drop. Refer to Section 2.14.1 - Flue System Design for further details and guidance on this issue.
2. Each FHE-250 module with internal intake ducting incorporates a coarse air lter. The installation of a recognised termination screen is required on all combined air intakes for multiple boiler modules.
3. Air intake ducts and ttings shall be galvanised steel or Schedule 30 PVC pipe.
Note: where these boilers are to be room-sealed,the internal air inlet ductwork and ttings and external connector
for ducted connections are all in galvanised steel.
4. If using PVC, all intake PVC piping must be assembled using suitable cement. This will ensure that the intake is airtight and will not allow contaminants from the boiler room into the
boiler.
5. Air intake terminations must be suitably weatherproofed to prevent ingress of moisture into the system.
2.12.1
COMMON AIR INTAKE AND EXHAUST VENTING OF MULTIPLE BOILERS
2.12.2
INTAKE DUCT SIZING
Page 21
FHE-250 MANUAL 09 2014 ISSUE 2
Page 15
2
Adhere to the following for installation:
1. All vents and ttings must be installed with a minimum of 100 mm air space clearances to
combustibles. These air space clearances apply to indoor or outdoor vents-whether they are
open, enclosed, horizontal or vertical or pass through oors, walls, roofs or framed spaces. The air space clearances should be observed to joists, studs, suboors, plywood, drywall or plaster
enclosures, insulating sheathing, rafters, roong, and any other material classed as combustible.
2. The required minimum air space clearances also apply to electrical wires and any kind of building insulation.
3. Adequate provision must be made to support the weight of the exhaust venting. It cannot be supported by the boiler exhaust connection.
4. Terminations must be adequately weatherproofed.
WARNING
Assure all electrical connections are powered down prior to attempting replacement or service of
electrical components or connections of the boiler.
!
2.13
EXHAUST VENTING TERMINATIONS (FLUES)
Page 22
FHE-250 MANUAL 09 2014 ISSUE 2
Page 16
2
IMPORTANT NOTE: Wherever horizontal runs of exhaust vents are installed, a minimum slope of 1:50 must be maintained, falling back toward the boiler(s).
Adhere to the following for installation:
1. Where the vent termination is joined to the vent pipe outside the wall. Use the same joining
procedures for vent pipe and ttings. The termination of the vent system must be at least 305 mm above the nished grade, or at least 305 mm above normal snow accumulation
level (for applicable geographical areas). The termination of the vent system should not be
located in trafc areas such as walkways, adjacent buildings, openable windows and building openings unless the venting system is at least 21.3 m above nished grade. The vent
terminations must be at least 1.22 m horizontally from electric meters, gas meters, regulators, and relief equipment.
2. When installing inlet and exhaust terminations on the same wall, the exhaust outlet must be
installed 0.914 m minimum above and downwind from air supply inlet to prevent exhaust
recirculation. Under certain wind conditions, some building materials may be affected by ue
products expelled in close proximity to unprotected surfaces. Sealing or shielding of the exposed surfaces with a corrosion resistant material may be required to prevent staining or deterioration.
3. The minimum vent height should extend to at least 0.914 m above the roof, or at least
0.609 m above the highest part of any structure within 3.04 m of the vent.
4. If the exhaust vent terminates within 3.04 m horizontally of the air inlet, the exhaust vent
must be at least 1.22 m above the inlet. Dimensions listed above and those illustrated are minimum, and may or may not be sufcient for conditions at a specic job site.
5. To prevent the possible re-circulation of ue gases,the vent designer must take into
consideration factors such as prevailing winds, eddy zones, building congurations, etc. Fulton cannot be responsible for the effects such adverse conditions may have on the operation of the boilers. It is important to locate the exhaust duct in such a way that it does not become blocked due to snow, ice, and other natural or man-made obstructions.
2.13.1
HORIZONTAL EXHAUST VENT TERMINATION
Page 23
FHE-250 MANUAL 09 2014 ISSUE 2
Page 17
2
IMPORTANT NOTE: It is the responsibility of the installer to ensure, in practice, that products of combustion discharging from the terminal cannot re-enter the building or any other adjacent building through ventilators, windows, doors, other sources of natural air inltration, or forced ventilation / air conditioning.
If this should occur the appliance MUST be isolated from the gas supply and labelled as ‘unsafe’ until corrective
action can be taken.
Terminal Position
Due to the high efciency of the boilers pluming will occur.
Particular care should be taken in the case of large output boiler installations, and ensuring that in the UK they comply with the requirements of the Clean Air Act.
The ue must be installed in accordance with the appropriate Building Regulations and standards
listed on page 4 and in compliance with BS6644. In IE refer to I.S.820:2000.
2.14
FLUE INSTALLATION
2.14.1
FLUE SYSTEM DESIGN
Due to the high efciency of these boilers, the ue gas temperatures are low and the buoyancy in
the stack will be relatively small. The boiler is supplied with an integral fan which is fully matched
to the boiler in each case to provide correct combustion air ow and overcome the ue resistance.
The power of this fan is such that there is a large reserve of pressure available to overcome a
signicant length of ue without affecting the combustion performance of the boiler.
The maximum pressure available at the base of the ue to overcome ue resistance is 2.5 mbar (250 Pa.) This gure should be reduced to 2 mbar (200 Pa) if the boiler is to be room sealed and incorporates a combustion air inlet duct. Care should be taken with tall ue systems to ensure excess buoyancy is not created. A negative pressure must not be created at the boiler ue outlet.
Refer to the tabulated data at the end of this section for ue and duct pressure losses.
IMPORTANT NOTE: If combustion air is drawn from within the boiler room, ensure no dust or airborne debris can be ingested into the appliance. Dusty concrete ooring should be sealed to reduce the presence of dust. Ideally where possible duct the air supply into the boiler room from a clean source outside the boiler room / building.
Material
With no requirement for buoyancy to discharge ue products and with low ue gas temperatures, single wall ues are suitable for most installations. Care should still be taken to maintain
compliance with building regulations and relevant standards.
The ue used should be a suitably approved ue for use on a pressurised condensing ue system. The boiler is not suitable for use on plastic ue systems.
Condensate produced in the ue should be drained separately.
Advice regarding the availability of proprietary types of ue system can be obtained by contacting
Fulton.
All joints or connections in the ue system must be impervious to condensate leakage. Low points in the ue system should be drained using pipe of material resistant to condensate corrosion.
All drains in the ue should incorporate a water trap.
Page 24
FHE-250 MANUAL 09 2014 ISSUE 2
Page 18
2
Note: Long Flues: It is recommended that a support bracket is tted at least every 1 m of ue length and a bracket must be tted at every ue joint to ensure ue seal and alignment of ue.
WARNING
Care should also be taken in the selection of ue terminals as these tend to accentuate the formation
of a plume and could freeze in cold weather conditions.
WARNING
Care should be taken to ensure the specication of the chimney is suitable for the application by
reference to the manufacturers literature.
WARNING
Where single walled ues are used on the appliance, surface temperatures of the ue can reach
temperatures in excess of 80°C.
!
!
!
Flue/Exhaust Vent
Item
Size
(mm Ø)
Pressure Drop
(Pa)
1 m of Flue/Vent 150 0.33
45 Degree Bend* 150 1.72
90 Degree Bend* 150 3.44
* All bends on Flue/Exhaust Vent systems should be long radius.
Inlet Duct/Pipe (For room sealed boilers only)
Item
Size
(mmØ)
Pressure Drop
(Pa)
1 m of Duct/Pipe 100 0.35
45 Degree Bend 100 0.19
90 Degree Bend 100 0.49
1 m of Duct/Pipe 80 1.00
45 Degree Bend 80 0.47
90 Degree Bend 80 1.18
2.14.2
FLUE GAS CONDITIONS
Following installation of the ue(s) for the boiler, and set-up/commissioning of the burner, the following should be used as a guide for the ue gas content and temperature.
For further details of the boiler set-up and commissioning, refer to section 3 of this manual.
Flue Gas Constituents
Item %
Carbon Dioxide (CO
2
) 9.5 ± 2.5
Carbon Monoxide (CO) 0.0075 ± 0.0075
Page 25
FHE-250 MANUAL 09 2014 ISSUE 2
Page 19
2
Condensate drains are provided on the boiler. These drains must be connected to a drainage point
on site. All pipework and ttings in the condensate drainage system MUST be made of plastic - no
other materials may be used.
Each module is provided with a condensate trap, the pipe size from the trap outlet is 22 mm. The routing of the drain must be made to allow a minimum fall of 1 in 20 away from the boiler, throughout its length.
Connect a condensate drain to each outlet and pipe to a suitable drain point preferably within the building.
IMPORTANT NOTE: Any external runs must be kept to a minimum and insulated to avoid freezing in cold weather
causing blocking.
2.15
CONDENSATE DRAIN
2.16
WATER AND GAS HEADER INSTALLATION (OPTIONAL EXTRA)
Water and gas header systems can be supplied as fully assembled self supporting units capable of connecting the water and gas services direct to the rear of the module/s. Each header system will be individually tailored to specic site/installation requirements. This is an optional extra, as detailed in Section 1.3, please contact Fulton for further details/designs.
FIG. 4 FLUE GAS CONDITIONS
Page 26
FHE-250 MANUAL 09 2014 ISSUE 2
Page 20
2
Wiring external to the appliance MUST be in accordance with the current I.E.E. (BS7671) Wiring Regulations and any local regulations which apply. For Ireland reference should be made to the current ETCI rules for electrical installations.
The point of isolation from the mains should be readily accessible and adjacent to the boiler.
!
WARNING
This appliance must be earthed.
Pressure Drop (kPa) Flow Rate (L/s)
4.31 0.83
15.67 1.67
30.39 2.43
44.12 3
FIG. 5 BOILER HYDRAULIC RESISTANCE
2.17
ELECTRICAL SUPPLY
2.18
HYDRAULIC RESISTANCE
The hydraulic resistance through each FHE-250 module is 441 mbar (44.12 kPa) at full duty
conditions, with a 20°C temperature differential between inlet (return) and outlet (ow).
Page 27
FHE-250 MANUAL 09 2014 ISSUE 2
Page 21
2
A mains supply of 230 V 50 Hz is required (Live, Neutral and Earth). An additional Earth is required to be
connected to the Master Module chassis Earth Bonding point on the front RHS vertical frame strut.
Where more than one module is to be installed, i.e. FHE-500, 750, 1000 each module chassis must also be bonded together using earth bonding straps.
Wiring external to the boiler MUST be in accordance with the current I.E.E. (BS7671) wiring Regulations and any local regulations. For Ireland reference should be made to the current ETCI rules for electrical installations. Connection should be made in a way that allows complete isolation of the electrical supply- such as a double pole switch, having a 3 mm (1/8”) contact separation in both poles. The means of isolation must be accessible to the user after installation.
When making mains electrical connections to the modules it is important that the wires are prepared in such a way that the earth conductor is longer than the current carrying conductors, such that if the cord anchorage should slip, the current carrying conductors become taut before the earthing conductor.
!
WARNING
This appliance MUST be earthed.
!
WARNING
Sensor cables must be separated from cables in the 230 V circuit.
External wiring MUST be in accordance with the current I.E.E. (BS7671) Wiring Regulations. For Ireland reference should be made to the current ETCI rules for electrical installations.
For wiring external controls to the boiler, reference should be made to the systems wiring diagram supplied by the relevant manufacturer.
Difculty in wiring should not arise, providing the following directions are observed:
All cables should be secured using cable glands in locations through the boiler panels to suit the individual arrangements.
Note: Care should be taken when positioning the holes for the wiring to ensure no clashes with any of the internal
structure of the boiler or the on-board electrical panel. All external devices should be wired to each boiler in the same way.
1. The appliance must be wired with a permanent live supply. External controls should NOT be wired in series with this mains input. Controlling the mains input in this way will prevent the pump over-run sequence and may cause damage to the heat exchanger.
2. Connection of Header Pump: A Cascade/System pump may be connected to the boilers via an external contact or relay with options for single speed pump (volt free contact - On/Off) or variable speed PWM (Pulse Width Modulation) pump. This pump is controlled from the boiler and runs whenever any module is active, also providing pump overrun. This output may also be used to provide pump overrun requirements to a BMS or control panel where multiple pumps or zones are installed. For details of the terminal connections to use for the different pump types, refer to the tables in Section 2.19.2 of this manual.
Note. The circuit protective device, isolation switch and wiring must be sized in accordance with the total load of
both the boiler and module pumps.
2.19
ELECTRICAL CONNECTIONS
2.19.1
EXTERNAL WIRING
Page 28
FHE-250 MANUAL 09 2014 ISSUE 2
Page 22
2
Heat Demand
1. A thermostat (or a volt free contact) can be wired into screw terminals for CH and/or DHW as applicable to the installation.
2. An external controller with OpenTherm communication port can be wired into the boilers. In this case the controller will generate the required setpoint for CH only. This needs to be wired
parallel to all of the boilers. Please nd the supported OpenTherm system messages in the
table below.
Master
Boiler
Slave 1
Boiler
Slave 2
Boiler
Slave 3
Boiler
15
14
17
16
19
18
20
15
14
17
16
19
18
20
15
14
17
16
19
18
20
15
14
17
16
19
18
20
ID Read/Write Description
0 R Status
1 W Control Setpoint
5 R Fault ags/code
2 W Master Conguration (dummy write)
3 R Slave Conguration
4 W Lockout Reset
17 R Relative Modulation Level
25 R CH Water Temperature
For details of the terminal connections to use for the thermostat(s) and OpenTherm controller, refer to the tables in Section 2.19.2 of this manual.
Cascade Temperature Sensor (Header Sensor)
A cascade temperature sensor is provided to monitor the desired set point temperature to
control the boiler outputs. This needs to be placed after the boiler header at an appropriate point in
the system ow pipework.
The sensor needs to be wired in parallel to all of the boilers.
Boiler Status Signals
A normally open volts free contact is provided to indicate a fault of the boiler to remote system
controls. Please refer to the tables in Section 2.19.2 - Terminal Connections for External Wiring.
Boiler Communication Cables
The gure below shows the wire connections between the boilers in a cascade system.
* Link Terminal 19 and 20
FIG. 6 BOILER COMMUNICATION CABLES
Page 29
FHE-250 MANUAL 09 2014 ISSUE 2
Page 23
2
2.19.2
TERMINAL CONNECTIONS FOR EXTERNAL WIRING
HIGH VOLTAGE TERMINALS
TERMINAL DESCRIPTION
1 Live Supply 240 Vac, max. 3.2 A
2 Neutral
3
29
CH pump neutral CH pump live, 240 Vac, max. 0.8 A
4
30
DHW 3 way valve neutral DHW 3 way valve live, 240 Vac, max. 0.8 A
5
31
CH 3 way valve or DHW water pump neutral CH 3 way valve or DHW water pump live, 240 Vac, max. 0.8 A
25 and 26 Common alarm volt free contact, 240 Vac, max 5 A resistive load
27 and 28 Cascade pump On/Off contact, 240 Vac, max 5 A resistive load or 0.5 A inductive
LOW VOLTAGE TERMINALS
TERMINAL DESCRIPTION
6
21
DHW sensor/volt free switch (DHW demand) neutral DHW sensor/volt free switch (DHW demand) live, max. 30 V
7 and 8 Cascade pump PWM outputs (variable speed)
9 and 10 OpenTherm communication port
11 and 23 External temperature sensor, RTD 10 kΩ @ 25 ˚C
12 and 24 Cascade temperature sensor, RTD 12 kΩ @ 25 ˚C
13 22
CH demand neutral CH demand live, max. 30 V
14 and 15 Terminal 14 on the Boiler connects to Terminal 15 on the following Boiler in line
16 and 17 Terminal 16 on the Boiler connects to Terminal 17 on the following Boiler in line
18 and 19 Terminal 18 on the Boiler connects to Terminal 19 on the following Boiler in line
20 Terminal 20 on the boiler needs to be linked to Terminal 19 on the slave boiler*
* Refer to Fig.6, Page 22
Boiler Terminal Plugs
The following terminal plugs need to be disconnected for the boilers to operate correctly:
Master Boiler: None
Slave in between other boilers: Terminals 3 to 13 and Terminal 20
Last Slave Boiler: Terminals 3 to 13 and Terminal 19
Note: Plugs do not need to be fully removed to be electrically disconnected. The terminal plugs have two positions: electrically disconnected and connected.
Fig. 7 shows electrical Terminal plugs 3-13 disconnected, while other terminals are electrically connected. Note that it is possible to remove the plugs, but not necessary for isolation.
Fig. 9 shows a jumper inserted between Terminal 19 and 20.
Page 30
FHE-250 MANUAL 09 2014 ISSUE 2
Page 24
2
FIG. 7 ELECTRICAL TERMINALS 3-13 DISCONNECTED
FIG. 8 JUMPER
FIG. 9 INSERTED JUMPER BETWEEN TERMINALS 19 AND 20
Inserted
jumper
Page 31
FHE-250 MANUAL 09 2014 ISSUE 2
Page 25
3
The following instructions are given for the guidance of the operator in the use of the FHE-250 boiler
and to provide adequate information to ensure that the boiler is used safely and without risk to health. Where original equipment Service Manuals are supplied, they must be read and understood in conjunction with this manual. All warnings and cautions MUST be observed.
WARNING
Use only your hand to turn the valve handle. Never use tools. If the knob will not turn by hand, do not try
to repair it. Call a qualied service technician. Force or attempted repair may result in a re or explosion.
!
WARNING
This boiler is equipped with an ignition device, which automatically lights the burner.
Do not try to light the burner by hand.
!
WARNING
Do not store or use gasoline or other ammable vapours and liquids in
the vicinity of this or any other appliances.
!
WARNING
Do not attempt to start the boiler for any testing before lling and purging the boiler. A dry re will
damage the boiler and may result in property damage or personnel injury, which is not covered by the
warranty.
!
SECTION 3 - OPERATION
3.1
GENERAL
3.2
PERFORM PRE-START-UP INSPECTION
Prior to start-up, perform the following:
1. Smell all around the boiler area for gas. Be sure to smell next to the oor, as some gas is
heavier than air and will settle. If you smell gas:
- Do not try to light any appliance.
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a safe location outside of the property.
2. Ensure the boiler is located with the proper clearances. A minimum of 600 mm should be
allowed for at the front of each FHE-250 unit. Please contact Fulton for clearances required for modular installations.
3. Ensure that relief valves where tted, have been properly piped to oor drains.
4. Ensure ue gas from the boiler is properly vented.
5. Ensure the water system has been ushed and is free of debris.
6. Ensure combustion air openings are not obstructed in any way and have adequate capacity.
7. Ensure there are no ammable liquids, materials or hazardous fumes present in the
environment.
8. Ensure nothing was damaged or knocked loose during installation and/or shipment, including
main gas train and trim assembly.
3.3
FILL AND PURGE THE SYSTEM
Refer to Section 2.9 - Filling the Boiler with Water for procedure. Attempting to start the boiler
prior to Fill and Purge may result in dry re, which can cause injury or property damage, and is not
covered by warranty.
Page 32
FHE-250 MANUAL 09 2014 ISSUE 2
Page 26
3
It is essential that the commissioning procedures listed below are carried out either by a Fulton Service Engineer or by an authorised professional who will have the necessary experience and testing equipment to ensure that the installation is not only correct, but is operating safely and
at optimum efciency.
1. Verify with authorised personnel that the gas lines have been purged. Do not proceed without
verication.
2. Familiarise all personnel on all aspects of boiler use, safety, and contents of this manual. This
includes, but is not limited to, the use of the controls, lighting/ring the boiler, and shutdown
procedures.
3. Review the unit-specic control schematics, and follow appropriate instructions.
WARNING
Before commissioning the boiler, verify with authorised personnel that the gas lines have been purged.
!
WARNING
Commissioning/Start up by a non-Fulton authorised person will void the product warranty.
!
!
WARNING
Whilst effecting the required gas soundness test and purging air from the gas installation, open all
windows and doors, extinguish naked lights and DO NOT SMOKE.
1. The whole of the gas installation, including the meter, should be inspected and tested for soundness and then purged in accordance with the recommendations of the relevant standards listed on Page 2. In IE refer to I.S.820:2000.
3.4
COMMISSIONING THE BOILER
3.4.1
ELECTRICAL INSTALLATION
3.4.2
GAS INSTALLATION
3.4.3
FLUE COMMISSIONING
1. Check to ensure electrical safety should be carried out by a competent person.
2. ALWAYS carry out the preliminary electrical system checks, i.e. earth continuity, polarity,
resistance to earth using a suitable meter.
Prior to initial ring of the boiler, the ue must be checked for leaks.
This is done by BOTH of the following methods:
Visual Inspection
Check joints between all ue sections for quality of seals. Where the ue passes through the structure of the building use your judgement as to the integrity of this section of the ue.
Smoke Test
With the ue capped, the drain stabiliser pipe (if tted) blanked and a smoke generator inserted into the ue, there should be no smoke visible from the ue.
If either of these tests fail or at any time during boiler operation there is doubt about the integrity of
the ue, shut down the boiler and contact Fulton Ltd immediately.
Note: Flues that are designed to operate with positive pressure should be tested to the latest regulations.
Page 33
FHE-250 MANUAL 09 2014 ISSUE 2
Page 27
3
Test the ignition system safety shutoff as follows:
1. Disconnect the boiler from the mains power supply.
2. Remove the grey plug/connector from the main gas valve (it is held on with a central screw).
3. Re-connect the boiler to the mains power supply.
4. With the main gas cock (inlet manual gas valve) open, the burner should be cycled on. After all
the safety limits such as gas pressure and temperature are satised, the blower will run and
pre-purge the boiler.
5. Once the purge is complete (5 seconds), the ignition transformer will be energised. There will be a 4 second trial for ignition period.
6. The main gas valve will not open because there is no power to the valve due to the
disconnected wires. Hence, no ame will be established and the ame safeguard will not
receive a ame signal from the ionisation probe.
7. After 4 seconds, the ame safeguard programmer will assume a “Flame Failure” condition and limits the boiler. Limiter will not require manual reset of the ame safeguard. The control will
allow three retries before limiting.
8. After completing this test, turn off the boiler and reconnect the plug to the main gas valve, ensuring the boiler is disconnected from the mains power supply prior to reconnecting the gas valve plug.
3.5
TEST OF IGNTION SAFETY SYSTEM
3.6
PERFORM TEST OF LOW GAS PRESSURE SWITCH
Test the low gas pressure switch as follows:
1. Turn off the gas cock, then start the boiler until a limiter is annunciated- Error code: E76.
2. Re-open the gas cock, restart the boiler.
H
Fire the boiler and test the condensate pressure switch as follows:
1. Remove the cover plate from the switch. At high re turn the adjustment on the switch counter
clockwise (reducing the switch set-point to below the 9 mbar factory setting) until the boiler shuts down. Error code: E77.
2. Reset the switch to the factory setting of 9 mbar.
3.7
TEST OF CONDENSATE PRESSURE SWITCH
Page 34
FHE-250 MANUAL 09 2014 ISSUE 2
Page 28
3
3.8
NORMAL OPERATION OF THE BOILER
Under normal operating circumstances, this boiler functions as a fully automatic appliance. The
automatic control senses the water outlet temperature and res the boiler when heat is needed by
the system. Additionally this boiler may function as part of an integrated building management
system. Outlet water temperature is shown on the display, on the front of the boiler.
3.8.1
BOILER TEST FIRE
There are two ways of testing the boiler; individually or all together (where there is more than one
boiler module included in an installation) – also called a cascade test. To complete the boiler test re,
proceed as follows:
1. Local Test
a) Switch on the boiler, if there is an error message, resolve the error rst- Refer to
Section 4.13 - Error Codes And Troubleshooting. Once any errors are resolved proceed to the next step.
b) Press and hold the “Test Mode” button for 3 seconds on the boiler to be tested.
c) The display will show “t 0”, this represents approximately 20% of the maximum output.
d) Push the “DHW +” button to instantly bring the boiler up to maximum ring rate. The display
now shows “t 100”, this represents 100% output. Pushing “DHW –” will bring it back to the minimum ring rate.
e) Pushing the “CH +” and “CH –” buttons will adjust the boiler output in increments of 1%.
f) Press and hold the “Test Mode” button for 3 seconds to exit the Local Test mode.
2. Cascade Test
a) Switch on the boiler, if there is an error message, resolve the error rst – Refer to
Section 4.13 - Error Codes And Troubleshooting. Once any errors are resolved proceed to the next step.
b) Press and hold the “Test Mode” and “Conrm” buttons for 3 seconds on the master boiler.
c) Adjust the ring rate as explained in the Local Test procedure above.
d) Press and hold the “Test Mode” and “Conrm” buttons for 3 seconds to exit the Cascade
Test mode.
Page 35
FHE-250 MANUAL 09 2014 ISSUE 2
Page 29
3
There are three ways that the boiler can be disabled without shutting down the whole system:
1. Press the “DHW Mode” button. Safety procedures and frost protection are still active, but the
boiler will not re on DHW demand. To exit, press the “DHW Mode” button again.
2. Press the “CH Mode” and “DHW Mode” buttons together to enter Suspend mode. Only frost protection is active in Suspend mode. To exit Suspend mode, press the “Conrm” button once.
3. If the DHW demand is controlled by a switch, move the switch into the “Off” position to stop the boiler. This will stop the boiler until the switch is turned back to the “On” position.
Note: Frost protection will be active at all times as long as the boilers are not disconnected from the power supply and they are not in error mode. Any boiler that is in error mode will not re until the error condition ceases.
3.8.2
DISABLING THE BOILER
3.8.3
CHANGING THE TEMPERATURE SETPOINT FOR DHW
1. Go into Installer+ mode by pressing the “Conrm” and “DHW Mode” buttons for 3 seconds.
2. Press “CH +” repeatedly, to go to parameter 24 - indicated as “P 24” on the display.
3. Press either the “DHW +” or “DHW –” button until the desired setpoint is reached.
4. Press the “Conrm” button to conrm the change.
5. Press the “Conrm” and “DHW Mode” buttons for 3 seconds.
6. Observe that “Para” is ashing on the display.
3.8.5
FINDING THE MASTER BOILER
The master boiler displays the water temperature if there is no error message. The slave boilers will
display “SLA X” where X is the address of the slave.
If there is an error message then the master boiler will display “XYZZ”, where: X is the address of the boiler, where the error is located Y can be the letter A or E depending on whether it is a lock out error (A), or only a limiting condition
(E)- ZZ is the error code. Refer to Section 4.13 for details of error codes.
A slave boiler will only display “YZZ”, where Y and Z are as described above.
3.8.6
BOILER OPERATION
The boiler will start ring by linking the DHW demand terminals, normally performed by a switch or a
thermostat. For the duration of the heat demand the boiler(s) will modulate to the setpoint
temperature. The boiler stops heating when it reaches the setpoint plus 5°C and starts up again
when the temperature drops below the setpoint.
Pumps will overrun a certain time, as specied by “P 07” in Installer+ mode.
Where there is more than one boiler module in the system, the active sensor will be the cascade
sensor, which is normally placed after the header on the common ow pipe.
In the case of one installed boiler, the temperature sensor can also be the cascade sensor. If there
is no cascade sensor installed, then the boiler will modulate according to the water ow temperature
sensor -this is an integral part of the boiler, factory tted as standard.
3.8.4
CHANGING THE TEMPERATURE SETPOINT FOR CH
1. Press either the “CH +” or “CH –” button until the desired setpoint is reached.
2. Press the “Conrm” button to conrm the change.
Page 36
FHE-250 MANUAL 09 2014 ISSUE 2
Page 30
3
1. Turn off electrical power.
2. Close all manual gas valves.
3.9
SHUTDOWN PROCEDURES
3.9.1
NORMAL SHUT OFF PROCEDURES
3.9.2
EMERGENCY SHUT OFF PROCEDURES
The main gas cock should be closed immediately. If overheating occurs or the gas supply fails to
shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the boiler.
3.9.3
SHUTTING THE BOILER DOWN FOR AN EXTENDED PERIOD OF TIME
Press ‘CH MODE’ and ‘DHW MODE’ on the display together and keep pressed for at least 3 seconds.
The boiler now enters suspend mode. Only frost protection is active. Refer to Section 2.6 for details
of Frost Protection operation.
3.9.4
STARTING THE BOILER AFTER PROLONGED SHUTDOWN
Perform initial start up procedures as described in this manual.
3.8.7
AUTO DETECTION
If error FE97 occurs, it is most likely a mismatch in the cascade system due to a change in the number of boilers or boiler settings. In this case perform an Auto Detection by holding “CH –” button on the display of the master boiler for 3 seconds.
Page 37
FHE-250 MANUAL 09 2014 ISSUE 2
Page 31
3
The user interface is an LCD display with 7 buttons. User interface functions are grouped to UI
operating modes described in Section 3.15.
FIG. 10 LCD GLASS LAYOUT
3.10
DISPLAY OPERATION
3.11
SYMBOLS ON THE LCD
The FHE-250 is equipped with an LCD display capable of showing four full 7-segment digits and a
set of additional icons showing information about the current state and operating mode of the device.
Four 7-segment digits and alternatively partially implemented fth digit are used for displaying
numeric values and some letter indication. Total number of LCD segments is 60. Their description
with details and placement are described on Fig. 10 and Fig. 11.
Page 38
FHE-250 MANUAL 09 2014 ISSUE 2
Page 32
3
Typical usage of segments:
ot OpenTherm master detected
i1 + i2 Installer mode indication
rf1 + rf2 Not used
reset1 Indication of possibility to reset lockout error
reset2 Not used
spn Installer+ mode indication
stb Suspend mode indication
otc Outside temperature sensor is connected
ch Indication of CH service or CH setpoint adjustment when blinking
sun Summer indication
pmp Pump activity indication
m Flame presence indication
doff DHW-off (eco) indication
dhw Indication of DHW service or DHW setpoint adjustment when blinking
dgr Degree symbol
bar Bar (pressure) symbol
col No specic usage
P1 Detected slave DSP device in chain below
P2 Various functions -mainly answer button indicator
P3 On, when information is related to MAXSYS1
P4 Detected master DSP device in chain above
P5 Not used yet
P6 On, when information is related to MAXSYS0
Page 39
FHE-250 MANUAL 09 2014 ISSUE 2
Page 33
3
The Display is equipped with 7 push-buttons placed round the LCD display as follows:
A B C
E
F
G
D
FIG. 11 PUSH-BUTTON LAYOUT
The Display is equipped with a blue LED backlight. The backlight operation is as follows:
The Backlight:
is activated for 10 seconds when Standby mode is entered.
is turned off immediately, when Suspend mode is entered.
is on during the Auto Detection procedure.
is activated for 30 seconds after any button activity.
blinks when an error is indicated.
3.12
PUSH-BUTTONS
3.13
BACKLIGHT
3.14
USER INTERFACE OPERATING MODES
The display supports switching among various user interface operating modes. The very rst
mode invoked after startup of the system is Initial mode.
3.14.1
INITIAL MODE
LCD- rst screen for 2 seconds
seg1 to seg4 : Displayed text “CASC”
LCD- second screen for next 2 seconds: seg1 to seg4 : Displayed DSP software version number
Buttons- no activity
Note: After 2 seconds of showing the second screen, the boiler is switched to Standby mode.
Page 40
FHE-250 MANUAL 09 2014 ISSUE 2
Page 34
3
The boilers are in standby mode unless they run into an error condition. In standby mode the
boiler displays the temperature of the supply water. Cascade temperature is displayed if the
cascade temperature sensor is installed (normally placed after the header). Otherwise the
supply temperature sensor is displayed on the LCD.
In error condition the boiler will show the error code starting with the address of the boiler that
produced the error code (F is related to the display), then the type of the error (A is lock-out
error, E is a limiting condition) and a two digit number which designates the type of the error.
Refer to Section 4.13 for details of error codes.
LCD -without error condition:
seg1 to seg3 Displayed CH supply temperature, otherwise blinking “--” is displayed dgr + seg5 Symbol °C or °F if CH supply temperature value is valid P1 Indication of presence of slave DSP, off on terminal DSP pmp Indication of pump running
m Indication of ame present
sun Displayed when CH mode is inhibited (SUMMER) doff Displayed when DHW mode is inhibited (DHW-OFF / ECO) ch Indication of CH mode service dhw Indication of DHW mode service ot OpenTherm master detected otc Outside temperature sensor is connected
LCD -during error condition:
seg1 Displayed source of error (master only). seg2 Displayed “A” for lockout error, “E” for non-locking error. seg3 to seg4 Error code displayed P1 Indication of presence of slave DSP, off on terminal DSP pmp Indication of pump running
m Indication of ame present
sun Displayed when CH mode is inhibited (SUMMER) doff Displayed when DHW mode is inhibited (DHW-OFF / ECO) ch Indication of CH mode service dhw Indication of DHW mode service ot OpenTherm master detected otc Outside temperature sensor is connected P2 Blinking when lockout error is displayed reset1 Blinking when lockout error is displayed P6 Blinking when error is related to MAXSYS0, or local device at position of MAXSYS0 P3 Blinking when error is related to MAXSYS1, or local device at position of MAXSYS1
3.14.2
STANDBY MODE ON MASTER DSP
Page 41
FHE-250 MANUAL 09 2014 ISSUE 2
Page 35
3
Button Press: Function:
Briey D Enter CH setpoint adjust mode Briey E Enter CH setpoint adjust mode Briey F Enter DHW setpoint adjust mode Briey G Enter DHW setpoint adjust mode Briey A Toggle SUMMER mode Briey B Reset lockout error (if lockout error is present) Briey C Toggle DHW-OFF mode
A+C for 3 sec. Enter Suspend mode A+B for 3 sec. Enter Cascade test mode
B+C for 3 sec. Enter Installer+ mode
A for 3 sec. Enter Local test mode
B for 3 sec. Enter Local installer mode C for 3 sec. Enter History mode D for 3 sec. Start of Auto Detection procedure E for 3 sec. Invoke parameter load on all DSPs
Note: The Master DSP is capable of displaying the source of error. Burners are indicated by their address “0” to
“E”(0,1,2,3,4,5,6,7,8,9,A,B,C,D,E). Source of error coming from DSP is identied by address “F”.
3.14.3
STANDBY MODE ON SLAVE DSP
In normal operation the slave boilers will be in standby mode, where “SLA” plus a one digit number is displayed, which is the address of the boiler. In error condition, the display will show the type of the error (A is lock-out error, E is a limiting condition) and a two digit number which designates the type of error. Refer to Section 4.13 for details of error codes
LCD:
seg1 to seg3 Displayed text “SLA” as slave device indication
seg4 Order of device in chain
P4 Indication of presence of master DSP in chain -always on
P1 Indication of presence of slave DSP, off on terminal DSP
pmp Indication of pump on local boiler
m Indication of ame on local boiler
Button Press: Function:
D for 3 sec. Start of Auto Detection procedure
B for 3 sec. Enter Local installer mode
A for 3 sec. Enter Local test mode
Page 42
FHE-250 MANUAL 09 2014 ISSUE 2
Page 36
3
LCD:
seg1 to seg3 Displayed setpoint value, if not available “--” is displayed, blinking when
adjusted
dgr + seg5 Symbol °C or °F if temperature value is valid
ch Always blinks
P2 Blinks when parameter is modied and can be saved.
Button Press: Function:
D (autorepeat) Decrement setpoint value
E (autorepeat) Increment setpoint value
Briey B Write setpoint value if modied and exit
Note: After 10 seconds of keyboard inactivity, mode exits without updating the setpoint value.
3.14.5
CH SETPOINT ADJUST MODE
3.14.4
SUSPEND MODE
LCD:
stb Always on
P2 Always blinking
Button Press: Function:
D for 3 secs. Start of Auto Detection procedure
Briey B Exit from Suspend mode to Standby mode
Note: In the Suspend mode, both BH and DHW service is inhibited with exception of frost protection.
A
B
C
E
D
G
F
A + C for 3 sec.
D briey.
A
B
C
E
D
G
F
Page 43
FHE-250 MANUAL 09 2014 ISSUE 2
Page 37
3
3.14.6
AUTO DETECTION MODE
LCD:
seg1 to seg4 Displayed blinking text “Auto” during local MAXSYS detection
Displayed blinking text “PArA” during parameter load from MAXSYS0
Displayed text “bu” when asking for burner count conrmation & burner count
Displayed blinking text “Auto” during cascade DSP detection
col Blinking when asking for burner count conrmation
P2 Blinking when asking for burner count conrmation
Button Press: Function:
Briey B Conrmation of burner count, when asked
Note: Auto Detection invalidates cascade structure information. If burner count is not conrmed by installer, normal operation is blocked by F97 error. To allow the system to function correctly, all devices must be present, cascade must be started again and burner count must be conrmed by installer.
3.14.7
CASCADE TEST MODE
LCD:
seg1 Displayed “C”
seg2 to seg4 Percentage of power demand of the cascade
Button Press: Function:
A+B for 3 sec. Exit cascade test mode
D (autorepeat) Decrement power demand
E (autorepeat) Increment power demand
Briey F Set power demand to 0% (absolute minimum).
Briey G Set power demand to 100% (absolute maximum).
D for 3 sec.
A
B
C
E
D
G
F
A
B
C
E
D
G
F
A + B for 3 sec.
Page 44
FHE-250 MANUAL 09 2014 ISSUE 2
Page 38
3
LCD:
seg1 Displayed “t”
seg2 to seg4 Percentage of power demand of the cascade
P6 Blinking when testing local device at position of MAXSYS0
P3 Blinking when testing local device at position of MAXSYS1
Button Press: Function:
A for 3 sec. Exit local test mode
D (autorepeat) Decrement power demand
E (autorepeat) Increment power demand
Briey F Set power demand to 0% (absolute minimum).
Briey G
Set power demand to 100% (absolute maximum).
Note: MAXSYS0 refers to a unit with LCD display and MAXSYS1 refers to a unit without display.
3.14.8
LOCAL TEST MODE
A for 3 sec.
A
B
C
E
D
G
F
Page 45
FHE-250 MANUAL 09 2014 ISSUE 2
Page 39
3
3.14.9
LOCAL INSTALLER MODE
LCD -when showing the parameter index:
seg1 Displayed “P”
seg2 to seg3 Index number (starting from 1)
i1 Installer mode indication
P6 Blinking when MAXSYS0 as the source is selected
P3 Blinking when MAXSYS1 as the source is selected
LCD -when showing the parameter value:
seg1 to seg3 Numeric value (refreshed every 3 sec.)
i1 Installer mode indication
P6 Blinking when MAXSYS0 as the source is selected
P3 Blinking when MAXSYS1 as the source is selected
Button Press: Function:
B for 3 sec. Exit local installer mode
Briey A Exchange burners (in case of two burners per display)
D Decrement index number
E Increment index number
P01 Flame current [uA]
P02 CH supply temperature [ºC -or-ºF]
P03 CH return temperature [ºC -or-ºF]
P04 DHW temperature [ºC -or-ºF] (only on MAXSYS0, if used)
P05 Water pressure [bar/10 -or-psi] (local MAXSYS0, where sensor is connected)
P06 Output level [rel. %] Actual relative output level of the burner
P07 Requested fan speed [50*rpm] Speed requested by control algorithm
P08 Actual fan speed [50*rpm] Fan speed
P09 Exhaust temperature [ºC]
P10 Cascade temperature [ºC -or-ºF], if cascade sensor is connected
P11 OTC temperature [ºC -or-ºF] temperature from external sensor
P12 Cascade mod. level [rel. %] relative modulation level of cascade
P13 CH control setpoint [ºC -or-ºF]
P14 DHW control setpoint [ºC -or-ºF]
P15 Total burners Total count of installed burners
P16 Total burners on Count of burners running
P17 Total displays Total count of boiler modules
Note: MAXSYS0 refers to a unit with LCD display and MAXSYS1 refers to a unit without display.
A
B
C
E
D
G
F
B for 3 sec.
Page 46
FHE-250 MANUAL 09 2014 ISSUE 2
Page 40
3
3.14.10
HISTORY MODE
LCD -when selecting the burner:
seg1 to seg2 Displayed “bu”
seg4 Burner number (from 0 to E)
LCD -when selecting the history index:
seg1 to seg2 Displayed “Hi”
seg3 to seg4 Index number (starting from 0)
LCD -when showing the error code:
seg2 to seg3 Numeric value (refreshed every 3 sec.)
Button Press: Function:
C for 3 sec. Exit history mode
Briey B Conrm selection and shift to the next page (burner -> index -> code)
D Decrement index number, skip to index selection screen
E Increment index number, skip to index selection screen
F Decrement burner number, skip to burner selection screen
G Increment burner number, skip to burner selection screen
Note: When the mode is invoked, indicates burner selection. User interface is switched to Index selection after 3 seconds or on demand. Index starts from number 0. After 1 second index is replaced by related error code.
A
B
C
E
D
G
F
C for 3 sec.
Page 47
FHE-250 MANUAL 09 2014 ISSUE 2
Page 41
3
LCD -when selecting the parameter index:
seg1 Displayed “P”
seg2 to seg3 Index number (starting from 1)
i1 + i2 + spn Installer+ mode indication
LCD -when showing value:
seg1 to seg3 Displayed value, if not available a string “--” is displayed, blinking when
adjusted
P2 Blinks when parameter is modied and can be saved
i1 + i2 + spn Installer+ mode indication
Button Press: Function:
B+C for 3 sec. Exit Installer+ mode
Briey B Write value if changed, switch between index and value screens
D (autorepeat) Decrement index number, skip to index selection screen
E (autorepeat) Increment index number, skip to index selection screen
F (autorepeat) Decrement parameter value
G (autorepeat) Increment parameter value
Note: After each exit of Installer+ mode, the parameter load request is sent to all DSPs in the chain. This takes approx 15 seconds to complete.
3.14.11
INSTALLER+ MODE
A
B
C
E
D
G
F
B + C for 3 sec.
Page 48
FHE-250 MANUAL 09 2014 ISSUE 2
Page 42
3
P01 CH setpoint [°C -or -°F]
P02 CH setpoint max. [°C -or -°F]
P03 CH hysteresis [°C -or -°F] (differential unit)
P04 CH anticycle [min]
P05 CH minimum time [min]
P06 CH slope [°C/min -or -°F/min] (differential unit)
P07 CH pump overrun [min]
P08 CH max. capacity [rel. %] limitation of maximum of the capacity
P09 CH min. capacity [rel. %] limitation of minimum of the capacity
P10 CH Kp CH PI control coefcient
P11 CH Ki CH PI control coefcient
P12 CH minimal mod. level [abs. %] absolute level related to minimum of modulation
P13 CH max burner power [kW -or -kBTU/h] power per burner
P14 OTC curve Slope number of the OTC curve
P15 OTC offset [°C -or -°F] Offset of the OTC curve
P16 DHW setpoint [°C -or -°F]
P17 DHW setpoint max. [°C -or -°F]
P18 DHW hysteresis [°C -or -°F] (differential unit)
P19 DHW pump overrun [sec] (not applied to cascade pump)
P20 DHW max. capacity [rel. %] limitation of maximum of the burner capacity
P21 DHW min. capacity [rel. %] limitation of minimum of the burner capacity
P22 DHW Kp DHW PI control coefcient
P23 DHW Ki DHW PI control coefcient
P24 DHW storage setpoint [°C -or -°F]
P25 DHW storage add.off [°C -or -°F] (differential unit)
P26 DHW overtemp. timer [sec]
P27 FAN max. speed [50*rpm]
P28 FAN min. speed [50*rpm]
P29 FAN Kp -up FAN PI control coefcient
P30 FAN Ki -up FAN PI control coefcient
P31 FAN Kp -down FAN PI control coefcient
P32 FAN Ki -down FAN PI control coefcient
P33 Ignition level [rel. %] 0..100% between min and max of burner
P34 Market zone 0..127 = metric units, 128..256 = imperial units
P35 Pump PWM -min. [%] minimum PWM duty of system pump
P36 Pump PWM -max. [%] maximum PWM duty of system pump
P37 DHW split burners number of burners for DHW service in case of splitted system
P38 Cascade frost on level [°C -or -°F] level to trigger frost protection on cascade sensor on
P39 Cascade frost off level [°C -or -°F] level to trigger frost protection on cascade sensor off
P40 Cascade switch delay [sec] time to
P41 DSP PI loop period [sec] period of PI calculation/integration step in DSP
Page 49
FHE-250 MANUAL 09 2014 ISSUE 2
Page 43
4
It is the law that any service work must be carried out by a Gas Safe Registered Engineer in the UK.
In IE service work must be carried out by a competent person.
SECTION 4 - MAINTENANCE
!
WARNING
Always turn off the gas supply at the gas service cock, and switch off and disconnect the electricity
supply to the appliance and any external controls before servicing or replacing components.
Maintenance on Gas appliances should only be carried out by competent, trained personnel who are
‘Gas Safe’ registered in the UK, and who have the necessary equipment to check combustion. If any
fault is found during these operations contact your Fulton representative.
Make the following checks for correct operation.
1. The correct operation of ANY secondary system controls should be proved. Operate each
control separately and check that the main burner or circulating pump, as the case may be, responds.
2. Water circulation system;
a) With the system HOT examine all water connections for soundness.
b) With the system still HOT, turn off the gas, water and electricity supplies to the boiler and
drain down to complete the ushing process.
c) Rell and vent the system, clear all air locks and again check for water soundness.
d) Balance the system.
3. Check the condensate drain for leaks and check it is discharging correctly.
4. Finally set the controls to the User’s requirements.
Note. If optional kits are tted then refer to the instructions supplied with the kits.
4.1
GENERAL
4.2
SAFETY
IMPORTANT NOTE: After completing the servicing or replacement of components always:
1. Test for gas soundness.
2. Test the burner manifold anges for soundness. This can be done with leak detection spray whilst
operating the boiler. The gas valve and controls must be shielded from the spray.
3. Check the water system is correctly lled and free of air. Air in the boiler could cause damage to the heat exchanger. For this reason a non-isolatable automatic air vent is tted as standard on
all FHE boilers.
4. Check the module cover panels are correctly tted.
5. With the system hot examine all water connections for soundness.
CONTINUED...
Page 50
FHE-250 MANUAL 09 2014 ISSUE 2
Page 44
4
250 kW
Flue Gas CO
2
@ Max Rate % 9.0 ± 0.3
G20/LNG @ Min. Rate % 9.0 ± 0.3
*Same values apply to models 500, 750 and 1000.
6. Check the gas rate and measure the combustion CO/CO2 content. The CO/CO2 ratio of the ue gas on each module should not be greater than 0.004. The CO2 values should be correct to the
following gures:
Carry out functional checks as appropriate.
4.3
PARTIAL ISOLATION OF BOILERS IN CASCADE SYSTEMS
It is possible to continue normal operation of the boilers without any changes to the wiring, in the event that one of the boilers in the chain is either not in working condition, or is under maintenance. Perform one of the following procedures depending on which boiler is not in service.
!
WARNING
Always isolate all of the boilers from the main electrical supply before
executing these procedures.
Note:
a) All changes to terminals as listed below are in accordance with the terminal number tables in Section 2.19.2
of this manual.
b) The letter “N” below indicates the total number of installed boilers.
1. Remove the lower front panel of any boilers requiring changes, to access the necessary electrical terminals.
2. After any changes on boiler setup always perform an Auto Detection procedure as detailed in
Section 3.8.7 of this manual.
Page 51
FHE-250 MANUAL 09 2014 ISSUE 2
Page 45
4
1. ISOLATING THE MASTER BOILER *
Master boiler: Disconnect all terminal plugs
Slave 1 boiler: Connect all of the terminal plugs
All remaining Slave boilers: No Change
2. ISOLATING A SLAVE BOILER IN THE CHAIN (EXCEPT THE LAST ONE) *
Master boiler: No Change
Slave boiler to isolate: Disconnect Terminal plugs 1-13 and insert jumpers between:
Terminal 14-15
Terminal 16-17
Terminal 18-19
All remaining Slave boilers: No Change
3. ISOLATING THE LAST SLAVE BOILER *
Master boiler: No Change
Slave boilers up to Slave N-2 boiler: No Change
Slave N-1 boiler: Disconnect Terminal 20 and connect Terminal 19
Last Slave boiler in chain: Disconnect all terminal plugs
4. ISOLATING THE MASTER BOILER AND A SLAVE BOILER *
Master boiler: Disconnect all terminal plugs
Slave boiler out of order: Disconnect Terminal plugs 1-13 and insert jumpers between:
Terminal 14-15
Terminal 16-17
Terminal 18-19
First working boiler in chain: Connect all of the terminal plugs
All remaining Slave boilers apart from last: No Change
Last working Slave boiler: To be set up as instructed for the last Slave in
Section 2.19.2
Note:
The isolated boiler becomes invisible to the controller.
The rst working boiler becomes the Master Boiler.
a) Boilers out of order after the new master need to have 3 jumpers inserted between:
• Terminal 14-15
• Terminal 16-17
• Terminal 18-19
b) Additionally Terminals 1-13 need to be disconnected.
c) Ensure Terminal 20 is connected and Terminal 19 is disconnected on the last working boiler.
* For details of terminal disconnection and jumper insertion, refer to Figs 7, 8 & 9 on page 24 of this manual
Page 52
FHE-250 MANUAL 09 2014 ISSUE 2
Page 46
4
To ensure the continued safe and efcient operation of the boiler, it is recommended that it is checked
at regular intervals and serviced as necessary. The frequency of servicing will depend upon the installation condition and usage but should be carried out at least annually.
Fulton Ltd does not accept any liability resulting from the use of unauthorised parts or the repair and servicing of appliances not carried out in accordance with the Company’s recommendations and
specications.
Note: Some build-up within the heat exchanger assembly is quite usual with this type of condensing boiler.
Thorough removal and cleaning is recommended annually, the heat exchanger must be inspected and cleaned
after a maximum of 2 years operation.
1. Light the boiler and carry out function checks, noting any operational faults.
2. Run the boiler for 5 minutes and then check the gas consumption rate.
3. For correct boiler operation, the CO/CO2 ratio of the ue gas on each module should not be greater than 0.004 and the CO2 values should be correct to the gures in Section 4.2.
4. Remove and inspect the fan/venturi assembly.
5. Remove the burner assembly and inspect the electrodes and sightglass.
6. Remove and clean the burner.
7. Inspect the heat exchanger through the burner opening. If there are signs of oxide build up, clean the exposed heat exchanger surface with a suitable brush.
8. Clean the condensate trap(s).
9. Check that the ue terminal and air inlet are unobstructed and that the uing and ducting are
correctly sealed.
REPEAT PROCEDURE FOR SLAVE AND MASTER MODULES.
10. After servicing refer to Section 4.2 for nal safety checks.
CAUTION
Use caution when using any cleaning solutions.
Refer to local regulations for proper cleaning solution disposal.
!
CAUTION
Do not allow oil leaks, dust, or dirt to accumulate around the boiler.
!
4.4
SERVICING SCHEDULE
Page 53
FHE-250 MANUAL 09 2014 ISSUE 2
Page 47
4
Daily maintenance and inspection must include the following:
1. Observe general conditions and operating temperature.
2. Make sure that the ow of combustion and ventilating air to the boiler is not obstructed.
3. Assure that boiler area is free and clear of any combustible materials, including ammable
vapours and liquids.
CAUTION
Hazard analysis should be performed by the end user to ensure the safety of employees/personnel.
!
4.4.1
DAILY MAINTENANCE AND INSPECTION
4.4.2
WEEKLY MAINTENANCE AND INSPECTION IN ADDITION
Weekly maintenance and inspection must include the following:
4. Observe the conditions of the main ame. A normal high re ame shows an orange screen with
a blue halo. In Low re the burner should display a reddish orange glow.
5. Correct air adjustment is essential for the efcient operation of this boiler. If an adjustment to the
combustion is necessary, the ue gas composition should be checked with a carbon dioxide
(CO2) or oxygen (O2) analyser to set conditions.
4.4.3
MONTHLY MAINTENANCE AND INSPECTION IN ADDITION
Monthly maintenance and inspection must include the following:
6. Remove and clean out the condensate trap pipework arrangement.
7. Test high-limit control by reducing setting below the operating temperature. Burner should shut
off. Return high limit to previous setting.
8. Test operating temperature control by reducing temperature setting as necessary to check burner operation.
9. Check ue gas temperature at outlet. If there is a temperature increase over previous readings, the probable cause is soot or water-scale build-up on the tubes. Consult Fulton immediately if there is a concern.
10. Test low gas pressure switch utilising the procedure in Section 3.6.
11. If an air inlet lter is included with the boiler, inspect and clean lter of any dust or lint.
See Section 4.5 Procedure for Cleaning the Air Inlet Filter.
12. Verify the water loop style traps in the exhaust venting system are ooded.
Page 54
FHE-250 MANUAL 09 2014 ISSUE 2
Page 48
4
Annual maintenance and inspection must be performed prior to each heating season, and includes
the following tasks which must be done by a factory trained technician.
Observe the general operation of the unit to verify the following:
13. Stack temperature readings are in line with factory test re and regular maintenance reports.
14. Boiler is lighting reliably and quietly.
15. There are no unusual sounds coming from the burner or blower assembly.
16. It is considered good practice to remove and inspect the burner and ignition assembly on an annual basis. Follow Section 4.7 Procedure for Removing/Cleaning Burner in this manual if there is evidence of foreign matter built up on the burner or ignition assembly.
17. The heat exchanger must be inspected and cleaned, as needed. Follow Section 4.9 Procedure
for Cleaning the Heat Exchanger in this manual.
CAUTION
Any damage to the burner or any other aspect of the boiler because of an air lter that was not cleaned
and maintained regularly will void the warranty.
!
4.4.4
ANNUAL MAINTENANCE AND INSPECTION IN ADDITION
4.5
PROCEDURE FOR CLEANING THE AIR INLET FILTER
The air lter is an optional part and does not come with every boiler.
Proceed as follows:
1. Remove the lter. The lter sits between the air inlet connection to the venturi and an adapter plate, bolted to each corner of the venturi ange, accessible from the front of the boiler.
2. Remove all debris and dirt from the lter using a vacuum cleaner.
3. Return the lter to its original position in the slot.
Note: Where an internal ductwork arrangement is also included in the boiler for room sealed applications, the lter
will not be accessible for cleaning and it must be removed along with the foam gasket tape between the venturi and adapter plate and both the tape and lter should be replaced.
4.6
EXAMINE THE FLUE SYSTEM
1. Check all joints and pipe connections for tightness.
2. Check vent for corrosion or deterioration. If any venting needs replacing, do so immediately.
3. Perform any recommended maintenance as required by the vent material manufacturer.
4. Check to ensure loop traps are ooded.
4.7
INSPECT HEATING SYSTEM FOR OTHER PROBLEMS
1. Perform combustion analysis and adjust if necessary.
2. Leak test gas valves. Leak Test must be performed only by qualied personnel, who have been
trained in this procedure by Fulton.
Page 55
FHE-250 MANUAL 09 2014 ISSUE 2
Page 49
4
Note: Ensure the gas supply to the boiler and the mains electricity supply have been isolated prior to commencing this work.
Perform the following to remove/clean the burner:
1. Remove the top and both front panels from the boiler frame, carefully disconnecting the 3 block connectors on the controller on the top front panel:
black 12 pin connector block, with wiring labelled “DSP X01”
black 10 pin connector block, with wiring labelled “DISP X04”
white 6 pin connector block, with wiring labelled “DSP X05”
Store all panels in a safe location.
2. Disconnect both block connectors from the pre-mix blower:
white 3 pin connector block, with wiring labelled “FAN X1”
white 4-pin connector block, with wiring labelled “FAN X2”
3. Disconnect the 2 grey angled block connectors from the gas valve and gas pressure switch:
wiring labelled “GAS PL1” from the gas valve
wiring labelled “GAS PS1” from the gas pressure switch
Note: Each of these connectors in point 3 is secured in place with a screw headed M4 bolt.
4. Ensure the entire gas valve/venturi/blower assembly is supported ready for removal.
5. Disconnect the four allen bolts from the bottom of the gas valve. Inspect the o-ring located
between these two anges for signs of deterioration, replace if required.
6. Disconnect the 4 M8 bolts securing the gas valve/venturi/blower assembly to the apper, lift the
entire assembly out of the unit and put in a safe position where no dust or other contaminants
can get into the assembly. Inspect the square rubber gasket between the blower and the apper
for signs of deterioration, replace if necessary.
Note: Adequate preparation and care should be taken when removing this assembly, as it is heavy.
7. Disconnect the cables from the ignition transformer, the ionisation probe and the ignition
electrode:
brown cable with an angle rajah connector, labelled “ION” from the ionisation probe on the
bottom front of the heat exchanger
orange cable with an angle rajah connector between the ignition transformer (top left corner)
and the ignition electrode on the right hand side of the front of the heat exchanger
green & yellow cable with a spade connector, labelled “earth” from the connector next to the
ignition electrode
white 6-pin connector block, with wiring labelled “FLAP X3” from the apper block connector
8. Undo the four nuts holding the apper-mounting plate to the heat exchanger.
4.8
PROCEDURE FOR REMOVING/CLEANING THE BURNER
Page 56
FHE-250 MANUAL 09 2014 ISSUE 2
Page 50
4
9. Remove the burner, being careful not to scrape it on the heat exchanger. Inspect the gasket for signs of deterioration, replace if necessary.
10. Inspect the burner and wipe off (do not scrub or use a wire brush) any soot or foreign material that may have accumulated. If available, use compressed air to clear the burner. Wipe out the inside of the burner with a clean cloth.
11. Check the gap between the electrode and the ground rod. Gap should be 1/8 inch (3 mm) +/- 1/16.
12. Check the horizontal gap between the point of ignition and the exterior of the mesh burner. The required gap is 5/16-3/8 inch (8-10 mm).
13. To inspect the gasket between the apper mounting plate and mesh burner undo the 4 bolts.
14. Check for cracking of the electrode insulator. Do not over tighten the electrode.
15. Use a soft, clean cloth to remove accumulated contaminants from the sight glass.
16. Before re-installing the burner, check the cleanliness of the heat exchanger and the condition of the combustion chamber. If corrosion or leaks are noticed, contact Fulton.
17. Reverse removal steps for reinstallation of the burner assembly.
18. Reinstall front and top panels.
19. Test re the boiler and use a combustion analyser to ensure that the fuel/air ratio is set correctly
throughout the range.
Note: This work should normally be carried out in conjunction with the annual removal and cleaning of the burner,
as detailed in Section 4.8 above. Follow steps 1 to 9 above in order to gain access to the heat exchanger.
4.9
PROCEDURE FOR CLEANING THE HEAT EXCHANGER
Inspect the heat exchanger, and clean if necessary using the following procedure:
1. Inspect the tubes for any signs of damage.
2. Vacuum out any deposits inside the combustion chamber area if necessary.
3. If there is a buildup of any kind on the heat exchanger tubes, clean using a dry, stiff nylon bristle brush. Never use a metallic brush on heat exchanger surfaces.
4. Vacuum again to remove any debris from brushing the heat exchanger.
5. Wipe down with a clean wet cloth.
6. Inspect the refractory at the back of the combustion chamber.
7. If there are any signs of damage, the insulation disc must be replaced.
8. If the ignition assembly or ame rod were removed for any reason, inspect these gaskets for
signs of damage, and replace if damaged.
Page 57
FHE-250 MANUAL 09 2014 ISSUE 2
Page 51
4
If the boiler installation contains more than 1 module, each boiler module will be tted with individual
gas valves, all gas valves must be adjusted independently.
Note: The procedure for each boiler module will be the same, the ue gas analyser must be connected to each boiler ue prior to its’ connection into any common ue header.
Maximum rate adjustment (Throttle)
1. Switch the boiler on and operate for 5 minutes.
2. Set the module to maximum output.
3. Connect a suitable ue analyser to the ue sampling point of the boiler.
4. Using the maximum rate adjustment screw, adjust the master module gas valve, if necessary, until the CO2 measures 9.5% ± 2.5 (nb. clockwise reduces CO2).
Minimum rate adjustment (Offset)
5. Set the module to minimum output.
6. Connect a suitable ue analyser to the ue sampling point of the boiler.
7. Remove the protective cap and then using the offset adjustment screw, adjust the valve on the boiler until the CO2 value measures 9.5% ± 2.5 (nb. anti-clockwise reduces CO2 level).
Note: The offset adjustment is more sensitive than the throttle adjustment.
IMPORTANT NOTE: The CO measurement when the CO2 is set, should not exceed 50 ppm. Under no
circumstances should the CO/CO2 ratio exceed 0.004.
Adjust in steps of no more than 1/8 turn and wait 1 minute after each adjustment to allow setting to
stabilise.
8. Re-check the CO2 level at the boiler maximum output, repeating steps 2 to 7 if necessary.
9. Seal adjustment screw cap with tamper proof paint.
10. If the required CO2 level cannot be obtained with a CO/CO2 ratio below 0.004 then contact Fulton.
4.10
GAS VALVE ADJUSTMENT
Page 58
FHE-250 MANUAL 09 2014 ISSUE 2
Page 52
4
1. Follow Section 4.2 Safety in this manual and all relevant safety checks.
2. Fire the boiler and perform combustion check. Analyse combustion throughout the range and verify proper operation of safety devices.
3. Make any necessary adjustments.
4.11
AFTER ALL REPAIRS AND MAINTENANCE
4.12
HANDING OVER
Routine Operation
Draw the attention of the boiler owner or his representative to this manual. Give a practical demonstration of the lighting and shutting down of the boiler. Describe the function of the boiler and system controls and show how they are adjusted and used. Hand these Installation and Servicing Instructions/User’s Instructions and Log book to the customer and request him to keep them in a safe place for ready reference. For IE, it is necessary to complete a “Declaration of Conformity” to indicate compliance to the appropriate standard.
IMPORTANT NOTE: Point out to the owner that the boiler must have regular maintenance and cleaning, at least annually, in order to ensure reliable and efcient operation. Regular attention will also prolong the life of the boiler and should preferably be performed at the end of the heating season.
After servicing, complete the service section of the log book and return to the owner or their representative. Recommend that a contract for this work should be made with the regional gas authority or a Gas Safe Registered Engineer. In IE servicing work must be carried out by a competent person.
Page 59
FHE-250 MANUAL 09 2014 ISSUE 2
Page 53
4
Error codes can be divided into 2 groups:
1. Lock-out error codes
2. Blocking error codes
4.13
ERROR CODES AND TROUBLESHOOTING
Page 60
FHE-250 MANUAL 09 2014 ISSUE 2
Page 54
4
1. LOCK OUT ERROR CODES
Lock out error codes require a manual reset action after the source of the problem has been identied and eliminated. The meaning of the error numbers
are as follows:
ERROR
CODE
MEANING POSSIBLE CAUSE SOLUTION
A1
Lock out signal after no ame and all ignition trials are
expired
Description:
This error condition stops the boiler from operating and
manual/remote reset is required. Local resets are not
limited. However remote resets (communication or
Open Therm) are limited to 5 per hour.
a) Manually operated valves on the
gas train have been closed.
b) There is a blockage in the gas
line.
c) Modulating gas valve within the
d) Modulating gas valve within the
boiler has failed.
including the T-handle valve in the boiler shell.
connected upstream of the boiler, on the gas line.
c) Check the tube between the gas valve and the
Venturi and ensure that both ends are properly
connected.
d) Replace the modulating gas valve.
A2 False Flame Signal
A ame signal is seen without the
gas valve being open.
Clean isolation probe. Reset lockout.
A3
Overheat Protection
Description:
This error code can be generated by one of two methods of
overheat protection built into the boilers. A High Limit error
can be generated even after a CH supply or return sensor
short circuit condition occurs.
There is a signal coming from the
CH ow or return temperature
sensors in excess of 105°C, or the
heat exchanger body is higher than
95°C, so the circuit is open through
the high limit stat (this is normally
closed).
a) Clean CH ow and return temperature sensors.
b) Check wiring between the controller and the limit
stat and make sure that the wires connected are
not loose. If all the wiring is ne then replace the
high limit stat.
c) If the problem still persists, then replace ow and
return temperature sensors
A4
APS (Air Pressure Switch) Error
Description:
The APS is congured and does not close or does not open
within set time limits. Error 4 is generated.
APS ap valve has stuck open, or
closed.
Remove the apper house between the fan and the
heat exchanger and clean the housing inside. If this
does not solve the problem, then replace the APS
A5
Fan Speed Feedback Error
Description:
The control requires a certain fan speed, but does not
detect the correct signal.
The fan motor is not working
A6
APS (Air Pressure Switch) Error
Description:
If the APS is congured and it drops during burner
operation and the number of maximum re-trials has been
reached, Error 6 is generated.
A foreign body blocking the air
Check that the airway to the burner is clear from
obstructions.
Page 61
FHE-250 MANUAL 09 2014 ISSUE 2
Page 55
4
ERROR
CODE
MEANING POSSIBLE CAUSE SOLUTION
A9
Valve Circuit Error
Description:
During normal operation of the MaxSys controller, the valve
circuit is regularly checked. If the check fails, Error 9 will be
set.
There is a problem with the gas
valve.
Replace the modulating gas valve
A11
Temperature sensor self test on the boiler heat
exchanger has failed
a) Water ow in the system has
reversed.
b) Temperature sensors are scaled
up.
a) If it happens at rst start up then check that the
correctly. Check the direction of the water pump.
b) Clean or replace sensors
A13 Remote Reset Inhibit
The boiler has been attempted to
reset remotely more than 5 times in
15 minutes.
Inspection by a competent person is recommended.
Reset can be achieved by switching the isolation
switch off and on.
A15
Drift Test Error
Description:
When the boiler is unable to start up due to a consistent
error described under error code E81, then the boiler is
locked out with error code A15.
See error code E81 See error code E81
A16
Stuck at Test Error on CH Supply Sensor
Description:
When temperature rise cannot be detected on the supply
sensor after successful ignition, error code A16 is set.
a) The sensor has been removed
from the pocket.
a) Insert the sensor back into place
b) Replace the sensor
A17
Stuck at Test Error on CH Supply Sensor
Description:
When temperature rise cannot be detected on the supply
sensor after successful ignition, error code A17 is set.
a) The sensor has been removed
from the pocket.
a) Insert the sensor back into place
b) Replace the sensor
A18
Cracked Sensor Test Error
Description:
When a large crack in the CH Supply or CH Return Sensor
is detected, error code A18 is set.
The Supply or Return Sensor is
cracked.
Replace the sensor
Page 62
FHE-250 MANUAL 09 2014 ISSUE 2
Page 56
4
ERROR
CODE
MEANING POSSIBLE CAUSE SOLUTION
A30
CH supply sensor out of normal operating range
(short circuit)
A80
Supply-Return Reversed Error
Description:
CH Supply and Return temperature sensors are
monitored after ignition. If the return water temperature
is higher, then the boiler will be locked out.
The water ow is reversed in the
system
Check the circulation pumps and resolve the
problem
A31
CH supply sensor out of normal operating range
(open circuit)
A43
CH return sensor out of normal operating range
(short circuit) - resolving type
Description:
If NTC sensor goes outside the range, a warning will be
generated.
When the sensor is back to the normal operating range, the
warning is gone.
The warning will switch off the system. Heat demands will
be disabled.
Resolving the situation can be achieved only if the sensor
is within operating range again (a lockout reset is
necessary).
A44
CH return sensor out of normal operating range
(open circuit)
Page 63
FHE-250 MANUAL 09 2014 ISSUE 2
Page 57
4
2. BLOCKING ERROR CODES
The boiler controller also recognises fault situations that can block the heat demands but do not lead to lockout condition. When the error condition
becomes resolved, the error will disappear but will also be written into the history data. In some cases the Auto Detection function can resolve the problem,
if there is no logical reason for the error or communication error detected.
Hold the button labelled “-” on the central heating adjustment side (display, front panel) down for at least 3 seconds, then conrm the number of burner
units.
ERROR
CODE
MEANING POSSIBLE CAUSE SOLUTION
E7
TTB Exhaust Protection
Description:
The temperature measured on the TTB exhaust sensor is
too high. The TTB ‘trip point’ is the value which denes the
high limit of the exhaust gas. The limit changes depending on
burner load.
a) Air-fuel ratio has changed.
b) Water ow is not sufcient in
c) Heat exchanger has a low limit
water level.
a) Find the cause of the problem and re-commission
b) Investigate the causes of the insufcient ow and
exchanger works correctly and the water pressure
is within acceptable range
E8
MaxSys Controller Error
Description:
During normal operation of the ignition controller, the ame
circuit is regularly checked. If the check fails, Error 8 will be
set.
Internal circuit error. a) Perform a power cycle (Disconnect and reconnect
the power supply)
E32
DHW sensor out of normal operating range (short circuit)
Description:
This condition will inhibit DHW demand. The boiler can still
enter CH mode.
E33
DHW sensor out of normal operating range
(open circuit)
Description:
This condition will inhibit DHW demand. The boiler can still
enter CH mode.
Page 64
FHE-250 MANUAL 09 2014 ISSUE 2
Page 58
4
ERROR
CODE
MEANING POSSIBLE CAUSE SOLUTION
E34 Low Voltage Error
Low Mains voltage will trigger this
error (below 167 V).
Investigate the reason for low voltage supply.
Re-establish correct voltage.
E37 Low Water Pressure
The water pressure is insufcient. Investigate the cause of the water pressure drop and
E41
Water Pressure Signal Time-Out.
Description:
The water pressure value is not refreshed often enough.
Loose link wire on the MaxSys
Check & re-secure wiring connections.
E45
TTB sensor* out of normal operating range (short
circuit)
Loose link wire on the MaxSys
Check & re-secure wiring connections.
E46
TTB sensor* out of normal operating range
(open circuit).
Loose link wire on the MaxSys
Check & re-secure wiring connections.
E47 Water Pressure Sensor* Error
Loose link wire on the MaxSys
Check & re-secure wiring connections.
E74
Solar sensor* out of normal operating range
(short circuit)
Loose link wire on the MaxSys
Check & re-secure wiring connections.
E75
Solar sensor out of normal operating range
open circuit
Internal error in the MaxSys
E76
Gas Pressure Error
Description:
If the Gas Pressure Switch opens at any time for more than
5 s, Error 76 is generated and will switch off the system.
a) The Gas Pressure Switch is
a) Replace the Gas Pressure Switch.
E77 Condensate High Pressure (Blockage)
The condensate pipe has been
blocked and the water level has
risen to an unsafe level in the
Clear out the condensate piping system.
E78 Flapper does not open
a) A foreign body, or built up
contamination within the APS
apper house has built up.
b) The airway on the Venturi is
completely blocked.
persists, then change the APS apper housing.
* Not currently used in standard FHE setup
Page 65
FHE-250 MANUAL 09 2014 ISSUE 2
Page 59
4
ERROR
CODE
MEANING POSSIBLE CAUSE SOLUTION
E79 Flapper does not close
A foreign body, or built up
contamination within the APS
apper house is present.
Clean the APS apper housing. If the problem
persists, then change the APS apper housing.
E81
Drift Test Warning
Description:
Temperature difference between CH Supply and CH
Return Sensors are monitored to detect micro crack in
the sensors.
a) Micro crack has developed on
the CH Supply Sensor, or the
b) Large electromagnetic eld is
affecting the electrical circuit.
c) Wire connections are loose.
a) Replace the damaged sensor
b) Investigate for electromagnetic disturbances
c) Replace the relevant wire loom in the boiler
E90 Communication Error Refer to manufacturer (Honeywell).
E94 DSP Firmware Problem
DSP has encountered serious
internal problem due to corrupted
content of non-volatile memory.
Replace DSP device.
There is no relevant data about
CH supply temperature coming
from the Controller, or the
Check connection of CH supply sensor on the boiler
body and the Cascade sensor in the pipeline.
OTC control is activated by
sending OTC curve to non-zero
value and Outside Temperature
Sensor is not present
(open/short).
Check connection of Outside Temperature Sensor to
master DSP if OTC is used. Check if OTC curve is set
to zero when OTC is not used in the system.
Page 66
FHE-250 MANUAL 09 2014 ISSUE 2
Page 60
4
E97 Cascade Structure Mismatch
devices) has been changed.
The total count of reported
MAXSYS devices has been
changed.
Cascade structure has been
changed, some units’ DSP or
MAXSYS has been added or
removed.
Order of DSP connections in
chain has been changed.
Cascade has mixed structure with
non-equal count of burners per
DSP.
Last Auto Detection failed.
For further information on boiler
cascade, see Section 2.19.1.
Check if the order of DSPs has not been changed.
If cascade structure has been changed, re-do Auto
Detection.
Perform Auto Detection again
E98 Communication Error between two DSPs
There is missing communication
between two DSP boards due to
wiring, power supply problems or
board problems.
Cascade structure has been
have been removed.
Order of DSP connections in
chain has been changed.
device. If not successful, replace DSP board. Check
neighbouring MAXSYS devices for problems with
power supply or communication.
If cascade structure has been changed, re-do Auto
Detection.
Note: This error message is shown on the master DSP with indication of nearest affected burner as well as on the slave DSP affected - either on the one which has
Page 67
FHE-250 MANUAL 09 2014 ISSUE 2
Page 61
4
ERROR
CODE
MEANING POSSIBLE CAUSE SOLUTION
E99
Communication error between DSP and MAXSYS. Some MAXSYS boards are not
responding to DSP queries. There
might be a broken
communication cable, broken
power supply cable or fuse or
MAXSYS or DSP device has fatal
internal failure.
Cascade structure has been
changed, some DSP has lower
number of MAXSYS
connected.
Check cables and fuses related to affected MAXSYS
board.
If cascade structure has been changed, re-do Auto
Detection.
Page 68
FHE-250 MANUAL 09 2014 ISSUE 2
Page 62
4
This log should be completed regularly as a record of boiler maintenance.
Date Action Remarks Sig.
4.14
MAINTENANCE LOG
Page 69
FHE-250 MANUAL 09 2014 ISSUE 2
Page 63
4
This log should be completed regularly as a record of boiler maintenance.
Date Action Remarks Sig.
Page 70
FHE-250 MANUAL 09 2014 ISSUE 2
Page 64
Page 71
FHE-250 MANUAL 09 2014 ISSUE 2
Page 65
5
D
E
A
H
K
F
Q
N
J
M
G
P
L
C
B
SECTION 5 - GENERAL DATA
FIG.12 BOILER DIMENSIONS
5.1
BOILER DIMENSIONS
Note: Dimensions are for one FHE-250 model, further models (if being cascaded) would be stacked vertically or horizontally.
Adjust dimensions, according to number of models being cascaded.
Dimensions mm Dimensions are approximate and only intended as a guide to aid installation.
MODEL: FHE 250
A
Overall Width 650
B
Overall Depth 1420
C
Cabinet Depth 1360
D
Cabinet Height 785
E
Adjustable Foot Height 35 ± 10
F
Gas Inlet Height 160
G
Gas Inlet Distance From Edge 520
H
Flue Outlet Height 608
J
Flue Outlet Distance From Edge 407
K
Flow Pipe Height 270
L
Flow Pipe Distance From Edge 140
M
Return Pipe Height 475
N
Return Pipe Distance From Edge 140
P
Condensate Pipe Height 155
Q
Condensate Pipe Distance From Edge 155
Page 72
FHE-250 MANUAL 09 2014 ISSUE 2
Page 66
5
MODEL: FHE
UNIT 250 500 750 1000
The FHE-250 has been designed and manufactured to the following standards: BS EN 60335:2012, BS 6644:2011, BS EN 15420:2010, BS EN 15417:2006, BS EN 656:2000, BS EN 61000-4:2010, BS EN 55014-1:2006, BS EN 50371:2002, BS EN 55014-2:1997,
and complies with the following Directives: 2009/142/EC - the Gas Appliances Directive 2006/95/EC - the Low Voltage Directive 2004/108/EC - the Electromagnetic Compatibility Directive
92/42/EEC - the Boiler Efciency Directive
General
Output kW 250 500 750 1000 Gas Input (Gross) kW 255.1 510.2 765.3 1020.4 Minimum Flow Rate * L/s 1.25 1.25 1.25 1.25 Turn Down 1:6 1:12 1:18 1:24
Efciencies
Condensing Efciency (50°C Output, 30°C Return) ** % 108.9 108.9 108.9 108.9 Non-Condensing Efciency (80°C Output, 60°C Return) ** % 97.1 97.1 97.1 97.1
Weight
Shipping Weight kg 150 300 450 600 Operational Weight kg 170 340 510 680 Water Content L 15 30 45 60
Pressure
Minimum Gas Pressure mbar 5 5 5 5 Maximum Gas Pressure mbar 200 200 200 200 Minimum Water Pressure barg 1 1 1 1 Maximum Water Pressure barg 6 6 6 6 Hydraulic Pressure Drop Per Boiler kPa 45 45 45 45
Temperature
Heating Circuit Minimum Temperature °C 5 5 5 5 Heating Circuit Maximum Temperature °C 95 95 95 95
Ventilation Requirements for Combustion Purposes (Free Area)
Low Level inlet cm
2
1545 2820 4095 5370
High Level Outlet cm
2
773 1410 2048 2685
Electrical Requirements
Boiler Electrical Supply V 230 230 230 230 Power Consumption: Boiler Only W 350 700 1050 1400 Fuse Rating A 5 13 13 13
Connection Sizes All threads BSP F= Female, M=Male
Flue Outlet mm 150 2 x 150 3 x 150 4 x 150 Gas Inlet mm 28 2 x 28 3 x 28 4 x 28 Flow Pipe DN 50 2 x 50 3 x 50 4 x 50 Return Pipe DN 50 2 x 50 3 x 50 4 x 50
TI 127 ISSUE 6 03 2013
Gas Consumption Rate: 4 to 24.5 m3/hr
Flue Gas Conditions:
Volumetric owrate = 107.6 m3/hr
CO2 Content = 9.5 ± 2.5% Maximum Temperature = 98.5°C
Boiler Part Load Efciency: 101% nett.
5.2
BOILER SPECIFICATION
Up to 12 FHE-250 models can be cascaded, allowing a total output of 3000 kW. For simplicity, 250 - 1000 kW models are shown below, more details on request.
Note:
* Figures quoted are for a single boiler module running at
minimum output (41.66 kW) at a 8 °C
temperature differential between ow and return.
** Figures quoted are nett efciencies.
Page 73
FHE-250 MANUAL 09 2014 ISSUE 2
Page 67
5
5.3
SEASONAL EFFICIENCIES
C.I.B.S.E. Method
100.3% Net Efciency : "A" Rated
Boiler Rating Label Seasonal Efciency Range (net efciency)
A > 96
B 93 – 96
C 90 – 93
D 87 – 90
E < 87
HM Government Non-Domestic Building Services Compliance Guide Method
94.2% Gross Efciency : "A" Rated
90% and above
86% - 90%
82% - 86%
78% - 82%
74% - 78%
B
C
D
E
F
70% - 74%
Below 70%
G
A
A
Page 74
FHE-250 MANUAL 09 2014 ISSUE 2
Page 68
5
!
IMPORTANT
Recommended Water Conditions
It is very important that a strict water management program is followed to ensure trouble free boiler
operation.
The following are recommended for feedwater/boiler water
pH Value 8.5 to 9.5 tested at room temperature. Hardness less than 2.0 mg/kg in the form of CaCO
3
Suspended Solids None Chloride Less than 50 mg/kg Organic Matter Less than 5 mg/kg Oil None
Silica Less than 180 mg/kg, in the form of SiO
2
mg/kg = Milligrams per Kilogram CaCO
3
= Calcium Carbonate
SiO
2
= Silicon Dioxide
For practical purposes mg/kg = ppm
5.4
RECOMMENDED WATER CONDITIONS
Page 75
FHE-250 MANUAL 09 2014 ISSUE 2
Page 69
5
FIG. 13 NAME PLATES
5.5
NAME PLATES
Page 76
FHE-250 MANUAL 09 2014 ISSUE 2
Page 70
5
FULTON CONDENSING BOILER
MODEL FHE250
COUNTRY OF DESTINATION:
GAS CATEGORY:
GAS TYPE:
GAS SUPPLY PRESSURE: 20 mbar
WARNING
• THIS BOILER MAY ONLY BE INSTALLED IN A ROOM WHICH COMPLIES WITH THE APPROPRIATE VENTILATION REQUIREMENTS AND WHICH IS SEPARATED FROM LIVING ROOMS
• READ THE INSTALLATION INSTRUCTIONS BEFORE INSTALLING THE BOILER
• READ THE USER’S INSTRUCTIONS BEFORE LIGHTING THE BOILER
5.6
BOILER PACKAGING LABEL
For each boiler name plate and packaging, the following information will be completed, based on the country of destination:
Country of destination: AT, CH, CZ, DK, EE, ES, FI, GB, HU, IE, IT, LT, LV, NO, PT, RO, SE, SI, SK
Gas category: I
2H
Gas type: G20
Country of destination: FR, DE, BE, LU, PL, RO
Gas category: I
2E
, I2Er, I2E(R)
Gas type: G25 & G231
Country of destination: NL
Gas category: I
2L
Gas type: G25, G26 & G27
Page 77
FHE-250 MANUAL 09 2014 ISSUE 2
Fulton Ltd
Material & Workmanship Warranty
General Warranty
The Fulton general Guarantee is given in lieu of and in exclusion of any warranty expressed or implied, statutory or otherwise, as to the state,
condition, performance, quality or tness of the
goods. Save thereunder we shall be under no obligation or liability of any kind to you in regard
to the goods. In the case of new goods manufactured and supplied by us we will make
good any defect developing therein under proper use within 12 months of delivery, provided that after investigation in our sole discretion we are
satised that the defect arose from faulty design,
materials or workmanship and from no other cause whatsoever.
Defective goods or parts must be returned to us as soon as possible after discovery of the defect, Costs of carriage and of detaching and incorporating parts will be borne by you. ln all cases at the termination of such 12 months all liability on our part will cease. No liability whatsoever is to be incurred by us in respect of gauge or sight-glasses, packing glands or electric motors or any goods or
accessories not of our manufacture. But so far as
we are able, we shall let you have the benet of
any guarantee or warranty given to us in respect thereof.
2 Year Warranty
On the Fulton Boiler Pressure Vessel
Fulton Ltd will repair or replace EXW Bristol factory any parts which within two (2) years of the date
of delivery is found to be defective in workmanship, or material, provided this equipment is operated
and maintained by the buyer for the purpose for which it was designed and in accordance with the
Manufacturer’s Handbook. This Warranty does not cover damage or failures that can be attributed
to corrosion, scale or dirt accumulation or to low water conditions. This Warranty is good only in the
United Kingdom of Great Britain and Northern Ireland.
This Warranty does not include labour or delivery charges of any kind.
Page 78
FHE-250 MANUAL 09 2014 ISSUE 2
Fulton Ltd
5 Fernhurst Road Fishponds Bristol BS5 7FG England
Telephone: +44 (0) 117 972 3322 Fax: +44 (0) 117 972 3358
Email: sales@fulton.com
www.fulton.co.uk
Loading...