Thank you for purchasing our CANopen Communications Card OPC-G1-COP.
Mounting this communications card on your FRENIC-MEGA allows you to connect the FRENIC-MEGA to a
CANopen master unit (e.g., PC and PLC) and control it as a slave unit using run commands, frequency
commands, and access to function codes.
This communications card has the following features:
• Maximum cabling length: 25 m (1 Mbit/s) to 2500 m (20 kbit/s)
• Reading and writing all the function codes supported by the FRENIC-MEGA
This instruction manual does not contain inverter handling instructions. Read through this instruction manual in
conjunction with the FRENIC-MEGA Instruction Manual and be familiar with proper handling and operation of
this product. Improper handling might result in incorrect operation, a short life, or even a failure of this product.
Keep this manual in a safe place.
Related Publications
Listed below are the other materials related to the use of the CANopen communications card "OPC-G1-COP."
Read them in conjunction with this manual as necessary.
• RS-485 Communication User's Manual
• FRENIC-MEGA Instruction Manual
The materials are subject to change without notice. Be sure to obtain the latest editions for use.
Listed below are the CANopen specifications published by CAN in Automation (CiA). It is recommended that the
user of this communications card read them since this instruction manual is intended for the user who has a
basic knowledge of CANopen.
• DS 301 Ver. 4.02
• DSP 402 Ver. 2.0
These specifications are available as a free download from the CiA website at:
http://www.can-cia.de/
• Read through this instruction manual and be familiar with the CANopen communications card before
proceeding with installation, connections (wiring), operation, or maintenance and inspection.
• Improper handling might result in incorrect operation, a short life, or even a failure of this product as
well as the motor.
• Deliver this manual to the end user of this product. Keep this manual in a safe place until this product
is discarded.
Safety precautions
Read this manual thoroughly before proceeding with installation, connections (wiring), operation, or
maintenance and inspection. Ensure you have sound knowledge of the device and familiarize yourself with all
safety information and precautions before proceeding to operate the inverter.
Safety precautions are classified into the following two categories in this manual.
ENGLISH
Failure to heed the information indicated by this symbol may lead to
dangerous conditions, possibly resulting in death or serious bodily
injuries.
Failure to heed the information indicated by this symbol may lead to
dangerous conditions, possibly resulting in minor or light bodily injuries
and/or substantial property damage.
Failure to heed the information contained under the CAUTION title can also result in serious consequences.
These safety precautions are of utmost importance and must be observed at all times.
1
Installation and wiring
• Before starting installation and wiring, turn OFF the power and wait at least five minutes for inverters
with a capacity of 22 kW or below, or at least ten minutes for inverters with a capacity of 30 kW or
above. Make sure that the LED monitor and charging lamp are turned OFF. Further, make sure,
using a multimeter or a similar instrument, that the DC link bus voltage between the terminals P(+)
and N(-) has dropped to the safe level (+25 VDC or below).
• Qualified electricians should carry out wiring.
Otherwise, an electric shock could occur.
• Do not use the product that is damaged or lacking parts.
Doing so could cause a fire, an accident, or injuries.
• Prevent lint, paper fibers, sawdust, dust, metallic chips, or other foreign materials from getting into
the inverter and the communications card.
Otherwise, a fire or an accident might result.
• Incorrect handling in installation/removal jobs could cause a failure.
A failure might result.
• Noise may be emitted from the inverter, motor and wires. Implement appropriate measure to prevent
the nearby sensors and devices from malfunctioning due to such noise.
Otherwise, an accident could occur.
Operation
• Be sure to install the front cover before turning the inverter's power ON. Do not remove the cover
when the inverter power is ON.
Otherwise, an electric shock could occur.
• Do not operate switches with wet hands.
Doing so could cause an electric shock.
• If you configure the function codes wrongly or without completely understanding FRENIC-MEGA
Instruction Manual and the FRENIC-MEGA User's Manual, the motor may rotate with a torque or at a
speed not permitted for the machine. Confirm and adjust the setting of the function codes before
running the inverter.
Otherwise, an accident could occur.
Maintenance and inspection, and parts replacement
• Before proceeding to the maintenance/inspection jobs, turn OFF the power and wait at least five
minutes for inverters with a capacity of 22 kW or below, or at least ten minutes for inverters with a
capacity of 30 kW or above. Make sure that the LED monitor and charging lamp are turned OFF.
Further, make sure, using a multimeter or a similar instrument, that the DC link bus voltage between
the terminals P(+) and N(-) has dropped to the safe level (+25 VDC or below).
Otherwise, an electric shock could occur.
• Maintenance, inspection, and parts replacement should be made only by qualified persons.
• Take off the watch, rings and other metallic objects before starting work.
• Use insulated tools.
Otherwise, an electric shock or injuries could occur.
2
Disposal
• Treat the communications card as an industrial waste when disposing of it.
Otherwise injuries could occur.
Others
• Never modify the communications card.
Doing so could cause an electric shock or injuries.
Icons
The following icons are used throughout this manual.
This icon indicates information which, if not heeded, can result in the product not operating to full
efficiency, as well as information concerning incorrect operations and settings which can result in
accidents.
This icon indicates information that can prove handy when performing certain settings or operations.
This icon indicates a reference to more detailed information.
Unpack the package and check the following:
(1) A communications card, two screws (M3 8), and the CANopen Communications Card Instruction Manual
(this manual) are contained in the package.
(2) The communications card is not damaged during transportation--no defective parts, dents or warps.
(3) The model name "OPC-G1-COP" is printed on the communications card. (See Figure 2.1.)
If you suspect the product is not working properly or if you have any questions about your product, contact the
shop where you bought the product or your local Fuji branch office.
Neither an EDS file nor a terminating resistor comes with this communications card.
- An EDS file is required for registering this communications card to the configurator designed for
CANopen master node settings. It is available as a free download from our website at:
http://web1.fujielectric.co.jp/Kiki-Info-EN/User/index.html
Before downloading, you are requested to register as a member (free of charge).
- A terminating resistor of the following specifications must be used: 120 ohm ±1%, 1/4 watt,
metal-film resistor
1.2 Applicable Inverters
The CANopen communications card is applicable to the following inverters and ROM version.
Table 1.1 Applicable Inverters and ROM Version
Series Inverter type Applicable motor rating ROM version
FRENIC-MEGA FRNG1 -All capacities 1000 or later
* The boxes replace alphanumeric letters depending on the nominal applied motor, enclosure, power supply voltage, etc.
To check the inverter's ROM version, use Menu #5 "Maintenance Information" on the keypad. (Refer to the
FRENIC-MEGA Instruction Manual, Chapter 3, Section 3.4.6 "Reading maintenance information."
Display on LED Monitor Item Description
Inverter's ROM versionShows the inverter's ROM version as a 4-digit code.
ENGLISH
5
Chapter 2 NAMES AND FUNCTIONS
2.1 Parts Names
Figure 2.1 shows the names of the parts on the CANopen communications card.
Screw hole (left)
Model name
(Front) (Back)
Positioning cutout
LED status indicators
Figure 2.1 Names of Parts on CANopen Communications Card
Release knobTERM1
Screw hole (right)
CN1
2.2 CANopen Terminal Block (TERM1)
Connect the CANopen communications cable to the CANopen terminal block.
For details about wiring, refer to Chapter 4 "WIRING AND CABLING."
2.3 LED Status Indicators
This communications card has two LED status indicators that indicate the operation status of the
communications card as listed in Table 2.1.
Table 2.1 LED Status Indicators and Operation Status
LED Status Meaning
RUN OFF Powered off or communications error
(Green) Single flash *1 “Stopped”
Blinking *2 “Pre-Operational”ON "Operational”
ERR OFF No communications error
(Red) Single flash *1 The CAN controller is Error-passive.
Double flash *3 Network break detected by Heartbeat or Node Guarding
Blinking *
ON The communications card is Bus-off. *
Both RUN and ERR are ON. CPU error on the communications card
*1 Single flash: In cycles of 200-ms ON and 1-second OFF.
*2 Blinking: At 2.5 Hz (In cycles of 200-ms ON and 200-ms OFF).
*3 Double flash: In cycles of 200-ms ON, 200-ms OFF, 200-ms ON, and 1-second OFF.
*4 The ERR LED might flash at an indefinite frequency.
2
Wrong connection between the communications card and
FRENIC-MEGA
4
6
Chapter 3 INSTALLATION AND REMOVAL OF THIS COMMUNICATIONS CARD
Before starting installation and wiring, turn OFF the power and wait at least five minutes for inverters with a
capacity of 22 kW or below, or at least ten minutes for inverters with a capacity of 30 kW or above. Make
sure that the LED monitor and charging lamp are turned OFF. Further, make sure, using a multimeter or a
similar instrument, that the DC link bus voltage between the terminals P(+) and N(-) has dropped to the safe
level (+25 VDC or below).
Otherwise, an electric shock could occur.
• Do not use the product that is damaged or lacking parts.
Doing so could cause a fire, an accident, or injuries.
• Prevent lint, paper fibers, sawdust, dust, metallic chips, or other foreign materials from getting into
the inverter and the communications card.
Otherwise, a fire or an accident might result.
• Incorrect handling in installation/removal jobs could cause a failure.
A failure might result.
3.1 Installing the Communications Card
Before mounting the communications card, perform the wiring for the main circuit terminals and control
circuit terminals.
(1) Remove the front cover from the inverter and expose the control printed circuit board (control PCB). As
shown in Figure 3.1, the communications card can be connected to the A-port only, out of the three option
connection ports (A-, B-, and C-ports) on the inverter.
To remove the front cover, refer to the FRENIC-MEGA Instruction Manual, Chapter 2, Section 2.3.
For inverters with a capacity of 30 kW or above, open also the keypad enclosure.
(2) Insert connector CN1 on the back of the communications card (Figure 2.1) into the A-port (CN4) on the
inverter's control PCB. Then secure the communications card with the two screws that come with the card.
(Figure 3.3)
Check that the positioning cutout (shown in Figure 2.1) is fitted on the tab ( in Figure 3.2) and
connector CN1 is fully inserted ( in Figure 3.2). Figure 3.3 shows the communications card
correctly mounted.
(3) Perform wiring to the communications card.
For details, refer to Chapter 4 "WIRING AND CABLING."
(4) Put the front cover back into place.
To put back the front cover, refer to the FRENIC-MEGA Instruction Manual, Chapter 2, Section 2.3.
For inverters with a capacity of 30 kW or above, close also the keypad enclosure.
ENGLISH
7
Figure 3.1 In the case of 0.4 kW
Fit the positioning cutout of the
communications card over the tab on the
inverter to determine the mounting position.
Insert connector CN1 on the communications
card into the corresponding port on the
inverter's control PCB.
Note: Be sure to follow the order of and .
Inserting CN1 first may lead to insufficient
insertion, resulting in a contact failure.
Tab
Figure 3.2 Mounting the Communications Card (to A-port)
8
Figure 3.3 Mounting Completed (on A-port)
3.2 Removing the Communications Card
(Release knob)
Remove the two screws that secure the communications card and pull the release knob (shown above) to take
the communications card out of the inverter.
ENGLISH
9
Chapter 4 WIRING AND CABLING
• Before starting installation and wiring, turn OFF the power and wait at least five minutes for inverters with
a capacity of 22 kW or below, or at least ten minutes for inverters with a capacity of 30 kW or above.
Make sure that the LED monitor and charging lamp are turned OFF. Further, make sure, using a
multimeter or a similar instrument, that the DC link bus voltage between the terminals P(+) and N(-) has
dropped to the safe level (+25 VDC or below).
• Qualified electricians should carry out wiring.
Otherwise, an electric shock could occur.
• In general, the covers of the control signal wires are not specifically designed to withstand a high voltage
(i.e., reinforced insulation is not applied). Therefore, if a control signal wire comes into direct contact with
a live conductor of the main circuit, the insulation of the cover might break down, which would expose the
signal wire to a high voltage of the main circuit. Make sure that the control signal wires will not come into
contact with live conductors of the main circuit.
Failure to observe this precaution could cause an electric shock or an accident.
Noise may be emitted from the inverter, motor and wires. Take appropriate measures to prevent the nearby
sensors and devices from malfunctioning due to such noise.
An accident could occur.
4.1 Basic Connection Diagram
FRENIC-MEGA
L1/R
L2/S
L3/T
OPC-G1-COP
CANopen
terminal block
CAN
transceiver
U
V
W
1
CAN_GND
2
CAN_L
3
CAN_H
4
CAN_SHILD
*1
4
5
CAN_V+
*2
5
1
2
3
Motor
CANopen dedicated cable
M
G
G
*1 This wire is not connected to the internal circuit on the communications card. Perform functional grounding
if necessary.
*2 This wire is not connected to the internal circuit on the communications card. No output voltage is applied
to this wire.
G
Figure 4.1 Basic Connection Diagram
10
4.2 Wiring for CANopen Terminal Block
(1) CANopen terminal block (TERM1)
The pin assignment of the CANopen terminal block (TERM1) is shown in Figure 4.2 and Table 4.1.
1 2 3 4 4 5 5 1 2 3
CAN_
GND
(2) CANopen communications cable
To connect the communications card to CANopen network, be sure to use a CANopen dedicated cable. The
maximum cabling length is listed below.
CAN_LCAN_HCAN_
SHLD
Figure 4.2 Pin Assignment on CANopen Terminal Block
Table 4.1 Functions of CANopen Terminals
Pin # Name Description
1 CAN_GND Signal ground
2 CAN_L CAN L bus line
3 CAN_H CAN H bus line
4 CAN_SHLD *1 Terminal for connecting the cable shield
5 CAN_V+ *2 NC
*1 This terminal is not connected to the internal circuit on the communications
card. Perform functional grounding if necessary.
*2 This terminal is not connected to the internal circuit on the communications
card. No output voltage is applied to this terminal.
CAN_
SHLD
CAN
_V+
CAN
_V+
CAN_
GND
CAN_LCAN
_H
Table 4.2 Maximum Cabling Length for CANopen Communication
Baud rate (bit/s) 20 k 50 k 125 k 250 k 500 k 800 k 1 M
Maximum cabling length 2500 m1000 m500 m250 m100 m50 m 25 m
(3) Wiring to CANopen terminal block
Before connecting the CANopen communications cable to the terminal block, strip the wire ends as specified in
Figure 4.3 and twist the core and shield wires. Figure 4.4 shows the recommended terminal screw size and its
tightening torque.
Screw size: M3
5 to 7 mm
Figure 4.3 Strip Length of the CANopen
Cable Wire End
Tightening torque: 0.5 to 0.6: N·m
Figure 4.4 Connecting Wire to CANopen
Terminal Block
(4) Terminating resistor
When the communications card is mounted on the inverter at either end of the network, insert the terminating
resistor specified below between terminal pins #2 (CAN_L) and #3 (CAN_H).
1201%, 1/4 W
ENGLISH
Terminating resistors do not come with this communications card. They are separately necessary.
11
4.3 Wiring to Inverter
Route the wiring of the CANopen communications cable as far from the wiring of the main circuit as
possible. Otherwise electric noise may cause malfunctions.
Route the wires, taking care not to let them go over the control PCB, as shown in Figure 4.5.
Otherwise, malfunctions may occur.
• For inverters with a capacity of 22 kW or below
* Pass the wires from the communications card between the
control circuit terminal block and the front cover.
In the case of 0.4 kW
• For inverters with a capacity of 30 kW or above
In the case of 75 kW
Figure 4.5 Examples of Wiring
12
Chapter 5 CONFIGURING INVERTER'S FUNCTION CODES FOR CANopen
COMMUNICATION
To perform data transmission between the inverter equipped with this communications card and the CANopen
master, configure the function codes listed in Table 5.1.
Table 5.2 lists inverter's function codes related to CANopen communication. Configure those function codes if
necessary.
Table 5.1 Inverter's Function Code Settings Required for CANopen Communication
Function
codes
1
*
o31
2
*
o32
3
*
y98
Description
Specify Node-ID
(station address)
Specify baud rate
Select run/frequency
command source
Factory
default
setting
0 0 to 255
(Specify any of 0 to 127.)
0 0 to 255
(Specify any of 0 to 7.)
0: 125 kbit/s 1: 20 kbit/s
The baud rate specified
here should be consistent
with that of the master
node.
If there is no special
Frequency
command
Run
command
problem with your system,
y98 = 3 is recommended.
*1 After configuring the function code o31, turn the inverter power OFF and then ON or issue ResetNode from the
CANopen master to the communications card to validate the new settings.
*2 After configuring the function code o32, turn the inverter power OFF and then ON to validate the new setting.
*3 In addition to y98, the FRENIC-MEGA has other function codes related to the run/frequency command source.
Configuring those codes realizes more precise selection of the command sources. For details, refer to the
descriptions of H30 and y98 in the FRENIC-MEGA Instruction Manual, Chapter 5 "FUNCTION CODES."
Table 5.2 Other Related Function Codes
Function
codes
1
*
o27
Select the inverter’s operation mode to
apply when a CANopen communications
error occurs.
1
*
o28
Set the operation timer to apply when a
CANopen communications error occurs.
2
o40 to o43
o48 to o51
*1 For details about function codes o27 and o28, refer to Chapter 13 "INVERTER REACTIONS TO CANopen
NETWORK BREAKS."
*2 For details about how to configure the function codes o40 to o43 and o48 to o51, refer to Chapter 7, Section 7.2, (4)
"Configuring inverter's function codes o40 to o43, o48 to o51, and Indexes 5E00 and 5E01."
After configuring them, turn the inverter power OFF and then ON or issue ResetNode from the CANopen master to
the communications card to validate the new settings.
*
Specify the function code to be assigned
to TPDO 3 (for write).
2
*
Specify the function code to be assigned
to RPDO 3 (for readout).
Description
Factory
default
setting
0 0 to 15
0.0 s 0.0 s to 60.0 s
0
(No assignment)
0
(No assignment)
Function code
setting range
0000 to FFFF (hex) These settings
0000 to FFFF (hex)
Remarks
are used in PDO
3.
ENGLISH
13
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.