Fuji Electric FRN0025C2S-2U, FRN0033C2S-2U, FRN0060C2S-2U, FRN0013C2S-4U, FRN0024C2S-4U Instruction Manual

...
Instruction Manual
Supplement for FRN-C2S-2U/4U (7.5 to 20 HP)
Compact Inverter
Three-phase 200 V series: FRN0025 to 0060C2S-2U Three-phase 400 V series: FRN0013 to 0030C2S-4U
Thank you for purchasing our FRENIC-Mini series of inverters.
• This manual is a supplement to the FRENIC-Mini Instruction Manual (INR-SI47-1729-E, INR-SI47-1745-E). It describes the FRENIC-C2S (Inverter types FRN0025 to 0060C2S-2U and FRN0013 to 0030C2S-4U). For other descriptions, refer to the original manu
al.
• Improper handling might result in incorrect operation, a short life, or even a failure of this product as well as the motor.
• Deliver this manual to the end user of this product. Keep this manual in a safe place until this product is discarded..
Fuji Electric Co., Ltd. INR-SI47-1833-E
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Chapter 2 MOUNTING AND WIRING OF THE INVERTER
2.3.2 Terminal arrangement and screw specifications (1) Arrangement of the main circuit terminals
Table 2.3 Main Circuit Terminals
Power supply
voltage
Nominal ap-
plied motor
(HP)
Inverter type
Terminal
screw size
Tightening
torque
(lb-in)
Refer to:
7.5 FRN0025C2S-2U
10 FRN0033C2S-2U
M5 26.6 Figure E
15 FRN0047C2S-2U
Three-
phase 200 V
20 FRN0060C2S-2U
M6
51.3
Figure
F
7.5 FRN0013C2S-4U
10 FRN0018C2S-4U
M5 26.6 Figure E
15 FRN0024C2S-4U
Three-
phase 400 V
20 FRN0030C2S-4U
M6
51.3 Figure F
Figure E
Figure F
2.3.3 Recommended wire sizes
Table 2.6 lists the recommended wire sizes. The recommended wire sizes for the main circuit ter­minals for an ambient temperature of 50
C are indicated for two types of wire: HIV single wire (for the maximum allowable temperature 75°C) (before a sla sh (/)) and IV single wire (for 6 0°C) (after a slash (/))
Table 2.6 Recommended Wire Sizes
Recommended wire size (AWG) *1
Main circuit
Main circuit power input
[L1/R, L2/S, L3/T]
[L1/L, L2/N]
Grounding [
G]
Power supply voltage
Nomi-
nal
applied
motor
(HP)
Inverter type
w/ DCR*2w/o DCR
Inverter
output
[U, V, W]
DCR
[P1, P (+)]
Braking resistor
[P (+), DB]
Control
circuit
7.5
FRN0025C2S-2U
14/10 12/ 8 12/10 12/10
10
FRN0033C2S-2U
12/ 8 10/ 6 12 /8 10/ 6
15
FRN0047C2S-2U
10/ 6 6/ 4 8/ 6 8/ 4
Three-phase
200 V
20
FRN0060C2S-2U
6/ 4 4/ 2 6/ 4 6/ 2
14/14
20
16
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Table 2.6 Recommended Wire Sizes (Continued)
Recommended wire size (AWG) *1
Main circuit
Main circuit power input
[L1/R, L2/S, L3/T]
[L1/L, L2/N]
Grounding [
G]
Power supply voltage
Nomi-
nal
applied
motor
(HP)
Inverter type
w/ DCR w/o DCR *2
Inverter
output
[U, V, W]
DCR
[P1, P (+)]
Braking resistor
[P (+), DB]
Control
circuit
7.5
FRN0013C2S-4U
14/12
(13)
14/14
(13)
14/14
(13)
10
FRN0018C2S-4U
14/14
(13)
14/10
(11)
14/12
(13)
14/12
(13)
15
FRN0024C2S-4U
14/10
(11)
12 /8
(9)
14/10
(11)
12/10
(11)
Three-phase
400 V
20
FRN0030C2S-4U
12 /8
(9)
10/ 6
(7)
12/ 8
(9)
10 /6
(9)
14/14
(13)
20
16
DCR: DC reactor
*1 Use crimp termina ls covered with an insulated shea th or insulating tube. Recom mended wire sizes are
for HIV
/IV (PVC in the EU).
*2 Wire sizes are calcul ated on the basis of inp ut RMS current under the c ondition that the po wer suppl
y
capacity and impedance are 500 kVA and 5%, respectively.
*3 Insert the DC reactor (DCR) in either of the primary power input lines. Refer to C hapter 10 for more
details.
2.3.5 Wiring for main circuit terminals and grounding terminals Inverter output terminals, U, V, W and grounding terminal ( G)
1) Connect the three wires of the three-phase motor to terminals U, V, and W, aligning phases each other.
2) Connect the grounding wire of terminals U, V, and W to the grounding terminal (
G).
3) If the cable from the inverter to the motor is very long, a high-frequency current may be generated by stray
capacitance between the cables and resul t in an over current trip o f the inverter, an increase in leakage current, or a reduction in current indication precision.
When a motor is driven b y a PWM-type inverter, the motor terminals may be subject to surge voltage gen ­erated by inverter element switching. If the motor cable (with 460 V series motors, in particular) is particularly long, surge voltage will deteriorate motor insulation. To prevent this, use the following guidelines:
Inverters of 7.5 HP or above Motor Insulation Level 1000 V 1300 V 1600 V 460 VAC Input Voltage 66 ft (20 m) 328 ft (100 m) 1312 ft (400 m)* 230 VAC Input Voltage 1312 ft (400 m)* 1312 ft (400 m)* 1312 ft (400 m)*
Inverters of 5 HP or below Motor Insulation Level 1000 V 1300 V 1600 V 460 VAC Input Voltage 66 ft (20 m) 165 ft (50 m) 165 ft (50 m)* 230 VAC Input Voltage 328 ft (400 m)* 328 ft (100 m)* 328 ft (100 m)*
* For this case the cable length is determined by secondary effects and not voltage spiking.
When a motor protective thermal O/L relay is inserted between the inverter and the motor, the thermal O/L relay may malfunction (particularly in the 460 V series), even when the cabl e length is 165 ft (50 m) or less. T o correc t, insert a fil ter or red uce the carri er frequenc y. (Use function code F26 (Motor sound).)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Chapter 5 FUNCTION CODES
5.1 Function Code Tables
Table A Fuji Standard Motor Parameters
Fuji's standard
torque
boost (%)
Nominal rated
current of
Fuji standard
motor (A)
Nominal rated
capacity of
Fuji standard
motor (kW)
Restart Mode
after Momentary
Power Failure
(s)
Function codes
F11/A07/ E34/E37
Power supply
voltage
Applicable
motor rat-
ing
(HP)
Inverter type
Function code
F09/A05
Shipping destina-
tion (version)
Function code
P02/A16
Function
code
H13
7.5 FRN0025C2S-2U
4.9
20.06
5.50 0.5
10 FRN0033C2S-2U
4.4
25.72
7.50 0.5
15 FRN0047C2S-2U
3.5
37.21
11.00 1.0
Three­phase
200 V
20 FRN0060C2S-2U
2.8
48.50
15.00
1.0
7.5 FRN0013C2S-4U
4.9
10.24
5.50 0.5
10 FRN0018C2S-4U
4.4
12.86
7.50 0.5
15 FRN0024C2S-4U
3.5
18.60
11.00 1.0
Three­phase
400 V
20 FRN0030C2S-4U
2.8
24.25
15.00 1.0
The following function code , in the ROM version 0800 or later, the data setting range and the
factory default is change.
Code Name Data setting range Default setting
Refer
to
page:
F44 Current Limiter (Level)
20 to 180 : 3.7kW or below 20 to 200 : 5.5kW or above
(The data is interpreted as the rated output cur­rent of the inverter for 100%.)
3.7kW or below : 160
5.5kW or above : 180
5-42
H27
Thermistor for Motor
(Level)
0.00 to 5.00 1.6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5.2 Details of Function Codes
F50, F51
Electronic Thermal Overload Protection for Braking Resistor (Discharging capability and Allowable average loss)
External Braking Resistors
Standard models
Braking resistor
Continuous braking
(100% braking torque)
Intermittent braking
(Period: 100 s or less)
Power supply
voltage
Inverter type
Type Qty.
Resistance
(
)
Discharging
capability
(kWs)
Braking
time
(s)
Allowable
average loss
(kW)
Duty
(%ED)
FRN0025C2S-2U
DB5.5-2 20 55
20
0.138
FRN0033C2S-2U
DB7.5-2 15 37 0.188
FRN0047C2S-2U
DB11-2 10 55 0.275
Three­phase
200 V
FRN0060C2S-2U
DB15-2
1
8.6 75
10
0.375
5
FRN0013C2S-4U
DB5.5-4 80 55
20
0.138
FRN0018C2S-4U
DB7.5-4 60 38 0.188
FRN0024C2S-4U
DB11-4 40 55 0.275
Three­phase
400 V
FRN0030C2S-4U
DB15-4
1
34.4 75
10
0.375
5
10%ED
Braking resistor
Continuous braking
(100% braking torque)
Intermittent braking
(Period: 100 s or less)
Power supply
voltage
Inverter type
Type Qty.
Resistance
(
)
Discharging
capability
(kWs)
Braking
time
(s)
Allowable
average loss
(kW)
Duty
(%ED)
FRN0025C2S-2U
DB5.5-2C 20 55
20
0.275
FRN0033C2S-2U
DB7.5-2C 15 37 0.375
FRN0047C2S-2U
DB11-2C 10 55 0.55
Three­phase
200 V
FRN0060C2S-2U
DB15-2C
1
8.6 75
10
0.75
10
FRN0013C2S-4U
DB5.5-4C 80 55
20
0.275
FRN0018C2S-4U
DB7.5-4C 60 38 0.375
FRN0024C2S-4U
DB11-4C 40 55 0.55
Three­phase
400 V
FRN0030C2S-4U
DB15-4C
1
34.4 75
10
0.75
10